BM On-Line Condensive Bushing PowerFactor and Capacitance MonitorsCondensive bushings are accessories applied on high and extra-high voltage equipment, such
as power transformers, shunt reactors and high voltage circuit breakers. In general, despite the
equipments individual cost being relatively low as compared to the overall cost of the equipment to
which it is attached, a failure in the bushings insulation can bring about severe damage to the
equipment.Capacitance and dissipation factor (tangent delta) are important factors in the early detection
of deterioration of the insulation in bushings, current transformers and other apparatus. The Treetechs
Bushing Monitor BM allows these parameters to be monitored on-line during regular operation. This
condition based assessment technique allows potentially catastrophic failures to be avoided, bydetecting problems while still in the incipient phase.
Main Features
Autonomous monitoring system, to be installed on the body of the equipment (transformer, reactor,etc.). Does not require installation of computers and/or special software for operation;
Operating temperatures -40...+85C;
Universal voltage input, 38 to 265Vdc/Vac; Spare bushings pre-programmed for operation in case of single-phase transformer banks;
Modular system: configurable for monitoring of 3, 6 or 9 bushings;
Protection against bushing tap opening, with activation indicated by an alarm;
Inputs for 2 Pt100 0C temperature sensors, allowing recording and correlation of insulation variation with changes in ambienttemperature, oil temperature or others;
Local indication on displays: current values for capacitance (C1), tangent Delta (C1), evolution trends for capacitance and tangent
delta, forecasted time to reach alarm levels, phase-to-ground and phase-to-phase voltages, leakage currents and temperatures;
8 output contacts, 1fixed (NC) for autodiagnostic and 7 configurable (5 NO and 2 NC) for alarms by absolute values, high evolutiontrends or low leakage curents. Operation mode programmable NO or NC;
2 programmable analog outputs for remote readings of capacitances and tangent delta. Configurable output range: 0...1mA,0...5mA, 0...10mA, 0...20mA or 4...20mA;
Internal clock and non volatile memory for storage of history of capacitance and tangent delta data and alarm events;
Serial communication port selectable RS485 or RS232 with Modbus RTU and DNP3.0 protocols;
Communication via fiber optic cable, using external electrical-optical converter;
Simplified programing divided into basic settings (sufficient for most applications) and advanced parameters.User password protected programming menu.
CA-008 2006/07/20 Rev. 201 Sistemas Digitais
Bushing Monitor- BM
7/28/2019 Catalog_BM_E_2006.07.20_rev2
2/10
BMThe constructive structure of condensive bushings gives rise to the appearance of a capacitance between the bushings central conductor and
ground, as shown in figure 1. Once the bushing has been energized, this capacitance allows the passage of a leakage current to ground,
90 ahead of the voltage as shown in figure 2. In this same figure, we can see that, due to losses in the dielectric, this leakage current also
has a resistive component, in phase with the voltage.
Operating Principle
Therefore, any change in these two parameters of the insulation of the bushing (capacitance and tan d) causes a corresponding
change in the leakage current (capacitive and resistive components, respectively).
The Bushing Monitor BM operates by continually measuring the leakage currents of the three bushings in a three-phase set, through
adapters connected to the test taps or bushing voltage taps. Processing the readings of the leakage currents allows the variationsoccurring in capacitance and tangent delta to be charted, which associated to programming of initial values for these variables
allows on-line indication of their current values. Initial values can be obtained from factory tests for new bushings or from off-line
tests performed at BMs installation.
One of the techniques employed in processing the readings is using the sum of leakage currents. This technique is based on the fact
that any change in one of the leakage currents is mirrored equally in the sum of the 3 currents, as shown in figure 3. This allows
detection of even small changes in the value of tangent delta, since the resistive portion of the leakage current, which is associated
to the insulation's tangent delta, has a very small participation in the overall leakage current. This way, variations that might not be
detected directly in the leakage current are detectable in the sum of currents. Variations detected are always imputed to only one of
the bushings in the three-phase set, chosen according to the angle of the sum current Change Vector .
Figure 3 - Leakage currents of three bushings in a three-phase system and their sum;(a) For a given initial condition;(b) With change in phase A bushing's capacitance and dissipation factor
02 Sistemas Digitais
CONDUCTING LAYERSFOR EQUALIZING
ELECTRICAL FIELD
OIL IMPREGNATEDPAPER INSULATION
LAYERS
Figure 1 - Constructive structure ofCondensive bushing
C1
Ifuga
Vf
Figure 2 Equivalent circuit of anenergized condensive bushing
(a)
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
(b)
7/28/2019 Catalog_BM_E_2006.07.20_rev2
3/10
BM Topology of theBM SystemThe BM bushing monitoring system has a modular conception, and is composed of three basic parts (see figure 4):
Adapter for test tap or voltage tap provides the electric connection to the tap of the bushing, also ensuring its mechanical rigidity and
weatherproofing seal. It incorporates protection against overvoltages and overcurrents due to transient phenomena and also against accidental
opening of the measuring circuit, preventing the tap from remaining open. This protection can provide a low impedance path for the leakage current
for unlimited time. In case of operation the Measurement Module closes its autodiagnostic contact and the Interface Module provides visual alarm
besides closing the user programmed contacts.
Measuring Module BM-MM receives the leakage currents from the three bushings in a three-phase set, carries out measuring of these currents and
a first level of mathematical and statistical processing of the information, making this data available to the Interface Module (BM-HMI) through a
serial communication port RS485;
Interface Module BM-HMI receives information from one, two or three measuring modules (BM-MM) and carries out their mathematical and
statistical processing, making the results available as the current values for capacitance and tangent delta for each bushing displaying these on the
front panel displays.
Figure 4 Component parts of the Bushing Monitoring System BM;
(a) Tap Adapter; (b) Measuring Module BM-MM; (c) Interface Module BM-HMI
Figure 5 displays the connections between the different parts for a three-phase transformer monitoring 3 bushing sets. Figure 6
shows an example for banks of single-phase transformers
Sistemas Digitais
Figure 5 Connections between the parts comprising the Bushing Monitoring System BM
(A) (B) (C)
TRANSFORMER
CONTROL CABINET
MEASUREMENTMODULE 1
INTERFACEMODULE
DRY CONTACTSANALOG OUTPUTS mA
SERIAL PORTS
RS485
PRIMARY SECONDARY
TERTIRY
RS485
MEASUREMENTMODULE 2
MEASUREMENTMODULE 3
TAP
ADAPTERS
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
7/28/2019 Catalog_BM_E_2006.07.20_rev2
4/10
BM
Sistemas Digitais04
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
Figure 6 Example of Bushing Monitoring System BM for banks of single-phase transformers
PHASEA
B
ANK1
CENTRALIZING
CABINETBANK
1
MEASUREMENT
MODULE
1
INTERFACE
MODULE
DRYCONTACTS
ANALOG
OUTPUTSm
A
SERIALPORTS
RS485
HV
LV
PHASEB
PHASEC
HV
LV
H
V
LV
MEASUREMENT
MODULE2
PHASEA
BANK2
CENTRALIZ
ING
CABINETBA
NK2
MEASUREMENT
MODULE
1
INTERFACE
MODULE
DRY
CONTACTS
AN
ALOG
OUTPUTSmA
SERIALPORTS
RS485
HV
LV
PHASEB
PHASEC
HV
LV
HV
LV
MEASUREME
NT
MODULE2
PHASEA
CENT
RALIZING
CABINET
RE
ACTORSBANK
MEASUREMENT
MODULE3
RS485
HV
PHASEB
PHASEC
HV
HV
REACTO
R
BANK
SPARE
TR
ANSFORMER
SIGNALSFROM
BUSHINGSOFSPARE
XFMR
BROUGHTTO
SHORTING-TYPE
TERMINALBLOCKS
ATINDIVIDUAL
CONTROLCABINET.
IN
CASEOFSPARE
UNITBEING
PUTIN
SERVICE,THESE
SIGNALSMUSTBE
CONNECTED
TO
THE
CORRESPONDING
M
EASURING
MODULE
IN
PLACEOFTHE
UNITTAKEN
OUTOF
SERVICE.
HI S
U S HING
T
B
EXC HANG EO PER
TA
IO N
M
U
T
E
FO RME
I
S
B
IN
D
N
T
C O R
S PO ND
G
HE
RE
IN
M
EN
INT
RFAC E
U
O F
E
7/28/2019 Catalog_BM_E_2006.07.20_rev2
5/10
BM
Interface Module BM-HMIInput Voltage:Maximum Consumption:Operating Temperature:Protection Level:Fixation:Wire size - removable connectors:Temperatue measurement:
Input:Measurement range:Maximum error @ 20CDeviation by temperature variation:Connection options:
Output relays:
Type and functions (standard):Maximum switching power:Maximum switching voltage:Maximum conduction current:
Analog outputs:Variable:Output range:Maximum error:Maximum load
Serial Communication Ports:Communication Protocols:
Measurement Module BM-MMInput Voltage:Maximum Consumption:Operating Temperature:Protection Level:Fixation:Wire size:AC current measurement inputs:Monitored quantities:
Capacitance:Tangent Delta:
Output relay:
Mass MemoryRecording interval:Capacity:
38 to 265 Vac/Vdc 50/60Hz
7/28/2019 Catalog_BM_E_2006.07.20_rev2
6/10
BM Connection Diagram
06 Sistemas Digitais
Application example monitoring 3 sets of bushings on a three-phase transformer
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
W
7/28/2019 Catalog_BM_E_2006.07.20_rev2
7/10
BM Dimensions
07 Sistemas Digitais
Interface Module BM-HMI
Measurement Module BM-MM
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
7/28/2019 Catalog_BM_E_2006.07.20_rev2
8/10
BM
Surge Immunity (IEC 60255-22-5):phase-neutral surges:phase-ground and neutral-ground surges:
Electrical transients Immunity (IEC 60255-22-1) and (IEEE C37.90.1):1st cycle peakFrequency:time and repetition rate:decay to 50%:
Voltage Impulse (IEC 60255-5):
Wave form:Amplitude and energy:Number of pulses:
Insulation Voltage (IEC 60255-5):Industrial frequency insulation voltage
Irradiated electromagnetic field Immunity (IEC 61000-4-3/IEC60255-22-3):Frequency:Field intensity:
Conduced electromagnetic perturbations immunity (IEC60255-22-6):
Frequency:Field intensity:
Electrostatic Discharge immunity (IEC 60255-22-2) and (IEEEC37.90.3):Air mode:Contact mode:
Fast electrical transient immunity (IEC60255-22-4) and (IEEEC37.90.1):Power supply, inputs and outputs:Serial communication port:
Climatic test: (IEC 60068-2-14):Temperature range:Total test time:
Vibration response: (IEC 60255-21-1):Application mode:Amplitude:Intensity:Duration:
Vibration resistance: (IEC 60255-21-1):Application mode:FrequencyIntensity:Duration:
Type Tests
08 Sistemas Digitais
1 kV, 5 per polarity (+/-)2 kV, 5 per polarity (+/-)
2.5 kV1.1 MHz2 seconds, 400 surges/sec.5 cycles
1,2 / 50 ms5kV3 negative e 3 positive, 5s interval
2 kV 60Hz 1 min. to ground
26 to 2000 MHz10 V/m
0.15 to 80 MHz10 V/m
8 kV, ten discharges per polarity6 kV, ten discharges per polarity
4 kV - 2,5kV2 kV - 5,0kV
-40 to +85C120 hours
3 axis (X, Y e Z), sinusoidal0,075mm from 10 to 58 Hz1G from 58 to 150 Hz8 min/axis
3 axis (X, Y e Z), sinusoidal10 to 150 Hz2G160 min/axis
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
7/28/2019 Catalog_BM_E_2006.07.20_rev2
9/10
BM
09 Sistemas Digitais
Order specification
The Bushing Monitor BM is a universal device. Its features are selected by using the programming menus. These adjustments
can be made directly on the device's front panel or by way of the serial communication ports RS232 or RS485. The power feed
input is universal.
Therefore, in purchase orders for the equipment only the following need to be informed:
Quantity of Measurement Modules BM-HMI (with each BM-HMI receiving signals from 3 bushings on a three-phase set);
Quantity of Interface Modules BM-HMI (with one BM-HMI being able to connect to 1, 2 or 3 BM-MM modules).
Number of Adapters for bushing taps and the respective manufacturers, models of bushings to monitor and type of tap
(voltage or test tap).
Example of order specification :
For one transformer (or bank of transformers) where is necessary to monitor three 500kV and three 230kV bushings
the order specification could be:
- 2 Measurement Modules BM-MM- 1 Interface Module BM-HMI
- 3 Tap adapters for bushings ABB brand, type GOE with voltage tap
- 3 Tap adapters for bushings Trench brand, type COTA with test tap
CA-008 2006/07/20 Rev. 2Bushing Monitor- BM
Specification subject to change without notice
7/28/2019 Catalog_BM_E_2006.07.20_rev2
10/10
BM
Sistemas Digitais
10 Sistemas Digitais
BrazilTreetech Sistemas Digitais Ltda.
Praa Claudino Alves, 141 - CentroCEP 12940-040 - Atibaia - SP
Fone: +55 11 4413 5787E-mail: [email protected]
www.treetech.com.br
United StatesTechnical Sales - NorthwestP.O. Box: 230427 - Portland
Phone: 503 345 9710E-mail: [email protected]
www.treetechusa.com
MexicoMonitoreo e Control de Transformadores S.A. de C.V.
Calle Sur 4, 9 - Zona IndustrialCP 43805 - Tizayuca - Hydalgo
Tel.: +52 55 5300 8733
E-mail: [email protected]
PakistanShaukat Associates
306 Gul Plaza - Civic CentreNew Garden Town - Lahore
Tel.: 042 5860662 Fax: 042 586 6649E-mail: [email protected]
ParaguayEMQUIMICA
Av. General Santos, 785 - Las MercedesP.O. Box 901 - Asuncin
Tel.: 595 21 214 814E-mail: [email protected]
PeruLogytec - Instrumentos Electro-ElectrnicosIsidoro Surez, 219 - San Miguel - LimaTel.: 511 452 3111 Fax: 511 464 4889
e-mail:[email protected]
Russia, Ukraine and other countries of CEI(Newly Independent States)
Tridex Ltd.13 Minskaya St., Zaporozhye 69015
Ukraine
Tel./Fax: +38 (0612) 13-91-05+38 (0612) 12-65-01
e-mail: [email protected]