Upload
phungthuy
View
220
Download
1
Embed Size (px)
Citation preview
DETAILED REPORT ON OVERHAULING OF 30 MW GTG # 5 AT
RELIANCE INDUSTRIES LTD., HAZIRA Work Order Ref : Duration : 08.02.2008 to22.02.2008 Customer Coordinators : R. K. Bansal & Makarand Phadnis Site Engineer : Julius Tuscano Analysis by : Aditya Korde
Diagnostic Technologies India Pvt. Ltd.
1
TABLE OF CONTENTS
Page No.
Generator details 2
Executive summary 3
Visual inspection & corrective actions 4
Mechanical measurements 6 ♦ Mechanical clearances ♦ Air-gaps ♦ Interferences & dimensions ♦ Swing run-out ♦ Coupling bolt elongation ♦ Alignment
Electrical measurements 12 ♦ Insulation Resistance, Polarization Index & Dielectric Discharge ♦ Winding Circuit Analysis ♦ Step Voltage Test ♦ Digital Surge Comparison Test (Rotor & Stator) ♦ Diode Health Check ♦ Tan Delta & Capacitance Analysis ♦ Flux Loop Test ♦ ELCID Test ♦ Partial Discharge Analysis
On-line tests 31 ♦ Electrical Signature Analysis ♦ Vibration Analysis ♦ Acoustic Emission Analysis
Diagnostic Technologies India Pvt. Ltd.
2
GENERATOR DETAILS
Make : BHEL
KW : 30000
RPM : 3000
Power Factor : 0.80
Hertz : 50
KVA : 37500
Phase : 3
Stator Volts : 11000
Connection : Y
Stator Amps : 1968
Coolant : Air
Rotor Volts : 61
Rotor Amps : 221
Insulation Class : B
Type : TARI 800-26P
Specification : IS5422
Sr. No. : 1336
Division : Hyderabad
Year : 1996
BRUSHLESS EXCITER DETAILS
Type : ELR/44/22-30/6-3
Sr. No. : 10490
Insulation Class : B
KW : 136
Amps : 681
RPM : 3000
Excitation : 638 Watt
Volts : 51
Amps : 13
Diagnostic Technologies India Pvt. Ltd.
3
EXECUTIVE SUMMARY
Overall, the generator seems to be in healthy condition with no significant faults detected. Insulation resistance, polarization index, dielectric discharge ratio, step voltage test, surge test, circuit analysis, tan delta & capacitance analysis, rotor surge comparison test, ELCID and electrical signature analysis did not detect any defects. The PD levels on the generator are higher than on other identical generators at Hazira complex, indicating early insulation degradation. We recommended installing capacitive couplers on the generator so that PD can be monitored on-line in the future. The exciter bearing was found to have excessive clearances & was replaced. The new bearing’s condition is not very good (as revealed by vibration & acoustic emission analyses) & we recommend that original bearings be procured from the manufacturer for the future. For Diagnostic Technologies India Pvt. Ltd.
Aditya Korde Executive Director
Diagnostic Technologies India Pvt. Ltd.
4
GENERATOR VISUAL INSPECTION & CORRECTIVE ACTIONS
• Generator Stator: The bellow between inner end shields (EE) and exciter passage was found to be
in good condition. The same bellow was installed during assembly.
Oil deposition with carbon dust was observed on the stator overhang portion and core portion. This was thoroughly cleaned by spraying with solvents.
Stator overhang supports’ tightness was checked and found to be intact.
The stator overhang jumper support bolts were found intact.
Stator core bolts’ locking was checked and found to be intact.
Stator winding lacing was checked and found in good condition.
Stator core ventilating ducts were checked. No blockage was found in the holes.
Stator slot wedge mapping was done on all 54 slots. The readings were found
within the limits. The mapping chart is enclosed.
• Generator Rotor: Rotor was visually checked for any hotspot or flash over. Nothing was found.
Rotor wedges’ tightness was checked. No looseness was found.
The wedge locking grub screws’ tightness was checked. No looseness was
found.
Rotor cooling ducts were checked.
The retaining rings’ locking system was found to be intact.
Both sides’ shaft journals were found in good condition.
• Generator Exciter/PMG Stator: Stator wedges’ tightness was checked. No looseness was found.
Stator locking/pole locking tightness was checked and found to be intact.
Diagnostic Technologies India Pvt. Ltd.
5
• Generator Exciter/PMG Rotor:
Rotating diode fuses’ tightness & locking were checked. No looseness was found.
Rotor journal was checked with Ultrasonic & DP. No crack or deformities were
observed.
Exciter bearing clearance was high. New bearing was installed during assembly.
Diagnostic Technologies India Pvt. Ltd.
6
MECHANICAL MEASUREMENTS
(ALL READINGS IN MM) 1. Clearances of generator end shields before dismantling:
Turbine End Exciter End 0.65 0.80 0.50 0.40 0.45 0.50
0.25 0.25
2. Clearances of generator end shields after assembly: Turbine End Exciter End 0.30 0.50 0.25 0.28 0.50 0.50
0.15 0.10
3. Fan blades clearances of generator w.r.t. end shields (exciter side): BEFORE: AFTER:
4. Fan blades clearances of generator w.r.t. end shields (turbine side): BEFORE: AFTER:
Diagnostic Technologies India Pvt. Ltd.
7
5. Diode cover clearances of generator w.r.t. gen-exciter coupling: BEFORE: AFTER:
6. Air gap between exciter stator & rotor:
4.60 4.65 4.40 4.55
4.40 4.65
7. Air gap between PMG stator and rotor: BEFORE: AFTER:
8. Clearances of generator exciter end bearing oil deflector w.r.t. shaft:
Front side Back side
0.20 0.15 0.15 0.10 0.10 0.10 0.02 0.04
9. Clearances of generator turbine end bearing oil deflector w.r.t. shaft: Front side Back side
0.25 0.25 0.25 0.20 0.22 0.18 0.10 0.05
Diagnostic Technologies India Pvt. Ltd.
8
10. Side clearance of generator T/E bottom bearing:
0.37 RS 0.33
0.35 LS 0.35
11. Side clearance of generator E/E bottom bearing:
0.37 RS 0.33
0.35 LS 0.35
12. Generator T/E bearing clearance by lead wire: 0.33 mm 13. Generator E/E bearing clearance by lead wire: 0.34 mm
14. Exciter bearing clearance by lead wire: 0.26 mm
15. Generator T/E bearing interference : 0.02 mm 16. Generator E/E bearing interference : 0.03 mm
17. Exciter bearing interference: 0.02 mm
18. Insulation resistance of generator E/E bearing: 41.8 MΩ (500 V)
Diagnostic Technologies India Pvt. Ltd.
9
19. Generator alignment with load gear:
Axial reading taken by slip gauge:
Position Top Right Bottom Left 0° 7.42 7.38 7.37 7.38
90° 7.38 7.38 7.37 7.38 180° 7.39 7.37 7.37 7.38 270° 7.40 7.37 7.38 7.39 Total 29.59 29.51 29.49 29.53
Average 7.397 7.375 7.372 7.382
Radial Axial 0.00 0.00 -0.02(L) -0.03(R) (L) -0.02 - 0.01(R) -0.05 -0.02
20. Generator coupling bolt elongation after assembly:
Bolt no. Before Tightening
After Tightening Elongation
1 235.00 235.14 0.14
2 235.00 235.13 0.13
3 234.90 235.04 0.14
4 235.20 235.36 0.16
5 235.00 235.17 0.17
6 235.20 235.37 0.17
7 234.95 235.12 0.17
8 235.30 235.46 0.16
9 235.80 235.96 0.16
10 235.16 235.30 0.14
11 234.90 235.31 0.14
12 235.60 235.22 0.15
Diagnostic Technologies India Pvt. Ltd.
10
21. Stator Slot Wedge Mapping Chart:
Total no. of wedges: 540 Total no. of slots: 54 Wedge nos. 1 & 10 indicate end wedges
Wedge nos. 1 2 3 4 5 6 7 8 9 10 Slot nos.
1 0.43 0.72 2 0.37 0.35 3 0.29 0.44 4 0.52 0.70 5 0.40 0.40 6 0.46 0.65 7 0.44 0.69 8 0.25 0.56 9 .0.19 0.45 10 0.64 0.44 11 0.38 0.35 12 0.40 0.62 13 0.29 0.80 14 0.19 0.50 15 0.55 0.50 16 0.16 0.36 17 0.37 0.37 18 0.10 0.50 19 0.64 0.71 20 0.60 0.60 21 0.24 0.57 22 0.20 0.58 23 0.59 0.41 24 0.58 0.35 25 0.33 0.58 26 0.38 0.60 27 0.57 0.40 28 0.38 0.80 29 0.20 0.33 30 0.53 0.48 31 0.44 0.37 32 0.55 0.19 33 0.29 0.62 34 0.46 0.45 35 0.33 0.21 36 0.50 0.41 37 0.70 0.19 38 0.46 0.62 39 0.71 0.29
Diagnostic Technologies India Pvt. Ltd.
11
Wedge nos. 1 2 3 4 5 6 7 8 9 10 Slot nos.
40 0.50 0.35 41 0.52 0.42 42 0.35 0.29 43 0.19 0.44 44 0.62 0.58 45 0.32 0.40 46 0.45 0.24 47 0.64 0.32 48 0.29 0.43 49 0.21 0.69 50 0.36 0.15 51 0.62 0.33 52 0.56 0.45 53 0.29 0.46 54 0.75 0.38
Diagnostic Technologies India Pvt. Ltd.
12
ELECTRICAL MEASUREMENTS
1. Insulation Resistance, Polarization Index & Dielectric Discharge Ratio of Stator (at 5 kV, before cleaning):
Parameter R - Phase Y - Phase B - Phase R01 (GΩ) 3.39 3.01 3.15 R10 (GΩ) 16.4 14.9 15.1 R30 (GΩ) 41.4 43.3 41.7
PI 4.84 4.95 4.78 DD 1.25 1.24 1.24
Leakage Current (nA) 127.0 121.0 126.0 Capacitance (nF) 211.0 211.0 211.0
2. Insulation Resistance, Polarization Index & Dielectric Discharge Ratio of Stator (at 5 kV, after overhauling):
Parameter R - Phase Y - Phase B - Phase R01 (GΩ) 2.75 2.59 2.81 R10 (GΩ) 15.70 16.10 17.20 R30 (GΩ) 35.60 41.20 41.30
PI 5.73 6.23 6.12 DD 1.48 1.49 1.40
Leakage Current (nA) 147.0 127.0 127.0 Capacitance (nF) 213.0 213.0 210.0
3. Insulation Resistance of Rotor, Exciter Rotor & PMG (250 V):
Main Rotor 4.64 GΩ PMG Stator 3.16 GΩ Excitation Field 2.01 GΩ Exciter Rotor 560 MΩ
Diagnostic Technologies India Pvt. Ltd.
13
4. Resistance of Stator, Rotor, Exciter & PMG (with digital micro-ohmmeter):
Main Stator (Temp. 30° C): R1 – R2 Y1 – Y2 B1 – B2
5.03 mΩ 4.99 mΩ 5.04 mΩ
Main Rotor (Temp.30° C): 231 mΩ
Exciter stator (F1-F2) (Temp. 30° C): 2.219 mΩ Exciter Rotor (Temp. 30° C): R – Y Y – B B – R
5.55 mΩ 5.59 mΩ 5.52 mΩ
PMG (Temp. 30° C): R – Y Y – B B – R
71.92 mΩ 71.50 mΩ 71.86 mΩ
5. Generator Stator Winding Circuit Analysis with All Test IV (400 Hz): R Phase Y Phase B Phase
Resistance (Ω) 0.006 0.005 0.006
Impedance (Ω) 6 6 6
Inductance (mH) 1.23 1.24 1.23
I/F (%) -46 -45 -45
Phase angle (º) 57 57 57
6. Generator Rotor Winding Circuit Analysis with All Test 31 (400 Hz): Resistance (Ω)
Impedance (Ω) 33.5
Inductance (mH)
I/F (%) -38
Phase angle (º) 52
7. Exciter Field Winding Circuit Analysis with All Test IV (200 Hz): Resistance (Ω)
Impedance (Ω) 280
Inductance (mH) 229
I/F (%) -39
Phase angle (º) 60
Diagnostic Technologies India Pvt. Ltd.
14
8. Exciter Rotor Winding Circuit Analysis with All Test IV (400 Hz): U PHASE V PHASE W PHASE
Resistance (Ω)
Impedance (Ω) 0.26 0.26 0.26
Inductance (mH) 0.160 0.161 0.160
I/F (%) -2 -2 -2
Phase angle (º) 4 4 4
9. PMG Stator Winding Circuit Analysis with All Test IV (400 Hz): U PHASE V PHASE W PHASE
Resistance (Ω)
Impedance (Ω) 2.11 2.11 2.11
Inductance(mH) 0.861 0.862 0.860
I/F (%) -23 -24 -24
10. Diode Healthiness:
Diode No. Forward Bias Voltage (mV)
1 419 2 419 3 376 4 378 5 386 6 392 7 423 8 432 9 371
10 371 11 419 12 419 13 383 14 421 15 429 16 381 17 376 18 378
Diagnostic Technologies India Pvt. Ltd.
15
11. Step Voltage Test at 5 kV (by Tera-ohm meter):
Insulation Resistance (GΩ) Applied Voltage (V)
R Phase Y Phase B Phase
1058 53.50 5.91 1000.0
2108 6.92 4.81 10.10
3158 6.01 5.12 7.27
4205 6.08 5.57 6.94
5261 6.23 5.87 6.93
12. Digital surge comparison test of rotor winding (RSO): Connection between +ve to –ve:
Connection Reversed:
Perfectly congruent waveforms reveal that no inter-turn & earth faults are present in the rotor winding insulation. The rotor winding insulation system is in healthy condition.
Diagnostic Technologies India Pvt. Ltd.
16
13. Digital surge comparison test of stator winding:
R Phase:
Y Phase:
B Phase:
Diagnostic Technologies India Pvt. Ltd.
17
14. Tan Delta & Capacitance Test:
TAN DELTA CURVE
0
0.5
1
1.5
2
2.5
3
0 1000 2000 3000 4000 5000 6000 7000
APPLIED VOLTAGE (V)
TAN D
ELTA
(%)
R PHASEY PHASEB PHASE
CAPACITANCE CURVE
207
207.5
208
208.5
209
209.5
210
210.5
211
0 1000 2000 3000 4000 5000 6000 7000
APPLIED VOLTAGE (V)
CAPA
CIT
ANCE
(nF)
R PHASEY PHASEB PHASE
APPLIED VOLTAGE
(kV)
TAN DELTA (%) R Y B
CAPACITANCE (nF) R Y B
1.5 2.002 1.876 1.966 209.3 209.6 207.2
3 2.044 1.905 1.888 209.7 209.7 207.4
4.5 2.047 1.911 1.957 209.9 209.9 207.7
6 2.420 2.108 2.282 210.7 210.2 208.5 TIP-UP
(%) 0.14 0.14 0.11 0.67 0.29 0.63
Diagnostic Technologies India Pvt. Ltd.
18
15. Flux Loop Test on Generator Stator:
Number of turns: 3 Applied voltage: 440 V. Current passed: 140 Amps. Duration: 2 hrs Amb. Temp.: 280 Temp. after 1 hour 340 Purpose: Stator core hot spot checking & uniform heating of stator
core for drying out. No hot spot was observed. Stator core surface: Scanned by Raytek Infrared Thermometer Temperature difference at any two spots did not exceed 10° C Temperature monitoring chart (using above method):
Temperature 0C
Date
Time
Current (Amps)
Core (top)
Core (bottom)
EE Winding
TE Winding
10.02.08 20:00 HRS 134 24 24 24 24
21:00 “ 29 28 27 26
22:00 “ 32 31 29 28
23:00 “ 36 35 32 31
11.02.08 0:00 “ 40 38 32 31
1:00 “ 43 41 33 33
2:00 “ 45 43 38 38
3:00 “ 47 45 41 40
4:00 “ 51 50 41 41
5:00 “ 54 51 44 44
6:00 “ 57 55 44 44
7:00 “ 60 56 48 46
8:00 “ 60 56 48 46
9:00 “ 60 56 48 46
10:00
Stopped the heating and washing & cleaning cycle was done on stator winding
11.02.08 13:00 139 54 52 41 42
14:00 “ 55 54 42 44
15:00 “ 59 56 45 45
16:00 “ 63 59 49 48
17:00 “ 60 62 52 51
Diagnostic Technologies India Pvt. Ltd.
19
Temperature
0C
Date
Time
Current (Amps)
Core (top)
Core (bottom)
EE Winding
TE Winding
18:00 137 67 63 55 53
19:00 “ 69 66 57 56
20:00 “ 70 69 58 57
21:00 136 71 70 59 58
22:00 Washing and cleaning cycle was done in hot condition
12.02.08 1:00 126 74 74 54 53
2:00 75 74 56 54
3:00 76 75 58 57
4:00 77 76 59 58
5:00 78 77 60 59
6:00 79 77 61 60
7:00 79 76 61 60
Heating stopped for varnishing
Diagnostic Technologies India Pvt. Ltd.
20
16. Computerized Digital ELCID test:
Stator Core Details: No of slots : 54 Core length without step packets : 2.37 m
Standard Test Details: The required trace winding test voltage at 4% excitation level is given by 0.04 * Vp-p Vt = ----------------- 2√3 k Tp Vt - Test voltage measured in trace winding Vp-p - Rated phase - to - phase voltage Tp - Turns in series per phase k - Pitch factor (A value of 0.92 is used for all generators) From the above formula single turn excitation voltage at 4% of rated flux : 15.34 V Excitation Current : 10 A No of excitation turns : 9 Note:
i) In the graphs x - axis represents slot length excluding step packets & Y-axis represents leakage currents.
ii) Slot numbering was taken as per marked by the customer approximately at 6 'o clock position as Slot # 1 and progressed in clockwise direction from Exciter end (NDE)
All the slots were scanned with Chattock coil fitted on sense head trolley and the graphs showing leakage currents with core length were recorded. The leakage currents found in all the slots were less than the threshold value of 100 mA, indicating the healthiness of the core.
Diagnostic Technologies India Pvt. Ltd.
21
Diagnostic Technologies India Pvt. Ltd.
22
Diagnostic Technologies India Pvt. Ltd.
23
Diagnostic Technologies India Pvt. Ltd.
24
Diagnostic Technologies India Pvt. Ltd.
25
Diagnostic Technologies India Pvt. Ltd.
26
Diagnostic Technologies India Pvt. Ltd.
27
17. Off – Line Partial Discharge Analysis Test: Test was conducted by connecting 80 pF Epoxy Mica Capacitive Coupler to the energized winding and other LV side of the coupler is connected to the instrument via termination box. AC high voltage of 6 kV is applied between each phase and ground for 10 minutes. After 10 minutes the partial discharges graphs showing magnitude, pulse count and polarity of each individual phase are recorded. Test results are given overleaf.
Normalized Quantity Number
(NQN)
Maximum Pulse Amplitude
(Qmax)
Voltage
(kV)
Phase
Negative Positive Negative Positive
Gain
R 935 972 533 533 Y 645 731 300 300
6.0
B 876 922 466 433
3
Predominance of positive NQN values in all the phases indicates that the partial discharges are at semi-conductive coating / surface. The most likely locations for this activity are the coil sides within the slot or at the slot exits. Level of NQN and Q max values indicate the symptoms of insulation system ageing. Since this is the first time that the PDA test is conducted on stator winding, these values may be taken as base values for future reference and for trend analysis.
Diagnostic Technologies India Pvt. Ltd.
28
R – PHASE: A) PULSE HEIGHT: B) MAX. PULSE AMPLITUDE:
C) NQN: D) PULSE DISTRIBUTION
Diagnostic Technologies India Pvt. Ltd.
29
Y PHASE : A) PULSE HEIGHT B) MAX. PULSE AMPLITUDE:
C) NQN : D) PULSE DISTRIBUTION:
Diagnostic Technologies India Pvt. Ltd.
30
B PHASE: A) PULSE HEIGHT B) MAX. PULSE AMPLITUDE:
C) NQN: D) PULSE DISTRIBUTION:
Diagnostic Technologies India Pvt. Ltd.
31
Empath 2000 4.4 Analysis Results PERFORMANCE SUMMARY Bottom Line X This generator is operating normally, no action is required. This generator exhibits suspicious operation, trending of the generator is warranted. This generator exhibits abnormal indications, action is warranted, NOW. Power Factor Commentary Power factor exceeds 0.85. X Power factor is below 0.85, see detailed report. Current Commentary X Current variation is within normal limits. Current variation is beyond normal limits, see detailed report. Voltage Commentary X Voltage variation is within normal limits. Voltage variation is beyond normal limits, see detailed report. RMS voltage differs from nameplate by more than 5%. Load Commentary X Load on the generator is consistent with nameplate values. Load on the generator exceeds nameplate values, see detailed report. Load on the generator is less than 25%. Phase Connection Commentary X Connections are normal. Voltage ground reference is NOT neutral. Loose connection. Stator Commentary X Stator health is normal. Stator mechanical health is questionable. Turn to turn short. Harmonic Distortion Commentary X There is no evidence of harmonic distortion. There is evidence of harmonic distortion, see detailed report.
Diagnostic Technologies India Pvt. Ltd.
32
INPUT SUMMARY NAMEPLATE INFORMATION
Units Manufacturer BHEL Serial Number 1322 Model Number TARI 800-26P Generator type Generator Power 30000.0 KW RPM 3000 Rpm AC/DC AC Poles 2 Phases: 3 Voltage 11000.0 Volt Full Load Current 1968.00 Amp Number Stator Slots 54 Rotor Bars 24 Torque 95414 N.m CT Ratio 3000.000 PT Ratio 100.000 Duty Cycle **** Service Factor 115 Frame Size **** Insulation Type F Ambient Temperature 70.0 F° Generator efficiency -1.000 Power factor -1.000 LEGENDS: Impedance = Complex Impedance = vi/ci CF = Crest Factor = (waveform peak)/(waveform rms) THDF = Transformer Harmonic De-rating Factor = sqrt (2)/CF, % VDF = Voltage De-rating Factor = 100 - (voltage unbalance, %)^2, % Thd = Total harmonic distortion +Ve = Positive sequence harmonic -Ve = Negative sequence harmonic Zero = Zero sequence harmonic
Diagnostic Technologies India Pvt. Ltd.
33
Detailed Calculations
Running Speed = 49.986 Hz / 2999 Rpm Load = 75.0 %
Time RMS Peak CF Current 1 1470.000 2424.300 1.649 Current 2 1440.000 2127.000 1.477 Current 3 1440.000 2172.000 1.508 Average 1450.000 2241.100 1.545 % dev 1.4 8.2 6.8
THDF = 91.5
Time RMS Peak CF Voltage 1 11110.000 15823.000 1.424 Voltage 2 11120.000 15719.000 1.414 Voltage 3 11140.000 15772.000 1.416 Average 11123.000 15771.000 1.418 % dev 0.1 0.3 0.4
VDF = 100.0
App. Power Real Power Reac. Power Power factor Impedance kVA kW kVARS Phase 1 0.795 7.558 9437.400 7500.000 5728.400 Phase 2 0.813 7.722 9230.400 7500.000 5380.500 Phase 3 0.813 7.736 9230.400 7500.000 5380.500 Avg/Total 0.807 7.672 27898.000 22500.000 16489.000 % dev 1.5 1.5
Demand Pwr = 22500.0 KW
Harmonic Distortion Results: Voltage input, from 49.988 Hz harmonics THD Odd % THD Even % +ve% -ve % Zero % THD All % Current 1 0.586 0.561 0.356 0.604 0.409 0.811 Current 2 *** *** *** *** *** Current 3 *** *** *** *** *** Voltage 1 0.210 0.141 0.154 0.149 0.089 0.264 Voltage 2 *** *** *** *** *** Voltage 3 *** *** *** *** ***
Diagnostic Technologies India Pvt. Ltd.
34
Figure- 1: Current Harmonic distortion graph
Figure- 2: Voltage Harmonic distortion graph
Description: Plain bearings
Harmonic distortion table Hz Cur1 Vlt1 Cur2 Vlt2 Cur3 Vlt3 50 1589.7 10633 *** *** *** *** 100 5.1 0 *** *** *** *** 150 4.1 5 *** *** *** *** 200 3.8 0 *** *** *** *** 250 6.8 14 *** *** *** *** 300 2.6 0 *** *** *** *** 350 2.3 33 *** *** *** *** 400 1.8 0 *** *** *** *** 450 1.7 19 *** *** *** *** 500 2.0 0 *** *** *** *** 550 1.4 10 *** *** *** *** 600 1.3 0 *** *** *** *** 650 2.1 19 *** *** *** ***
Diagnostic Technologies India Pvt. Ltd.
35
Figure-3 Ch-1 Current-1
Figure-4 Ch-1 Current-1
Figure-5 Ch-2 Voltage-1
Figure-6 Ch-2 Voltage-1
Diagnostic Technologies India Pvt. Ltd.
36
Figure-7 Ch-9 Current-1 RMS
Figure-8 Ch-1 Current-1 spectra
Figure-9 Ch-9 Current-1 RMS spectra-Demod
Diagnostic Technologies India Pvt. Ltd.
37
GTG-5 - DE
orders0 20 40 60 80 100
mm
/s rm
s
0
1
2
O/All 3.068 mm/s rms
1
0
1
0
Machine Note (10/18/2005 3:08:56 PM)30 MW, 3000 RPM, 11 kV, 2099 A, BHELSr. No. 1336Point Note (10/11/2005 11:42:29 AM)Plain Bearing
HorizontalVel Freq 5000 Hz3/6/2008 2:27:28 PM
O/All 3.068 mm/s rms2998.203 RPM
VerticalVel Freq 5000 Hz3/6/2008 2:28:21 PM
O/All 1.885 mm/s rms2998.203 RPM
AxialVel Freq 5000 Hz3/6/2008 2:28:38 PM
O/All 1.71 mm/s rms2998.203 RPM
GTG-5 - NDE
orders0 20 40 60 80 100
mm
/s rm
s
0
1
2
3
4
5
6
O/All 6.882 mm/s rms
5
0
5
0
Machine Note (10/18/2005 3:08:56 PM)30 MW, 3000 RPM, 11 kV, 2099 A, BHELSr. No. 1336Point Note (10/11/2005 11:41:58 AM)Plain bearings
HorizontalVel Freq 5000 Hz3/6/2008 2:32:57 PM
O/All 6.882 mm/s rms2998.203 RPM
VerticalVel Freq 5000 Hz3/6/2008 2:33:51 PM
O/All 3.794 mm/s rms2998.203 RPM
AxialVel Freq 5000 Hz3/6/2008 2:32:29 PM
O/All 4.248 mm/s rms2998.203 RPM
VIBRATION ANALYSIS:
Diagnostic Technologies India Pvt. Ltd.
38
GTG-5 - Exciter NDE
orders0 20 40 60 80 100
mm
/s rm
s
0123456789
O/All 8.619 mm/s rms
6
0
6
0
Machine Note (10/18/2005 3:08:56 PM)30 MW, 3000 RPM, 11 kV, 2099 A, BHELSr. No. 1336
HorizontalVel Freq 5000 Hz3/6/2008 2:35:05 PM
O/All 8.619 mm/s rms2998.203 RPM
VerticalVel Freq 5000 Hz3/6/2008 2:34:21 PM
O/All 5.343 mm/s rms2998.203 RPM
AxialVel Freq 5000 Hz3/6/2008 2:34:42 PM
O/All 6.378 mm/s rms2998.203 RPM
GTG-5 - Exciter NDE
revs0 2 4 6 8 10
g
-10
0
10
O/All 1.209 g rms
0
-10
0
-10
Machine Note (10/18/2005 3:08:56 PM)30 MW, 3000 RPM, 11 kV, 2099 A, BHELSr. No. 1336
Bearing condition is poor, significant impacting evident.
HorizontalAcc Time 213 ms3/6/2008 2:34:58 PM
O/All 0.427 g rms2998.203 RPM
VerticalAcc Time 213 ms3/6/2008 2:34:15 PM
O/All 1.209 g rms2998.203 RPM
AxialAcc Time 213 ms3/6/2008 2:34:36 PM
O/All 0.64 g rms2998.203 RPM
Diagnostic Technologies India Pvt. Ltd.
39
ACOUSTIC EMISSION CHARTS: