DCS I/O List 1 2 3 4 5 6 7 Sr. No. Tag No. Description Service From To Type of signal Normal value Indicati ng range Low Indicatin g range high Unit History Sqrt. Function Remarks High Low 1 LT-483501A Steam Drum Level A Water / Steam BMS PLC DCS S.P 50 0 100 % No NA Control Note 5 2 LT-483501B Steam Drum Level B Water / Steam BMS PLC DCS S.P 50 0 100 % No NA Control Note 5 3 LT-483501C Steam Drum Level C Water / Steam BMS PLC DCS S.P 50 0 100 % No NA Control Note 5 4 PT-483272A Steam Drum Pressure A Steam Field DCS 2 wire L.P 131 0 200 Bar G No NA Compensation IS Barrier 5 PT-483272B Steam Drum Pressure B Steam Field DCS 2 wire L.P 131 0 200 Bar G No NA Compensation IS Barrier 6 PT-483272C Steam Drum Pressure C Steam Field DCS 2 wire L.P 131 0 200 Bar G No NA Compensation IS Barrier 7 FT-483402A Main Steam Flow A Steam Field DCS 2 wire L.P 175 0 250 TPH Yes Yes Control IS Barrier 8 FT-483402B Main Steam Flow B Steam Field DCS 2 wire L.P 175 0 250 TPH Yes Yes Control IS Barrier 9 FT-483402C Main Steam Flow C Steam Field DCS 2 wire L.P 175 0 250 TPH Yes Yes Control IS Barrier 10 PT-483274A Main Steam Pressure A Steam Field DCS 2 wire L.P 117 0 150 Bar G Yes NA Control, Compensation IS Barrier 11 PT-483274B Main Steam Pressure B Steam Field DCS 2 wire L.P 117 0 150 Bar G Yes NA Control, Compensation IS Barrier 12 PT-483274C Main Steam Pressure C Steam Field DCS 2 wire L.P 117 0 150 Bar G Yes NA Control, Compensation IS Barrier 13 TT-483010A Main steam temperature A Steam Field DCS 2 wire L.P 520 0 700 Deg. C Yes NA Control, Compensation IS Barrier 14 TT-483010B Main steam temperature B Steam Field DCS 2 wire L.P 520 0 700 Deg. C Yes NA Control, Compensation IS Barrier 15 TT-483010C Main steam temperature C Steam Field DCS 2 wire L.P 520 0 700 Deg. C Yes NA Control, Compensation IS Barrier 16 TT-483007A SH2 Inlet Steam Temperature A Steam BMS PLC DCS S.P 350 0 600 Deg C No NA Control Note 5 17 TT-483007B SH2 Inlet Steam Temperature B Steam BMS PLC DCS S.P 350 0 600 Deg C No NA Control Note 5 18 TT-483007C SH2 Inlet Steam Temperature C Steam BMS PLC DCS S.P 350 0 600 Deg C No NA Control Note 5 19 FT-483401A Feed Water Flow A Feed water Field DCS 2 wire L.P 175 0 250 TPH No Yes Control IS Barrier 20 FT-483401B Feed Water Flow B Feed water Field DCS 2 wire L.P 175 0 250 TPH No Yes Control IS Barrier 21 FT-483401C Feed Water Flow C Feed water Field DCS 2 wire L.P 175 0 250 TPH No Yes Control IS Barrier 22 TT-483001A Feedwater temperature at battery limit A Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C Yes NA Compensation IS Barrier 23 TT-483001B Feedwater temperature at battery limit B Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C Yes NA Compensation IS Barrier 24 TT-483001C Feedwater temperature at battery limit C Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C Yes NA Compensation IS Barrier 25 FT-483406A Combustion Air Flow A Combustion Air Field DCS 2 wire L.P 229 0 300 TPH No Yes Control IS Barrier 26 FT-483406B Combustion Air Flow B Combustion Air Field DCS 2 wire L.P 229 0 300 TPH No Yes Control IS Barrier 27 FT-483406C Combustion Air Flow C Combustion Air Field DCS 2 wire L.P 229 0 300 TPH No Yes Control IS Barrier 28 PT-483277 FD fan outlet pressure Combustion Air Field DCS 2 wire L.P 45 0 80 mBar G No NA Compensation IS Barrier 29 TT-483025 FD fan outlet air temperature Combustion Air Field DCS 2 wire L.P 40 0 100 Deg. C No NA Compensation IS Barrier 30 PT-483276A Steam to sootblower pressure A Steam Field DCS 2 wire L.P 43 0 60 Bar G No NA Control IS Barrier 31 PT-483276B Steam to sootblower pressure B Steam Field DCS 2 wire L.P 43 0 60 Bar G No NA Control IS Barrier Notes: All the signal exchanges between BMS and DCS except signals specifically listed in corresponding document shall be through serial communication and are not included here. Ranges & Alarm values mentioned below are tentative & subject to revision after getting actual process data Abbreviations used: LP means loop powered, SP means seperately powered. All flow signals shall be totalised (in DCS) and all Analog inputs shall be Trend displayed Alarm These signals are re-transmitted from BMS PLC, hardwired in 4-20mA format. Analog inputs (4~20m DC) Close Loop Indication, trend functions are required for all analog inputs, in general, though they are not specifically listed below. Only additional functions are specified below. Alarm values will be filled up later, once all the relevant info from vendors / process is available. Made By Chkd. By Appd. By NVK AKS AKS CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191 Drg. No.I11-TO-CS-38894 Rev.0 Sheet 1 of 11

Dcs Io List Rev0

Embed Size (px)

Citation preview

Page 1: Dcs Io List Rev0

DCS I/O List

1234567

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

1 LT-483501A Steam Drum Level A Water / SteamBMS PLC

DCS S.P 50 0 100 % No NA Control Note 5

2 LT-483501B Steam Drum Level B Water / SteamBMS PLC

DCS S.P 50 0 100 % No NA Control Note 5

3 LT-483501C Steam Drum Level C Water / SteamBMS PLC

DCS S.P 50 0 100 % No NA Control Note 5

4 PT-483272A Steam Drum Pressure A Steam Field DCS 2 wire L.P 131 0 200 Bar G No NA Compensation IS Barrier 5 PT-483272B Steam Drum Pressure B Steam Field DCS 2 wire L.P 131 0 200 Bar G No NA Compensation IS Barrier 6 PT-483272C Steam Drum Pressure C Steam Field DCS 2 wire L.P 131 0 200 Bar G No NA Compensation IS Barrier 7 FT-483402A Main Steam Flow A Steam Field DCS 2 wire L.P 175 0 250 TPH Yes Yes Control IS Barrier 8 FT-483402B Main Steam Flow B Steam Field DCS 2 wire L.P 175 0 250 TPH Yes Yes Control IS Barrier 9 FT-483402C Main Steam Flow C Steam Field DCS 2 wire L.P 175 0 250 TPH Yes Yes Control IS Barrier

10 PT-483274A Main Steam Pressure A Steam Field DCS 2 wire L.P 117 0 150 Bar G Yes NAControl, Compensation

IS Barrier

11 PT-483274B Main Steam Pressure B Steam Field DCS 2 wire L.P 117 0 150 Bar G Yes NAControl, Compensation

IS Barrier

12 PT-483274C Main Steam Pressure C Steam Field DCS 2 wire L.P 117 0 150 Bar G Yes NAControl, Compensation

IS Barrier

13 TT-483010A Main steam temperature A Steam Field DCS 2 wire L.P 520 0 700 Deg. C Yes NAControl, Compensation

IS Barrier

14 TT-483010B Main steam temperature B Steam Field DCS 2 wire L.P 520 0 700 Deg. C Yes NAControl, Compensation

IS Barrier

15 TT-483010C Main steam temperature C Steam Field DCS 2 wire L.P 520 0 700 Deg. C Yes NAControl, Compensation

IS Barrier

16 TT-483007A SH2 Inlet Steam Temperature A SteamBMS PLC

DCS S.P 350 0 600 Deg C No NA Control Note 5

17 TT-483007B SH2 Inlet Steam Temperature B SteamBMS PLC

DCS S.P 350 0 600 Deg C No NA Control Note 5

18 TT-483007C SH2 Inlet Steam Temperature C SteamBMS PLC

DCS S.P 350 0 600 Deg C No NA Control Note 5

19 FT-483401A Feed Water Flow A Feed water Field DCS 2 wire L.P 175 0 250 TPH No Yes Control IS Barrier20 FT-483401B Feed Water Flow B Feed water Field DCS 2 wire L.P 175 0 250 TPH No Yes Control IS Barrier21 FT-483401C Feed Water Flow C Feed water Field DCS 2 wire L.P 175 0 250 TPH No Yes Control IS Barrier22 TT-483001A Feedwater temperature at battery limit A Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C Yes NA Compensation IS Barrier23 TT-483001B Feedwater temperature at battery limit B Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C Yes NA Compensation IS Barrier24 TT-483001C Feedwater temperature at battery limit C Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C Yes NA Compensation IS Barrier

25 FT-483406A Combustion Air Flow ACombustion Air

Field DCS 2 wire L.P 229 0 300 TPH No Yes Control IS Barrier

26 FT-483406B Combustion Air Flow BCombustion Air

Field DCS 2 wire L.P 229 0 300 TPH No Yes Control IS Barrier

27 FT-483406C Combustion Air Flow CCombustion Air

Field DCS 2 wire L.P 229 0 300 TPH No Yes Control IS Barrier

28 PT-483277 FD fan outlet pressureCombustion Air

Field DCS 2 wire L.P 45 0 80 mBar G No NA Compensation IS Barrier

29 TT-483025 FD fan outlet air temperatureCombustion Air

Field DCS 2 wire L.P 40 0 100 Deg. C No NA Compensation IS Barrier

30 PT-483276A Steam to sootblower pressure A Steam Field DCS 2 wire L.P 43 0 60 Bar G No NA Control IS Barrier31 PT-483276B Steam to sootblower pressure B Steam Field DCS 2 wire L.P 43 0 60 Bar G No NA Control IS Barrier

Notes:All the signal exchanges between BMS and DCS except signals specifically listed in corresponding document shall be through serial communication and are not included here. Ranges & Alarm values mentioned below are tentative & subject to revision after getting actual process dataAbbreviations used: LP means loop powered, SP means seperately powered.All flow signals shall be totalised (in DCS) and all Analog inputs shall be Trend displayed

Alarm

These signals are re-transmitted from BMS PLC, hardwired in 4-20mA format.

Analog inputs (4~20m DC) Close Loop

Indication, trend functions are required for all analog inputs, in general, though they are not specifically listed below. Only additional functions are specified below.Alarm values will be filled up later, once all the relevant info from vendors / process is available.

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 1 of 11

Page 2: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

32 PT-483276C Steam to sootblower pressure C Steam Field DCS 2 wire L.P 43 0 60 Bar G No NA Control IS Barrier33 PT-483275A HP steam pressure PRDS A Steam Field DCS 2 wire L.P 25 0 40 Bar G No NA Control IS Barrier34 PT-483275B HP steam pressure PRDS B Steam Field DCS 2 wire L.P 25 0 40 Bar G No NA Control IS Barrier35 PT-483275C HP steam pressure PRDS C Steam Field DCS 2 wire L.P 25 0 40 Bar G No NA Control IS Barrier

36 TT-483012A HP steam temperature PRDS outlet A SteamBMS PLC

DCS S.P 230 0 400 Deg. C No NA Control Note 5

37 TT-483012B HP steam temperature PRDS outlet B SteamBMS PLC

DCS S.P 230 0 400 Deg. C No NA Control Note 5

38 TT-483012C HP steam temperature PRDS outlet C SteamBMS PLC

DCS S.P 230 0 400 Deg. C No NA Control Note 5

39 AT-483701A Oxygen Analyser A Flue gas Field DCS 2 wire S.P 2 0 10 % Yes NA Control IS Barrier40 AT-483701B Oxygen Analyser B Flue gas Field DCS 2 wire S.P 2 0 10 % Yes NA Control IS Barrier41 AT-483701C Oxygen Analyser C Flue gas Field DCS 2 wire S.P 2 0 10 % Yes NA Control IS Barrier

42 PT-483292A Fuel oil pressure at control valve outlet A Fuel OilBMS PLC

DCS S.P 3 0 12 Bar G No NA Control Note 5

43 PT-483292B Fuel oil pressure at control valve outlet B Fuel OilBMS PLC

DCS S.P 3 0 12 Bar G No NA Control Note 5

44 PT-483292C Fuel oil pressure at control valve outlet C Fuel OilBMS PLC

DCS S.P 3 0 12 Bar G No NA Control Note 5

45 FT-483409 Fuel Oil flow Fuel oil Field DCS 2 wire S.P 14.5 0 20 TPH Yes NA Control IS Barrier

46 PT-483293A Atomising media Pressure Steam/AirBMS PLC

DCS S.P 8 0 12 Bar G No NA Control Note 5

47 PT-483293B Atomising media Pressure Steam/AirBMS PLC

DCS S.P 8 0 12 Bar G No NA Control Note 5

48 PT-483293C Atomising media Pressure Steam/AirBMS PLC

DCS S.P 8 0 12 Bar G No NA Control Note 5

49 PT-483288A Fuel Gas Pressure at control valve outlet A Fuel gasBMS PLC

DCS S.P 40 0 50 mBar G No NA Control Note 5

50 PT-483288B Fuel Gas Pressure at control valve outlet B Fuel gasBMS PLC

DCS S.P 40 0 50 mBar G No NA Control Note 5

51 PT-483288C Fuel Gas Pressure at control valve outlet C Fuel gasBMS PLC

DCS S.P 40 0 50 mBar G No NA Control Note 5

52 FT-483408A Fuel Gas Flow A Fuel gas Field DCS 2 wire L.P 11.6 0 15 TPH Yes Yes Control IS Barrier53 FT-483408B Fuel Gas Flow B Fuel gas Field DCS 2 wire L.P 11.6 0 15 TPH Yes Yes Control IS Barrier54 FT-483408C Fuel Gas Flow C Fuel gas Field DCS 2 wire L.P 11.6 0 15 TPH Yes Yes Control IS Barrier55 PT-483287A Fuel gas pressure at battery limit A Fuel gas Field DCS 2 wire L.P 5 0 10 Bar G Yes NA Compensation IS Barrier56 PT-483287B Fuel gas pressure at battery limit B Fuel gas Field DCS 2 wire L.P 5 0 10 Bar G Yes NA Compensation IS Barrier57 PT-483287C Fuel gas pressure at battery limit C Fuel gas Field DCS 2 wire L.P 5 0 10 Bar G Yes NA Compensation IS Barrier58 TT-483046 Fuel gas Temperature Fuel gas Field DCS 2 wire L.P 40 0 80 Deg C Yes NA Compensation IS Barrier59 PT-483286A Scanner Fan outlet air pressure A Air Field DCS 2 wire L.P 60 0 120 mBar G No NA Interlock IS Barrier60 PT-483286B Scanner Fan outlet air pressure B Air Field DCS 2 wire L.P 60 0 120 mBar G No NA Interlock IS Barrier61 PT-483286C Scanner Fan outlet air pressure C Air Field DCS 2 wire L.P 60 0 120 mBar G No NA Interlock IS Barrier62 LT-483504A Continuous blowdown tank level A Condensate Field DCS 2 wire L.P 50 0 100 % No NA Control IS Barrier63 LT-483504B Continuous blowdown tank level B Condensate Field DCS 2 wire L.P 50 0 100 % No NA Control IS Barrier64 LT-483504C Continuous blowdown tank level C Condensate Field DCS 2 wire L.P 50 0 100 % No NA Control IS Barrier

65 PT-483273A Main Steam Pressure vent control A Steam Field DCS 2 wire L.P 117 80 130 Bar G No NAControl, Compensation

IS Barrier

66 PT-483273B Main Steam Pressure vent control B Steam Field DCS 2 wire L.P 117 80 130 Bar G No NAControl, Compensation

IS Barrier

67 PT-483273C Main Steam Pressure vent control C Steam Field DCS 2 wire L.P 117 80 130 Bar G No NAControl, Compensation

IS Barrier

68 TT-483013A Soot Blower Drain temperature A Steam Field DCS 2 wire L.P 350 0 600 Deg. C No NA Interlock IS Barrier69 TT-483013B Soot Blower Drain temperature B Steam Field DCS 2 wire L.P 350 0 600 Deg. C No NA Interlock IS Barrier70 TT-483013C Soot Blower Drain temperature C Steam Field DCS 2 wire L.P 350 0 600 Deg. C No NA Interlock IS Barrier71 AT-483706 Conductivity in Blow down water Water Field DCS 2 wire L.P 150 0 200 Micro S Yes NA Control IS Barrier72 Spare IS Barrier73 Spare IS Barrier

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 2 of 11

Page 3: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

74 Spare IS Barrier75 Spare IS Barrier76 Spare IS Barrier77 Spare IS Barrier78 Spare IS Barrier79 Spare IS Barrier80 Spare IS Barrier81 Spare IS Barrier82 Spare IS Barrier83 Spare IS Barrier84 Spare IS Barrier85 Spare IS Barrier86 Spare IS Barrier

1 TT-483038 SH1 Tube Skin temperature 1 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier2 TT-483039 SH1 Tube Skin temperature 2 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier3 TT-483040 SH1 Tube Skin temperature 3 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier4 TT-483041 SH1 Tube Skin temperature 4 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier5 TT-483034 SH2 Tube Skin temperature 1 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier6 TT-483035 SH2 Tube Skin temperature 2 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier7 TT-483036 SH2 Tube Skin temperature 3 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier8 TT-483037 SH2 Tube Skin temperature 4 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier9 TT-483030 SH3 Tube Skin temperature 1 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier

10 TT-483031 SH3 Tube Skin temperature 2 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier11 TT-483032 SH3 Tube Skin temperature 3 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier12 TT-483033 SH3 Tube Skin temperature 4 NA Field DCS 2 wire L.P 500 0 700 Deg C Yes NA IS Barrier13 TT-483026 Steam Drum Skin temperature 1 NA Field DCS 2 wire L.P 300 0 500 Deg C Yes NA IS Barrier14 TT-483027 Steam Drum Skin temperature 2 NA Field DCS 2 wire L.P 300 0 500 Deg C Yes NA IS Barrier15 TT-483028 Steam Drum Skin temperature 3 NA Field DCS 2 wire L.P 300 0 500 Deg C Yes NA IS Barrier16 TT-483929 Steam Drum Skin temperature 4 NA Field DCS 2 wire L.P 300 0 500 Deg C Yes NA IS Barrier17 TT-483015 FD Fan DE Bearing temperature NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier18 TT-483016 FD Fan NDE Bearing temperature NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier19 TT-483017 FD Fan Motor DE Bearing temperature NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier20 TT-483018 FD Fan Motor NDE Bearing temperature NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier21 TT-483019 FD Fan Motor Winding temperature 1 NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier22 TT-483020 FD Fan Motor Winding temperature 2 NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier23 TT-483021 FD Fan Motor Winding temperature 3 NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier24 TT-483022 FD Fan Motor Winding temperature 4 NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier25 TT-483023 FD Fan Motor Winding temperature 5 NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier26 TT-483024 FD Fan Motor Winding temperature 6 NA Field DCS 2 wire L.P 60 0 200 Deg C Yes NA IS Barrier27 BT-483801A Flame Scanner 1 Burner 1 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier28 BT-483801B Flame Scanner 2 Burner 1 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier29 BT-483803A Flame Scanner 1 Burner 2 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier30 BT-483803B Flame Scanner 2 Burner 2 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier31 BT-483805A Flame Scanner 1 Burner 3 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier32 BT-483805B Flame Scanner 2 Burner 3 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier33 BT-483807A Flame Scanner 1 Burner 4 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier34 BT-483807B Flame Scanner 2 Burner 4 Intensity UV Radiation Field DCS S.P 50 0 100 % No NA IS Barrier

35 FV-483401A Position Transmitter-Feedwater (100%) control valve A Feed Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

36 FV-483401B Position Transmitter-Feedwater (100%) control valve B Feed Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

37 LV-483501 Position Transmitter-Feedwater (30%) control valve Feed Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier38 PV-483273 Position Transmitter-Start Up Vent control valve Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

Analog inputs (4~20m DC) Open Loop

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 3 of 11

Page 4: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

39 TV-483007 Position Transmitter-Attemperator 1 control valve Spray Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier40 TV-483010 Position Transmitter-Attemperator 2 control valve Spray Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

41 FV-483406 Position Transmitter-FD fan damper actuatorCombustion Air

Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

42 FV-483408 Position Transmitter-Fuel Gas Flow control valve. Fuel gas Field DCS 2 wire L.P NA 0 100 % No NA43 PV-483288 Position Transmitter-Fuel gas pressure control valve. Fuel gas Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier44 FV-483409 Position Transmitter-Fuel Oil flow control valve. Fuel Oil Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier45 PV-483292 Position Transmitter-Fuel oil pressure control valve. Fuel Oil Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

46 PV-483293Position Transmitter-Atomising media pressure control valve.

Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

47 AV-483706 Position Transmitter-Drum conductivity control valve. Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

48 LV-483504Position Transmitter-Continuous blow down tank level control valve.

Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

49 PV-483275Position Transmitter-PRDS steam pressure control valve.

Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

50 TV-483012 Position Transmitter- PRDS Attemperator control valve Spray Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

51 PV-483276Position Transmitter-soot blower steam pressure control valve.

Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier

52 MV-483M026 Position Transmitter-Main Steam vent isolation valve Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier53 MV-483M024 Position Transmitter-Superheater drain valve Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier54 MV-483M034 Position Transmitter-IBD valve Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier55 MV-483M029 Position Transmitter-Main Steam line drain valve Water Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier56 MV-483M022 Position Transmitter-Drum vent valve Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier57 MV-483M027 Position Transmitter-Main steam stop valve Steam Field DCS 2 wire L.P NA 0 100 % No NA IS Barrier58 TT-483045 Cooling Water Inlet temperature Cooling Water Field DCS 2 wire L.P 30 0 80 Deg C No NA IS Barrier59 TT-483014 IBD Tank Outlet temperature Condensate Field DCS 2 wire L.P 60 0 140 Deg C No NA IS Barrier60 AT-483707 pH in Blow down water Water Field DCS 2 wire L.P 9 4 14 pH Yes NA IS Barrier61 AT-483703 pH in Saturated steam Steam Field DCS 2 wire L.P 8 4 14 pH Yes NA IS Barrier62 AT-483705 pH in Super heated steam Steam Field DCS 2 wire L.P 8 4 14 pH Yes NA IS Barrier63 AT-483702 Conductivity in Saturated steam Steam Field DCS 2 wire L.P 0.1 0 1 Micro S Yes NA IS Barrier64 AT-483704 Conductivity in Super heated steam Steam Field DCS 2 wire L.P 0.1 0 1 Micro S Yes NA IS Barrier65 PT-483271 Feed water pressure at battery limit Feed Water Field DCS 2 wire L.P 156 0 260 Bar G Yes NA IS Barrier66 TT-483002 Feedwater temperature at Economiser 1 inlet Feed Water Field DCS 2 wire L.P 125 0 200 Deg. C No NA IS Barrier67 TT-483003 Feedwater temp at Economiser 1 outlet Feed Water Field DCS 2 wire L.P 235 0 400 Deg. C No NA IS Barrier68 TT-483004 Feedwater temp at Economiser 2 outlet Feed Water Field DCS 2 wire L.P 290 0 400 Deg. C No NA IS Barrier69 FT-483405 PRDS 1 Attemperator spray water flow Spray Water Field DCS 2 wire L.P 2100 0 3000 Kg/hr No Yes IS Barrier70 FT-483403 Attemperator 1 spray water flow Spray Water Field DCS 2 wire L.P 18 0 30 TPH No Yes IS Barrier71 FT-483404 Attemperator 2 spray water flow Spray Water Field DCS 2 wire L.P 16 0 30 TPH No Yes IS Barrier

72 PT-483278 Windbox pressureCombustion Air

Field DCS 2 wire L.P 34 0 60 mBar G No NA IS Barrier

73 PT-483279 Furnace pressure Flue gas Field DCS 2 wire L.P 18 0 30 mBar G No NA IS Barrier74 PT-483283 Flue gas at economiser 2 inlet pressure Flue gas Field DCS 2 wire L.P 10 0 15 mBar G No NA IS Barrier75 PT-483284 Flue gas at economiser 1 outlet pressure Flue gas Field DCS 2 wire L.P 0 (-)5 5 mBar G No NA IS Barrier76 TT-483042 Flue gas Temperature at Economiser 2 inlet Flue gas Field DCS 2 wire L.P 580 0 800 Deg. C No NA IS Barrier77 TT-483043 Flue gas Temperature at Economiser 2 outlet Flue gas Field DCS 2 wire L.P 430 0 600 Deg. C No NA IS Barrier78 TT-483044 Flue gas Temperature before stack Flue gas Field DCS 2 wire L.P 170 0 300 Deg. C No NA IS Barrier79 PT-483291 Fuel Oil pressure at BL Fuel Oil Field DCS 2 wire L.P 15 0 25 Bar G Yes NA IS Barrier80 TT-483005 Saturated Steam temperature Steam Field DCS 2 wire L.P 335 0 500 Deg. C No NA IS Barrier81 TT-483006 SH 1 Outlet Steam temperature Steam Field DCS 2 wire L.P 417 0 600 Deg. C No NA IS Barrier82 TT-483008 SH 2 Outlet Steam temperature Steam Field DCS 2 wire L.P 482 0 600 Deg. C No NA IS Barrier

83 LT-483503A Steam Drum Level A Water / Steam Field DCS S.P 50 0 100 % No NA

IS Barrier, Conductivity type stepped input

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 4 of 11

Page 5: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

84 LT-483503B Steam Drum Level B Water / Steam Field DCS S.P 50 0 100 % No NA

IS Barrier, Conductivity type stepped input

85 Spare IS Barrier86 Spare IS Barrier87 Spare IS Barrier88 Spare IS Barrier89 Spare IS Barrier90 Spare IS Barrier91 Spare IS Barrier92 Spare IS Barrier93 Spare IS Barrier94 Spare IS Barrier95 Spare IS Barrier96 Spare IS Barrier97 Spare IS Barrier98 Spare IS Barrier99 Spare IS Barrier100 Spare IS Barrier101 Spare IS Barrier

1 FV-483401A Feedwater (100%) control valve A Feed Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier2 FV-483401B Feedwater (100%) control valve B Feed Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier3 LV-483501 Feedwater (30%) control valve. Feed Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier4 PV-483273 Start up vent control valve. Steam DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier5 TV-483007 Attemperator 1 control valve. Spray Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier6 TV-483010 Attemperator 2 control valve. Spray Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier

7 FV-483406 FD fan damper actuatorCombustion Air

DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier

8 FV-483408 Fuel Gas Flow control valve. Fuel gas DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier9 PV-483288 Fuel gas pressure control valve. Fuel gas DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier

10 FV-483409 Fuel Oil flow control valve. Fuel oil DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier11 PV-483292 Fuel oil pressure control valve. Fuel oil DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier12 AV-483706 Drum conductivity control valve. Steam DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier13 LV-483504 Continuous blowdown tank level control valve. Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier14 PV-483275 PRDS 1 steam pressure control valve. Steam DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier15 TV-483012 PRDS 1 attemperator control valve. Spray Water DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier16 PV-483276 Soot blower steam pressure control valve. Steam DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier17 PV-483293 Atomising media pressure control valve Steam/Air DCS Field 2 wire L.P NA 0 100 % NA NA No NA Control IS Barrier18 Spare IS Barrier19 Spare IS Barrier20 Spare IS Barrier21 Spare IS Barrier

1 ZSO-483M021 Feedwater stop valve Open position. Feed Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier2 ZSC-483M021 Feedwater stop valve Close position. Feed Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier3 TSO-483M021 Feedwater stop valve Open torque switch Feed Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier4 TSC-483M021 Feedwater stop valve Close torque switch Feed Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier5 XA-483M021 Feedwater stop valve Remote Available Feed Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier6 ZSO-483M022 Drum vent valve 2 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier7 ZSC-483M022 Drum vent valve 2 Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier8 TSO-483M022 Drum vent valve 2 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier9 TSC-483M022 Drum vent valve 2 Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier

10 XA-483M022 Drum vent valve 2 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier

Digital inputs (Potential free) from field / MCC

Analog outputs (4~20m DC) Closed Loop

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 5 of 11

Page 6: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

11 ZSO-483M023 Drum vent valve 1 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier12 ZSC-483M023 Drum vent valve 1 Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier13 TSO-483M023 Drum vent valve 1 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier14 TSC-483M023 Drum vent valve 1 Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier15 XA-483M023 Drum vent valve 1 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier16 ZSO-483M024 Superheater drain valve 1 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier17 ZSC-483M024 Superheater drain valve 1 Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier18 TSO-483M024 Superheater drain valve 1 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier19 TSC-483M024 Superheater drain valve 1 Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier20 XA-483M024 Superheater drain valve 1 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier21 ZSO-483M025 Superheater drain valve 2 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier22 ZSC-483M025 Superheater drain valve 2 Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier23 TSO-483M025 Superheater drain valve 2 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier24 TSC-483M025 Superheater drain valve 2 Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier25 XA-483M025 Superheater drain valve 2 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier26 ZSO-483M026 Main steam vent valve Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier27 ZSC-483M026 Main steam vent valve Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier28 TSO-483M026 Main steam vent valve Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier29 TSC-483M026 Main steam vent valve Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier30 XA-483M026 Main steam vent valve Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier31 ZSO-483M027 Main steam stop valve Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier32 ZSC-483M027 Main steam stop valve Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier33 TSO-483M027 Main steam stop valve Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier34 TSC-483M027 Main steam stop valve Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier35 XA-483M027 Main steam stop valve motor Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier36 ZSO-483M028 Main steam stop valve bypass Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier37 ZSC-483M028 Main steam stop valve bypass Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier38 TSO-483M028 Main steam stop valve bypass Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier39 TSC-483M028 Main steam stop valve bypass Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier40 XA-483M028 Main steam stop valve bypass Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier41 ZSO-483M029 Main steam drain valve 1 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier42 ZSC-483M029 Main steam drain valve 1 Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier43 TSO-483M029 Main steam drain valve 1 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier44 TSC-483M029 Main steam drain valve 1 Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier45 XA-483M029 Main steam drain valve 1 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier46 ZSO-483M030 Main steam drain valve 2 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier47 ZSC-483M030 Main steam drain valve 2 Close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier48 TSO-483M030 Main steam drain valve 2 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier49 TSC-483M030 Main steam drain valve 2 Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier50 XA-483M030 Main steam drain valve 2 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier51 ZSO-483M031 SB steam inlet valve Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier52 ZSC-483M031 SB steam inlet valve close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier53 TSO-483M031 SB steam inlet valve Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier54 TSC-483M031 SB steam inlet valve Close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier55 XA-483M031 SB steam inlet valve Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier56 ZSO-483M032 SB steam drain valve 1 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier57 ZSC-483M032 SB steam drain valve 1 close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier58 TSO-483M032 SB steam drain valve 1 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier59 TSC-483M032 SB steam drain valve 1 close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier60 XA-483M032 SB steam drain valve 1 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier61 ZSO-483M033 SB steam drain valve 2 Open position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier62 ZSC-483M033 SB steam drain valve 2 close position. Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier63 TSO-483M033 SB steam drain valve 2 Open torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier64 TSC-483M033 SB steam drain valve 2 close torque switch Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 6 of 11

Page 7: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

65 XA-483M033 SB steam drain valve 2 Remote Available Steam Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier66 ZSO-483M034 Drum drain valve 1 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier67 ZSC-483M034 Drum drain valve 1 Close position. Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier68 TSO-483M034 Drum drain valve 1 Open torque switch Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier69 TSC-483M034 Drum drain valve 1 Close torque switch Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier70 XA-483M034 Drum drain valve 1 Remote Available Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier71 ZSO-483M035 Drum drain valve 2 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier72 ZSC-483M035 Drum drain valve 2 Close position. Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier73 TSO-483M035 Drum drain valve 2 Open torque switch Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier74 TSC-483M035 Drum drain valve 2 Close torque switch Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier75 XA-483M035 Drum drain valve 2 Remote Available Water Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier

76 ZSC-483M051 FD Fan damper Close position.Combustion Air

Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier

77 ZSO-483M051 FD Fan damper Open position.Combustion Air

Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier

78 TSC-483M051 FD Fan damper Close torque switchCombustion Air

Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier

79 TSO-483M051 FD Fan damper Open torque switchCombustion Air

Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier

80 XA-483M051 FD Fan damper Remote AvailableCombustion Air

Field DCS Potential free NA NA NA NA NA NA NA NA Indication IS Barrier

81 XI-483K001 FD fan motor runningCombustion Air

MCC DCS Potential free NA NA NA NA NA NA NA NA Indication

82 XA-483K001 FD fan motor trippedCombustion Air

MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm

83 XS-483K001 FD fan motor Auto Selected Combustion Air

MCC DCS Potential free NA NA NA NA NA NA NA NA Indication

84 XI-483K002A Scanner fan 1 motor running Air MCC DCS Potential free NA NA NA NA NA NA NA NA Indication85 XA-483K002A Scanner fan 1 motor tripped Air MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm86 XS-483K002A Scanner fan 1 motor Auto Selected Air MCC DCS Potential free NA NA NA NA NA NA NA NA Indication87 XI-483K002B Scanner fan 2 motor running Air MCC DCS Potential free NA NA NA NA NA NA NA NA Indication88 XA-483K002B Scanner fan 2 motor tripped Air MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm89 XS-483K002B Scanner fan 2 motor Auto Selected Air MCC DCS Potential free NA NA NA NA NA NA NA NA Indication90 XI-483P010A HP Dosing Pump 1 motor running Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Indication91 XA-483P010A HP Dosing Pump 1 motor Auto Selected Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Indication92 XS-483P010A HP Dosing Pump 1 motor tripped Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm93 XI-483P010B HP Dosing Pump 2 motor running Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Indication94 XA-483P010B HP Dosing Pump 2 motor tripped Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm95 XS-483P010B HP Dosing Pump 2 motor Auto Selected Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Indication96 XI-483N01 HP Dosing stirrer motor running Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Indication97 XA-483N01 HP Dosing stirrer motor tripped Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm98 XS-483N02 HP Dosing stirrer motor Auto Selected Chemicals MCC DCS Potential free NA NA NA NA NA NA NA NA Indication99 TSH-483111 Continuous blowdown sample temperature high Water Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier100 TSH-483112 Superheated steam sample temperature high Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier101 TSH-483113 Saturated steam sample temperature high Steam Field DCS Potential free NA NA NA NA NA NA NA NA Alarm IS Barrier

102 ZSO-STHS100 Drum Level Switch 1 isolation valve 1 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

103 ZSO-STHS101 Drum Level Switch 1 isolation valve 2 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

104 ZSO-STHS102 Drum Level Switch 1 isolation valve 3 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

105 ZSO-STHS103 Drum Level Switch 1 isolation valve 4 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

106 ZSO-STHS104 Drum Level Switch 2 isolation valve 1 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 7 of 11

Page 8: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

107 ZSO-STHS105 Drum Level Switch 2 isolation valve 2 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

108 ZSO-STHS106 Drum Level Switch 2 isolation valve 3 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

109 ZSO-STHS107 Drum Level Switch 2 isolation valve 4 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

110 ZSO-STHS108 Drum Level Switch 3 isolation valve 1 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

111 ZSO-STHS109 Drum Level Switch 3 isolation valve 2 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

112 ZSO-STHS110 Drum Level Switch 3 isolation valve 3 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

113 ZSO-STHS111 Drum Level Switch 3 isolation valve 4 Open position. Water Field DCS Potential free NA NA NA NA NA NA NA NA IndicationProximity / IS Barrier

114 XA-Fire1 Fire System Common Alarm NAFire System

DCS Potential free NA NA NA NA NA NA NA NA Indication

115 XA-Fire2 Fire System Fault Alarm NAFire System

DCS Potential free NA NA NA NA NA NA NA NA Indication

116 XA-UPS UPS Fault Alarm NA UPS DCS Potential free NA NA NA NA NA NA NA NA Indication117 ZLO-483K003 Soot Blower 1 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication118 ZLC-483K003 Soot Blower 1 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication119 XS-483K003A Soot Blower 1 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication120 XS-483K003B Soot Blower 1 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication121 XA-483K003A Soot Blower 1 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm122 XA-483K003B Soot Blower 1 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication123 ZLO-483K004 Soot Blower 2 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication124 ZLC-483K004 Soot Blower 2 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication125 XS-483K004A Soot Blower 2 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication126 XS-483K004B Soot Blower 2 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication127 XA-483K004A Soot Blower 2 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm128 XA-483K004B Soot Blower 2 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication129 ZLO-483K005 Soot Blower 3 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication130 ZLC-483K005 Soot Blower 3 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication131 XS-483K005A Soot Blower 3 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication132 XS-483K005B Soot Blower 3 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication133 XA-483K005A Soot Blower 3 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm134 XA-483K005B Soot Blower 3 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication135 ZLO-483K006 Soot Blower 4 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication136 ZLC-483K006 Soot Blower 4 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication137 XS-483K006B Soot Blower 4 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication138 XS-483K006B Soot Blower 4 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication139 XA-483K006B Soot Blower 4 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm140 XA-483K006B Soot Blower 4 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication141 ZLO-483K007 Soot Blower 5 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication142 ZLC-483K007 Soot Blower 5 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication143 XS-483K007A Soot Blower 5 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication144 XS-483K007B Soot Blower 5 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication145 XA-483K007A Soot Blower 5 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm146 XA-483K007B Soot Blower 5 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication147 ZLO-483K008 Soot Blower 6 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication148 ZLC-483K008 Soot Blower 6 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication149 XS-483K008A Soot Blower 6 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication150 XS-483K008B Soot Blower 6 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication151 XA-483K008A Soot Blower 6 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 8 of 11

Page 9: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

152 XA-483K008B Soot Blower 6 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication153 ZLO-483K009 Soot Blower 7 in forward position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication154 ZLC-483K009 Soot Blower 7 in rest position Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication155 XS-483K009A Soot Blower 7 forwarding Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication156 XS-483K009B Soot Blower 7 retracting Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication157 XA-483K009A Soot Blower 7 motor tripped Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm158 XA-483K009B Soot Blower 7 Auto Selected Steam MCC DCS Potential free NA NA NA NA NA NA NA NA Indication159 XA-LV MCC1 LV MCC Incomer Fault NA MCC DCS Potential free NA NA NA NA NA NA NA NA Alarm160 XA-LV MCC2 LV MCC Incomer Output Supply Available NA MCC DCS Potential free NA NA NA NA NA NA NA NA Indication161 Spare IS Barrier162 Spare IS Barrier163 Spare IS Barrier164 Spare IS Barrier165 Spare IS Barrier166 Spare IS Barrier167 Spare IS Barrier168 Spare IS Barrier169 Spare IS Barrier170 Spare IS Barrier171 Spare IS Barrier172 Spare IS Barrier173 Spare IS Barrier174 Spare IS Barrier175 Spare IS Barrier176 Spare IS Barrier177 Spare IS Barrier178 Spare IS Barrier179 Spare IS Barrier180 Spare IS Barrier181 Spare IS Barrier182 Spare IS Barrier183 Spare IS Barrier184 Spare IS Barrier185 Spare IS Barrier186 Spare IS Barrier187 Spare IS Barrier188 Spare IS Barrier189 Spare IS Barrier190 Spare IS Barrier191 Spare IS Barrier192 Spare IS Barrier193 Spare IS Barrier194 Spare IS Barrier

1 HSO-483M021 Feedwater stop valve Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier2 HSC-483M021 Feedwater stop valve Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier3 HSO-483M022 Drum vent valve 2 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier4 HSC-483M022 Drum vent valve 2 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier5 HSO-483M023 Drum vent valve 1 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier6 HSC-483M023 Drum vent valve 1 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier7 HSO-483M024 Superheater drain valve 1 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier8 HSC-483M024 Superheater drain valve 1 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier9 HSO-483M025 Superheater drain valve 2 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier

10 HSC-483M025 Superheater drain valve 2 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier

Digital outputs (Potential free) to field/MCC/panels per Boiler

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 9 of 11

Page 10: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

11 HSO-483M026 Main steam vent valve Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier12 HSC-483M026 Main steam vent valve Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier13 HSO-483M027 Main steam stop valve Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier14 HSC-483M027 Main steam stop valve Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier15 HSO-483M028 Main steam stop valve bypass Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier16 HSC-483M028 Main steam stop valve bypass Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier17 HSO-483M029 Main steam drain valve 1 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier18 HSC-483M029 Main steam drain valve 1 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier19 HSO-483M030 Main steam drain valve 2 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier20 HSC-483M030 Main steam drain valve 2 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier21 HSO-483M031 SB steam inlet valve open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier22 HSC-483M031 SB steam inlet valve close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier23 HSO-483M032 SB steam drain valve 1 open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier24 HSC-483M032 SB steam drain valve 1 close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier25 HSO-483M033 SB steam drain valve 2 open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier26 HSC-483M033 SB steam drain valve 2 close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier27 HSO-483M034 Drum drain valve 1 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier28 HSC-483M034 Drum drain valve 1 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier29 HSO-483M035 Drum drain valve 2 Open command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier30 HSC-483M035 Drum drain valve 2 Close command. DCS Field Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier31 HSO-483M051 FD fan damper open command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier32 HSC-483M051 FD fan damper close command DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock IS Barrier33 HSO-483K001 FD fan motor start command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type34 HSC-483K001 FD fan motor stop command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous

35 HSO-483K002A Scanner fan 1 motor start command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type

36 HSC-483K002A Scanner fan 1 motor stop command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 37 HSO-483K002B Scanner fan 2 motor start command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type38 HSC-483K002B Scanner fan 2 motor stop command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 39 HSO-483P010A HP dosing pump 1 motor start command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type40 HSC-483P010A HP dosing pump 1 motor stop command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 41 HSO-483P010B HP dosing pump 2 motor start command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type42 HSC-483P010B HP dosing pump 2 motor stop command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 43 HSO-483N01 HP dosing stirrer motor start command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type44 HSC-483N01 HP dosing stirrer motor stop command. DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 45 HSO-483K003 Soot Blower 1 Forward DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type46 HSC-483K003 Soot Blower 1 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 47 HSO-483K004 Soot Blower 2 Start DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type48 HSC-483K004 Soot Blower 2 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 49 HSO-483K005 Soot Blower 3 Start DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type50 HSC-483K005 Soot Blower 3 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 51 HSO-483K006 Soot Blower 4 Start DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type52 HSC-483K006 Soot Blower 4 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 53 HSO-483K007 Soot Blower 5 Start DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type54 HSC-483K007 Soot Blower 5 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 55 HSO-483K008 Soot Blower 6 Start DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type56 HSC-483K008 Soot Blower 6 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 57 HSO-483K009 Soot Blower 7 Start DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Pulse type58 HSC-483K009 Soot Blower 7 Emergency Stop DCS MCC Potential free NA NA NA NA NA NA NA NA Interlock Continous 59 HSC-483801 Oil / Gas Firing Stop Command burner 1 DCS BMS Potential free NA NA NA NA NA NA NA NA Interlock Continous 60 HSC-483802 Oil / Gas Firing Stop Command burner 2 DCS BMS Potential free NA NA NA NA NA NA NA NA Interlock Continous 61 HSC-483803 Oil / Gas Firing Stop Command burner 3 DCS BMS Potential free NA NA NA NA NA NA NA NA Interlock Continous 62 HSC-483804 Oil / Gas Firing Stop Command burner 4 DCS BMS Potential free NA NA NA NA NA NA NA NA Interlock Continous 63 Spare IS Barrier

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 10 of 11

Page 11: Dcs Io List Rev0

DCS I/O List

Sr. No. Tag No. Description Service From To Type of signalNormal value

Indicating range Low

Indicating range high

Unit History Sqrt. Function Remarks

High Low

Alarm

64 Spare IS Barrier65 Spare IS Barrier66 Spare IS Barrier67 Spare IS Barrier68 Spare IS Barrier69 Spare IS Barrier70 Spare IS Barrier71 Spare IS Barrier72 Spare IS Barrier73 Spare IS Barrier74 Spare IS Barrier75 Spare IS Barrier

Made By Chkd. By Appd. ByNVK AKS AKS

CLIENT : M/s EGYPTIAN FERTILIZER COMPANY Boiler No. PR0191

Drg. No.I11-TO-CS-38894 Rev.0

Sheet 11 of 11