EFFICIENCY AND PERFORMANCE MEASUREMENTS OF A PDC …
Upload
others
View
5
Download
0
Embed Size (px)
344 x 292
429 x 357
514 x 422
599 x 487
Citation preview
STAGE DIAPHRAGM HYDROGEN COMPRESSOR
In Partial Fulfillment
Master of Science
August, 2009
EFFICIENCY AND PERFORMANCE MEASUREMENTS OF A PDC INC. SINGLE
STAGE
DIAPHRAGM HYDROGEN COMPRESSOR
HUMBOLDT STATE UNIVERSITY
Dr. Peter Lehman, Major Professor Date
Dr. Charles Chamberlin, Committee Member Date
Dr. Christopher J. Dugaw, Committee Member Date
Dr. Christopher J. Dugaw, Graduate Coordinator Date
Dr. John Lyon, Dean Date Research & Graduate Studies
ABSTRACT
EFFICIENCY AND PERFORMANCE MEASUREMENTS OF A PDC INC. SINGLE
STAGE
DIAPHRAGM HYDROGEN COMPRESSOR
Andrea Leticia Allen
In this thesis I used measured data from Humboldt State
University’s hydrogen fueling
station, and ideal gas thermodynamic models, to calculate the
specific energy (kWh/kg)
and 2nd Law efficiency for a hydrogen compressor. I used adiabatic,
isothermal, and poly-
tropic thermodynamic models and found that the measured specific
energy was substan-
tially greater than that predicted using the models. The measured
specific energy was
approximately 8 kWh/kg compared to 1-1.5 kWh/kg for the
thermodynamic models. The
2nd Law efficiencies for the models varied from approximately 17%
relative to the adia-
batic model to approximately 11% relative to the polytropic model.
I speculate that the
large discrepancy between the measured and calculated specific
energies, and the low effi-
ciencies, is due to the details of the process the compressor uses
to compress gas; it is not
well modeled by an ideal gas process. I propose a preliminary model
that more accurately
represents the compressor’s operation, based on the Bernoulli
equation for fluid flow.
While collecting data for this analysis, my colleagues and I
noticed that the power used
by the compressor varies depending on the time of day. We
speculated that this was caused
by variation in the incoming line voltages for the compressor. I
monitored the line voltages
for ten days and found that they do vary depending on the time of
day. The compressor
power variation is correlated with that of the line voltage.
iii
ACKNOWLEDGEMENTS
There are many people who helped me along the way. Many thanks to
my committee
members. Peter, thank you for letting me take on this project and
putting up with all my
run-on sentences. Charles, thank you for your helpful data insights
and all your thoughtful
comments. Chris, thank you for all the LATEX help and introducing
me to the wonders of
find and replace.
Thanks to everyone at SERC for providing such a supportive work
environment. I’d
especially like to thank Greg Chapman for all the hard work as
project manager for the
fueling station, and for the insight about the compressor
operation. Scott and Marc, thank
you for your help in all things data acquisition.
Thanks to PGE’s Pacific Energy Center and their tool lending
library for use of the
ElitePro data logger. The lending library has been a valuable
resource for this and other
projects.
To my colleague, husband and best friend Peter Johnstone, I don’t
have enough space
to thank you for everything you’ve helped me with so I’ll keep it
short. Thanks for all the
MATLAB help and letting me hack apart you code for my own uses.
Thank you for all the
emotional support, shoulder rubs, cooked dinners, washed dishes and
thesis conversations.
Most importantly thank you for letting me love you and loving me
back.
Last, but certainly not least, thanks to Jumping Bean for
motivating me, like no one else
could, to get this thing finished. I can’t wait to meet you.
iv
METHODS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 25
RESULTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 32
Performance and Efficiency . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 53
CONCLUSION . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 69
BIBLIOGRAPHY . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 71
APPENDIX B: SAMPLE DATA FILE . . . . . . . . . . . . . . . . . . .
. . . . . . 75
APPENDIX C: EQUIPMENT DATA SHEETS . . . . . . . . . . . . . . . . .
. . . 76
APPENDIX D: MASS FLOW TRANSDUCER CALIBRATION . . . . . . . . . .
97
APPENDIX E: PROGRAM LISTING . . . . . . . . . . . . . . . . . . . .
. . . . . 102
vii
Figure Page
1 Ribbon cutting ceremony. Peter Lehman, SERC director cuts the
ribbon
while, left to right, congressman Mike Thompson, HSU president
Rollin
Richmond, and SERC engineer Greg Chapman, P.E. look on. . . . . . .
. . 3
2 HSU hydrogen fueling station with hydrogen powered Prius parked
in fu-
eling bay. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 4
3 A schematic of the fueling station. . . . . . . . . . . . . . . .
. . . . . . . 6
4 Schematic drawing of Humboldt State University’s Hydrogen Fueling
Station 8
5 Specific work curve for an adiabatic compression process with a
constant
suction pressure of 190 psig, suction temperature of 12 C, and
discharge
pressure varying from 200- 6000 psig. . . . . . . . . . . . . . . .
. . . . . 15
6 Specific work curve for an isothermal compression process with a
constant
temperature of 12 C, suction pressure of 190 psig, and discharge
pressure
varying from 200- 6000 psig. . . . . . . . . . . . . . . . . . . .
. . . . . . 17
7 Specific work curves for a polytropic compression process with
various
polytropic exponents. For all the curves the suction pressure is
190 psig,
suction temperature is 12 C, and discharge pressure varies from
200- 6000
psig. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 19
viii
8 Diaphragm compressor is shown at BDC at the start of compression
stroke.
At this part of the compression stroke there is low oil pressure
and low
hydrogen pressure. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 21
9 Diaphragm compressor shown mid compression stroke. The piston is
trav-
eling from BDC to TDC resulting in intermediate oil pressure and
interme-
diate hydrogen pressure. . . . . . . . . . . . . . . . . . . . . .
. . . . . . 23
10 Diaphragm compressor shown at TDC at the end of compression
stroke.
The oil pressure is high enough to flow past the relief valve
resulting in
high pressure hydrogen being pushed into storage. . . . . . . . . .
. . . . . 24
11 Measured compressor power for filling of both tanks . . . . . .
. . . . . . 33
12 Measured compressor power for versus time of day for filling
both tanks . . 35
13 Measured hydrogen flow versus compressor discharge pressure for
filling
of both tanks. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 37
14 Suction, discharge temperatures, and their difference versus
compressor
discharge pressure for filling of both tanks. The dips in
temperature occur
when the compressor is shut down. The temperature rises as the
compressor
head heats up while running. . . . . . . . . . . . . . . . . . . .
. . . . . . 39
15 Measured compressor suction pressure versus compressor discharge
pres-
sure for filling of both tanks. Notice the y-axes do not contain
the origin. . . 41
ix
16 Calculated ideal adiabatic power versus compressor discharge
pressure for
filling of both tanks. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 43
17 Calculated ideal isothermal power versus compressor discharge
for filling
of tank A. The curves are nearly identical due to the small
temperature
difference between the suction and discharge temperatures. . . . .
. . . . . 45
18 Calculated ideal isothermal power versus compressor discharge
for filling
of tank B. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 46
19 Calculated polytropic exponent versus compressor discharge
pressure for
filling of both tanks. The average value was use to calculate the
polytropic
power. Notice the y-axes do not contain the origin. . . . . . . . .
. . . . . 48
20 Calculated ideal polytropic power versus compressor discharge
pressure for
filling both tanks. For tank A, n=1.027. For tank B, n=1.026 . . .
. . . . . 50
21 All power curves, calculated and measured, versus compressor
discharge
pressure for filling of both tanks. Note the polytropic and
isothermal (using
the suction temperature) power curves are difficult to read because
they are
all very similar and overlap each other. . . . . . . . . . . . . .
. . . . . . . 52
22 Specific energy as measured and calculated for each ideal
thermodynamic
model for both tanks. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 54
23 2nd Law efficiency relative to each ideal thermodynamic model
for both tanks. 55
x
24 Percentage of energy used for compression compared to the LHV of
hydro-
gen as measured and for each ideal thermodynamic model for each
tank. . . 56
25 Compressor motor efficiency curve based on the manufacturer’s
data. . . . . 61
26 2nd Law efficiency as versus flow rate for compressor motor
efficiencies of
55 and 65% . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 63
27 Incoming compressor line voltages, with respect to ground,
versus time of
day. Notice the y-axis does not contain the origin. . . . . . . . .
. . . . . . 65
28 Compressor power versus line 1 voltage. Notice the y-axis does
not contain
the origin. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 66
29 Compressor power versus line 2 voltage. Notice the y-axis does
not contain
the origin. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 67
30 Compressor power versus line 3 voltage. Notice the y-axis does
not contain
the origin. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 68
31 Schematic of experimental setup used to calibrate the mass flow
transducer . 98
32 Apparent hydrogen flow versus mass flow transducer voltage. This
curve
was used to find the voltage offset at zero. . . . . . . . . . . .
. . . . . . . 100
33 Hydrogen flow measured by mass flow transducer versus measured
flow.
This plot was used to find the calibration curve for the MFT. . . .
. . . . . 101
xi
1 Data collected by the DAQ system and units . . . . . . . . . . .
. . . . . . 25
2 Data acquisition system measurements, transducers, and write
thresholds . . 27
3 Calculated power for different oil flow rates and motor
efficiencies and 2nd
Law efficiency . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 62
LIST OF VARIABLES
Symbol Definition Units k Ratio of specific heats Dimensionless,
specific to gas
(1.41 for hydrogen) m Mass flow rate kg/sec n Polytropic exponent
Dimensionless P0 Initial pressure (Suction) Pa or psig P1 Final
pressure (Discharge) Pa or psig R Gas constant (specific to gas)
4.1243 kJ/kg-K for hydrogen T Temperature C or K T0 Initial
(Suction) temperature C or K T1 Final (Discharge) temperature C or
K V Velocity m/s v0 Initial specific volume m3/kg W Work J w
Specific work J/kg W Power W Z Elevation m
1
INTRODUCTION
Hydrogen based transportation is becoming a feasible alternative to
petroleum based trans-
portation. A major advantage of hydrogen over petroleum is that it
can be produced from a
variety of fuel feedstocks, including renewable energy. When
hydrogen is used as a vehicle
fuel, the only emissions are water, and in the case of an internal
combustion engine, NOx.
For hydrogen to become a mainstream fuel, the economics of the
refueling infrastruc-
ture need to be favorable. Hydrogen has to be able to compete
economically with petroleum
for auto manufacturers, drivers, and fueling station owners to make
the switch. An impor-
tant aspect of the economics is the energy required to produce,
compress and dispense
hydrogen fuel. This thesis will focus on the compression fraction
of the energy required,
by studying the compressor at Humboldt State University’s hydrogen
fueling station. I
will calculate the efficiency of the compressor and the energy
required, on a mass basis, to
compress hydrogen produced at the station to our storage pressure.
The goal of this anal-
ysis is to provide efficiency and performance values for hydrogen
compressors for use in
economic modeling of hydrogen transportation.
Economic models can play an important part in determining the most
cost effective
ways to build a hydrogen infrastructure. Currently most economic
models rely on assump-
tions, rather than empirical data, for the costs and energy
requirements associated with
hydrogen refueling infrastructure. There are now hundreds of
fueling stations worldwide
(Fuel Cells 2000, 2009) that are in operation and these stations
should be used to provide
empirical values to refine economic models. To date there have been
very few studies that
use empirical data to determine the energy requirements to make and
compress hydrogen.
2
3
System Overview
On September 4, 2008 Humboldt State University (HSU) celebrated the
grand opening of
its hydrogen fueling station, Figure 1. The fueling station was
designed by engineers at
the Schatz Energy Research Center (SERC) at HSU, and built largely
by SERC and HSU
Plant Operations personnel. Funding for the station was provided by
Chevron Technology
Ventures, CalTrans, North Coast Air Quality Management District,
HSU and SERC. The
hydrogen station is the 23rd and currently the northernmost and
only rural link in Califor-
nia’s Hydrogen Highway Network (CaH2Net), Figure 2.
Figure 1: Ribbon cutting ceremony. Peter Lehman, SERC director cuts
the ribbon while, left to right, congressman Mike Thompson, HSU
president Rollin Richmond, and SERC engineer Greg Chapman, P.E.
look on.
4
Figure 2: HSU hydrogen fueling station with hydrogen powered Prius
parked in fueling bay.
5
Hydrogen for the fueling station is generated, compressed, and
stored on site. A simple
schematic of input and output flows can be found in Figure 3.
Hydrogen is generated by
a Proton Energy Systems1 HOGEN S40 proton exchange membrane
electrolyzer capable
of producing 2.3kg of hydrogen per day at a pressure of 200 pounds
per square inch gauge
(psig). The medium pressure hydrogen is pressurized to 6000 psig
for storage by a PDC2
single stage diaphragm compressor. High pressure gas is stored in
CPI3 storage tanks that
hold a total of 12 kg of hydrogen at 6000 psig. FTI4 manufactured
the dispenser, which
is capable of filling a vehicle storage tank to 5000 psig. A more
detailed schematic of the
fueling station can be found in Figure 4.
Currently the station is serving one vehicle, a Toyota Prius
converted by Quantum Tech-
nologies to run on hydrogen5. We estimate the fueling station has
the capacity to serve 3-4
total vehicles. An important part of all of SERC’s projects is data
collection and dissem-
1www.protonenergy.com 2www.pdcmachines.com 3www.cp-industries.com
4www.fuelingtech.com 5The Prius uses an internal combustion engine,
not a fuel cell like most of new hydrogen powered vehicles.
6
7
ination. Because the design work was done by SERC, we were able to
incorporate data
collection into the system. Our data acquisition (DAQ) system
measures and records:
• Power used by the electrolyzer
• Power used by the compressor
• Pressure of the hydrogen exiting the electrolyzer, which is also
the compressor suc- tion pressure
• Pressure of each storage tank. The discharge pressure of the
compressor corresponds to the pressure of the tank with the lowest
pressure. If both tanks are at the same pres- sure the compressor
discharge pressure corresponds to the uniform tank pressure6
• Hydrogen flow, either from the electrolyzer (hydrogen generated)
or to the compres- sor (hydrogen compressed), depending on a valve
setting.
• Two temperatures. The thermocouples have the ability to be placed
in four different locations see Figure 4. The location depends on
the data desired; for this report they were located on the
compressor suction and discharge lines.
Our DAQ system enables SERC to report accurate information
regarding the energy
requirements for producing and delivering high purity, high
pressure hydrogen.
6The station was designed for cascade fueling and bulk storage tank
filling. This means that when a car is fueled, gas is taken from
one tank at a time, for our station, tank A followed by tank B.
This allows one tank to end up at a higher pressure than it would
have been if fueling took place from both tanks simultaneously.
This is useful when more than one vehicle fuels before the storage
tanks are fully replenished with hydrogen.
Bulk filling of the tanks means that both tanks are filled
simultaneously. However, because of check valves in the lines from
the compressor discharge to the tanks’ inlets, the tank with the
lower pressure is filled exclusively until it reaches the same
pressure as the higher pressure tank. Once the tanks are at the
same pressure they are filled simultaneously. This is not relevant
to this analysis as the tanks were filled independently to provide
more data. For this analysis the compressor discharge pressure
corresponded to the pressure in the tank being filled.
8
Fi gu
re 4:
Sc he
m at
ic dr
aw in
g of
H um
bo ld
tS ta
te U
ni ve
rs ity
’s H
yd ro
ge n
Fu el
in g
St at
io n
LITERATURE REVIEW
Hydrogen Transportation
There has been interest in hydrogen based transportation for as
long as there has been in-
terest in the internal combustion engine. The first internal
combustion engine was built by
Francois Isaac de Rivaz in 1807 using hydrogen for fuel (Holland
and Provenzano, 2007).
Modern automakers have made cars that use hydrogen as a fuel since
at least the 1940’s
with several vehicles manufactured from the late 1960’s through
modern times (H2 mobil-
ity, 2009). SERC built the first highway legal proton exchange
membrane (PEM) hydrogen
fuel cell vehicle in 1998 (Schatz Energy Research Center, 2009).
Currently many major
automobile companies are developing hydrogen vehicles. Honda has
begun leasing 200
PEM fuel cell vehicles, called the Clarity, in Southern California
(American Honda Motor
Co., 2009). Daimler also has a fuel cell vehicle under development,
the Mercedes-Benz
F-Cell, expected to be available to the public in 2010
(Mercedes-Benz, 2009). American
auto manufacturers are also developing hydrogen cars. General
Motors launched “Project
Driveway” in 2008, deploying a test fleet of fuel cell Chevrolet
Equinox vehicles in New
York City, Washington D.C. and Southern California (General Motor
Company, 2009).
Ford has a plug-in hybrid fuel cell vehicle, the Ford Edge, being
road tested, as well as 30
fuel cell Focus vehicles that have accumulated over 300,000 miles
as of this writing (Ford
Motor Company, 2009).
Even though hydrogen as a transportation fuel has been around for
as long as there
has been internal combustion, it has never threatened to replace
gasoline as the dominant
transportation fuel. Petroleum, and therefore gasoline, has been
inexpensive7 since World
7The real price of gasoline at the pump has generally decreased
from the 1940s until the terrorist attacks on September 11, 2001
and the start of the Iraq and Afghanistan wars. The major
exceptions to this trend occurred in 1970s and 80s and were caused
by the OPEC embargo and the Iraq/Iran wars (Energy
Information
9
10
War II (Vatter and Walker, 1996), and we did not know the long term
consequence of fos-
sil fuel use, namely global climate change, until relatively
recently. A major hurdle for
switching to a new transportation fuel is building new
infrastructure; there is currently a
vast infrastructure in place to deliver gasoline to drivers, but
very little for delivering hy-
drogen (Department of Energy, 2009). Switching to an alternative
fuel, such as hydrogen
would pose a ‘chicken and egg’ problem. Auto manufacturers do not
want to make hy-
drogen vehicles if there is no infrastructure to support them and
investors do not want to
build hydrogen fueling stations if there is not enough demand for
the fuel due to a lack of
available vehicles.
To help solve this problem, the California state government
initiated the California
Hydrogen Highway Network (CaH2Net) in April 2004 by Executive Order
S-07-04. The
stated purposes of the order are to encourage the transition to
hydrogen based transportation
in California, reduce dependence on foreign oil, reduce greenhouse
gas emissions, improve
air quality, and stimulate the economy (Schwarzenegger,
2004).
For a transition to a hydrogen based transportation system to be
successful, it has to
be economically feasible. A major aspect to the economics of
hydrogen transportation is
the production of hydrogen itself. Hydrogen, though the most
abundant element in the
universe, does not occur naturally on earth in its elemental state.
It is always found in
molecules with other elements. To produce elemental hydrogen, it
must be cracked out of
molecules that contain it, either chemically or electrolytically.
Thus, hydrogen is an energy
carrier rather than a fuel source like fossil fuels. This means
that there is more energy
associated with producing hydrogen than energy contained in the
hydrogen.
Since hydrogen is an energy carrier rather than an energy source,
the amount of energy
required to produce it affects the economics. For my analysis I
will use the term specific
Agency, 2009). These spikes also created a demand for fuel
efficient vehicles.
11
energy to quantify the energy intensity of producing hydrogen.
Specific energy is the en-
ergy required to produce a unit of mass of hydrogen, with the units
of kWh/kg. Specific
energy can be calculated for any step, or combination of steps, in
the production chain,
i.e. the specific energy for electrolysis, compression, or the
entire generation, compression
and dispensing process. The specific energy for the entire
production chain needs to be
accounted for to get a realistic view of the economics of hydrogen
transportation. For the
purpose of this analysis, I will focus on one aspect of the chain,
compression.
Hydrogen in its elemental state at normal everyday conditions
(temperature and pres-
sures) is a diatomic gas. For hydrogen to have a large enough
volumetric energy density
to be useful as a vehicle fuel it must be compressed. Gasoline has
the advantage of be-
ing a liquid with a high volumetric energy density. The average
volumetric energy density
for regular gasoline is 8,700 Wh/liter. Hydrogen at atmospheric
pressure and temperature
contains less than 35 Wh/liter (Fuel Cells for Power, 2009). Thus
compression is necessary.
There are several studies that estimate the specific energy to
compress hydrogen gas,
most of those coming out of the Institute for Transportation
Studies at the University of
California, Davis (ITS-Davis). ITS-Davis has been a leader in
studying the transition to
hydrogen transportation. Yang and Ogden (2007) estimated that the
energy for hydrogen
compression is 0.7-1 kWh/kgH2, approximately 2-3% of the lower
heating value (LHV)8
of the the hydrogen. The authors do not state the assumed type of
compressor, suction and
discharge pressures, or the mass flow rate of hydrogen through the
compressor. In another
ITS-Davis paper, Weinert et al. (2007) state that, for a diaphragm
compressor with an
isentropic efficiency of 65% operating between 200 psig and 6250
psig, the specific energy
for compression is 2.1 kWh/kgH2, approximately 6% of the LHV. Again
the assumed mass
flow rate of hydrogen is not stated. However, the suction and
discharge pressures cited by
8The lower heating value of hydrogen is 33.39 kWh/kg
12
Wienert et al. are very close to the operating pressures of the HSU
compressor, and both are
diaphragm compressors. Amos (1998) states that the energy to
compress hydrogen from
atmospheric pressure to 2800 psig can be 8-10% of the energy
content of hydrogen 9.
Each of these studies use thermodynamic models (to be discussed in
greater detail
below) to calculate the specific energy, and not empirical data
from actual compressors.
One company, Linde, has an ionic compressor, as part of a hydrogen
refueler package,
that they state uses 2.3 kWh/kg. It was introduced into US markets
at the 2009 National
Hydrogen Association conference (Linde Group, 2009). I was unable
to find similar data
from other compressor manufacturers.
Definitions of Efficiency
In this analysis the definition of efficiency that I will be using
is 2nd Law efficiency based
on the second law of thermodynamics. This definition of efficiency
compares the energy
of an ideal (reversible) process to the energy required by a real
process. For a compressor,
or any energy consuming device, it is given below (Cengel and
Boles, 1998).
ηII = Wideal
Wideal is the ideal process work requirement (J)
Wactual is the work required for the real process (J)
I will use this definition to find the efficiency of the compressor
based on various ideal
gas thermodynamic models.
9Amos did not state whether the LHV or HHV was used for this
calculation.
13
Thermodynamic models
In this section I present the three thermodynamic models of
compression used for my anal-
ysis: adiabatic, isothermal, and polytropic. Each model will be
used to calculate the mini-
mum required specific work. Power can then be found from the
specific work by multiply-
ing by the mass flow rate of hydrogen, as shown in equation
(2).
W = wm (2)
m is hydrogen mass flow (kg/s)
For all the models I assume that hydrogen is an ideal gas. This is
a good assumption for
our compressor at the suction pressure and temperature and low
discharge pressures and
temperatures. The compressibility factor, Z, varies from 1.0088 at
the suction temperature
and pressure (approximately 35 C and 200 psig, to 1.04511 at 1160
psig and 65 C (Perry
et al., 1997). At higher discharge pressures hydrogen acts less as
an ideal gas; Z is 1.2359 at
5800 psig and 65 C. Assuming that hydrogen is an idea gas affects
the 2nd Law efficiency
of each of the models. However, the deviation between treating
hydrogen as ideal versus a
real gas is less than 10%. Appendix A shows the analysis I used to
compare the effects of
treating hydrogen as a real rather than ideal gas.
Adiabatic Compression
An adiabatic process is one in which there is no heat transfer into
or out of the system. For a
reversible process this would indicate that it is also isentropic.
An ideal gas that undergoes
14
adiabatic compression has a temperature increase dependent on the
compression ratio, or
the ratio of inlet pressure to the outlet pressure. The equation
for finding the specific work
required by an adiabatic process is given below (Cengel and Boles,
1998).
w = kRT0
k − 1
where w is the specific work required (J/kg)
k is the ratio of specific heats of the gas (1.41 for
hydrogen)
R is the gas constant (4.1243 kJ/kgK for hydrogen)
T0 is the initial Temperature (K)
P0 is the initial pressure (Pa)
P1 is the final pressure (Pa)
An example adiabatic compression process is shown in Figure 5
below. To calculate
this curve I assumed conditions similar to our compressor:
• Suction pressure of 190 psig,
• Suction temperature of 12 C,
• Discharge pressure varies from 200 psig to 6000 psig.
Notice that as the discharge pressure increases the specific work
required for compression
also increases.
15
Figure 5: Specific work curve for an adiabatic compression process
with a constant suction pressure of 190 psig, suction temperature
of 12 C, and discharge pressure varying from 200- 6000 psig.
16
Isothermal Compression
An isothermal process is one in which the temperature remains
constant throughout the
process. The equation for specific work for an ideal gas undergoing
isothermal compression
is given by equation (4) below (Cengel and Boles, 1998).
w = RTln ( P1
where T is the process temperature (K)
A lower process temperature leads to a smaller specific work. An
actual isothermal
compressor would require some type of cooling to keep the gas at a
constant temperature
throughout the process. This adds complication, and hence cost,
both initial and ongoing, to
the compressor. Large compressors, however, often have some type of
cooling mechanism
to improve their efficiency. An example curve for an isothermal
compression process is
given in Figure 6 below. The temperature is assumed to be 12 C with
a suction pressure of
190 psig and discharge pressure varying from 200-6000psig. Notice
that the specific work
is lower than for the adiabatic curve. At 6000 psig discharge
pressure, the specific work
for the adiabatic process is approximately 7000 kJ/kg while for the
isothermal process, the
specific work is approximately 4750 kJ/kg, 32% less.
17
0
1000
2000
3000
4000
5000
6000
7000
8000
Sp ec
ific W
or k
(k J/
Discharge Pressure (psig)
Figure 6: Specific work curve for an isothermal compression process
with a constant tem- perature of 12 C, suction pressure of 190
psig, and discharge pressure varying from 200- 6000 psig.
18
A polytropic process is one defined by equation (5) below.
PV n = C (5)
n is an exponent that depends on the process.
If n = 1 the process is isothermal; if n = k the process is
adiabatic.
The equation for specific work for a polytropic compression process
is given below
(Cengel and Boles, 1998).
− 1
(6)
Example curves for several polytropic exponents are given in Figure
7 below for n =
1.1, 1.2, and 1.3. All of the curves assume:
• Suction temperature of 12 C
• Suction pressure 190 psig
19
0
1000
2000
3000
4000
5000
6000
7000
8000
S pe
cif ic
W or
k (k
J/ kg
n=1.1
n=1.2
n=1.3
Figure 7: Specific work curves for a polytropic compression process
with various poly- tropic exponents. For all the curves the suction
pressure is 190 psig, suction temperature is 12 C, and discharge
pressure varies from 200- 6000 psig.
20
There was limited literature available concerning hydrogen
compressor efficiency. Amos
(1998) states that large compressors have an efficiency of 65-70%,
while small compressors
have an efficiency of 40-50%, though there is no quantification for
“big” and “small”.
The Department of Energy’s Hydrogen Analysis (H2A) Project,
developed a Microsoft
ExcelTM based economic analysis tool to estimate the costs of
different types of hydrogen
fueling stations. For compressors the default assumption is an
isentropic (adiabatic) model
with an efficiency of 70% (H2A Group, 2006). The default can be
changed by the user if
sufficient data are available.
An adiabatic process is a common assumption for positive
displacement compressors.
Positive displacement compressors, of which a diaphragm compressor
is one type, are usu-
ally considered adiabatic (which for a reversible process would
also be isentropic) (Marks,
1996).
PDC Inc. Single Stage Diaphragm Compressor
The compressor under study is a single stage diaphragm compressor
configured specifically
for our application by Pressure Dynamic Consultants (PDC Machines,
Inc.). The compres-
sor can compress hydrogen with an inlet pressure range of 75-200
psig to a maximum
discharge pressure of 6000 psig.
The diaphragm compressor has a head consisting of two chambers
separated by a flex-
ible metal diaphragm as shown in Figure 8. Hydrogen gas is confined
to one chamber and
oil to the other. The hydrogen suction and discharge lines have
one-way poppet valves (a
type of check valve) to prevent reverse hydrogen flow. The oil
injection line has a check
valve allowing oil flow in one direction. Oil flow out of the oil
side occurs through a pres-
21
sure relief valve set to open once the desired oil pressure has
been reached, 6800 psig for
our compressor. Oil pressure in the head is increased with a
piston, causing the diaphragm
to flex, compressing the hydrogen.
Figure 8: Diaphragm compressor is shown at BDC at the start of
compression stroke. At this part of the compression stroke there is
low oil pressure and low hydrogen pressure.
A compression cycle works as follows. During the inlet stroke the
piston moves to its
bottom dead center (BDC) position and the pressure on the gas side
of the cavity decreases
allowing the suction valve to open and gas to flow into the cavity
as shown in Figure 8. Gas
flows into the cavity until the piston reaches BDC. As the piston
starts to move upward, the
22
suction check valve closes and the gas compression begins. As the
piston moves towards
top dead center (TDC), pressure inside the gas cavity increases
until the pressure inside the
cavity is greater than the storage pressure and the discharge check
valve opens allowing
gas to flow to storage as shown in Figure 9. Flow will continue out
of the cavity until
the piston reaches TDC. At TDC the diaphragm is completely flexed
ensuring most of the
gas in the cavity is pushed into storage as shown in Figure 10. The
piston then returns to
BDC stopping the discharge flow. During the downward stroke to BDC,
pressure inside
the hydrogen cavity decreases allowing gas to flow in through the
suction valve starting the
cycle again. To replace the oil that flows out of the cavity
through the pressure relief valve,
make-up oil is injected at the beginning of each stroke.
23
Figure 9: Diaphragm compressor shown mid compression stroke. The
piston is travel- ing from BDC to TDC resulting in intermediate oil
pressure and intermediate hydrogen pressure.
24
Figure 10: Diaphragm compressor shown at TDC at the end of
compression stroke. The oil pressure is high enough to flow past
the relief valve resulting in high pressure hydrogen being pushed
into storage.
METHODS
The data for my analysis were recorded during the initial filling
of the fueling station stor-
age tanks between June 28, 2008 and July 7, 2008. The tanks were
filled independently to
gather more data and have replicate measurements. I extracted the
data during the times
when the system was in standby to eliminate standby losses in my
analysis. For my data
analysis I used The MathworksTM MATLAB R© programming language to
write analysis
scripts for the data files created by the data acquisition (DAQ)
system. A more detailed
account of data analysis is given below in the Data Analysis
section.
Data Acquisition
Our DAQ system records the information shown in Table 1.
Table 1: Data collected by the DAQ system and units
Measurement Range Units Time Stamp 00:00:00 -1:00:00 HH:MM:SS
Program Run Hours none Hours Compressor Suction Temperature
-100−260 C Compressor Discharge Temperature -100−260 C Tank A
Pressure 0−7,000 psig Tank B Pressure 0−7,000 psig Hydrogen Flow
0−100 slm Suction Pressure 0−250 psig Electrolyzer Power 0−20,000
Watts Compressor Power 0−6,000 Watts
Data acquisition is controlled by an AdvantechTM field computer
running a LabviewTM
program written specifically for our application. Data are measured
on a digital back plane
with separate differential channels for each transducer. The
channels are scanned at 1000
25
26
Hz. To reduce noise in the signals, 100 sequential points from each
channel are averaged
together resulting in a time average sampling rate of 10 samples
per second for all the
channels. To reduce the amount of data actually written to a data
file, a sample (a set of
values for all 10 channels) must meet one of the following
conditions to be written to a data
file.
• The data acquisition program is reset.
• A new data file is created (this happens at midnight or if there
is a safety shutdown).
• A sample differs from the previously written data point by an
amount equal to or greater than that channel’s threshold.
Thresholds are shown in Table 2.
• More than 60 seconds have passed since the last data write.
• A minimum interval of 2 seconds has passed.
If none of the conditions are met, the sample is discarded and the
next sample is tested
against the conditions. Table 2 lists the transducers we are using
for the measurements
needed for this thesis, the write thresholds for each channel and
the accuracy and response
time for the transducers. An example data file is shown in Appendix
B and specification
sheets for components of our DAQ system are given in Appendix
C.
Data Analysis
I used the MATLAB R© programming language for all my data
processing. For each row of
data in the data files I calculated the power that would be
required for each of the thermo-
dynamic models, using equations (7) - (10) presented below,
assuming the same operating
conditions as those measured . I then used numerical integration to
estimate the total energy
actually used by the compressor, and the minimum required energy
for each of the models
27
28
using equation (11). To find the specific energy, I needed to
estimate the total amount of
hydrogen that was compressed. I again used numerical integration
for the hydrogen flow
rate using equation (12). I calculated the specific energy based on
compressor measure-
ments and for each of the models by dividing the total energy
consumption by the total
mass of hydrogen compressed, see equation (13). To find the 2nd Law
efficiencies I divided
the specific energies predicted for each of the models by the
measured specific energy, as
shown in equation (15).
Thermodynamic models
To find the ideal power consumption of the compressor, I used three
different thermody-
namic models: adiabatic, isothermal, and polytropic. The inputs to
the models were the
measured operating temperatures and pressures of the suction and
discharge lines, as well
as the measured mass flow into the compressor. Each of the inputs
was converted to appro-
priate units within the MATLAB R© scripts.
Adiabatic Power
To find the ideal adiabatic power I used the following
equation.
W = mwadiabatic (7)
m is the measured hydrogen flow rate (kg/s)
wadiabatic is the specific work (J/kg) required for an ideal
adiabatic process with
the same operating parameters, i.e. suction and discharge
pressures.
29
The equation for power of an isothermal compression process
is
W = mwisothermal (8)
wherewisothermal is the specific work required for an ideal
isothermal process with the same
operating parameters (J/kg)
Polytropic Power
For the polytropic case I first needed to calculate the polytropic
exponent n. According
to Marks’ Handbook (1996), if the suction and discharge
temperatures and pressures are
known, n can by found by using equation (9) below.
n = 1
) (9)
I found n for each row in the data file and then found the average
for the all the data. I
used the average to calculate the power for the polytropic process.
The power required for
a polytropic compression process is then given by:
W = mwpolytropic (10)
where wpolytropic is the specific work required for an ideal
polytropic process with the same
operating parameters (J/kg)
Specific Energy and Efficiency
To find the total energy required for each of the models, as well
as the measured data, I
used the trapezoidal Riemann sum, given in equation (11) to
numerically integrate power
over time. The power for each time step (a row in the data file)
was either measured
or found using equations (7) - (10). I then found the energy for
each time step in the
data file and summed them to get the total energy, in kWh, for
filling each tank. To find
the total hydrogen mass compressed, I again used the trapezoidal
Riemann sum, given in
equation (12). The mass flow measured by the mass flow transducer
for each row of data
was converted from slm to kg/hr. I assumed standard conditions of 1
atmosphere and 20C
to do the conversion, based on the mass flow transducer’s
calibration. I calculated the
mass compressed for each row in the data file and summed them to
estimate the total mass
of hydrogen compressed for each tank filling. I then used equation
(13) to calculate the
specific energy. I also found the specific energy as a percentage
of the of energy contained
in the hydrogen on a LHV basis using equation (14).
E = N∑
j=0
where E is the total energy used for compression (kWh)
tj is the time stamp in the jth row of the data file (hr)
Wj is the power (measured or calculated) in the jth row of the data
file (W)
mtotal = N∑
j=0
where mtotal is the total mass of hydrogen compressed (kg)
tj is the time stamp in the jth row of the data file (hr)
31
mj is the mass flow in the jth row of the data file (kg/hr)
w = E
mtotal
(13)
where w is the specific energy for the given process (kWh/kg)
E is the total energy required for compression (kWh)
mtotal is the total mass of hydrogen compressed (kg)
%LHV = w
LHV ∗ 100% (14)
where %LHV is the percentage of energy contained in 1 kg of
hydrogen, on a LHV
basis, that is used in the compression process
w is the specific energy for the give process (kWh/kg)
LHV is 33.39 kWh/kg for hydrogen
To find the 2nd Law efficiency relative to each of the models I
divided the theoretical
specific energy for each by the measured specific energy as shown
in equation (15) below.
ηII = wcalc
where ηII is the 2nd Law efficiency
wcalc is the ideal specific work for the thermodynamic model
(kWh/kg)
wmeasured is the measured specific work of the fill (kWh/kg)
RESULTS
This chapter presents the results of my analysis. It is divided
into three sections. The first
section presents the data measured during the tank fills, the
second section presents the
predicted power results for the various thermodynamic models using
the measured data as
inputs, and the third section presents the specific energy and 2nd
Law efficiencies of each
of the models for both tank fills.
Measured Data
This section presents the data measured from the compressor. The
suction and discharge
temperatures and pressures, and the hydrogen flow rates were used
as input to the thermo-
dynamic models that I investigated.
Power
Figure 11 presents the measured power used to fill tanks A and B.
The fluctuations seen are
caused by fluctuations in the incoming line voltage and are
discussed in more detail in the
Discussion chapter.
Measured Power
Po we
r ( W
Po we
r ( W
Figure 11: Measured compressor power for filling of both
tanks
34
Looking at the measured compressor energy versus pressure, note
that there are sur-
prising fluctuations in the power. When the same data are looked at
in a different way a
more obvious pattern emerges: the power fluctuates as a function of
the time of the day as
seen in Figure 12.
35
600
650
700
750
800
850
900
950
1000
0 2 4 6 8 10 12 14 16 18 20 22 24
Compressor Power
Po we
r ( W
600
650
700
750
800
850
900
950
1000
0 2 4 6 8 10 12 14 16 18 20 22 24
Compressor Power
Po we
r ( W
Hour of Day
(b) Tank B
Figure 12: Measured compressor power for versus time of day for
filling both tanks
36
Hydrogen Flow
Figure 13 presents measurements of hydrogen flow versus discharge
pressure for each tank.
The spikes in the flow rate occur when the compressor is first
turned on and the ballast tank
is full. The system was initially powered down at the end of the
day so that it did not
run unsupervised before we were confident that everything was
running properly. Because
of this the compressor was cycled on and off several times during
both fills causing the
observed spikes. Oscillations in the flow rate result as the
electrolyzer goes into and out
of standby mode. The flow decreases until the ballast tank pressure
drops to 185 psig,
at which point the electrolyzer comes out of standby and flow
increases. This cycling is
clearly seen at higher pressures (>5000 psig).
37
0
10
20
30
40
50
60
Hydrogen Flow
Hy dr
og en
F lo
w (s
Hydrogen Flow
Hy dr
og en
F lo
w (s
Figure 13: Measured hydrogen flow versus compressor discharge
pressure for filling of both tanks.
38
Temperature
Figure 14 presents the measured temperature for the suction and
discharge lines of the
compressor, and the difference between them. The suction and
discharge temperatures
generally track each other and the difference between them is
relatively constant when the
compressor is running.
Te m
pe ra
tu re
( o C)
Te m
pe ra
tu re
( o C)
Discharge Pressure (psig)
(b) Tank B
Figure 14: Suction, discharge temperatures, and their difference
versus compressor dis- charge pressure for filling of both tanks.
The dips in temperature occur when the compres- sor is shut down.
The temperature rises as the compressor head heats up while
running.
40
Suction Pressure
This section presents the relationship between the suction pressure
and the discharge pres-
sure for both fills. The suction pressure steadily increases until
the it reaches 200 psig, the
maximum pressure output of the electrolyzer. When the ballast tank
reaches this pressure,
the electrolyzer goes into standby and does not resume hydrogen
production until the bal-
last pressure decreases to 185 psig. This is the reason for the
cycling at higher discharge
pressures that is observed for both tanks. Spikes in the suction
pressure result when the
compressor is stopped and the electrolyzer has a chance to fill the
ballast tank before the
compressor is turned on again. This is the case when the system is
shut down overnight.
Dips in the suction pressure happen when the electrolyzer is not
producing hydrogen while
the compressor is running.
Suction Pressure
Su ct
io n
Pr es
su re
(p sig
Suction Pressure
Su ct
io n
Pr es
su re
(p sig
42
Thermodynamic Models
Below are the theoretical minimun power requirements, as a function
of discharge pressure,
for each of the models investigated using the measured inputs shown
above.
Adiabatic
Figure 16 shows the results for the adiabatic model for filling
both tanks. The spikes and
dips in the power curves are caused by spikes and dips in the
hydrogen flow and temperature
observed in Figures 13 and 14 above.
43
0
50
100
150
200
250
Adiabatic Power
Id ea
Adiabatic Power
Id ea
Figure 16: Calculated ideal adiabatic power versus compressor
discharge pressure for fill- ing of both tanks.
44
Isothermal
For the isothermal model I produced ideal power curves using both
the suction temperature
and the discharge temperature. Figure 17 shows the predicted power
curves for tank A
for both the suction and discharge temperatures. Figure 18 shows
the predicted power
curves for tank B for both the suction and discharge temperatures.
For both tanks the
predicted power curves are nearly identical because of the small
difference in the suction
and discharge temperatures.
Isothermal Power (Suction Temperature)
Isothermal Power (Discharge Temperature)
Discharge Pressure (psig)
(b) Discharge Temperature
Figure 17: Calculated ideal isothermal power versus compressor
discharge for filling of tank A. The curves are nearly identical
due to the small temperature difference between the suction and
discharge temperatures.
46
0
50
100
150
200
250
Isothermal Power (Suction Temperature)
Isothermal Power (Discharge Temperature)
Figure 18: Calculated ideal isothermal power versus compressor
discharge for filling of tank B.
47
Polytropic
Figure 19 shows the instantaneous polytropic exponents calculated
at each time step for
filling both tanks. Rather than using the instantaneous polytropic
exponent to calculate the
power at each time step, I used the average value for each tank
seen as the horizontal line in
Figures 19(a) and 19(b). The average value for tank A is 1.026 and
1.027 for tank B. The
exponent for each tank fill is close to 1, indicating the process
is close to isothermal. This
is why the power predicted by the polytropic model, shown below in
Figure 20, is similar
to the power predicted by the isothermal model shown in Figures 17
and 18.
48
0.98
1
1.02
1.04
1.06
1.08
n
n
Discharge Pressure (psig)
n ave = 1.026
(b) Tank B
Figure 19: Calculated polytropic exponent versus compressor
discharge pressure for filling of both tanks. The average value was
use to calculate the polytropic power. Notice the y-axes do not
contain the origin.
49
Figure 20 shows the results for the polytropic model for filling
both tanks. The spikes
and dips in the power curves are caused by spikes and dips in the
hydrogen flow and tem-
perature observed in Figures 13 and 14 above.
50
0
50
100
150
200
250
Polytropic Power
Id ea
Polytropic Power
Id ea
51
Measured and Theoretical Power
In this section the measured power and ideal calculated powers are
presented together for
comparison. All the models investigated predicted smaller power
requirements, by a factor
of 4-5 depending of the model, than the compressor actually used.
In the following chapter
I discuss reasons I think this discrepancy exists.
52
0
200
400
600
800
1000
Measured Power Adiabatic Power Polytropic Power Isothermal Power
(Suction Temperature) Isothermal Power (Discharge
Temperature)
Po we
r ( W
Measured Power Adiabatic Power Polytropic Power Isothermal Power
(Suction Temperature) Isothermal Power (Discharge
Temperature)
Po we
r ( W
Discharge Pressure (psig)
(b) Tank B
Figure 21: All power curves, calculated and measured, versus
compressor discharge pres- sure for filling of both tanks. Note the
polytropic and isothermal (using the suction temper- ature) power
curves are difficult to read because they are all very similar and
overlap each other.
53
Performance and Efficiency
This section presents the measured and calculated specific
energies, the 2nd law efficiencies,
and the energy used for the compression process as a percentage of
energy contained in the
hydrogen. These values facilitate comparisons to other compressors,
and are the most
widely cited performance measures in the literature.
Figure 22 shows the specific energy as measured and as calculated
for each of the ideal
thermodynamic models, for both tanks. The actual specific energy
used by the compressor
is much higher than what was predicted in all of the models,
indicating a low 2nd Law effi-
ciency, as seen in Figure 23. Figure 24 provides a different way of
presenting the efficiency;
the power required for compression is given as a percentage of the
energy contained in the
hydrogen that is compressed.
Sp ec
ific E
ne rg
y (k
W h/
kg )
Figure 22: Specific energy as measured and calculated for each
ideal thermodynamic model for both tanks.
55
0
5
10
15
20
2nd L
aw E
ffi cie
nc y
(% )
Figure 23: 2nd Law efficiency relative to each ideal thermodynamic
model for both tanks.
56
0
5
10
15
20
25
% L
HV
Figure 24: Percentage of energy used for compression compared to
the LHV of hydrogen as measured and for each ideal thermodynamic
model for each tank.
DISCUSSION
As can be see from Figure 21, none of the ideal thermodynamic
models closely approx-
imates the actual behavior of the compressor. The adiabatic model
predicts the highest
specific energy and therefore has the highest 2nd Law efficiency.
However, the predicted
curve (Figure 16) does not approximate the measured power curve of
the compressor (Fig-
ure 11). One reason the compressor is not well modeled by an
adiabatic process is that
the compressor head is very large compared to the compressor cavity
and since hydrogen is
such an effective heat transfer medium, the temperature increase
caused by the compression
is quickly dissipated to the compressor head and across the
diaphragm to the oil.
The polytropic and isothermal models provide similar predictions of
specific energy
and efficiency. This is because the estimated polytropic exponent
for both tank fills is
close to 1, which is characteristic of an isothermal process.
Though there is a temperature
difference between the gas at the suction and discharge of the
compressor, the difference is
small, approximately 10% or 30 K. The process has a small
temperature difference, again
because hydrogen is an effective heat transfer medium. The gas is
able to quickly transfer
heat its surroundings, as noted above.
The measured specific energy is larger than those stated in the
literature. Values in the
literature range from 0.7-2.1 kWh/kg. I measured a specific energy
of 8.3 kWh/kg for both
tank fillings. This is 400 -1200% greater than literature values.
Some factors that may
contribute to this large discrepancy are the size of compressor,
the size of the compressor
motor, and the fact that the compressor is single stage.
Our compressor has a small capacity; it was sized to match the
electrolyzer which can
produce about 2 kgH2 a day. This is small for a fueling station.
Larger compressors in
general are more efficient than smaller ones (Amos, 1998) and this
could affect the energy
57
58
requirements.
The motor that runs the compressor is grossly oversized. It has a
rating of 5.6 kW (7.5
horse power) but is seldom run over 1 kW. This affects the motor’s
efficiency (discussed in
more detail below).
The compressor is single stage which can affect the energy
consumption. The compres-
sion ratio is the ratio of the discharge pressure to the suction
pressure. The compression
ratio affects how much energy is needed to compress a given mass of
gas as can be seen in
each of the ideal thermodynamic models; a lower compression ratio
requires less energy.
Multi stage compressors take advantage of this by bringing suction
pressure gas up to an
intermediate pressure. The intermediate pressure gas is then
compressed to the discharge
pressure, or a higher intermediate pressure depending on the number
of stages. The total
energy required for all of the stages is less than if the gas had
been compressed from a low
suction pressure to a high discharge pressure as it is in the case
of a single stage compressor.
However, multiple stages add complexity and cost to a compressor.
For the HSU fueling
station, SERC was trying to minimize both cost and complexity and
chose to use a single
stage compressor, which likely affects the specific energy required
for compression.
Another reason the measured power differs significantly from the
calculated power is
because the PDC compressor is not well modeled by ideal gas
thermodynamic models. This
is because of how the compressor works. In order for the oil to
reach sufficient pressure to
compress the gas to the desired output pressure, an oil pressure
relief valve is used. This
valve causes the motor to work to bring the oil pressure up to 6800
psig (or the setpoint
of the given compressor, ours is 6800 psig) for every stroke
regardless of the discharge
pressure. If the oil pressure relief valve were somehow variable so
that the oil pressure
were maintained only slightly above the storage pressure, the
compressor would be more
efficient and perhaps better modeled by the thermodynamic models
presented. As is, a
59
better approach to modeling the compressor would be to use a fluid
dynamics model, such
as the Bernoulli equation, to find the work done on the oil rather
than on the gas.
For a reversible, steady-state process, the specific work required
to increase the pressure
of an incompressible fluid can be found using:
w = − ∫ P1
2 + g (Z1 − Z0) (16)
where w is the specific energy for the given process (kWh/kg)
υ is the specific volume (m3/kg)
P1 − P0 is the change in pressure for the process (Pa)
V1 is the velocity of the oil out of the pressure relief valve
(m/s)
V0 is the velocity of the oil injected into the oil cavity
(m/s)
Z1 is the elevation of oil exiting the pressure relief valve
(m)
Z0 is the elevation of oil entering the oil cavity (m)
g is the acceleration due to gravity (9.8 m/s2)
To simplify the equation I will assume that the difference in
velocity of the oil into and
out of the system is zero, the change in elevation is negligible,
and that the specific volume
is constant. After performing the integration the equation
simplifies to
w = −υ (P1 − P0) (17)
The negative sign indicates that work is done on the system rather
than by the system.
The power can then be found by multiplying the specific work by the
mass flow rate of the
oil in through the system. I performed some preliminary calculation
using the density of the
oil (6.92 lbs/gallon or 0.830 kg/L) in our compressor and estimated
oil flow rates. Obtaining
accurate measurements of the oil flow rate would require plumbing
modifications for the
60
compressor and is beyond the scope of this analysis. I contacted
PDC Inc. to inquire about
the oil flow rates and was informed that they are proprietary, but
I was given a range that
they could fall into, which I used for this analysis. The oil flow
rate range I used is 0.1-0.5
liters per minute. Because the flow rate is dependent on the oil
relief valve setting, it is
impossible to know the flow rate without measuring it. I also
wanted to take into account
the efficiency of the compressor motor because it is running at a
low efficiency. After
looking up data that make up the performance curve for our motor,
see Figure 25, I found
the motor was oversized by a factor of 5-9 for the application it
is being used for, leading to
a low efficiency. I estimate that the efficiency varies from 55-65%
for the range of power we
obeserve. I based this estimate range off the high and low power
measurements observed
for the compressor. At the low range of compressor power, 650 W,
the compressor motor
is running at approximately 11% of its rated full load of 5590 W
(7.5 hp). At the high
range of measured compressor power, 1100 W, the motor is running at
approximately 20%
of its rated full load. Table 3 below gives calculated power
requirements for different oil
flow rates and different motor efficiencies. It also shows the
calculated 2nd Law efficiencies
assuming that the nominal compressor power is 700 W, approximately
the modal value of
compressor power. The 2nd Law efficiencies are a strong linear
function of the flow rate,
see Figure 26, note that the two line have identical intercepts and
the slopes are inversely
proportional to the motor efficiency. The 2nd Law efficiencies
calculated with this method
are higher than those calculated using the ideal thermodynamic
models, which indicates
that this might be a better method for evaluating our compressor’s
2nd Law efficiency. A
more thorough analysis should be done that carefully measures the
flow rate and takes into
account other variables such as oil compressibility and friction
losses.
61
0
20
40
60
80
100
Motor Efficiency
M ot
or E
ffi cie
nc y
Load (% of Rated)
Figure 25: Compressor motor efficiency curve based on the
manufacturer’s data.
62
55% Motor Efficiency 65% Motor efficiency
y = 0.019997 + 197.6x R= 1
y = 0.02 + 167.2x R= 1
2 n d L
Oil Flow Rate (L/min)
Figure 26: 2nd Law efficiency as versus flow rate for compressor
motor efficiencies of 55 and 65%
64
Time of Day Variations
My colleagues and I speculated that the time of day variations
observed in Figure 12 are
caused by fluctuations in the incoming line voltages. To verify
this I used a DENT Instru-
ments ELITEpro10 data logger to monitor each incoming line voltage.
Each of the three
line voltages (three phase power is required by the compressor)
were measured with respect
to ground. The voltages were measured every three seconds and
averaged over ten minutes.
The ten minute averages were recorded by the data logger. The
voltages were measured
upstream of the power transducer that measures the compressor
power. The text data files
generated by the data logger did not need any further
processing.
To analyze whether the compressor power was varying in a pattern
similar to the line
voltage, I looked at data when the compressor was running and the
line voltages were mea-
sured. In total 65 hours of compressor run time were included in
the analysis. The hours
were non-consecutive, but represented four separate tank filling
episodes that occurred be-
tween June 8 and June 18, 2009. To plot the compressor power data
versus the line voltages
I created 10 minute averages of the compressor power for the same
time frame the voltages
were monitored using a MATLAB R© script. I then plotted the
compressor power versus the
line voltage for each of the three lines.
The line voltages do fluctuate during the day in a similar pattern
to our compressor
power fluctuations as shown in Figure 27. All three incoming
voltages fluctuate in a similar
manner, but one leg, line 1, varies more than the other two.
10http://www.dentinstruments.com/detailsElitePro.htm
65
Compressor power is well correlated to the each the line voltages
as shown in Figures
28-30. Line 1 showed the least amount of scatter. Why the voltages
vary diurnally, how the
three lines interact with each other and the compressor, and the
mechanism by which this
might affect the compressor power are questions beyond the scope of
this analysis.
Figure 27: Incoming compressor line voltages, with respect to
ground, versus time of day. Notice the y-axis does not contain the
origin.
66
650
700
750
800
850
900
950
1000
1050
Compressor Power
Po we
r ( W
1.654238.126m2 NA6.5594e+05Chisq NA0.75979R
Figure 28: Compressor power versus line 1 voltage. Notice the
y-axis does not contain the origin.
67
650
700
750
800
850
900
950
1000
1050
Compressor Power
Po we
r ( W
Voltage (V)
Figure 29: Compressor power versus line 2 voltage. Notice the
y-axis does not contain the origin.
68
650
700
750
800
850
900
950
1000
1050
Compressor Power
Po we
r ( W
Voltage (V)
Figure 30: Compressor power versus line 3 voltage. Notice the
y-axis does not contain the origin.
CONCLUSION
In this thesis, I have shown that the diaphragm compressor at HSU’s
hydrogen refueling
station is not well modeled by ideal gas thermodynamic models. The
calculated power and
specific energy for the models I investigated (adiabatic,
isothermal and polytropic) were
all lower than the measured values by a factor of 4-5 depending on
the ideal model. The
adiabatic model had the highest 2nd Law efficiency of the models,
but it was still low, as
were the efficiencies of the other models.
The compressor is not well modeled by the thermodynamic models
because of its op-
erating principles. The compressor motor works to bring the
compressor oil to a set 6800
psig for each piston stroke, regardless of the gas discharge
pressure. Because of this the
power is relatively constant throughout the the range of discharge
pressures. All of the ther-
modynamic models predict an increase in the power requirements as
the discharge pressure
increases.
A better way to model the compressor would be to look at the oil
side of the diaphragm
rather than the gas side. Using principles of steady-state fluid
flow, I developed a prelimi-
nary mechanical model that can predict the power requirement and
more closely matches
the power actually measured.
Our compressor power exhibits an interesting dependence on the time
of day. This phe-
nomenon has been noted since start up and continues as of this
writing. The incoming line
voltages to the compressor were monitored for 10 days to see if
fluctuations in the voltage
could be causing the fluctuations in compressor power. There is a
correlation between the
line voltages and compressor power consumption, suggesting that the
motor performance
depends strongly on the line voltage.
69
70
Suggestions for further research would be to carefully measure the
flow rate of the oil
through the compressor to obtain an improved prediction for the
required power using fluid
dynamics. Also, a more thorough model of the oil side of the
compressor would include
parameters such as the compressibility of the oil and the
efficiency of the motor and the
injection pump. A model such as this would be very useful in
determining the specific
energy requirements for a diaphragm compressor. Further study of
the effects of voltage
on power consumption and methods to avoid them would also be
interesting.
The results of this analysis suggest that more work needs to be
done to characterize
hydrogen compressor efficiency for economic modeling. The HSU
compressor is only one
data point for compressor efficiency, but the efficiency is based
on empirical data and not
models. Our data suggest that some of the assumptions commonly used
for economic mod-
eling may be incorrect. To validate or invalidate the assumptions
behind economic models,
more empirical analyses should be performed on compressors, and
other equipment in the
production chain. If most of the fueling stations currently in
operation contributed opera-
tional data, the economic models currently in use could be made
more robust, benefiting
those making decisions about a hydrogen based transportation
system.
BIBLIOGRAPHY
American Honda Motor Co. 2009. Honda fcx clarity - hydrogen fule
cell vehicle - official web site. URL
http://automobiles.honda.com/fcx-clarity/.
Amos, W. A. 1998. Costs of storing and transporting hydrogen. Tech.
Rep. 570-25106, National Renewable Energy Laboratory.
Cengel, Y. A. and M. A. Boles. 1998. Thermodynamics: An Engineering
Approach. WCB/McGraw-Hill, San Francisco, 3rd ed.
Department of Energy. 2009. Hydrogen, fuel cells and
infrastructure. URL
http://www1.eere.energy.gov/hydrogenandfuelcells/delivery/current
technology.html.
Energy Information Agency. 2009. Short-term energy outlook - real
gasoline prices. URL
http://www.eia.doe.gov/emeu/steo/pub/fsheets/real
prices.html.
Ford Motor Company. 2009. Hydrogen fuel technology and research.
URL
http://www.ford.com/innovation/environmentally-friendly/hydrogen.
Fuel Cells 2000. 2009. World wide hydrogen fueling stations. URL
http://fuelcells.org/info/chartsh2fuelingstations.pdf.
Fuel Cells for Power. 2009. Fuel cells for power - energy density.
URL http://www.fuelcellsforpower.com/Energy-Density.html.
General Motor Company. 2009. The best emissions strategy is a
zero-emissions strategy. URL
H2 mobility. 2009. Hydrogen vehicles worldwide - timeline. URL
http://www.netinform.net/h2/H2Mobility/H2MobilityStart.aspx?CATID=1.
H2A Group. 2006. H2A Delivery Components Model Version 1.1: Users
Guide.
Holland, G. B. and J. J. Provenzano. 2007. The Hydrogen Age:
Empowering A Clean- Energy Future. Gibbs-Smith.
Linde Group. 2009. Linde unveils ground-breaking technology for
fueling hydrogen- powered vehicles. URL
http://www.lindeus.com/international/
web/lg/us/likelgus30.nsf/0/AB77A765F8A64F68C1257582005DC0F7.
Marks, L. 1996. Mark’s Standard Handbook for Mechanical Engineers.
McGraw- Hill: New York, 10th ed.
71
72
Mercedes-Benz. 2009. F-cell vehicle. URL
http://www.mbusa.com/mercedes//greenFuelCell/.
Perry, R. H., D. W. Green, and J. O. Maloney, eds. 1997. Perry’s
Chemical Engineers’ Handbook. McGraw- Hill: New York, 7th ed.
Schatz Energy Research Center. 2009. Projects- real world
appications. URL http://schatzlab.org/projects/real
world/vehiclefactsheet.html.
Schwarzenegger, A. 2004. Executive order s-7-04.
Vatter, H. G. and J. F. Walker. 1996. History of the U.S. economy
since World War II. M.E. Sharpe.
Weinert, J. X., L. Shaojun, J. M. Ogden, and M. Jianxin. 2007.
Hydrogen refueling station costs in shanghai. International Journal
of Hydrogen Energy, 32:4089–4100.
Yang, C. and J. Ogden. 2007. Determining the lowest-cost hydrogen
delivery mode. Inter- national Journal of Hydrogen Energy,
32:268–286.
APPENDIX A: INVESTIGATION OF THE IDEAL GAS ASSUMPTION
For my analysis I assumed that hydrogen is an ideal gas. This
assumption is good at low
pressures and high temperatures but becomes poor at higher
pressures and low tempera-
tures. Here I investigate one scenario treating hydrogen as a real
gas using the Z compress-
ibility factor to see what affect it has on the total specific
energy and 2nd Law efficiency
predicted by thermodynamic models. For this analysis I used a real
gas adiabatic model
shown in equation (18), (Marks, 1996) to calculate the power
predicted for a real gas ther-
modynamic model. For the Z factors I used tabulated data published
in Perry’s Handbook
(1997). There was only a limited number of calculated Z factors
available ranging from
10 bar (145 psi) to 600 bar (8700 psi) for temperatures of 300 K
and 400 K. I wanted Z
factors in more finely spaced pressure ranges so I assumed that
they varied linearly and
used linear interpolation to find Z factors for the pressures and
temperatures observed in
our compressor and not available in Perry’s Handbook. For
simplification I assumed a con-
stant suction temperature and pressure of 300 K and 200 psig (15
bar) respectively, and a
constant discharge temperature of 330 K.
W = mkRT0
k − 1
where W is the power predicted (W)
k is the ratio of specific heats of the gas (1.41 for
hydrogen)
R is the gas constant (4.1243 kJ/kgK for hydrogen)
T0 is the initial Temperature (K)
P0 is the initial pressure (Pa)
P1 is the final pressure (Pa)
Z0 is the initial compressibility factor
73
74
Z1 is the final compressibility factor
For this investigation I looked at the filling of tank A. I broke
my data file into blocks
with pressure ranges of 20 bar (290 psi) increments, i.e., a 20-40
bar block, 40-60 bar
block up to 400-420 bar. I used bars for the pressure increments
rather than psi because the
compressibility factors were given in bars, I then converted from
bars to psi. For all the data
I assumed Z0 was constant, 1.0088, and within each 20 bar pressure
range I assumed Z1
was constant. I then calculated the Z correction factor Z0+Z1
2Z0 . I multiplied the Z correction
factor by the ideal gas adiabatic power I previously calculated. I
then used numerical
integration to find the total energy predicted by the real gas
adiabatic model. For tank A,
I calculated a total energy requirement of 9.76 kWh or a specific
energy of 1.58 kWh/kg.
The ideal adiabatic model predicted a total energy requirement of
8.92 kWh/kg or a specific
energy of 1.44 kWh/kg. The real gas model results differs from the
ideal gas model by 0.84
kWh/kg or 9.4%.
Because the real gas model predicts higher energy consumption the
2nd Law efficiency
for the compressor would increase. In this example it would
increase from 17.4% to 19.0%.
This does not affect my conclusion that the compressor is not well
modeled with thermo-
dynamic gas models.
Test Started: 7/1/2008
Compressor
75
Features
All product specifications are subject to change without notice
Last updated : 1-Mar-2007
Onboard Intel® ULV 600 MHz processor
Intel 82852GM Chipset
One DIMM socket supports up to 1 GB DDR 200/266 SDRAM
2-CH LVDS, DVI
Four COM, six USB 2.0, 16-bit GPIO
RoHS COMPLIANT 2002/95/EC
AIMB-251 Fanless Mini-ITX Motherboard Supports Dual Display for
CRT, LVDS, DVI and TV-Out
Specifications
Processor System
CPU Onboard Intel ULV Celeron® 600 MHz Max. Speed 600 MHz Front
Side Bus 400 MHz L2 Cache 512 KB Chipset Intel 82852GM + ICH4 BIOS
Award™ 4 Mb FWH
Expansion Slot PCI 32-bit/33MHz, 1 slot Mini-PCI 32-bit/33MHz, 1
slot
Memory Technology DDR 200/266 SDRAM Max. Capacity 1GB Socket One
184-pin DIMM socket
Graphic
Controller Chipset Integrated VGA Controller VRAM Shared system
memory up to 64 MB video memory LVDS Single channel 18-bit/
Dual-channel 36-bit LVDS
TV-Out Supports both S-video and composite video Chrontel CH7009A
TV encoder supports both NTSC/PAL
DVI Chrontel CH7009A DVI transmitter up to 135M pixels/second Dual
Display CRT + LVDS, or DVI/TV-out + LVDS or CRT + DVI
Ethernet Interface 10/100/1000Base-T Controller 1 LAN 1 Realtek™
RTL8110S Gigabit LAN (PCI) Connector 1 (RJ45)
EIDE Mode 2 x EIDE (Ultra DMA 100) Channel 2
Rear I/O
VGA 1 Ethernet 1 USB 2 (USB 2.0 ports) Audio Mic-In, Line-In,
Line-Out (VIA VT1616 supports 5.1 CH AC97 Audio) Parallel 1 Serial
1 (RS-232/422/485), supply 5 V or 12 V via jumper PS/2 2 (keyboard
and mouse)
Internal Connector
LVDS 1 TV-Out 1 DVI 1 USB 4 (USB 2.0 ports) Serial 3 (RS-232) IDE 2
(40/44 Pin) Compact Flash 1 IrDA 115k bps, IrDA 1.0 compliant FDD 1
DIO 16-bit General Purpose I/O for DI and DO
Watchdog Timer Output System reset Interval Programmable 1 ~ 255
sec
Power Requirement Typical Celeron 600 MHz, 1 GB DDR SDRAM
+5 V +3.3 V +12 V +5 VSB 1.58 A 4.66 A 0.05 A 0.4 A
Environment Operating
Temperature 0 ~ 60° C (32 ~ 140° F) Physical Characteristics
Dimensions 170 mm x 170 mm (6.69" x 6.69")
NEW
76
77
Ordering Information Part Number Specification
AIMB-251F-00A1E Intel® ULV Celeron 600 MHz Mini ITX Motherboard
with VGA, 2-CH LVDS, DVI, TV-out, 5.1 CH Audio, Gb LAN, CF, PCI,
Mini PCI, 4 COM, 6 USB 2.0 & GPIO
Bracket View
FSB 400
2 IDE Ports (UltraDMA100)
Gb NIC Realtek
1 PCI Slot
Packing List Description Quantity AIMB-251 SBC x 1 IDE HDD cable
(40 pin) x 1 IDE HDD cable (44 pin) x 1 FDD cable x 1 CPU Cooler x
1 I/O port bracket x 1 Startup Manual x 1 Driver CD x 1 Serial
cable (RS-232) x 3
Accessory Part Number Description 1700003434 TV-Out cable
1700003433 USB cable 1700003435 DVI cable
AIMB-251F-00A1E
78
Manual Print History
The print history shown below lists the printing dates of all
revisions and addenda created for this manual. The revision level
letter increases alphabetically as the manual undergoes subsequent
updates. Addenda, which are released between revisions, contain
important change information that the user should incorporate
immediately into the manual. Addenda are numbered sequentially.
When a new revision is created, all addenda associated with the
previous revision of the manual are incorporated into the new
revision of the manual. Each new revision includes a revised copy
of this print history page.
Revision A (Document Number 141-0999)
..........................................................................September
1999 Revision B (Document Number
141-1199)............................................................................November
1999 Revision C (Document Number 141-102002)
...........................................................................October
2002 Revision D (Document Number 141-082005)
.............................................................................August
2005 Revision E (Document Number
141-062008)..................................................................................
June 2008 Revision F (Document Number
141-092008)........................................................................September
2008 Revision F (Document Number
141-022009)..........................................................................
February 2009
Visit www.teledyne-hi.com for WEEE disposal guidance.
Hastings Instruments reserves the right to change or modify the
design of its equipment without any obligation to provide
notification of change or intent to change.
The instruments described in this manual are available with
multiple pin-outs.
Ensure that all electrical connections are correct. CAUTION:
The instruments described in this manual are designed for Class 2
installations
in accordance with IPC standards
CAUTION:
CAUTION:
The instruments described in this manual are designed for INDOOR
use only.
80
Table of Contents
4.
MAINTENANCE..............................................................................................................................................................
15 4.1. AUTHORIZED
MAINTENANCE.....................................................................................................................................
15 4.2. TROUBLESHOOTING
...................................................................................................................................................
15 4.3. ADJUSTMENTS
...........................................................................................................................................................
16 4.4. END CAP
REMOVAL:..................................................................................................................................................
17 4.5. PRINTED CIRCUIT BOARD
REPLACEMENT..................................................................................................................
17 4.6. SENSOR REPLACEMENT:
............................................................................................................................................
17 4.7. ORIFICE CHANGES:
....................................................................................................................................................
17 4.8. REPLACEMENT
PARTS................................................................................................................................................
18
5. WARRANTY
....................................................................................................................................................................
20 5.1. WARRANTY REPAIR POLICY
......................................................................................................................................
20 5.2. NON-WARRANTY REPAIR POLICY
.............................................................................................................................
20
81
141-022209 - 201/203 Series Page 4 of 20
1. General Information The Hastings HFM-201/HFC-203 series Mass
flow meter (HFM-201) and controller (HFC-203) are designed to
accurately measure and control mass flow over the range of 30 slm
to 500 slm, without corrections or compensations for gas pressure
and temperature with an accuracy of better than ±1% from the mean
(±2% FS for 500 slm). Hastings mass flow instruments do not require
any periodic maintenance under normal operating conditions with
clean gases. No damage will occur from the use of moderate
overpressures (~500 psi/3.45MPa) or overflows. Instruments are
normally calibrated with the appropriate standard calibration gas
(nitrogen) then a correction factor is used to adjust the output
for the intended gas. Special calibrations for other gases, such as
oxygen, helium and argon, are available upon special order.
1.1. Features
• LINEAR BY DESIGN. The HFM-201/HFC-203 series is inherently linear
(no linearization circuitry is employed). Should recalibration in
the field be desired (a calibration standard is required), the
customer needs to simply set the zero and span points. There will
be no appreciable linearity change of the instrument when the
flowing gas is changed.
• MODULAR SENSOR. The HFM-201/HFC-203 series incorporates a
removable/replaceable sensor module. Field repairs to units can be
achieved with a minimum of production line downtime.
• METER SETTLING TIME. Changes in flow rate for the HFM-201 are
detected in less than 2 seconds when using the speed up
circuitry.
• LOW TEMPERATURE DRIFT. The temperature coefficient of span for
the HFM-201/HFC-203 series is typically less than 0.05% of full
scale/°C from 15-45°C. The temperature coefficient of zero is
typically less than 0.1 % of reading/°C from 0-50°C.
• FIELD RANGEABLE. The HFM-201/HFC-203 series is available in
ranges from 30 slm to 500 slm. For HFC-203 controller’s, an orifice
change is required as well. Calibration is required after all
changes.
• CURRENT LOOP. The 4-20 mA option gives the user the advantages of
a current loop output to minimize environmental noise pickup.
82
1.2. Specifications
Repeatability
..............................................................................................................<±0.1%
of F.S.
Operating temperature
........................................................0-50°C in
non-condensing environment
Temperature coefficient (span)
..................................................±0.1 ppm/°C
(±0.05%/0C typical)
Zero drift
.............................................................................................................................±0.1%FS
Flow ranges
..............................................................................
30, 50, 100, 300, 500, 600 slm (N2)
Output
...............................................................................................................................
0-5 VDC
Power requirements
........................................................................................
±(15) VDC @ 50 mA
Wetted materials
......................................................................
304 & 316 stainless steel, nickel 200,
..........................................................................................................................
Viton, Au13Ni braze
Attitude sensitivity of zero
.................................................. < ±6.5% F.S.
for 90° without re-zeroing
..............................................................................................................{N2
at 19.7 psia (135 KPa)}
Controller weight
......................................................................................................5.6
lb (2.54 kg)
83
1.3. Optional 4-20 mA Current Output
An option to the standard 0-5 VDC output is the 4-20 mA current
output that is proportional to flow. The 4 - 20 mA signal is
produced from the 0 - 5 VDC output of the flow meter. The current
loop output is useful for remote applications where pickup noise
could substantially affect the stability of the voltage
output.
The current loop signal replaces the voltage output on pin 6 of the
“D” connector. The current loop may be returned to either the power
supply common or the -15 VDC connection on the power supply. If the
current loop is returned to the power supply ground, the load must
be between 0 and 600 ohm. If it is returned to the -15VDC, the load
must be between 600 and 1200 ohm. Failure to meet these conditions
will cause failure of the loop transmitter.
The 4-20 mA I/O option can accept a current input. The 0-5 VDC
command signal on pin 14 can be replaced by a 4-20mA command
signal. The loop presents an impedance of 75 ohms and is returned
to the power supply through the valve common.
1.4. Other Accessories
1.4.1. Totalizer (TR-1J) The Hastings Flow Totalizer integrates the
0-5 VDC signal generated by the flow meter to give a total flow
reading. Count rates from 0 to 999 counts per minute are selectable
by internal setting.
1.4.2. Hastings Model 40/200/400 Power Supply Hastings power
supplies are available in either two or four channel versions. They
convert 115 or 230VAC to the ±15 VDC required to operate the flow
meter. Interface terminals for the ±15 VDC input and the 0-5 VDC
linear output signal are located on the rear of the panel. Also, a
cable can be supplied with the power supply that provides the +15
VDC on pin 11 of a 15-pin “D” connector and the 0 - 5VDC output
measurement on pin 6. Pins 5, 7 and 12 are common, and pin 7 is
chassis ground. Throughout this manual, when reference is made to a
power supply, it is assumed the customer is using a Hastings Model
200/400/40 supply. Hastings power supplies do not meet CE standards
at this time.
84
PHONE (614) 889-6152 TECH. ASSISTANCE (614) 876-8308
FAX # (614) 876-85386625 McVey Blvd. Columbus, Ohio 43235 Div.
Morlan & Associates, Inc.
94
• Accurate regardless of variations in voltage,current, power
factor, or load.
• Available with 1, 2, 2 1/2, or 3 element configurations. Provides
bi-directional operation.
• Accuracy maintained over wide temperature range, calibration
traceable to NIST.
• Equipment monitoring for process control.
• Integration into energy management systems, or a variety of
sub-metering applications.
• Measurement using direct-connection, current and/or potential
transformers.
PRECISION AC WATT TRANSDUCER
To calculate full scale Watts when using potential and/or current
transformers: a = initial transducer calibration (from table above)
b = current transformer ratio (e.g. 100:5, or 20) c = potential
transformer ratio (e.g. 600:120, or 5) F.S. WATTS = a x b x c NOTE:
UL recognized current tra
LOAD MORE