Caribbean Disaster Mitigation Project

Embed Size (px)

Citation preview

  • 8/2/2019 Caribbean Disaster Mitigation Project

    1/36

    Caribbean Disaster Mitigation ProjectImplemented by the Organization of American StatesUnit of Sustainable Development and Environment

    for the USAID Office of Foreign Disaster Assistance and the CaribbeanRegional Program

    Drawings to Accompany the BuildingGuidelines

    Section B: Concrete Construction

    Introduction|Section A| Section B|Section C|Section D| Section E|Section F |Section G

    Download AutoCAD DWG files (zip archive):Section A|Section B|Section C|Sections D-G

    Figure B-1: Permissible Arrangement of Strip Footings

    All exterior walls and interior load-bearing walls should be supported on reinforced concrete stripfootings. Interior walls may be supported by thickening the slab under the wall and suitably reinforcing it.

    The foundations should generally be located on a layer of soil or rock with good bearing characteristics.

    Such soils would include dense sands, marl, other granular materials and stiff clays.

    The foundation should be cast not less than 1 6" to 2 0" below ground, its thickness not less than 9" and

    its width not less than 24" or a minimum of three times the width of the wall immediately supported by

    it. Where clays must be used as the foundation bearing material, the width of the footing should be

    increased to a minimum of 2 6".

    http://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-b-1.gifhttp://www.oas.org/http://www.info.usaid.gov/http://www.oas.org/cdmp/document/codedraw/images/fig-b-1.gifhttp://www.oas.org/http://www.info.usaid.gov/http://www.oas.org/cdmp/document/codedraw/images/fig-b-1.gifhttp://www.oas.org/http://www.info.usaid.gov/http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htm
  • 8/2/2019 Caribbean Disaster Mitigation Project

    2/36

    Figure B-2: Typical Spread Footing Detail

    When separate reinforced concrete columns or concrete block columns are used they should be supported

    by square footings not less than 2-0" square and 12" thick. For columns footings, the minimum

    reinforcement should be " diameter bars at 6" centres in both directions forming a 6" mesh.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-2.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    3/36

    Figure B-3: Reinforcement of Strip Footings

    Reinforcement in the foundation is needed to ensure the continuity of the structure. This is particularly

    important in cases of bad ground or where the building may be subjected to earthquake forces. The

    reinforcement is assumed to be deformed high yield steel bars which are commonly supplied in theOECS. For strip footings, the minimum reinforcement should consist of 2 No. 4 (") bars placed

    longitudinally and " diameter bars placed transversely at 12" centres.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-3.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    4/36

    Figure B-4: Concrete Floor in Timber Construction

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-4.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    5/36

    Figure B-5: Concrete Strip Footing and Concrete Base with Timber Construction

    An acceptable arrangement for a foundation of a small timber building with a concrete or wood floor isshown in these figures. This construction is suitable in reasonably stiff soils or marl. Where the building

    will be on rock, the thickness of the footing may be reduced, but timber buildings are very light and can

    easily be blown off of their foundations. Therefore the building must be securely bolted to the concrete

    footing, and the footings must be heavy enough to prevent uplift.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-5.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    6/36

    Figure B-6: Typical Block Masonry Details

    Concrete blocks used in walls should be sound and free from cracks and their edges should be straight and

    true. The nominal width of blocks for exterior walls and load bearing interior walls should be a minimum

    of 6 inches and the face shell a minimum thickness of 1". It is better to construct exterior walls of 8" thickconcrete block. Non-load bearing partitions may be constructed using blocks with a nominal thickness of

    4" or 6". Blockwork walls should be reinforced both vertically and horizontally; this is to resist hurricane

    and earthquake loads. It is normal practice in most of the OECS to use concrete columns at all corners and

    intersections. Door and window jambs must be reinforced.

    The recommended minimum reinforcement for concrete block construction is as follows:

    i. 4-" diameter bars at corners vertically.ii. 2-" diameter bars at junctions vertically.

    iii. 2-" diameter bars at jambs of doors and windowsiv. for horizontal wall reinforcement use "Dur-o-waL (or similar) or " bars every other

    course as follows:

    4" blocks 1 bar

    6" blocks 2 bars

    8" blocks 2 bars

    v. For vertical wall reinforcement use " bars spaced as follows:

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-6.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    7/36

    4" blocks 32

    6" blocks 24

    8" blocks 16

    Figure B-7: Concrete Column Detail

    Columns should have minimum dimensions of 8" x 8" and may be formed by formwork on four sides or

    formwork on two sides with blockwork on the other two. The minimum column reinforcement should be4- diameter bars with " stirrups at 6" centres. A filled core column or poured concrete column should

    be placed full height to the belt course (ring beam) at each door jamb.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-7.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    8/36

    Figure B-8: Alternate Footing Arrangements for Block Masonry

    This reinforced concrete footing is constructed monolithically with the floor slab. It consists of a series of

    slab thickenings under the walls with a minimum 12"deep downstand on the perimeter. The footing is

    placed entirely on well compacted granular material.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-8.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    9/36

    Figure B-9: Floor Slab Detail

    The reinforced concrete floor slab is kept free of the perimeter walls. The mesh reinforcement in the slab

    is placed in the top with 1" covers. The slab is constructed on well compacted granular fill, crushed stone

    or marl.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-9.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    10/36

    Figure B-10: Alternative Floor Slab Detail

    The suspended reinforced concrete slab is tied into the external capping beam at floor level. The top

    (steel) reinforcement is important. The main reinforcement should be of the order of " diameter at 9"

    centres, and the distribution steel 3/8" diameter at 12" centres.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-10.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    11/36

    Figure B-11: Fixing Detail for Vernadah Rail to Column

    It is important that the rails be adequately fixed into the side column. At a minimum the bolts should be

    galvanised to prevent corrosion. Epoxy grout or chemical anchors are recommmended for fixing the

    baluster into the concrete column.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-11.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    12/36

    Figure B-12: Reinforcement Arrangement for Suspended Slabs

    The reinforcement should be bent and fixed by knowledgeable workmen. Care must be taken to maintain

    the top steel in the top with adequate cover.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-12.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    13/36

    Figure B-13: Reinforcement Arrangement for Suspended BeamsThe reinforcement should be bent and fixed by knowledgeable workmen. Care must be taken to maintainthe top steel in the top with adequate cover.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-13.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    14/36

    Figure B-14: Reinforcement Arrangement for Suspended Cantilever BeamsThe reinforcement should be bent and fixed by knowledgeable workmen. Care must be taken to maintain

    the top steel in the top with adequate cover.

    http://www.oas.org/cdmp/document/codedraw/images/fig-b-14.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    15/36

    Figure B-15: Reinforcement Arrangement for Suspended Stairs

    Drawings to Accompany the BuildingGuidelines

    Section C: Timber Construction

    Introduction|Section A|Section B| Section C |Section D| Section E|Section F |Section G

    Download AutoCAD DWG files (zip archive):Section A|Section B|Section C|Sections D-G

    http://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-b-15.gifhttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htm
  • 8/2/2019 Caribbean Disaster Mitigation Project

    16/36

    Figure C-1: Alternative Foundation for a Small Timber Building

    With timber construction the foundation must ensure that the building is adequately supported. For most

    timber buildings the foundation must be firmly anchored to the ground to prevent the building from being

    moved by high winds. This foundation alternative describes a timber post concreted into a hole in firmsoil. Greenheart or pressure treated timber must be used.

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-c-1.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    17/36

    Figure C-2: Fixing Detail for Timber Joist Bearing on a Concrete Beam

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-c-2.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    18/36

    Figure C-3: Fixing Detail for Timber Rafter to a Timber Header

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-c-3.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    19/36

    Figure C-4: Alternative Fixing Arrangements for Pillar Supports at Floors to Resist Uplift

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-c-4.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    20/36

    Drawings to Accompany the BuildingGuidelines

    Section D: Steel ConstructionIntroduction|Section A|Section B|Section C| Section D | Section E|Section F |Section G

    Download AutoCAD DWG files (zip archive):Section A|Section B|Section C|Sections D-G

    Figure D-1: Steel Column Pedestal and Footing

    Foundations for steel framed buildings generally consist of a reinforced concrete pad located at a

    suitable depth on a bearing stratum. The pad supports a stub column which has the column

    holding down bolts cast into it. The height of the stub column is such that the column base islocated at the desired elevation.

    Since steel framed buildings are comparatively light weight structures, the footing size isdetermined by the size of the adequate anchor required to prevent uplift due to wind. The size of

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-d-1.gifhttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htm
  • 8/2/2019 Caribbean Disaster Mitigation Project

    21/36

    footing should therefore be provided by the designer or supplier, and the horizontal restraint

    needed at the column bases must also be shown on the drawing.

    Because of this, it is not possible to provide specific design guidelines for the footing, since the

    size of the footing is dependent upon the forces which would be generated by the wind.

    Experienced engineers would be required to carry out a wind analysis, the result of which wouldpermit design of the footing to be undertaken.

    Drawings to Accompany the BuildingGuidelines

    Section E: Fire Prevention and Fire Safety

    Introduction|Section A|Section B|Section C|Section D| Section E |Section F |Section G

    Download AutoCAD DWG files (zip archive):Section A|Section B|Section C|Sections D-G

    http://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htm
  • 8/2/2019 Caribbean Disaster Mitigation Project

    22/36

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-e1a.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    23/36

    Figure E-1(a): Cover Details for Reinforced Concrete Members

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.zip
  • 8/2/2019 Caribbean Disaster Mitigation Project

    24/36

    http://www.oas.org/cdmp/document/codedraw/images/fig-e1b.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    25/36

    Figure E-1(b): Cover Details for Reinforcement Concrete Members

    Adequate concrete cover to reinforcement is required for both durability and fire resistance. The covers

    recommended should provide a fire resistance of about 4 hours.

    Drawings to Accompany the BuildingGuidelines

    Section F: Plumbing, Sanitation, Water Supply andGas Installations

    Introduction|Section A|Section B|Section C|Section D| Section E| Section F |Section G

    Download AutoCAD DWG files (zip archive):Section A|Section B|Section C|Sections D-G

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-f-1.gifhttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/sectiong.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htm
  • 8/2/2019 Caribbean Disaster Mitigation Project

    26/36

    Figure F-1: Schematic Drawing Showing Connection of Fixtures for a Single Storey

    Dwelling

    The general arrangement for connection of fixtures to a single stack is depicted. It is important

    that no soil or waste pipes discharge into bends attached to a water closet (WC) bowl. The pipes

    must be laid to adequate falls to the service manhole.

    Figure F-2: Detail of Manhole Construction

    Manholes are to be installed at every change of direction and gradient, spaced no more than 60

    feet apart. Manholes are constructed of reinforced concrete or blockwork and the drain where itpasses through the manhole shall be carried in an open benched channel. Manhole covers are

    typically of steel, cast iron or concrete and are to be airtight and fitted with lifting handles to

    facilitate removal.

    http://www.oas.org/cdmp/document/codedraw/images/fig-f-2.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    27/36

    Figure F-3: Conventional Privy

    Pit privies shall preferably be located on the leeward side of a building and shall be ventilated.Privies shall not be used in areas where the water table is within 2 feet of the surface since they

    will not function well. The precast concrete slab pit privy has been adopted by many health

    authorities.

    There shall be openings at the top of the walls to dissipate odours. For maximum odour control a

    vent pipe can be installed in the tank to carry odours away from the privy. The vent pipe shall beat least 6.0 inches (150 mm) in diameter, painted black, screened with a wire gauze and located

    on the sunny side of the latrine so that air inside the pipe will heat up and create an up-draft. The

    pipe shall extend a minimum of 2 feet above the roof of the privy.

    The door should open outwards to minimize the internal floor area.The toilet shall be sufficiently

    screened to discourage flies. The walls and roof shall be weatherproof, shall provide privacy,

    exclude vermin and be architecturally compatible in external appearance with the main house.

    http://www.oas.org/cdmp/document/codedraw/images/fig-f-3.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    28/36

    http://www.oas.org/cdmp/document/codedraw/images/fig-f-4.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    29/36

    Figure F-4: Details of Construction of Water Cistern

    In areas without a public water supply, a water storage cistern should be constructed for each

    house or dwelling, along with a rainwater collection system from the roof or other suitable

    catchment. The size of a typical storage tank or cistern is as shown.

    The water storage cistern can be located under one or more buildings of a dwelling group orconsist of a separate tank remotely located. The cistern shall be located uphill and as far as

    practical from any septic tank, privy, soakaway, or leaching tile field. The water storage cistern

    shall be preferably reinforced concrete and provided with access hatches to allow cleaning out

    and repairs.

    The cover of the water storage cistern shall be of a durable, non-rotting material. Wood or

    plywood is generally not satisfactory. The cover must be tightly fitting to prevent mosquitobreeding. Light should be excluded from the cistern water to prevent the growth of algae.

    Sufficient overflows must be provided to prevent flooding of dwellings. The overflows must be

    screened to prevent the entrance of mosquitoes, frogs, or other vermin.

    Figure F-5: Standard Septic Tank Details

    http://www.oas.org/cdmp/document/codedraw/images/fig-f-5.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    30/36

    The basic function of a septic tank is to receive domestic sewage, partially treat it, segregate the

    solids, and discharge the liquid to a tile field or soakaway. Anaerobic bacterial action breaksdown much of the solid matter into liquids and gases. While in an efficiently operating tank the

    liquid discharge is comparatively clear, tanks do not accomplish a high degree of bacteria

    removal and infectious agents including pathogenic organisms may be widespread in the effluent

    which is "septic". The primary purpose of the tank is to condition sewage. To provide formaximum solids removal, adequate tank capacity is necessary.

    Figure F-6: Alternative Arrangements of Sanitary Fixtures in a Bathroom

    Six different arrangements of small two- and three-fixture bathrooms are depicted. The

    dimensions shown are the minima for proper use of the spaces.

    http://www.oas.org/cdmp/document/codedraw/images/fig-f-6.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    31/36

    Figure F-7: Typical Plumbing Layout for a Small House

    All plumbing shall be installed in a workmanlike manner. The water supply pipes should be

    provided with a properly protected and easily accessible stop cock or gate valve near to the

    boundary. The fixtures should be of smooth, hard, durable, impervious and corrosion-resistant

    http://www.oas.org/cdmp/document/codedraw/images/fig-f-7.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    32/36

    materials, free from flaws and blemishes. All fixtures connected to foul drawings shall be

    trapped as close to the fixture as possible. The water closets shall have a vent pipe of not lessthan 1 inches in diameter. A drain laid under a floor on fill, must be laid in a straight line for its

    entire length beneath the building, and should not exceed 40 feet in length.

    Figure F-8(a): Soak-Aways in Areas with a High Water Table

    http://www.oas.org/cdmp/document/codedraw/images/fig-f8a.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    33/36

    Figure F-8(b): Soak-Aways in Areas with a Low Water Table

    Soakaways shall be used as alternatives to shallow absorption fields where sub-surfaceconditions are feasible. They shall never be used where there is likelihood of contaminating

    underground water supplies, such as areas with fresh water wells. The most suitable disposal

    http://www.oas.org/cdmp/document/codedraw/images/fig-f8b.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    34/36

    system is dependant on the percolation rate and this is generally determined by the Public Health

    Authority.

    In the construction of soakaways, proper precautions shall be taken to prevent the side walls

    from collapsing while workmen are in the hole.The soakaway pit is to be lined with stones,

    bricks, or concrete blocks laid up dry with open joints backed up with at least 3" of gravel. Thebottom of the pit is to be filled with coarse gravel (pea rock), to depth of at least two feet. The

    cover is to be made of reinforced concrete or steel. Where two soakaways are to be constructedthey shall be located not less than three times the largest of the surface dimensions apart.

    Soakaways may be used in all areas for the disposal of excess rainwater or run-off from

    buildings that is not of a septic nature.

    Drawings to Accompany the BuildingGuidelines

    Section G: Electrical Guidelines

    Introduction|Section A|Section B|Section C|Section D| Section E|Section F | Section G

    Download AutoCAD DWG files (zip archive):Section A|Section B|Section C|Sections D-G

    http://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionc.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectionb.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/sectiona.ziphttp://www.oas.org/cdmp/document/codedraw/sectionf.htmhttp://www.oas.org/cdmp/document/codedraw/sectione.htmhttp://www.oas.org/cdmp/document/codedraw/sectiond.htmhttp://www.oas.org/cdmp/document/codedraw/sectionc.htmhttp://www.oas.org/cdmp/document/codedraw/sectionb.htmhttp://www.oas.org/cdmp/document/codedraw/sectna1.htmhttp://www.oas.org/cdmp/document/codedraw/intro.htm
  • 8/2/2019 Caribbean Disaster Mitigation Project

    35/36

    Figure G-1: Typical Electrical Plan for a Small House

    Electrical installations, including the service capacity of the installation, and the number and

    distribution of circuits shall meet the requirements of the relevant Electricity Regulations. Thissketch covers single-phase electrical services for residential construction under 2000sq.ft.

    All electrical services shall be installed by an experienced electrician in accordance with theElectricity Regulations governing the installation of electrical service, and in accordance with the

    relevant Electrical Code. Only experienced and/or licensed electricians should install electrical

    systems.

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-g-1.gif
  • 8/2/2019 Caribbean Disaster Mitigation Project

    36/36

    Figure G-2: Typical Sections of Wall Showing Locations of Fixtures

    http://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/autocad/secd_g.ziphttp://www.oas.org/cdmp/document/codedraw/images/fig-g-2.gif