8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 1/28
N OVA Technology
Kyle ® NOVA™ Recloser
THE ULTIMATE GAS-FREE, OIL-FREE AND
MAINTENANCE-FREE SOLUTION FOR
AUTOMATION, PROTECTION AND SWITCHING
APPLICATIONS
U SER B ENEFITS
Environmentally-Safe
Reduced Maintenance Costs
Easier Handling and Installation
Maximum Operating Safety
Reliable and Dependable Operation
P RODUCT F EATURES
SF 6 Gas-Free and Oil-Free
Maintenance-Free
Lightweight Design
Axial-Magnetic Vacuum Interruption
Kyle Manufacturing Expertise
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 2/28
The Shape of Things to ComeÉ
2
ooper Power Systems introduces a revolution indistri bution switchgear. The new three-phase,
microprocessor-controlled NOVA recloser utilizes
advanced polymer and vacuum technologies to increasevalue for distribution systems. Kyle has combined solidcycloaliphatic-epoxy polymer-encapsulated vacuuminterrupters with a reliable, lightweight operatingmechanism which utilizes a magnetic actuator to providea lifetime of trouble-free recloser operation.
This state-of-the-art design completely replaces liquid andgas dielectric media. It is the maintenance-free alternativein distribution system protection. The NOVA recloser isthe shape of things to come .
Superior Solid InsulationProvides Maintenance-Free andEnvironmentally-Safe OperationThe key to the NOVA recloser is the successfulcombination of two technologies: cycloaliphatic-epoxyencapsulation and the high-performance Kyle vacuuminterrupter.
All existing insulation systems require seals to defendagainst environmental exposure. Life and maintenance aredetermined by these sealing systems. When breached, thedielectric is compromised and must be repaired orreplaced.
As an oil alternative, SF6 gas introduces new and growingconcerns about its effects on the atmosphere. SF6 has anextremely long atmospheric lifetime, estimated between800 to 10,000 years, and has a global warming potential24,900 times that of carbon dioxide. As a result, SF6 isamong the most potent of greenhouse gases. NOVA’ssolid insulation construction eliminates all concern by itsenvironmentally-friendly design. The future is green withNOVA.
Solid dielectric insulation eliminates the need for
insulating gas or liquid, thereby greatly reducing recloserlife-cycle maintenance costs. There is no longer the needto monitor SF6 gas pressure or oil levels, to filter orreplenish the dielectric, to take special precautions whenhandling the dielectric during maintenance, or to worryabout environmental regulations regarding disposal of toxic or environmentally-unfriendly materials.
Kyle Advances Filled EpoxyDesign for Outdoor ApplicationsFilled epoxy casting systems have been successfully utilizedas insulating material in high and low voltage indoor
applications for over 30 years. Recent materialadvancements provide durable environmental propertieswhich enhance epoxy success for outdoor applications.State-of-the-art manufacturing techniques also bring keyimprovements in absorption of elastic energy, resistance tocracking, and crack propagation.
NOVA Cycloaliphatic Epoxy Advantages
Surface TrackingNOVA’s exceptional ability to resist electrical trackingreduces both flashovers and the associated cost of repairs.Results of the industry-standard incline plane test (per
ASTM D2303) revealed that cycloaliphatic epoxy is 50percent more resistant to tracking than polyurethane. Inaddition, independent testing by Arizona State University(per IEC 815) confirmed that NOVA cycloaliphaticepoxy is highly resistant to contaminants and resistedtracking and flashovers under extreme pollution levels.
HydrophobicityNOVA cycloaliphatic epoxy maintains excellenthydrophobicity (a property characterized by waterbeading into isolated drops) and is highly resistant tomoisture absorption. Hydrophobicity prevents continuous
sheets of water from forming leakage current paths which,when heated by continuous flow, create a dry band paththat deteriorates the creepage withstand level.
Ultraviolet ResistanceNOVA cycloaliphatic epoxy resists the damage caused byultraviolet radiation. Over 25 years of proven experienceof cycloaliphatic epoxy in harsh climates confirms thatNOVA maintains a smooth, self-cleansing, unblemishedsurface with low-adhesion to contaminants when exposedto ultraviolet radiation.
Tensile Strength
NOVA modules are tough and non-fragmenting as theypossess outstanding tensile and flexural strengthcharacteristics. A 12-gauge shotgun test supports the non-fragmenting performance and displays the ability of NOVA to thwart vandalism by successfully passing ahigh-potential withstand test.
Combining advanced vacuum technology, a sophisticatedsolid epoxy insulation system, and a proprietary,dielectrically-sound active component, Cooper PowerSystems now provides a non-oil, non-gas, solid insulationsystem destined to be the shape of things to come .
C
THE KYLE® NOVA™ RECLOSER
The Shape of Things to Come…
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 3/28
ÉThe Shape of Things to Come
3
Kyle Leads Vacuum Technologyyle revolutionized the protection of high voltagecircuits with the first commercially-successful
recloser, the Kyle Type H. Today, many Kyle reclosers
incorporate vacuum technologies which have advanced thedurability and extended the application base for vacuumproducts. Kyle’s constant development effort represents adetailed understanding of arc control, thermal loads, andcontact erosion. Each is pivotal to the successfulapplication of vacuum to solid dielectric systems.
The patented axial-magnetic field vacuum interrupter,designed and manufactured by Kyle DistributionSwitchgear‚ is the most advanced vacuum interrupterdesign in the world. Rely on Kyle vacuum interrupters toprovide many years of dependable operation.
Axial-Magnetic Design• Provides fast, low-energy arc interruption• Ensures long contact and interrupter life• Experiences low mechanical stress while ensuring
maximum operating safety• Eliminates the production of toxic byproducts
Innovative Design
Many vacuum interrupters employ radial-magnetic fieldcontacts. These use slots that are machined into the contactstructure to affect the direction of current flow during arcinterruption in such a way as to induce a radial-magneticfield. This radial-magnetic field pushes the arc around thecircumference of the contact, minimizing wear in any onespot. Though this method is sufficient for low andmedium current density applications, higher current levelscan cause significant contact erosion or shield burn-out.
Kyle interrupters employ axial-magnetic contacts. Slots aremachined into the contact support structure producing acoil that induces a magnetic field along the axis of theinterrupter. This axial-magnetic field keeps the arc in an
easier-to-interrupt diffuse mode, resulting in less arc powerthat needs to be dissipated. Furthermore, Kyle’s patentedVSAM design uses the entire contact surface, resulting infar less contact erosion. Less power to dissipate means lowthermal stress and longer life. Consequently, Kyle isuniquely qualified to encapsulate vacuum interrupters.
World-Class ProcessElectrically, the heart of the interrupter is the contactmaterial and structure. During the interruption of highcurrent, the surface of the contacts can reach its meltingtemperature, liberating any residual gases or contaminants
into the vacuum.
At Kyle, high purity chrome powder is analyzed, pressedinto a porous disk, infiltrated with copper, and machinedinto contacts. After electro-polishing, parts are assembledin a contaminant-free Class 1000 clean room, then loadedinto a vacuum brazing furnace for final production. Allprocesses are certified to ISO 9001 quality standards.
Cooper Power Systems, Kyle Distribution Switchgear,manufactures the most advanced vacuum interrupter inthe world. Superior to oil interruption and radial-magnetic
field vacuum interruption (see duty cycle comparison), thepatented axial-magnetic field Kyle vacuum interruptersprovide the longest life of any vacuum interrupter in theindustry.
K
AXIAL-MAGNETIC FIELD VACUUM INTERRUPTION
Kyle axial-magneti c field vacuum interrupter.
HIGH-ALUMINA CERAMICDesigned for maximum life and long-term vacuum integrity.
BELLOWSPermits ful l stroke for contactseparation without affecting vacuumseal.
CONTACT ASSEMBLYCopper alloy chosen for anti-weldingand high current interruptingcapabilities.
VAPOR SHIELD
Numberof
Trip
Operations
10
20
30
40
5060
80
100
Fault Interrupting Level (Symmetrical Amperes)
1000 2000 3000 4000 5000 6000 7000 80 00 9 000 10 00 0 11000 12000
70
90
200
300
400
500
600
800
1000
700
900
2000
3000
4000
50006000
8000
10000
7000
9000
Axial-MagneticVacuum Interruption
Radial-MagneticVacuum Interruption
Oil Interruption
Duty cycle compari son of oil , radial-magneti c fi eld, and axial-
magneti c field fault i nterruption.
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 4/28
The Shape of Things to ComeÉ
4
Compact, Lightweight Design
OVA microprocessor-controll ed, three-phaseautomatic circuit reclosers provide reliable and
economical overcurrent protection for distribution
circuits rated through 38kV. Extremely compact andlightweight in design, the NOVA recloser is easilyinstalled on poles or in substations.
Commanded by a Kyle microprocessor-based reclosercontrol, the NOVA automatic circuit recloser offerssuperior coordination and application capabilityunmatched by other system protection apparatus.
Application expertise, backed by worldwide recloserapplication experience, is available when needed.Knowledgeable design capability—based on more than
55 years of recloser manufacturing experience—hasmade Kyle the industry leader.
NOVA reclosers, like all Kyle reclosers, are designed andmanufactured in accordance with ANSI C37.60. Inaddition, the quality system at the Cooper PowerSystems Kyle Distribution Switchgear plant isISO-9001 certified.
Recloser and control accessories provide additionalcustomization of the protective program to achievemaximum system operating flexibility. Mounting
equipment is available for pole or substationapplications.
Operation
Current-sensing transformers, mounted on the recloser,supply fault-sensing information to the electroniccontrol. Trip and close signals from the control energizethe operating circuits in the recloser. By using a singlecurrent-sensing transformer ratio for all ratings,minimum-trip values of the electronic control areindependent of the continuous-current and interrupting
ratings of the recloser. Additional flexibility incoordination with other protective devices is providedby dual time-current characteristics available from awide choice of customizable curves, minimum tripvalues, reclosing and reset time settings, and a selectionof accessories. Stand-by power is supplied by internalsealed lead-acid batteries. The NOVA recloser with dcinterface provides deadline closing independent of
system voltage.
Operational FlexibilityOperational flexibility is provided by offering thecustomer a choice of either ac or dc interface. Whileeach interface employs the same magnetic actuator and
is essentially mechanically equivalent, they differ inelectrical operation.
Ac InterfaceThe NOVA recloser utilizes a unique ac interface thatprovides exclusive operation with standard Kyle Form4C, Form 5, and FXB microprocessor-based controlsand standard control cables. Ac power is connectedthrough a two-pin connector and cable to theswitchgear.
Dc InterfaceThe NOVA recloser with dc interface is fullyoperational with Kyle Form 4C and Form 5microprocessor-based controls specially equipped with adc-to-dc converter, interface circuit, and a fully shielded19 pin control cable.
N
NOVA DESCRIPTION
ElectronicControl
PotentialTransformer(120/240Vac)
120Vac/240Vac
Power Cable
14 PinControl Cable
2 Pin120/240VacLow-VoltageClosing Cable
NOVA ac
OP
2 Pin120Vac/240Vac
AlternativePower Connection
NOVA recloser configuration wi th ac interface.
ElectronicControl
PotentialTransformer(120/240Vac)
120Vac/240VacPower Cable
19 PinControl Cable
NOVA dc
OP
NOVA recloser configuration with dc interface.
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 5/28
ÉThe Shape of Things to Come
5
Vacuum Interruption
Vacuum interruption, used in NOVA reclosers, offersgreatly enhanced contact life. A single break on eachphase is accomplished by separating contacts inside thevacuum interrupter. All arcing is contained within the
vacuum envelope. Low-energy arc interruption,provided by axial-magnetic field technology, results infar less mechanical shock, extending the recloser’smechanical life.
Mechanism
The Kyle NOVA recloser meets and exceedsANSI/IEEE C37.60, as it is designed for a minimum of 10,000 operations. The mechanism is operated by amagnetic actuator, which uses a low-voltage powersource for operation. A fully-charged battery and trip
and close capacitors provide interrupter operation uponloss of control power. This feature provides the recloserwith dead-line operation capability–a requirement formany SCADA applications.
Magnetic Actuator
The heart of NOVA is a bi-stable linear actuator whichutilizes neodymium magnets, two opposing coils, aplunger, and a laminated frame. The magnetic actuator
provides a plunger holding force in excess of 136kilograms (300 pounds). It also permits a transfer of theplunger between two stable positions, by means of pulsed energy, to either of two opposing coils.
Advantages
Magnetic actuators provide several distinct advantageswhen utilized in a switchgear mechanism:
Latching – Mechanical latches are replaced by theactuator. Elimination of mechanical latches andassociated linkages leads to longer, trouble-freeoperation of the switchgear mechanism.
Response Time – The magnetic actuator is an electro-mechanical device capable of extremely fast responsetimes. This attribute is particularly advantageous forminimizing response and clearing time in providinginstantaneous reclose.
Size – The magnetic actuator is compact and requiresminimum mounting space. It’s overall dimensions are:20,3 cm x 17,8 cm x 11,4 cm (8 in. x 7 in. x 4.5 in.).
Power – A typical 8 amp-hour control battery hassufficient energy to provide hundreds of open-closeoperations in the absence of ac power.
Kyle Type NOVA™ recloser (dc version) mechani sm (view of operating mechani sm with housing cover removed).
Heater Magnetic Actuator
Stainless SteelMechanism Housing
(Standard)
OPEN/CLOSEContact Posit ion
Indicator
Actuator Board Control CableReceptacle
CT Protection Board Manual OPEN HandleTrip & Close Capacitors
Ground Connector#10 - #2 Stranded
MechanicalOperations Counter
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 6/28
The Shape of Things to ComeÉ
6
his specification applies to three-phaseautomatic circuit reclosers with a rated maximum
continuous current of 630 Amps and a 12.5kAsymmetrical interrupting rating. The recloser shall bedesigned to operate at system voltages of 15kV, 27kVand 38kV. Overcurrent sensing, recloser sequencing andtripping shall all be electronically-controlled. Currentinterruption shall be accomplished with axial-magneticfield vacuum interrupters encapsulated in cycloaliphaticepoxy modules. The cycloaliphatic epoxy is a solidpolymer insulation system free of gas and oil. Unit shallbe designed for pole-mount or substation installation.Unit shall be in complete conformance with applicableANSI C37.60 (recloser), IEEE, IEC, and NEMA
standards.
QualityThe quality system of the manufacturing facility shallbe independently certified to meet the followingstandards: ISO 9001 (International Standards),ANSI/ISO/ASQC Q9001 (American NationalStandards), BS EN ISO 9001 (European Standards),and CAN/CSA ISO 9001 (Canadian Standards).
RatingsSee complete ratings information on page 9.
Microprocessor-Based ControlsThe recloser shall be tested as an integrated package tobe compatible with all Cooper Power Systems’ three-phase microprocessor-based recloser controls.
Current SensingCurrent sensing shall be provided by three epoxy-encapsulated current transformers mounted at theterminals of the recloser. Output from thesetransformers is sent to the control for currentmeasurement for protection, instrumentation, andmetering. The current-sensing transformers shall beeasily interchangeable.
ConstructionGeneral Design1. The recloser shall consist of a mechanism housing
that contains a magnetic actuator, which provideslinear trip and close motion to three encapsulatedvacuum interrupter modules.
2. The recloser shall utilize an environmentally-safesolid polymer insulation system.
3. The recloser shall use non-corrosive componentshoused in a stainless steel mechanism housing.
4. SF6 gas and oil are not acceptable for interruption orinsulation mediums.
5. The unit shall be designed for 10,000 open/closeoperations.
6. The unit shall be of lightweight design, constructednot to exceed 136 kilograms (300 pounds), includingcurrent-sensing transformers.
7. Provisions shall be included for electrical close,electrical and manual trip, contact position
indication, and operations counter.8. Operating temperature range shall be -40ºC to +55ºC.
9. The mechanism cabinet shall be designed to permitaccess for service.
Mechanism1. The mechanism shall utilize a bi-stable magnetic
actuator capable of fast closing and openingfunctions. The magnetic actuator is powered byenergy storage capacitors housed in the mechanismcabinet.
2. Design shall permit multiple operations after loss-of-primary-control voltage to allow dead-line operation.
3. The fi rst reclosing interval shall not exceed 0.4seconds.
4. Total clearing time of the recloser shall not exceed 42milliseconds.
Solid Dielectric Insulation1. The recloser system shall employ a cycloaliphatic
epoxy solid polymer insulation system and not relyon gaseous or liquid dielectric.
2. The solid polymer insulation shall be highly resistantto ozone, oxygen, moisture, contamination, andultraviolet light.
3. The solid dielectri c insulation shall contain noenvironmentally-hazardous or toxic components.
Vacuum InterruptersCurrent interruption shall occur in vacuuminterrupters, providing long contact life whileeliminating the production of toxic by-products.
T
NOVA SPECIFICATIONS
Scope
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 7/28
The Shape of Things to ComeÉ
Vacuum interrupters in a high-vacuum brazing furnace.
The Kyle ® NOVA™ Recloser
Microprocessor-Based Recloser Control/Protective Options and Ordering Information:
• Selection Guide for Kyle Microprocessor-Based Recloser Controls
• Kyle ® Form 5 Microprocessor-Based Recloser Cont rol
• Kyle ® FXB M icroprocessor-Based Recloser Cont rol
• Protocol Converters for Kyle ® Form 4C Microprocessor-Based Recloser Control: DNP 3.0 / MODBUS • Kyle ® Form 4C M icroprocessor-Based Recloser Control Custom Control Accessori es
• Kyle ® Form 4C M icroprocessor-Based Recloser Control
• Kyle ® Form 5/LS/UDP Loop Secti onalizing Recloser Control System wi th Swi tch Mode
• Kyle ® NOVA Recloser Ordering Informati on
• Swi tch vs. Recloser
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 8/28
The Shape of Things to ComeÉ
8
286
(11.25) 1000(39.37)
140(5.5)
A
286
(11.25)
OP
EN
B
C
D
NOTE: All dimensions are mm (inches).Dimensions shown are approximate.
Terminal
Connectors1/0 - 500 MCM
TerminalConnectors
1/0 - 500 MCM
E
394(15.5)
394(15.5)
ControlReceptacle
Auxiliary SwitchAccessory Receptacle
GroundConnector
#10 - #2 Stranded
NOVA three-phase recloser dimensions.
NOVA DIMENSIONS
A B C D E
15kV 729 508 285 178 427(28.7) (20) (11.2) (7) (16.8)
27kV 790 569 285 178 427(31.1) (22.4) (11.2) (7) (16.8)
38kV 914 660 325 218 462(36) (26) (12.8) (8.6) (18.2)
Description 15kV 27kV 38kV
Terminal to terminal* 699 699 851(27.5) (27.5) (33.5)
Lower terminal to ground/earth 630 798 1077(24.8) (31.4) (42.4)
Creepage Distances
* On the same phase.
Description 15kV 27kV 38kV
NOVA recloser - kilograms (pounds) 111 (245) 118 (260) 125 (275)
Mass (Weight)
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 9/28
The Shape of Things to ComeÉ
9
• Axial-magnetic field vacuum interrupters encapsulated incycloaliphatic epoxy resin
• Current sensing provided by three epoxy-
encapsulated current transformers
• Mechanism utilizes a bi-stable magnetic actuator forclosing and opening and is powered by energy storagecapacitors housed in the mechanism cabinet
• Electronic interface circuit issues opening and closingsignals to the magnetic actuator in response to inputsignals from the remote control
• Manual operation provided via manual handle
• Position indicator provides OPEN/CLOSE status
STATE OF THE ART DESIGN AND CONSTRUCTION
NOVA Recloser Data 15 kV 27 kV 38 kV
Voltage Ratings
Maximum Voltage. . . . . . . . . . . . . . . . . . . . . . 15.5kV 27.0kV 38.0kV
Rated Basic Impulse Level . . . . . . . . . . . . . . . . 110.0kV 125.0kV 170.0kV
Radio Noise Limit (Microvolts). . . . . . . . . . . . 100 @9.4kV 100 @16.4kV 100 @23.0kV
Power Frequency Withstand (Dry) . . . . . . . . . 50.0kV 60.0kV 70.0kV
Power Frequency Withstand (Wet) . . . . . . . . . 45.0kV 50.0kV 60.0kV
Current Ratings
Rated Continuous Current . . . . . . . . . . . . . . . 630A 630A 630A
Short Circuit Current, Symmetrical. . . . . . . . . 12.5kA 12.5kA 12.5kA
Making Current, Asymmetrical Peak. . . . . . . . 31.0kA 31.0kA 31.0kA
Making Current, Asymmetrical RMS . . . . . . . 20.0kA 20.0kA 20.0kA
Mechanical Ratings
Minimum Mechanical OperationsWithout Maintenance (C-O) . . . . . . . . . 10,000 10,000 10,000
Minimum Electrical OperationsWithout Maintenance (C-O) . . . . . . . . . 10,000 10,000 10,000
M ass (Weight) - Kilograms (Pounds) . . . . . . . . 100 (220) 104 (230) 115 (253)
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 10/28
The Shape of Things to ComeÉ
International Offices:
Miami, Florida USA (Latin America)
Phone: 305-477-9400Fax: 305-477-9414
Markham, Ontario CanadaPhone: 905-940-8400Fax: 905-940-8405
Sao Paulo, Brazil
Phone: 011-55-11-524-0051Fax: 011-55-11-524-5250
Athens, GreecePhone: 011-30-1-964-6332Fax: 011-30-1-964-6336
Sydney, Australia
Phone: 011-61-2-9683-1122Fax: 011-61-2-9683-6840
Jakarta, IndonesiaPhone: 011-62-21-523-9155Fax: 011-62-21-523-9191
Taipei, Taiwan
Phone: 011-886-2-2758-4530Fax: 011-886-2-2758-4535
SingaporePhone: 011-65-298-3191
Fax: 011-65-298-0559
KYLE DISTRIBUTION SWITCHGEAR
SOUTH M ILWAUKEE, WI USA
The quality system at Cooper Power SystemsKyle Distribution Switchgear is ISO 9001 certified.
Over 55 Years Experience
Kyle is a long-established, international leader in theproduction of distribution switchgear, with more than ahalf century of design, testing, and manufacturingexperience, and more than 1.3 million units operating
worldwide.
In 1933, Kyle was founded by W.D. Kyle, Sr. Under thedirection of William Kyle, Jr., the first Kyle automaticcircuit recloser was developed and marketed in 1941.Three years later, a more sophisticated recloser, utilizingdual-timing, quickly established Kyle as the leadingproducer of automatic circuit reclosers.
©1998 Cooper Industries, Inc.Kyle ® , McGraw Edison ® , RTE ® are registered trademarksof Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019 • October 1998 • Supersedes 6/97
P.O. Box 1640Waukesha, WI 53187 USA
http://www.cooperpower.com
KBP
10/9
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 11/28
SELECTION GUIDE FORKYLE MICROPROCESSOR-BASED RECLOSER CONTROLS
Features Control
FXB Form 4C Form 5
Power
Power Source Required
Back-Up Power
Battery Test
Function
Local Keypad Programming –
Local Status Indication
Programming Readout
Sensitive Earth/Ground Fault
Hot Line Tag optional
Power Metering – –
Programmable Cold Load Pick Up –
Fault Target Indication
Security Protection
Loop Scheme Option –
Switch Mode – optional optional
Loss of Phase Protection – optional
Under/Over Frequency – –
Directional SEF – – Extended Cabinet – optional –
Cabinet Heater
Interface/Communications
Software Programmable
Serial Communications Capability –
Discrete SCADA
Variable Communications Protocol – optional
Alarm For Events – –
Multiple Communications Ports – –
Data Reader – –
V-PRO Compatibility – –
Analog Current Metering – –
The Shape of Things to ComeÉ
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 12/28
Features Control
FXB Form 4C Form 5
Time-Current Curves
TCC Construction –
TCC Modifiers
Sequence Coordination
High Current Lockout
Minimum Response Time
High Current Trip
Ground Trip Precedence
Data and Metering
Current Metering, Inst. & Demand
Power Metering (KW/KVAR/KVA/pf) – –
Harmonics (2nd thru 15th) – –
Energy Metering – –
Event Recorder
Multiple Protection Profiles – –
Histograms – –
Load Profile
Data Profiler (Configurable) – –
Duty Cycle (Per Phase)
The Shape of Things to ComeÉ
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019A • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 13/28
The Shape of Things to ComeÉ
KYLE® FORM 5 MICROPROCESSOR-BASED
RECLOSER CONTROL
Reduced distribution automationcosts
Minimizes momentary “blinks”
Simplified system analysis
Extensive metering
Reduce planning costs through
histogram analysis
Lower maintenance costs
Future updates via modularconversions
Reliable, surge-resilient performance
Reduced outage times
Increase system reliability
Provides Operational Intelligence for the Entire Kyle Line of
Three-Phase, Electronically-Controlled Reclosers
F O R M 5
C O N T R O L
AC
COMMUNICATIONSYSTEM
FRONT PANELDISPLAY
ALTERNATECOMMUNICATIONS
SCADA OPERATIONS ENGINEERING
COMMUNICATIONS 1 COMMUNICATIONS 2 COMMUNICATIONS 3
METERING
HISTOGRAMS
PROFILES
ALARMS
TARGETS
RECLOSER
BATTERY
BACK-UPINTERFACE
CPU
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 14/28
The Shape of Things to ComeÉ
Multiple microprocessor-based design
Dual serial communication ports
Protocols 2179 and DNP 3.0
Microsoft ® Windows-based interfacesoftware
Modular design throughout, includinghardware, firmware and software
Voltage, current and power metering
Frequency and voltage loadshedding
Integrated communications platformdesign (combines RTU and control inone cabinet)
Configurable data profiler and eventrecorder
Easily retrofittable to all Cooper PowerSystems electronically-controlledreclosers
Histograms
Extensive harmonic analysis
KYLE® FORM 5 CONTROL FEATURES
Data Profi ler
Total Harmonic Distort ion.
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019B • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 15/28
The Shape of Things to ComeÉ
KYLE® FXB MICROPROCESSOR-BASED
RECLOSER CONTROL
Microprocessor-based operation
Front panel programmability
User-friendly, Microsoft ®
Windows-based programming
software
Sophisticated data collection
capabilities
Custom TCC construction capability
Designed and tested in accordance
with ANSI-C37.60
Menu-driven keypad operation
Front-panel RS-232 connection port
Fault targeting and status
Front panel indicators
Operator “Hot” keys
Reduced programming cost
Simplified, intuitive operation
Minimum training required
Advanced Overcurrent Protection for Kyle® NOVA™ Three-Phase, Electronically-Controlled Reclosers
DETAILED
REPORTS
TCC EDITOR
Time-current curvesmay be selected forviewing, printing, ormodification fromeither the FXBStandard CurveLibrary or the Custom
.
All standard curvesand customized curvescan be modified toprovide special systemcoordination solutions.
•
•
The Custom CurveEditor enables the userto create uniquecurves which can thenbe stored in theCustom Curve Library
•
User-friendly, Windowsapplication.
Control interrogation,programming, andoperation.
Manages load profile,event history, andrecloser duty cycledatabases.
Disk and hard copydocumentation of control parameters andcollected data.
•
•
•
•
FXB
STANDARD
LIBRARY
Kyle and IEC time-current curve libraryaccessed via the TCCEditor
CUSTOM CURVE
LIBRARY
User-defined curvescreated and savedwithin the TCCEditor environmentfor future access orediting.
SYSTEM
DATABASE
Provides convenientstorage of controlconfiguration files andcontrol databases.
Provides permanentdocumentation of controlconfiguration and controldatabase records.
FXB
PROGRAMMER
All curves can besaved and accessedfor use in the TCCEditor.
•
User-friendlykeyboard application
•
FRONT PANEL
PROGRAMMING
•Four-line, twenty-character LED
• Manual controlinterrogation,programming andoperation
•Load profile, eventhistory and recloserduty cycle viewing
•Five quick-accesskeys
•Menu-driveninterrogation and
programming
FXB
ProgrammableMinimum Trip Values
Programmable TCC's
Event Recorder
Load Profile Monitor
Duty Cycle Monitor
•
•
•
•
•
•
NOVA
For SpecificApplicationRequirements
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 16/28
The Shape of Things to ComeÉ
Four-line, twenty-character alpha-
numeric LCD display
Front-panel programmability
Contact position indication
Hot line tag
SCADA capability
Sensitive Ground/Earth fault
Five quick-access keys (“Hot Keys”)
Operations counter
Current metering
Battery test
KYLE® FXB CONTROL FEATURES
For more information on the Kyle FXB Microprocessor-Based Recloser Control, contact your Cooper PowerSystems representative.
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019D • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 17/28
The Shape of Things to ComeÉ
PROTOCOL CONVERTERS FOR KYLE® FORM 4C
MICROPROCESSOR-BASED RECLOSER CONTROL:
DNP 3.0 / MODBUS Converts the Form 4C native 2179
Protocol to DNP 3.0 or MODBUSProtocol
Eliminates the need for ancillary
equipment – connects directly to theTTL interface in the Form 4C
Directly-powered – no need
for a separate power supplywhen powered by the
revised Form 4C powersupply
Operates in polled, event-
driven or a combination ofboth modes
Provides a gateway into a
complete SCADA ormonitoring network
Operates over various
communication media
Backed-up power by the existing
battery in the Form 4C control
DNP 3.0 Protocol Converter Accessory for the Form 4C Control
provides fiber opti c or RS-232 output.
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 18/28
The Shape of Things to ComeÉ
Onboard battery-backed memory
allows for configuration andoperating parameters to be storedand modified when required
Provides fiber optic or RS-232 output
signal for connection to a substationLAN or external communicationstransceiver
Diagnostic LED’s for hardware and
communications status
Provides isolation in compliance with
IEC 255-4
PROTOCOL CONVERTERS FOR KYLE® FORM 4C
MICROPROCESSOR-BASED RECLOSER CONTROL:
DNP 3.0 / MODBUS FEATURES
For more information on the DNP 3.0 and MODBUS Protocol Converter for the Kyle Form 4CMicroprocessor-Based Recloser Control, contact your Cooper Power Systems representative.
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019E • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 19/28
The Shape of Things to ComeÉ
KYLE® FORM 4C MICROPROCESSOR-BASED
RECLOSER CONTROL
CUSTOM CONTROL ACCESSORIES
Incorporates all features of theKyle Form 4C Control PLUS:
Switch Mode
• Enables the Form 4C Control tobecome a switch control, providingindication of overcurrent conditionswithout issuing a trip signal.
Hot Line Tag
• Provides protection for line crews byinterrupting and disabling the closecircuit. Also includes a close circuitdisconnect which provides a remov-able link directly in series with theclose circuit for operating practicesrequiring a visible break in the closecircuit.
Sensitive Ground/Earth Fault ON/OFF
• Provides front-panel access to Sen-sitive Ground/Earth Fault functions.
Trip On TCC2
• Causes all overcurrent trips to timeon the TCC#2 curves for phase andground.
Load Tap Change Disable (LTCD)
Status Indicator
• Allows a regulator to ride through amultiple shot recloser sequencewithout changing tap in an attemptto react to a recloser.
Provides Operational Intelligence for Kyle
®
NOVA™ Three-Phase, Electronically-Controlled Reclosers
SWITCH MODE HOT LINE TAG
SENSITIVE
GROUND
FAULTTRIP ON TCC2
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 20/28
The Shape of Things to ComeÉ
KYLE® FORM 4C MICROPROCESSOR-BASED
RECLOSER CONTROL
CUSTOM CONTROL ACCESSORIES
For more information on the Kyle Form 4C Microprocessor-Based Recloser Control Custom Control Accessories,contact your Cooper Power Systems representative.
GROUND TRIPBLOCK
GROUND TRIPNORMAL
NONRECLOSING
NORMALRECLOSING
SWITCH MODE
ON
TRIP CLOSE(LOCKOUT) (HOLD FOR COLD
LOAD PICKUP)
SUPERVISORYON
SUPERVISORYOFF
ALTERNATEMINIMUM TRIP
NORMAL
HOT LINE TAG
NORMAL
KYLE ®
FORM 4C RECLOSER CONTROL
CLOSE
OPEN
LAMP TEST
PUSH TO TEST
HOTLINE TAG
ON
SWITCH MODE(AUTO TRIP OFF)
RECLOSER MODE
(AUTO TRIP ON)
CLOSE CIRCUIT
DISCONNECT
Hot Li ne Tag and Uni versal Device Protection features.
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019F • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 21/28
KYLE® FORM 4C MICROPROCESSOR-BASED
RECLOSER CONTROL
Incorporates microprocessor
technology for enhanced applicationversatility
All standard control operating
parameters are keyboardprogrammable
Convenient programming and
interrogation through simplekeyboard sequences and dedicated
function keys Large LCD display provides control
feedback during programming andinterrogation
Front panel LCD indicators provide
control and recloser status at aglance
Equipped with keyboard-selectable
time-current curves interchangeable
for phase or ground Modify time-current curves for
unlimited coordination flexibility
Provides Operational Intelligence for Kyle® NOVA™ Three-
Phase, Electronically-Controlled Reclosers
Communication Support Equipment
Form 4C INTERFACE™Software
Allows the control to beprogrammed and operated with apersonal computer. A digitalcommunications protocol is usedto ensure secure and reliablecommunications.
Digital CommunicationsAccessory
For SCADA Interface and remoteoperation. Provides real-timedigital communications. A pair of ST type fiber-optic connectors andan RS232 to fiber-optic converteris supplied to interface withcommunication systems.
Data Reader
Stores data gathered from theForm 4C control which can bedownloaded to a personalcomputer for system analysis.Capable of storing data from 20Form 4C controls.
The Shape of Things to ComeÉ
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 22/28
Data port for downloading data files
Event recorder
Sequence coordination
Phase and ground fault target
indicators and counters
Contact position indicator
Battery test panel
High current lockout
Minimum response time
Trip test
Alternate minimum trip
Supervisory close
Supervisory trip and lockout
Supervisory ON/OFF switch
Remote trip and lockout
Close-retry feature
Non-reclose operation
Earth trip precedence
Sensitive ground/earth fault
Duty cycle monitor
Load profile monitor
KYLE® FORM 4C CONTROL STANDARD FEATURES
Instructional Video Available
KSPV9 Descripti on and Operation of the Kyle Form 4C Control available in VHS and PAL formats.
More information on the Kyle Form 4C Microprocessor-Based Recloser Control and its accessories can be foundin Catalog section 280-77, Service Information S280-77-1, S280-77-2, S280-77-3, and S280-77-4, or contactyour Cooper Power Systems representative.
The Shape of Things to ComeÉ
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019G • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 23/28
The Shape of Things to ComeÉ
KYLE® FORM 5/LS/UDP LOOP SECTIONALIZING
RECLOSER CONTROL SYSTEM WITH SWITCH MODE
Provides Loop Sectionalizing Feeder Protection to Reduce
Momentary Blinks and Minimize Customer Outages
Sectionalizing Recloser
Sectionalizing Recloser
Normally OpenTie Recloser
Feeder 2SubstationBreaker
2A
1B
1C
2B
F1
1AFeeder 1SubstationBreaker
F2
Three Recloser Loop
Three-recloser loop diagram.
Provides immediate servicerestoration independent of anycommunication system
Two-, three-, and five-recloser loopoperation
Sectionalizing or tie operation
Programmable single- or three-phaseloss of voltage response mode
Front Panel LED’s provide at-a-glancestatus information for both sources
Performance enhancing supervisoryoperation features
SCADA-ready, communicationsadaptable with DNP and 2179Protocols
Reliable decentralized intelligence
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 24/28
The Shape of Things to ComeÉ
KYLE® FORM 5/LS/UDP LOOP SECTIONALIZING
RECLOSER CONTROL SYSTEM
For more information on the Kyle Form 5/LS/UDP recloser control contact your Cooper Power Systemsrepresentative.
SOURCE I & SOURCE II
Six LED indicators providestatus information for each
phase of Source I andSource II and indicate
which phase initiated LSoperation.
LS NOT RESETIndicates the status
position of the LS NOTRESET function.Following an LS
operation, the LED willilluminate.
LS DISABLEDIndicates the LS optionhas been disabled from
either supervisory controlor front panel.
SOURCE I DISABLED &SOURCE II DISABLEDThese function keys willdisable the LS control. In thesectionalizing mode, theSOURCE II disable key doesnot affect controlperformance.
LS RESETResets the LS control back toits normal “reset” position.Depressing this button turnsoff t he LS NOT RESETindicator LED.
Kyle Form 5/LS/UDP recloser control.
SECTIONALIZING/TIEThe LED’s indicate theconfiguration of the LScontrol as set by the Form 5Interface Software.
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019H • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 25/28
The Shape of Things to ComeÉ
KYLE® NOVA™ RECLOSER ORDERING INFORMATION
Ordering InformationAll NOVAreclosers include a TypeFXB microprocessor-based reclos-er control. To order a NOVA reclos-er, microprocessor-based control,and control cable:
1. Use the chart at right toconstruct a catalog number thatdescribes the required recloser.
2. Use the information in Table 1and Table 2 to specify therequired mounting provisions.
3. Use the information in Table 3to specify auxiliary switchrequirements.
4. Order the required electronic
control (recloser includes anFXB control):
A. From publication 280-01,Part 77 , specify the requiredForm 4C microprocessor-based recloser control.
B. From publication 280-01,Part 78 , specify the requiredFXB microprocessor-basedrecloser control. (For acNOVA only).
C. From publication 280-01,Part 79 , specify the requiredForm 5 microprocessor-based recloser control.
KNOVA Type NOVA recloser with Type FXB base recloser control*
15A Recloser Type:
15A for 15kV, 630A continuous, 12.5kA interrupting
27A for 27kV, 630A continuous, 12.5kA interrupting
1 Bushing Terminals:
1 for eyebolt terminal, 1/0 to 500MCM, 630Amaximum**
3 for 2-hole flat pad terminal, 630A maximum
1 Interface:
1 for AC NOVA - 120Vac closing
(14-pin receptacle & 2-pin receptacle)2 for AC NOVA - 240Vac closing
(14-pin receptacle & 2-pin receptacle)
3 for DC NOVA*** - (19-pin receptacle),120Vac Heater
4 for DC NOVA *** - (19-pin receptacle),
240Vac Heater
KNOVA 15A 1 1KNOVA15A11 is the catalog number for the required basic Type NOVArecloser.
* Include the base catalog number of the selected control when ordering the recloser.
** Price included when ordering a Type NOVA recloser.*** Not available with FXB controls.
Constructing a Catalog NumberTo order a basic Type NOVA recloser with eyebolt terminals, for usewith 120Vac closing, and a 14-pin control cable, the catalog number
would be constructed like this:
Catalog
Description Number
Single pole-mounting hanger with stainless steel hardware . . . . . KNOVA54-2
Surge arrester mounting brackets with stainless steel hardwareInboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA61-2Outboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA61-1
Alley pole-mounting hanger with stainless steel hardware . . . . . . KNOVA352-1Arrester brackets (set of 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA353-1
Arrester brackets (set of 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA353-2Substation mounting frame with stainless steel hardware
includes control mounting bracket for FXA, FXB, Form 4C(single and double-size cabinet) and Form 5 . . . . . . . . . . . . . . . KNOVA59-1
Field kit for NOVA on substation mounting frame KA89WV1 . . . . KNOVA457-1
Field kit for NOVA on substation mounting frame KA584R1 . . . . . KNOVA457-2
TABLE 1Mounting Equipment
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 26/28
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.
Bulletin 97019I • October 1998 • Supersedes 6/97
P.O. Box 1640
Waukesha, WI 53187 USAhttp://www.cooperpower.com
K BP10/98
The Shape of Things to ComeÉ
CatalogDescription Number
Three-stage auxiliary switch with six independent contactsand receptacle for KNOVA178 cable . . . . . . . . . . . . . . . . . . . . . KNOVA66-1
Auxiliary switch cable for KNOVA66-1, auxiliary switch tocontrol, 0 - 80 feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA178
Auxiliary switch cable, maximum 200 feet. Replace “X” withnumber of feet. Price per foot over 10 feet . . . . . . . . . . . . . . . . KA1119R2-X
TABLE 3Auxiliary Switch
KYLE® NOVA™ RECLOSER ORDERING INFORMATION
Catalog
Description Number
Recloser in single pole-mounting hanger KNOVA54-2 . . . . . . . . . KNOVA354-1
Recloser in single pole-mounting hanger KNOVA54-2 witharrester brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA354-2
Recloser on substation mounting frame KNOVA59-1 . . . . . . . . . . KNOVA355-1
Recloser on alley pole-mounting hanger KNOVA352-1 . . . . . . . . KNOVA456-1
Recloser on alley pole-mounting hanger KNOVA352-1 witharrester brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA456-2
TABLE 2Factory Assembly of NOVA Recloser and Mounting Equipment*
*Covers factory assembly only; recloser, control, and mounting equipment must be ordered separately.
Catalog
Description NumberLow voltage ac input cable (ac NOVA only) . . . . . . . . . . . . . . . . . KA11ME1-15
Source and load wildlife guards (set of 6) . . . . . . . . . . . . . . . . . . . KNOVA56-2
TABLE 4Miscellaneous Accessories
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 27/28
The Shape of Things to ComeÉ
SWITCH VS. RECLOSER
Switch vs. Recloser
• By definition, switches and reclosershave basic differences in their appli-cation on a distribution system.
Switches are designed solely for exe-cuting load switching commands,while reclosers execute load switch-ing commands and autonomouslyinterrupt fault currents.
• This autonomous operation can beextended to the entire distributionfeeder, providing either a centralizedor decentralized approach.
Minimum Trip Sensitivity
• The use of a recloser on the distribu-tion system increases the ability tosense additional faults.
• Increased sensitivity and isolation oflower magnitude faults protects distri-bution line equipment, minimizes con-ductor burn down, and reduces thelikelihood of a temporary fault evolv-ing to a permanent fault.
X
F1 Recloser
X
F2
X
F3
50 0 Cu st omer s 5 00 Cus tomer s 500 Customers
Recloser Applications
MAIFI = 1500 + 1000 + 500 + 500 = 2.33E
1500
Recloser
Recloser application diagram.
X
F1 Switch Switch
X
F2
X
F3
500 Customers 500 Customers 500 Customers
Switch Applications
MAIFI = 1500 + 1500 + 1500 + 1500 = 4.00E
1500
Switch application diagram.
Centralized
• Substation breaker is required for fault interruption.
• Entire distribution feeder requires a momentary outage.
• Centralized system with switches for fault isolationrequires 100% reliability of the communication system.
• Switches are to be opened during periods of de-ener-gized line, or load-break ratings.
• Communication and sectionalizing equipment costs
are required for operation.
Decentralized
• Multiple reclosers used on the distribution circuit.
• Only affected areas see momentary outage.
• No communication system is required for immediatefault isolation. Inherent system reliability isimproved due to multiple independent devices.
• Full maximum fault interrupting ratings provideincreased safety.
• Sectionalizing costs only.
8/14/2019 Cooper - Recloser - Type NOVA.pdf
http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 28/28
The Shape of Things to ComeÉ
Momentary Outages
• More than 20 percent of utilities todaytrack momentary operations of“blinks.”
• Continual process operations, factoryautomation, and residential demandsrequire new enhancements to theapplication of distribution equipment.
• MAIFI and MAIFIE statistics arebecoming more common indices tomeasure momentary blinks.
• Traditional fault protection based onsubstation device (circuit breaker orrecloser) protection and lateral fusingis being replaced with the addition ofdistribution reclosers to provide faultprotection, minimizing substation tripsand momentary outages.
• Extensive flexibility in time-currentcurves, minimum trip values, andoperation sequences result in simpleinstallations to existing systems pro-viding trip coordination.
Cooper Power Systems Leads inDistribution Automation
• The economic evaluation of momen-tary outages indicates that the cost ofpurchasing a recloser is negligible for
application with industrial and com-mercial facilities.
• Cooper Power Systems is stronglycommitted to improving the reliabilityof the electric power industry.
• Technological advances, including thenewest microprocessor-based con-trols and solid insulation NOVA distrib-ution switchgear products representour investment in the future.
The Shape of Things to ComeÉ
©1998 Cooper Industries, Inc.Kyle ® is a registered trademark of Cooper Industries, Inc.
P.O. Box 1640
Waukesha, WI 53187 USAh //
For more information on reclosers and switches in Distribution Automation, refer to Bulletin 98011 or contactyour Cooper Power Systems representative.
MAIFI = Momentary Average Interruption Frequency Index
= Total number of customer momentary interruptions
Total number of customers served
MAIFIE = Momentary Average Interruption Event Frequency Index
= Total number of customer momentary interruptions events
Total number of customers served