Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 1
F
Installation rules
INSTALLATION
Wire the products and connect the optional modules
Sepam Installation EN 2007_01.ppt2
? Sepam series 20 & 40
ACE949-2ACE959ACE937ACE969TPACE969FOcommunicationmodules
MES148-2temperature sensor modules
MSA141analog output module
MES114optional input/output modules
DSM303remote UMI
Sepam Installation EN 2007_01.ppt3
? Sepam series 80
ACE949-2ACE959ACE937ACE969TPACE969FOcommunicationmodules
MES148-2temperature sensor modules
MCS025synchro-checkmodule
MSA141analog outputmodule
MES120 optional input/output modules
DSM303remote UMI
Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 4
F
Installation rules
MOUNTING
Mounting
Sepam Installation EN 2007_01.ppt5
Before use : storage conditions
Sepam must be stored in good condition to avoid any life time reduction :
– In it’s factory package
– In dry and clean place
– Temperature does not have to exceed -25°C/-13°F and +70°C/+158°F
– Exposure to continuous damp heat : 93%RH +40°C +104°F does not have to exceed 56 days
– If storage must be longer than a year, Sepam should be energized for one or two days every year
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt6
Summary of characteristics of the base unit
Flush-mounting in front panel– Thickness of plate:
– 1.5 to 3 mm for Series 20 and 40– 1.5 to 6 mm for Series 80
Assembly at back of compartment– Mounting plate:
– AMT840 for Series 20 and 40– AMT880 for Series 80
Sealing gasket according to NEMA12 / IP52 requirements
Weight– Sepam with advanced UMI and 1 input / output module:
– 1.7 kg for Series 20– 1.9 kg for Series 40– 2.9 kg for Series 80
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt7
Series 20 & 40 base unit
Simple flush mounting in panel– Held by 2 mounting clips
Groove
Mounting clip
Series 20Series 40
Sepam Installation EN 2007_01.ppt8
Series 80 base unit
Mounted using spring clips The direction in which the spring clips are mounted depends on the thickness of the mounting plate.
1.5 mm ≤ thk. ≤ 4 mm
4 mm ≤ thk. ≤ 6 mm
Series 80
Sepam Installation EN 2007_01.ppt9
MES114 module
Installation of the module– insert the 2 pins on the module into the slots on the base unit– push the module flat up against the base unit to plug it into the connector– tighten the mounting screwsSeries 20
Series 40
Sepam Installation EN 2007_01.ppt10
MES120 module
Installation of the module– insert the 2 pins on the module into the slots on the base unit– push the module flat up against the base unit to plug it into the connector– tighten the mounting screwsSeries 80
Sepam Installation EN 2007_01.ppt11
Remote modules
DSM303 and MCS025– Same mounting principle as Series 20 and 40
MET148-2, MSA141, all communication modules– Mounting on symmetrical DIN rail
Series 20Series 40Series 80
Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 12
F
Installation rules
INSTALLATION RULES
Installation rules
Sepam Installation EN 2007_01.ppt13
Generic rules : earthing
Refer to document :
“MV protection relay installation assistance guide” ref 51312779F0 A2
Guarantee an equipotent bonding network
Connect every equipment to earth
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt14
Generic rules : disturbing and sensitive cables
Disturbing cables are :– Power circuit in general, Welding machine power supply in particular– PEN and PE conductors– Control circuit including inductive loads : relays, contactors,…
sensitive cables are :– Communication circuits– Analogue measurement circuits : unbalance CT input, Temp sensors
Avoid the parallel running of disturbing and sensitive cables
Or assure separation distance between disturbing and sensitive cables
Disturbing and sensitive cables must cross at right angle
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt15
Generic rules : ground loop
Minimize ground loop areas : cables must be as close as possible from earthed metallic part
A ground loop results from the area between an active conductor and the ground.
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt16
Generic rules : I/O
Outgoing and incoming I/O cables must be together
Shielded cables are grounded at both ends
(only if both sides are equipotent by an other way !!!) Free conductors in cables must be earthed at both ends Unused input must be shorted to earth
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt17
Cubicle prerequisite
Switchgear must be connected to building earth
Every metallic parts of cubicle, including doors, must be connected together and to earth by wide conductor on non paint parts
Series 20Series 40Series 80
CTs and VTs secondary common point should be connected to main earth terminal (rectangular copper bare) of cubicle in MV compartment
LV compartment should also have a main earth terminal directly connected to the LV compartment one and on witch each equipment should be connected
Sepam Installation EN 2007_01.ppt18
Power supply requirements
Nominal range : 24 / 250 VDC or 110 / 250 VAC (47.5 / 63 Hz) Absolute range ( -20 / +10% ) : 19.2 / 275 VDC or 88 / 275 VAC
Series 80 accept only DC voltage supply Nominal range : 24 / 250 VDC Absolute range ( -20 / +10% ) : 19.2 / 275 VDC
Focus on DC supply :– Rectified only should not be used because it will reduce lifetime – Acceptable ripple content on DC voltage : 12%
Series 20Series 40
Series 80
Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 19
F
Installation rules
CONNECTION OF SEPAM
Connection of Sepam
Sepam Installation EN 2007_01.ppt20
Wiring requirements and accessories
Power supply and I/O : 2 different types of connector :
CCA620 : screw type CCA622 : ring / spade lugs Ø4mm
Telemecanique ZD5 series
For both type, wires are single 0.2 to 2.5mm² / AWG 24 to 12or maximum 2 wires 0.2 to 1 mm² / AWG 24 to 16
1mm² will be preferred for I/0 when used I/O number is high and if this size is correct for the application
Sepam Installation EN 2007_01.ppt21
Series 20 & 40 base unit
A 21-pin connector– auxiliary power supply
– mechanical grounding A
C D
Series 20Series 40
C RJ45 connector– Modbus communication ports
D RJ45 connector– connection of remote modules
Connecting terminal 17 to earth by 2.5 mm² cable, length < 200 mm is COMPULSORY
Sepam Installation EN 2007_01.ppt22
S20, T20 & M20 current sensors
Series 20
B
A
A 21-pin connector– 1 residual current input
B SubD9 connector– CCA630 connection of CTs– CCA670 connection of LPCTs
Sepam Installation EN 2007_01.ppt23
B21 & B22 voltage sensors
B SubD9 connector– CCT640 connection of VTs
B
Series 20
Sepam Installation EN 2007_01.ppt24
Series 40 current and voltage sensors
A 21-pin connector– 1 residual current input
B SubD9 connector– CCA630 connection of CTs
– CCA670 connection of LPCTs
E 6-pin connector– connection of VTs
B
A
ESeries 40
Sepam Installation EN 2007_01.ppt25
Series 80 base unit
Series 80
A 21-pin connector– auxiliary power supply
C1 and C2
RJ45 connector– Modbus ports
D1 and D2
RJ45 connector– connection of remote
modules
F spare
A
C2 C1 F
D2
D1
B2 B1
H3 H2 H1
Connection to the grounding circuit is compulsory by 9 mm² tinned copper braid,length < 300 mm
Sepam Installation EN 2007_01.ppt26
Current and voltage sensors for Series 80 - all applications
Series 80 E
B1
E 21-pin connector– connection of VTs– 2 residual current inputs
B1 SubD9 connector– CCA630 connection for CTs – CCA671 connection of LPCTs
Sepam Installation EN 2007_01.ppt27
Additional current sensors forT87, M87, M88, G87 & G88
Series 80
B2 B2 SubD9 connector– CCA630 connection for
CTs – M87 and G87
CCA671 connection of LPCTs
Sepam Installation EN 2007_01.ppt28
Additional voltage sensorsB83
Series 80
B2 B1B2 SubD9 connector
– CCT640 connection of V'Ts
Sepam Installation EN 2007_01.ppt29
Current sensor inputs
CCA630/CCA634 connector
The CCA630 connector is used to connect 3 phase current transformers to Sepam
The CCA634 adds an input for a residual current transformer : do not connect a core balance ct
With CCA634 Io input on A or E connector must not be used.
Both contain interposing ring CTs with through primaries and be disconnected with the power on since disconnection does not open the CT secondary circuit.
Series 20Series 40Series 80
CT 1 or 5A
Sepam Installation EN 2007_01.ppt30
Phase current inputs : 3 CTs / 2 CTs
CCA630/634 connector– connection of 2 or 3 CTs
– complete parameter setting using SFT2841 software
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt31
Phase current inputs : CTs wiring
Series 20Series 40Series 80
Power consumption in cables :
CT must feed all connected equipments : SEPAM, ammeter,…, and cables !!
Pwire = I² x ρ x L / S ρ = 1,728 10-8 at 20C° L = wire length, go and back, in meter
e.g. : CT secondary : 5A S = 1.5mm² L=30m P = 8.6 VA
CT secondary : 5A S = 4mm² L=30m P = 2.2 VA
Sepam Installation EN 2007_01.ppt32
Phase current inputs : LPCTs
CCA670 or CCA671 connector– connection of 3 LPCTs
(Low Power Current Transducers)– parameter setting using SFT2841
software, completed by hardware setting of microswitches
Sepam Installation EN 2007_01.ppt33
Residual current inputs : CSH 30/120/200
Series 20Series 40Series 80
CSH120 or CSH200 core balance CT– ratio of 1/470
CT + CSH30– connection of CT with secondary
– 1A: 2 turns– 5A: 4 turns
– Or direct on CCA634
Sepam Installation EN 2007_01.ppt34
Residual current inputs : recommendations
Series 20Series 40Series 80
Cabling recommendations The CSH120 or CSH200 core-balance CT is connected directly to the Sepam
connector. Recommended cables:
A twisted two-wire connection is recommended.
Shielded cable may also be used
The maximum resistance of the Sepam connection wiring should not be more than 4 Ω.
CSH 30 must be placed in a low magnetic activity area in LV compartment : e.g. away from auxiliary transformer
Sepam Installation EN 2007_01.ppt35
Residual current inputs : recommendations
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt36
Residual current inputs : core adaptation
Series 20Series 40Series 80
ACE990 interface– use of a core balance CT with a ratio of 1/50 to 1/1500– Only one core by ACE990
Sepam Installation EN 2007_01.ppt37
Series 40 voltage inputs
3 phase-to-neutral voltages
OR
2 phase-to-phase voltages
OR
1 phase-to-phase voltage
1 residual voltage
(open delta arrangement)
possibility of using VTs with double
secondary winding
AND/ORexcept for3 phase-to-neutral voltages
The E connector may be used to connect the following
Series 40
Sepam Installation EN 2007_01.ppt38
Additional voltage inputs for B21, B22 & B83
3 phase-to-neutral voltages
OR
2 phase-to-phase voltages
OR
1 phase-to-phase voltage
1 residual voltage
(open delta arrangement)AND/OR
The CCT640 may be used to connect the following:
Series 20Series 80
Sepam Installation EN 2007_01.ppt39
Series 80 voltage inputsfor all applications except for B80
3 phase-to-neutral voltages
OR
2 phase-to-phase voltages
OR
1 phase-to-neutral voltage
OR
1 phase-to-phase voltage
1 residual voltage
open delta arrangement
or
neutral point
AND/OR
The E connector may be used to connect the following
Series 80
Sepam Installation EN 2007_01.ppt40
B80 voltage inputs
3 BB1 phase-to-neutral voltages and an additional BB2 voltage
OR
2 BB1 phase-to-phase voltages and a residual voltage and an additional BB2 voltage
The E connector may be used to connect the following
BB1 BB2
Series 80
Sepam Installation EN 2007_01.ppt41
VT wiring variants
Series 20Series 40Series 80
VT wiring 3V + Vres 3 V U21 + U21 + 1 U + 1 U 1 V 1 V +Vres
U23 + U23Values Vres
Ph-to-neutral voltages measured measured calculated not avail. not avail. not avail. V1 V1
Ph-to-ph voltages calculated calculated U21, U23 U21, U23 U21 U21 not avail. not avail. measured measured measured measured
U32, U13 U32, U13 U32, U13 U32, U13 calculated calculated not avail. not avail.
Residual voltage measured calculated measured not avail. measured not avail. not avail. measured
Pos. seq. voltage calculated calculated calculated calculated not avail. not avail. not avail. not avail.
Neg. seq. voltage calculated calculated calculated calculated not avail. not avail. not avail. not avail.
Protection functions 67N, 59Nnot available
67, 32P, 32Q, 37P, 40, 78PS, 51V, 21B, 27D, 47, 81R
67, 67N, 32P, 32Q, 37P, 40, 78PS, 51V, 21B, 27D, 59N, 47, 81R
67, 67N, 32P, 32Q, 37P, 40, 78PS, 51V, 21B, 27D, 59N, 47, 81R
67, 32P, 32Q, 37P, 40, 78PS, 51V, 21B, 27D, 47, 81R
Sepam Installation EN 2007_01.ppt42
Series 20 & 40 inputs / outputs
Series 20Series 40
On the base unitA On the base unit
– 4 outputs– O1 and O2: control (8A)– O3 and O4: indication (2A)
A
On Series 40, from Mars 2006 O1,O2 and O3 have control capabilities
Sepam Installation EN 2007_01.ppt43
Series 20 & 40 inputs / outputs
Series 20Series 40
On the optional moduleK 10-pin connector
– 6 inputs– I21: independent– I22 to I26: common point
L 12-pin connector– 4 outputs
– O11: control (8A)– O12 to O14: indication (2A)
M 12-pin connector– 4 independent inputs
K
L
M
Sepam Installation EN 2007_01.ppt44
Series 20 & 40 inputs / outputs
Series 20Series 40
Sepam Installation EN 2007_01.ppt45
Series 80 inputs / outputs
Series 80
H3 H2 H1
On the base unit
A 21-pin connector– 5 outputs
– O1 to O4: control (8A)– O5: indication (2A)
On the optional modules– 14 inputs, 6 outputs
– Ox01: control (8A)– Ox02 and Ox06: indication
(2A)
H1 : I101 to I114, O101 to O106
H2 : I201 to I214, O201 to O206
H3 : I301 to I314, O301 to O306
Maximum configuration– 42 inputs (3 x 14)– 23 outputs (3 x 6 + 5)
B2 B1
AH1H2H3
Sepam Installation EN 2007_01.ppt46
Series 80 inputs / outputs
Series 80
Sepam Installation EN 2007_01.ppt47
Circuit breaker shunt trip coil
01 : trippingNormally open
O11 : closeorder
02 : Closinginhibition
Tripping coilClosing coil
Sepam Installation EN 2007_01.ppt48
Circuit breaker with under voltage opening coil
Voltage lossTripping coil
01 : trippingNormally closed
O11 : closeorder
02 : Closinginhibition
Closing coil
Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 49
F
Installation rules
Connection of remote modules
Connection of remote modules
Sepam Installation EN 2007_01.ppt50
MET 148-2 module : wiring
Connection of temperature sensors to screw-type terminals– Cross-section of 0.2 to 2.5 mm²
– Maximum distance: 1 km
– Use shielded cable– Connect the shielding at the module end– Do not connect the shielding at the sensor end
Series 20Series 40Series 80
Compulsory connection of the earthing terminal–2.5 mm² cable with 4 mm ring lug–Length < 200 mm
Separate the sensors cables ( very sensitive cables) from CCA77X cord
Sepam Installation EN 2007_01.ppt51
Line impedance matching (interlinking of modules)–RC: if the module is not the last one–RC: if the module is the last one
MET 148-2 module : settings
Series 20Series 40Series 80
Selection of the module number–MET1: 1st module–MET2: 2nd module (Series 40 and 80 only)
Sepam Installation EN 2007_01.ppt52
MSA 141 module : wiring
Connection of the analog output to screw-type connector– Cross-section of 0.2 to 2.5 mm²– Maximum load impedance: 600Ω– Use shielded cable
– Connect the shielding at the module end only
Series 20Series 40Series 80
Separate the sensors cables ( very sensitive cables) from CCA77X cord
Compulsory connection of the earthing terminal–2.5 mm² cable with 4 mm ring lug–Length < 200 mm
Sepam Installation EN 2007_01.ppt53
MSA 141 module : settings
Line impedance matching (interlinking of modules)– RC: if the module is not the last one– RC: if the module is the last one
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt54
Synchro-check module
A 21-pin connector– auxliary power supply
– 4 standard outputs– O1 to O3: enable closing– O4: not used
– mechanical grounding
Compulsory connection by
2.5 mm² cable, length < 200 mm
B CCT640 connector– phase-to-neutral or phase-to-phase
voltages to be monitored
D RJ45 connector– connection to the base unit
– Use the special CCA785 cord delivered with the module
A
X D
B
X RJ45 connector– not used
Series 80
Sepam Installation EN 2007_01.ppt55
Synchro-check module
Wiring diagram
Series 80
Sepam Installation EN 2007_01.ppt56
Series 20Series 40
DSM303
Interlinking of modules with Series 20 & 40
Principle– D on Sepam Da on
module
– Dd on module Da on following module
Rules– 3 modules maximum
– DSM303 modules at end of chain
– The MSA141 module must be the first in the chain
MET148-2
Da Dd
MSA141
DdDa
D
MET148-2
Da Dd
MET1 MET2
RC RC
Series 40 only
Sepam Installation EN 2007_01.ppt57
MET148-2
MSA141DSM303
Interlinking of modules with Series 80
Principle– D1 (or D2) on Sepam
Da on module– Dd on module Da on
following module
Rules– 3 modules maximum per
chain– DSM303 and MCS025
modules at end of chain– Special CCA785 cord for
connection of MCS025
MET1 MET2
MET148-2
Da
D1
Dd
Da Dd
RC RC
Da
D2
Dd D
CCA785
Series 80
Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 58
F
Installation rules
Connection of communication accessories
Connection of communication accessories
Sepam Installation EN 2007_01.ppt59
Anticipate electromagnetic compatibility problems
Connect every ACE 9xx to earth and use EMC clamp as below :
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt60
ACE949-2 and ACE959 communication interface
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt61
ACE969 and ACE969-2 communication interfaces Rajouter schéma 969-2
Sepam Installation EN 2007_01.ppt62
ACE909-2 / 919 communication interfaces
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt63
Communication with a PC
Supply the modules Anticipate electromagnetic compatibility problems Polarize and impedance-match lines
Series 20 Series 40 Series 80
110 to 220 Vacpower supply50 to 60 Hz
CCA612 CCA612 CCA612
RS 485 - 2 wire
Distributed power supply 12 or 24 Vdc – 2 wire
RS 232 – 3 wire
ACE909-2 ACE949-2 ACE949-2 ACE949-2
12 or 24 Vdcpower supply
If distance is too long (see documentation)
RP+ ONRP- ONRC ON
RCRCRC
SupervisionOR
Parameter setting via SFT2841
Compulosry cnnection of earthing terminal.2.5 mm² cable with a 4 mm ring lugLength < 200 mm
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt64
Communication with a PLC
Supply the modules Anticipate electromagnetic compatibility problems Polarize and impedance-match lines
Series 20 Series 40 Series 80
Power supplyACE919CA: 110 to 220 Vac 50 to 60 HzACE919CC:24 to 48 Vdc
CCA612 CCA612 CCA612
RS 485 - 2 wire
Distributed power supply12 or 24 Vdc – 2 wire
RS 485 – 2 wire
ACE919 ACE949-2 ACE949-2 ACE949-2RP+ ONRP- ONRC ON
RCRCRC
Supervision
12 or 24 Vdcpower supply
Polarization not done by the PLCPolarization done by the PLC
RP+ ONRP- ONRC ON
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt65
Communication with an Ethernet network
Series 20Series 40Series 80
Supply the modules Anticipate electromagnetic compatibility problems Polarize and impedance-match lines
Series 20 Series 40 Series 80
24 Vdcpower supply100-240 Vacadapter supplied
CCA612 CCA612 CCA612
RS 485 - 2 wire
Distributed power supply12 or 24 Vdc – 2 wire
EGX400 ACE949-2 ACE949-2 ACE949-2RP+ ONRP- ONRC ON
RCRCRC
SupervisionAND / ORParameter
settingvia SFT2841
12 or 24 Vdc power supply
Ethernet
Modbus TCP/IP
Sepam Installation EN 2007_01.ppt66
Communication with an Ethernet network
Example of 4-wire RS 485 network
ACE959 ACE959 ACE959
Series 20 Series 40 Series 80
24 Vdcpower supply100-240 Vacadapter supplied
CCA612 CCA612 CCA612
RS 485 - 4 wire
Distributed power supply12 or 24 Vdc – 2 wire
EGX400
RP+ ONRP- ONRC ON
RCRCRC
SupervisionAND / ORParameter
setting SFT2841
12 or 24 Vdc power supply
Ethernet
Modbus TCP/IP
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt67
Communication in disturbed environments
Use of optical fibre
Series 20 Series 40 Series 80
CCA612 CCA612 CCA612
ACE937 ACE937 ACE937
Optical star
Fiberoptics
SupervisionOR
Parameter setting via SFT2841
PCORPLC
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt68
Supervision and Parameter setting via SFT28412 independent networks
Series 20 Series 40 Series 80
CCA612 CCA612 CCA612
ACE969TP ACE969TP ACE969TP
RP+ ONRP- ONRC ON
RCRCRC
Supervisory system
Protocol:-Modbus-DNP3-IEC 60870-5-103
Sepam power supply
Distributed power supply12 or 24 Vdc – 2 wire
12 or 24 Vdc power supply
SFT2841ACE909-2
OREGX400
ORModem RTC
RS 485 - 2 wire
E-LAN
RS 4852 wire
ACE909-2OR
ACE919OR
EGX400
RP+ ONRP- ONRC ON
S-LAN
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt69
Supervision in disturbed environmentsand Parameter setting via SFT28412 independent networksUse of fibre optics
Series 20 Series 40 Series 80
CCA612 CCA612 CCA612
ACE969FO ACE969FO ACE969FO
RP+ ONRP- ONRC ON
RCRCRC
Supervisory system
Protocol:-Modbus-DNP3-IEC 60870-5-103
Sepam power supply
Distributed power supply 12 or 24 Vdc – 2 wire
12 or 24 Vdc power supply
SFT2841ACE909-2
OREGX400
ORModem RTC
RS 485 - 2 wire
E-LAN
HUBOR
Optical star
S-LAN
Fiberoptics in a ring or star arrangement
Series 20Series 40Series 80
Sepam Installation EN 2007_01.ppt70
Series 80
Redundancy
Series 80Series 80
RS 485 - 2 wire
RS 485 - 2 wire12 or 24 Vdc power supply
12 or 24 Vdc power supply
Series 80
Connection of remote modules
Connection of Sepam
Connection of communication accessories
Main points to remember
B
C
D
E
MountingA? Situate SEPAM and
its optional modules
Sepam Installation EN 2007_01.ppt 71
F
Installation rules
Main points to remember
Main points to remember
Sepam Installation EN 2007_01.ppt72
Characteristics
Series 80Series 20 Series 40
Sensors 3 CTs + 1 core balance CT Or 4 VTs
3 CTs + 3 VTs + 1 core balance CT
3 CTs + 4 VTs + 2 core bal. CTs6 CTs + 4 VTs + 2 core bal. CTs
Or 3 CTs + 8 VTs + 1 cor. bal. CT
Communication port 1 1 2
Equation editor - Yes Yes
Logipam - Yes (optional)
Removable cartridge - Yes
Battery - Yes
0 inputs / 5 outputsBasic I/O 0 inputs / 4 outputs
42 inputs / 23 outputsMaximum I/O 10 inputs / 8 outputs
24 / 250 V DCPower supply 24 / 250 V DC110 / 240 V AC
No UMI Or advanced UMI
Or mimic-based UMI
User / MachineInterface
No UMI or remote advanced UMI
-
-
-
Sepam Installation EN 2007_01.ppt73
Main points to remember
Take care of storage conditions
Connecting Sepam and additional modules to earth is compulsory.
All output relays are not identical :– Some are control type with 8A continuous current
• For Sepam 20/40 : O1 / 02 / 011• For Sepam 80 :O1 -> 04 et O101 / O201 / O301
The availability of some protection functions depend on VTs wiring
ACExxx communication modules need to be powered with 12 or 24 V DC
3 communication protocol are available: DNP3 / IEC 870-5-103 / Modbus
Synchro check option only work with series 80 and need specific cable CCA 785