49
29 August 2012 1 Bus Bar Protection Manoj Barsaiyan

BUS BAR (1).pdf

Embed Size (px)

Citation preview

  • 29 August 2012 1

    Bus Bar Protection

    Manoj Barsaiyan

  • Presentation Outline

    Introduction Bus arrangements Bus protection techniques

  • INTRODUCTION: Importance of Busbars

    Busbars are the most important component in a power network.

    They can be open busbars in an outdoor switch yard, or inside a metal clad cubicle restricted within a limited enclosure with minimum phase-to-phase and phase-to ground clearances.

    They can be insulated as well as open

    They form an electrical node where many circuits come together, feeding in and sending out power

  • Bus bars : Taken for Granted

    Bus bars are frequently left without protection because:

    Low susceptibility to faults especially metal clad switchgear

    The bus bars and switchgear have a high degree of reliability, to the point of being regarded as intrinsically safe

    Rely on system back-up protection

    Problems with accidental operation greater than infrequent bus bar faults

    However, Bus bar faults do occur

  • Introduction: The requirements for good protection Speed

    Limit damage at fault point Limit effect on fault stability

    Selectivity Trip only the faulted equipment Important for busbars divided into zones

    Stability Not to operate for faults outside the zone Most important for busbars

    Stability must be guaranteed Reasons for loss of stability

    Interruption of CT circuits imbalance Accidental operation during testing

    Tripping can be arranged two-out-of-two Zone and check relays.

  • Bus Bar Protection Requirements High bus fault currents due to large number of circuits

    connected:

    CT saturation often becomes a problem as CTs may not be sufficiently rated for worst fault condition case

    large dynamic forces associated with bus faults require fast clearing times in order to reduce equipment damage

    False trip by bus protection may create serious problems:

    service interruption to a large number of circuits (distribution and sub-transmission voltage levels)

    system-wide stability problems (transmission voltage levels)

    With both dependability and security important, preference is always given to security

  • 1 2 3 n-1 n

    ZONE 1

    - - - -

    Distribution and lower transmission voltage

    levels

    No operating flexibility

    Fault on the bus trips all circuit breakers

    Bus arrangements : Single bus - single breaker

  • ZONE 1ZONE 2

    Distribution and lower transmission voltage

    levels

    Limited operating flexibility

    Bus arrangements : Multiple bus sections - single breaker with bus tie

  • ZONE 1

    MAIN BUS

    TRANFER BUS

    Increased operating flexibility

    A bus fault requires tripping all breakers

    Transfer bus for breaker maintenance

    Bus arrangements : Main and transfer buses

  • ZONE 1

    ZONE 2

    Very high operating flexibility

    Transfer bus for breaker maintenance

    Double bus single breaker with transfer bus

  • ZONE 1

    ZONE 2

    High operating flexibility

    Line protection covers bus section between two CTs

    Fault on a bus does not disturb the power to circuits

    Double bus - double breaker

  • ZONE 1

    ZONE 2

    Used on higher voltage levels

    More operating flexibility

    Requires more breakers

    Middle bus sections covered by line or other

    equipment protection

    Breaker-and-a-half bus

  • Higher voltage levels

    High operating flexibility with minimum breakers

    Separate bus protection not required at line

    positions

    B1 B2

    TB1

    L1 L2

    L3 L4

    TB1

    Ring bus

  • TYPES OF PROTECTION SYSTEM

    Frame-earth protection :

    Used mainly for smaller busbar protection schemes at distribution voltages and for metalclad busbars.

    Differential protection :

    Used for switchgears and EHV switchyards

  • Frame-earth protection for Switchgears

  • Bus Protection Techniques

    Overcurrent (unrestrained or unbiased) differential

    Overcurrent percent (restrained or biased) differential

    High-impedance bus differential schemes

    Low-impedance bus differential schemes

  • Overcurrent (unrestrained) Differential

  • Overcurrent (unrestrained) Differential

    Differential signal formed by summation of all currents feeding the bus

    CT ratio matching may be required

    On external faults, saturated CTs yield spurious differential current

    Time delay used to cope with CT saturation

    Instantaneous differential OC function useful on integrated microprocessor-based relays

    51

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PROTECTION CIRCULATING CURRENT DIFFERENTIAL PRINCIPLE

    CURRENT DISTRIBUTION EXTERNAL FAULT

    CURRENT DISTRIBUTION INTERNAL FAULT

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PRIOTECTION A. HIGH IMPEDANCE TYPE

    Relay Branch made High Impedance to limit differential

    current due to unequal CT saturation on external fault. Requires exclusive CT core of identical ratio and rating. Simple in design and execution.

  • Advantages Simple

    Low cost

    Different ratios of CTs can be used with the help of Aux CT

    High operating time All CTs must have equal ratio Low sensitivity Degree of CT saturation level to be very low

    Disadvantages

  • Complications of Bus Bar Differential

    All paralleled CTs must have the same ratio to ensure that all secondary currents are compared on the same base as the primary currents.

    Protection should perform identically under all conditions, including external faults with heavy through current.

  • Complications of Bus Bar Differential

    The reality is that all conventional iron-core current transformers, regardless of ratio and accuracy class, are susceptible to saturation.

    This causes a difference current that appears to the differential relay as an internal fault.

    Bus differential relays, regardless of the design, must differentiate between true internal bus faults, and false differential currents caused by CT saturation for a fault outside the bus differential zone of protection.

  • Complications of Bus Bar Differential

    Objective of protections scheme is to provide secure operation for external faults with CT saturation and still provide fast operation for internal bus faults. There are two most common techniques:

    Low-impedance bus differential, and

    High-impedance bus differential

  • High Impedance Differential Overvoltage element

    operates on voltage developed across resistor connected in secondary circuit

    Operating signal created by connecting all CT secondaries in parallel

    CTs must all have the same ratio

    Must have dedicated CTs

    Cannot easily be applied to reconfigurable buses and offers no advanced functionality

    59

  • High Impedance relay

    R

  • The relay branch is made high impedance either by using a voltage operated high impedance relay or by connecting an external series resistor (Stabilizing resistor) in case of current operated differential relay

    This type of protection requires special class PS CTs (with low turns ration errors) of identical ratio and ratings on all circuits

    Exclusive CT cores are required for high impedance schemes which cannot share common CT cores with other protections

    High Impedance Differential Protection

    31

  • Setting Criteria for High Impedance Relays

    Assuming CT-B completely saturated while CT-A fully active, the maximum voltage that can appear across the relay branch during through fault condition is

    Vs = (IF /n) (RCT + 2RL) volts

    The differential relay should be set above this voltage to ensure stability on through fault

    A B

    RCT

    RL

    VS

    32

    High Impedance Differential Protection

  • In case of over-current type of differential relays, the above voltage setting can be achieved by adding a series stabilizing resistor, such that the current is limited to less than differential pickup current

    Relay branch impedance Vs/Is, where Is = setting current of differential relay

    If relay burden at setting current "Is" = VA

    Relay impedance Rr = VA / (Is)2

    The external stabilizing resistor setting

    Rst = Total relay branch impedance - Relay impedance

    = [Vs / Is] [VA / (Is)2] 33

    High Impedance Differential Protection

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PROTECTION (87) HIGH IMPEDANCE SCHEME- Typical Setting Workout.

    Max. Through fault Current (If) = 20,000A (Prim) / 20A(SEC) Vs = 20 (5 + 1) = 120V Stabilising Resistor (RST) = 120/0.2 1.0/0.2 = 600 - 25 = 575 ,

    (assuming relay VA burden = 1 VA)

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PROTECTION HIGH IMPEDANCE SCHEME Typical Setting Workout. Primary Fault Current setting (assuming number of circuits

    connected to Bus Bar, N=10) = CT Ratio (Is + N. Im) = 1000 (0.20 + 10 x 0.03) = 500A.

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PROTECTION (87) HIGH IMPEDANCE SCHEME Need For Metrosils.

    Peak Voltage across CT Secondary for Max. Internal Fault = 2 2 [Vk x (Vp Vk)] Vk = 240V, Vp = 20 (575 + 25) = 12000V Peak Voltage = 22 [(240 x (12000-240)] = 5300V

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PROTECTION HIGH IMPEDANCE SCHEME Need For Metrosils. If Peak voltage exceeds 3000V threatening secondary

    insulation, Metrosils (Non-linear resistors) are used to limit voltage to safe value (within 1000V) on internal fault.

    Metrosil offers high resistance at lower voltage levels which

    drastically reduces at higher voltages, thereby quenching the voltage across relay branch.

    Typical Metrosil Equation V = C x I ( C = 900 , = 0.25)

  • Advantages

    It avoids the problem of unequal CT performances.

    It uses high impedance voltage relay.

    Highly sensitive and fast.

  • Disadvantages

    All CTs must have equal Turns ratio

    All CTs must have high Knee point voltage preferably twice the nominal value

    The CT must be exclusively used for differential protection.

  • Percent Differential

    Percent characteristic used to cope with CT saturation and other errors

    Restraining signal can be formed in a number of ways

    No dedicated CTs needed

    Used for protection of re-configurable buses possible

    5187

  • Low Impedance Differential (Distributed)

    Data Acquisition Units (DAUs) installed in bays

    Central Processing Unit (CPU) processes all data from DAUs

    Communications between DAUs and CPU over fiber using proprietary protocol

    Sampling synchronisation between DAUs is required

    Perceived less reliable (more hardware needed)

    Difficult to apply in retrofit applications

    52

    DAU

    52

    DAU

    52

    DAU

    CU

    copper

    fiber

  • Low Impedance Differential (Centralized)

    All currents applied to a single central processor

    No communications, external sampling synchronisation necessary

    Perceived more reliable (less hardware needed)

    Well suited to both new and retrofit applications.

    52 52 52

    CU

    copper

  • BUS BAR PROTECTION AND LBB PROTECTION

    BUS BAR PROTECTION HIGH IMPEDANCE SCHEME -CT SUPERVISION (95)

    Required to detect CT open circuit on load to prevent maloperation. Connected for alarm & short CT bus wires on operation. Time delayed to avoid operation on internal / external faults (3Sec) Voltage relay with sensitive setting (2 -14V) is used. Normally set to detect primary unbalance of 25A or 10% of least loaded

    circuit. Also should not operate with normal unbalance on load.

  • Isolators Reliable Isolator Closed signals are needed for the

    Dynamic Bus Replica

    In simple applications, a single normally closed contact may be sufficient

    For maximum safety: Both N.O. and N.C. contacts should be used

    Isolator Alarm should be established and non-valid combinations (open-open, closed-closed) should be sorted out

    Switching operations should be inhibited until bus image is recognized with 100% accuracy

    Optionally block 87B operation from Isolator Alarm

    Each isolator position signal decides: Whether or not the associated current is to be included in the

    differential calculations

    Whether or not the associated breaker is to be tripped

  • Isolator Typical Open/Closed Connections

  • 29 August 2012 53

    LBB PROTECTION

  • In EHV substations, reliability of fault detection is enhanced by providing duplicated protections (either main 1/main 2 or main and backup protection)

    The D.C. sources for protection are also duplicated for better redundancy, circuit breakers are provided with duplicated trip coils

    All these measures, improve the reliability of fault detection and isolation, however, the possibility of mechanical failures of the switchgear or interrupter flash over cannot be covered by these means

    A failure of the breaker therefore, result, in spite of correct operation of the protection and energisation of trip coils

    LBB Protection

    54

  • LBB Protection

    HasProtectionOperated?

    FaultCleared?

    Yes

    No

    Yes

    No

    NormalOperation

    StartBreakerFailure

    Protection

    Wait forFault

    Clearance

    ResetBreakerFailure

    Protection

    TripBack-up

    Breaker(s)

    TripMain

    Breaker(s)

    55

  • This situation can be corrected by providing local breaker backup (LBB) or breaker fail protection

    LLB protection comes into operation only if, the breaker fails to trip, following energisation of its trip coil, through the circuit trip relays

    The main component of LBB protection is a current check relay initiated by the circuit trip relays and a follower timer

    The current check relay, on initiation, checks the presence of the current in the faulted circuit and if it persists beyond a preset time, proceeds to trip all other circuits connected to the Bus bar to which the stuck breaker is connected, thereby, ensuring local isolation

    Tripping of remote breaker is also initiated through a separate carrier channel, in case of line breakers to arrest infeeds from remote end

    LBB Protection

    56

  • Phase A AC signals wired

    here, current status

    monitored here

    Phase B AC signals wired

    here, current status

    monitored here

    Phase C AC signals wired

    here, current status

    monitored here

    Breaker Fail Op command

    generated here and send to

    trip appropriate breakers

    Trip

    Trip Trip

    Example Architecture Breaker Failure Tripping Trip

  • Typical setting range for the current check relay and follower timer

    A more sensitive setting is generally adopted for Generator application in view of the fact, that a stuck breaker situation for certain abnormal conditions like motoring, may involve very low current infeeds

    LBB Protection

    Application Current

    Range

    check relay

    Recommended

    Setting

    Follower

    Range

    Timer

    Recommended

    Setting

    Generator Circuit 5-80% 5% 0.1-1sec 0.2 sec

    All other circuits (TFRs

    /Lines /Bus Coupler

    etc.)

    20-30% 20% 0.1-1sec 0.2 secs

    61

  • LBB Protection

    TIME- CHART Fault occurs

    Normal Clearing Time Current Detector

    Dropout Time Normal

    Clearing Protective

    Time

    ~30ms

    Breaker Interrupting

    Time

    ~60ms

  • THANK YOU

    29 August 2012 63