Upload
rajeevagrawal
View
181
Download
6
Tags:
Embed Size (px)
Citation preview
29 August 2012 1
Bus Bar Protection
Manoj Barsaiyan
Presentation Outline
Introduction Bus arrangements Bus protection techniques
INTRODUCTION: Importance of Busbars
Busbars are the most important component in a power network.
They can be open busbars in an outdoor switch yard, or inside a metal clad cubicle restricted within a limited enclosure with minimum phase-to-phase and phase-to ground clearances.
They can be insulated as well as open
They form an electrical node where many circuits come together, feeding in and sending out power
Bus bars : Taken for Granted
Bus bars are frequently left without protection because:
Low susceptibility to faults especially metal clad switchgear
The bus bars and switchgear have a high degree of reliability, to the point of being regarded as intrinsically safe
Rely on system back-up protection
Problems with accidental operation greater than infrequent bus bar faults
However, Bus bar faults do occur
Introduction: The requirements for good protection Speed
Limit damage at fault point Limit effect on fault stability
Selectivity Trip only the faulted equipment Important for busbars divided into zones
Stability Not to operate for faults outside the zone Most important for busbars
Stability must be guaranteed Reasons for loss of stability
Interruption of CT circuits imbalance Accidental operation during testing
Tripping can be arranged two-out-of-two Zone and check relays.
Bus Bar Protection Requirements High bus fault currents due to large number of circuits
connected:
CT saturation often becomes a problem as CTs may not be sufficiently rated for worst fault condition case
large dynamic forces associated with bus faults require fast clearing times in order to reduce equipment damage
False trip by bus protection may create serious problems:
service interruption to a large number of circuits (distribution and sub-transmission voltage levels)
system-wide stability problems (transmission voltage levels)
With both dependability and security important, preference is always given to security
1 2 3 n-1 n
ZONE 1
- - - -
Distribution and lower transmission voltage
levels
No operating flexibility
Fault on the bus trips all circuit breakers
Bus arrangements : Single bus - single breaker
ZONE 1ZONE 2
Distribution and lower transmission voltage
levels
Limited operating flexibility
Bus arrangements : Multiple bus sections - single breaker with bus tie
ZONE 1
MAIN BUS
TRANFER BUS
Increased operating flexibility
A bus fault requires tripping all breakers
Transfer bus for breaker maintenance
Bus arrangements : Main and transfer buses
ZONE 1
ZONE 2
Very high operating flexibility
Transfer bus for breaker maintenance
Double bus single breaker with transfer bus
ZONE 1
ZONE 2
High operating flexibility
Line protection covers bus section between two CTs
Fault on a bus does not disturb the power to circuits
Double bus - double breaker
ZONE 1
ZONE 2
Used on higher voltage levels
More operating flexibility
Requires more breakers
Middle bus sections covered by line or other
equipment protection
Breaker-and-a-half bus
Higher voltage levels
High operating flexibility with minimum breakers
Separate bus protection not required at line
positions
B1 B2
TB1
L1 L2
L3 L4
TB1
Ring bus
TYPES OF PROTECTION SYSTEM
Frame-earth protection :
Used mainly for smaller busbar protection schemes at distribution voltages and for metalclad busbars.
Differential protection :
Used for switchgears and EHV switchyards
Frame-earth protection for Switchgears
Bus Protection Techniques
Overcurrent (unrestrained or unbiased) differential
Overcurrent percent (restrained or biased) differential
High-impedance bus differential schemes
Low-impedance bus differential schemes
Overcurrent (unrestrained) Differential
Overcurrent (unrestrained) Differential
Differential signal formed by summation of all currents feeding the bus
CT ratio matching may be required
On external faults, saturated CTs yield spurious differential current
Time delay used to cope with CT saturation
Instantaneous differential OC function useful on integrated microprocessor-based relays
51
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PROTECTION CIRCULATING CURRENT DIFFERENTIAL PRINCIPLE
CURRENT DISTRIBUTION EXTERNAL FAULT
CURRENT DISTRIBUTION INTERNAL FAULT
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PRIOTECTION A. HIGH IMPEDANCE TYPE
Relay Branch made High Impedance to limit differential
current due to unequal CT saturation on external fault. Requires exclusive CT core of identical ratio and rating. Simple in design and execution.
Advantages Simple
Low cost
Different ratios of CTs can be used with the help of Aux CT
High operating time All CTs must have equal ratio Low sensitivity Degree of CT saturation level to be very low
Disadvantages
Complications of Bus Bar Differential
All paralleled CTs must have the same ratio to ensure that all secondary currents are compared on the same base as the primary currents.
Protection should perform identically under all conditions, including external faults with heavy through current.
Complications of Bus Bar Differential
The reality is that all conventional iron-core current transformers, regardless of ratio and accuracy class, are susceptible to saturation.
This causes a difference current that appears to the differential relay as an internal fault.
Bus differential relays, regardless of the design, must differentiate between true internal bus faults, and false differential currents caused by CT saturation for a fault outside the bus differential zone of protection.
Complications of Bus Bar Differential
Objective of protections scheme is to provide secure operation for external faults with CT saturation and still provide fast operation for internal bus faults. There are two most common techniques:
Low-impedance bus differential, and
High-impedance bus differential
High Impedance Differential Overvoltage element
operates on voltage developed across resistor connected in secondary circuit
Operating signal created by connecting all CT secondaries in parallel
CTs must all have the same ratio
Must have dedicated CTs
Cannot easily be applied to reconfigurable buses and offers no advanced functionality
59
High Impedance relay
R
The relay branch is made high impedance either by using a voltage operated high impedance relay or by connecting an external series resistor (Stabilizing resistor) in case of current operated differential relay
This type of protection requires special class PS CTs (with low turns ration errors) of identical ratio and ratings on all circuits
Exclusive CT cores are required for high impedance schemes which cannot share common CT cores with other protections
High Impedance Differential Protection
31
Setting Criteria for High Impedance Relays
Assuming CT-B completely saturated while CT-A fully active, the maximum voltage that can appear across the relay branch during through fault condition is
Vs = (IF /n) (RCT + 2RL) volts
The differential relay should be set above this voltage to ensure stability on through fault
A B
RCT
RL
VS
32
High Impedance Differential Protection
In case of over-current type of differential relays, the above voltage setting can be achieved by adding a series stabilizing resistor, such that the current is limited to less than differential pickup current
Relay branch impedance Vs/Is, where Is = setting current of differential relay
If relay burden at setting current "Is" = VA
Relay impedance Rr = VA / (Is)2
The external stabilizing resistor setting
Rst = Total relay branch impedance - Relay impedance
= [Vs / Is] [VA / (Is)2] 33
High Impedance Differential Protection
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PROTECTION (87) HIGH IMPEDANCE SCHEME- Typical Setting Workout.
Max. Through fault Current (If) = 20,000A (Prim) / 20A(SEC) Vs = 20 (5 + 1) = 120V Stabilising Resistor (RST) = 120/0.2 1.0/0.2 = 600 - 25 = 575 ,
(assuming relay VA burden = 1 VA)
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PROTECTION HIGH IMPEDANCE SCHEME Typical Setting Workout. Primary Fault Current setting (assuming number of circuits
connected to Bus Bar, N=10) = CT Ratio (Is + N. Im) = 1000 (0.20 + 10 x 0.03) = 500A.
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PROTECTION (87) HIGH IMPEDANCE SCHEME Need For Metrosils.
Peak Voltage across CT Secondary for Max. Internal Fault = 2 2 [Vk x (Vp Vk)] Vk = 240V, Vp = 20 (575 + 25) = 12000V Peak Voltage = 22 [(240 x (12000-240)] = 5300V
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PROTECTION HIGH IMPEDANCE SCHEME Need For Metrosils. If Peak voltage exceeds 3000V threatening secondary
insulation, Metrosils (Non-linear resistors) are used to limit voltage to safe value (within 1000V) on internal fault.
Metrosil offers high resistance at lower voltage levels which
drastically reduces at higher voltages, thereby quenching the voltage across relay branch.
Typical Metrosil Equation V = C x I ( C = 900 , = 0.25)
Advantages
It avoids the problem of unequal CT performances.
It uses high impedance voltage relay.
Highly sensitive and fast.
Disadvantages
All CTs must have equal Turns ratio
All CTs must have high Knee point voltage preferably twice the nominal value
The CT must be exclusively used for differential protection.
Percent Differential
Percent characteristic used to cope with CT saturation and other errors
Restraining signal can be formed in a number of ways
No dedicated CTs needed
Used for protection of re-configurable buses possible
5187
Low Impedance Differential (Distributed)
Data Acquisition Units (DAUs) installed in bays
Central Processing Unit (CPU) processes all data from DAUs
Communications between DAUs and CPU over fiber using proprietary protocol
Sampling synchronisation between DAUs is required
Perceived less reliable (more hardware needed)
Difficult to apply in retrofit applications
52
DAU
52
DAU
52
DAU
CU
copper
fiber
Low Impedance Differential (Centralized)
All currents applied to a single central processor
No communications, external sampling synchronisation necessary
Perceived more reliable (less hardware needed)
Well suited to both new and retrofit applications.
52 52 52
CU
copper
BUS BAR PROTECTION AND LBB PROTECTION
BUS BAR PROTECTION HIGH IMPEDANCE SCHEME -CT SUPERVISION (95)
Required to detect CT open circuit on load to prevent maloperation. Connected for alarm & short CT bus wires on operation. Time delayed to avoid operation on internal / external faults (3Sec) Voltage relay with sensitive setting (2 -14V) is used. Normally set to detect primary unbalance of 25A or 10% of least loaded
circuit. Also should not operate with normal unbalance on load.
Isolators Reliable Isolator Closed signals are needed for the
Dynamic Bus Replica
In simple applications, a single normally closed contact may be sufficient
For maximum safety: Both N.O. and N.C. contacts should be used
Isolator Alarm should be established and non-valid combinations (open-open, closed-closed) should be sorted out
Switching operations should be inhibited until bus image is recognized with 100% accuracy
Optionally block 87B operation from Isolator Alarm
Each isolator position signal decides: Whether or not the associated current is to be included in the
differential calculations
Whether or not the associated breaker is to be tripped
Isolator Typical Open/Closed Connections
29 August 2012 53
LBB PROTECTION
In EHV substations, reliability of fault detection is enhanced by providing duplicated protections (either main 1/main 2 or main and backup protection)
The D.C. sources for protection are also duplicated for better redundancy, circuit breakers are provided with duplicated trip coils
All these measures, improve the reliability of fault detection and isolation, however, the possibility of mechanical failures of the switchgear or interrupter flash over cannot be covered by these means
A failure of the breaker therefore, result, in spite of correct operation of the protection and energisation of trip coils
LBB Protection
54
LBB Protection
HasProtectionOperated?
FaultCleared?
Yes
No
Yes
No
NormalOperation
StartBreakerFailure
Protection
Wait forFault
Clearance
ResetBreakerFailure
Protection
TripBack-up
Breaker(s)
TripMain
Breaker(s)
55
This situation can be corrected by providing local breaker backup (LBB) or breaker fail protection
LLB protection comes into operation only if, the breaker fails to trip, following energisation of its trip coil, through the circuit trip relays
The main component of LBB protection is a current check relay initiated by the circuit trip relays and a follower timer
The current check relay, on initiation, checks the presence of the current in the faulted circuit and if it persists beyond a preset time, proceeds to trip all other circuits connected to the Bus bar to which the stuck breaker is connected, thereby, ensuring local isolation
Tripping of remote breaker is also initiated through a separate carrier channel, in case of line breakers to arrest infeeds from remote end
LBB Protection
56
Phase A AC signals wired
here, current status
monitored here
Phase B AC signals wired
here, current status
monitored here
Phase C AC signals wired
here, current status
monitored here
Breaker Fail Op command
generated here and send to
trip appropriate breakers
Trip
Trip Trip
Example Architecture Breaker Failure Tripping Trip
Typical setting range for the current check relay and follower timer
A more sensitive setting is generally adopted for Generator application in view of the fact, that a stuck breaker situation for certain abnormal conditions like motoring, may involve very low current infeeds
LBB Protection
Application Current
Range
check relay
Recommended
Setting
Follower
Range
Timer
Recommended
Setting
Generator Circuit 5-80% 5% 0.1-1sec 0.2 sec
All other circuits (TFRs
/Lines /Bus Coupler
etc.)
20-30% 20% 0.1-1sec 0.2 secs
61
LBB Protection
TIME- CHART Fault occurs
Normal Clearing Time Current Detector
Dropout Time Normal
Clearing Protective
Time
~30ms
Breaker Interrupting
Time
~60ms
THANK YOU
29 August 2012 63