114
0

EMES60 Manual.pdf

Embed Size (px)

Citation preview

0

1

EMES60 is a combined echosounder and speed log, providing both

speed and water depth from the same unit.

This manual gives the information necessary to install, use and

maintain the system.

Introduction

Issue 009.01 15-10-06 Copyright © Northern Solutions AS

1

Introduction ....................................................................................................... 1

Table of Contents ............................................................................................. 1

About this Manual ........................................................................................ 5

1.1 Glossary ................................................................................................ 5

1.2 Parts of the Manual ............................................................................ 7

2 Introduction to EMES60............................................................................. 8

2.1 Summary .............................................................................................. 8

2.2 Highlights .............................................................................................. 8

2.3 System Structure .................................................................................. 5

3 Operation ................................................................................................... 6

3.1 HMI Touch-Screen Controls ............................................................... 6

3.1.1 Structure of the screen .............................................................. 6

3.1.2 Summary data ............................................................................ 7

3.1.3 Changing display units .............................................................. 7

3.1.4 Control buttons ........................................................................... 8

3.1.5 Printing and screen snapshots ................................................. 8

3.1.6 Setting the time .......................................................................... 9

3.1.7 Alarms .......................................................................................... 9

3.1.8 Setting alarm limits ..................................................................... 9

3.1.9 Window navigation .................................................................. 10

3.1.10 Home screens ........................................................................... 11

3.1.11 Control buttons ......................................................................... 12

3.1.12 Brightness control ..................................................................... 13

3.1.13 Administrator mode ................................................................. 13

3.1.14 Hardware interface setup ...................................................... 14

3.1.15 Demo and Simulation modes................................................. 16

3.2 Echosounder ...................................................................................... 18

3.2.1 Saving files to USB key .............................................................. 18

3.2.2 Echosounder Home screen .................................................... 19

3.2.3 Echosounder main operational screen ................................ 20

3.2.4 Changing depth scale ............................................................ 21

3.2.5 Changing scroll speed ............................................................ 21

3.2.6 Setting the transceiver gain .................................................... 21

3.2.7 Setting the time-varying gain ................................................. 21

3.2.8 Setting the transmitter power ................................................. 21

3.2.9 Gain, TVG and Power slider .................................................... 22

Northern Solutions

Steinalderveien 2E

1407 Vinterbro

Norway

Org: 912 403 653

[email protected]

+47 90 16 72 84

Table of Contents

Org: 912 403 653

[email protected]

+47 90 16 72 84

2

3.2.10 Setting the draft offset ............................................................. 22

3.2.11 Echosounder digital indicator ................................................ 23

3.2.12 Echosounder communication screen .................................. 24

3.2.13 Saving communications data to file ..................................... 25

3.2.14 Communications port controls .............................................. 26

3.2.15 Echosounder alarm configuration screen ........................... 27

3.2.16 Echosounder hardware Interface screen ............................ 29

3.2.17 Echosounder history screen .................................................... 30

3.2.18 Echosounder oscilloscope screen ......................................... 31

3.2.19 Echosounder test and troubleshooting screen ................... 32

3.3 Speed log ........................................................................................... 33

3.3.1 Speed log Home screen ......................................................... 33

3.3.2 Speed log main operational screen ..................................... 34

3.3.3 Setting alarm speeds ............................................................... 35

3.3.4 Speed log single axis indicator .............................................. 35

3.3.5 Speed log communication screen ....................................... 36

3.3.6 Speed log alarm screen .......................................................... 37

3.3.7 Speed log hardware interface screen ................................. 38

3.3.8 Speed log history screen ......................................................... 39

3.3.9 Speed log oscilloscope screen .............................................. 40

3.3.10 Speed log test and troubleshooting screen ........................ 41

3.3.11 Speed log calibration screen ................................................. 42

4 Maintenance ........................................................................................... 43

4.1 Precautions ........................................................................................ 43

4.1.1 Operation in Air ........................................................................ 43

4.1.2 Sensor Head .............................................................................. 43

4.2 Tests and Checks .............................................................................. 43

4.2.1 Safety check ............................................................................. 43

4.2.2 Connector checks ................................................................... 43

4.2.3 Electronic Unit Checks ............................................................. 43

4.2.4 Inspect transducer for marine growth .................................. 44

4.2.5 Corrosion check ....................................................................... 44

4.2.6 Cleaning .................................................................................... 44

4.2.7 Functional checks .................................................................... 44

4.2.8 Routine Tests .............................................................................. 45

4.3 Troubleshooting ................................................................................. 47

5 Installation ................................................................................................ 49

5.1 Parts of the System ............................................................................ 49

5.1.1 HMI Units ..................................................................................... 49

5.1.2 Electronic Units and Cabling .................................................. 49

5.1.3 Sensor Head Assembly ............................................................ 50

5.1.4 Ball Valve Assembly ................................................................. 51

5.2 Mounting the Sensor on the Vessel ................................................ 52

5.3 Sensor Deployed and Inboard ....................................................... 53

5.3.1 Installing the sensor in the valve ............................................ 54

5.3.2 Cautions ..................................................................................... 54

5.3.3 Fitting the Bottom Flange to the hull ..................................... 54

3

5.3.4 Assembling the Sensor Head Assembly ................................ 55

5.3.5 Assembling the Ball Valve Assembly ..................................... 57

5.3.6 Fitting the Assembly to the Bottom Flange .......................... 58

5.3.7 Checks after assembly ............................................................ 59

5.3.8 When the vessel is afloat ......................................................... 59

5.3.9 Removing the sensor while the vessel is afloat .................... 60

5.3.10 Re-fitting the sensor while the vessel is afloat ...................... 60

5.3.11 Preparing for dry dock............................................................. 60

5.3.12 Cathodic protection................................................................ 61

5.4 Mounting Electrical Components .................................................. 62

5.4.1 Mounting the HMI units ............................................................ 62

5.4.2 Mounting Electronic Units ........................................................ 64

5.5 Electrical Installation ......................................................................... 65

5.5.1 Block Diagram .......................................................................... 65

5.5.2 Electronic Unit Layouts ............................................................ 66

5.5.3 Cable Diagram ......................................................................... 66

5.5.4 Cable Types .............................................................................. 67

5.5.5 Cable List ................................................................................... 67

5.5.6 Pluggable Terminal Block connectors .................................. 68

5.5.7 Connection Notes .................................................................... 68

5.5.8 Connecting to Electronic Unites ............................................ 69

5.5.9 Cable Wiring Schedules .......................................................... 70

5.5.10 Power ......................................................................................... 75

5.5.11 Signal Connections .................................................................. 76

5.6 Set-Up ................................................................................................. 76

5.6.1 Set Up the Hardware Interface .............................................. 76

5.7 Calibration ......................................................................................... 76

5.7.1 Calibrating the HMI touch-screen ......................................... 76

5.7.2 Water temperature calibration .............................................. 77

5.7.3 Speed log Calibration ............................................................. 77

6 Technical Details ..................................................................................... 82

6.1 Specifications .................................................................................... 82

6.2 Circuit board layouts ........................................................................ 84

6.2.1 Power Board Layout ................................................................ 84

6.2.2 Power Board LEDs ..................................................................... 85

6.2.3 Power Board Test Points .......................................................... 85

6.2.4 I/O Board Layout ...................................................................... 86

6.2.5 I/O Board LEDs .......................................................................... 87

6.2.6 I/O Board Test Points ................................................................ 88

6.3 Wiring Diagrams ................................................................................ 89

6.3.1 EMES Sensor Wiring ................................................................... 89

6.3.2 Speed Log Sensor Power Unit Wiring ..................................... 89

6.3.3 Echo Sounder Sensor Power Unit Wiring ............................... 90

6.3.4 Speed Log Interface Unit Wiring ............................................ 90

6.3.5 Echo Sounder Interface Unit Wiring ....................................... 91

6.4 System Drawings ............................................................................... 92

6.4.1 Bottom Flange .......................................................................... 92

4

6.5 Data Output and Input Formats ..................................................... 93

6.5.1 NMEA 0183/IEC61162-1 Messages ......................................... 93

6.5.2 Output Message Summary ..................................................... 93

6.5.3 Input Message Summary ......................................................... 94

6.5.4 DPT – Depth ............................................................................... 95

6.5.5 VBW – Dual ground/water speed .......................................... 95

6.5.6 VHW – Water Speed and heading ........................................ 95

6.5.7 VLW – Dual ground/water distance ...................................... 96

6.5.8 DPT - Depth................................................................................ 96

6.5.9 DBT – Depth below transducer .............................................. 96

6.5.10 DBS – Depth below surface .................................................... 96

6.5.11 DBK – Depth below keel .......................................................... 97

6.5.12 ALA – Report detailed alarm conditions .............................. 98

6.5.13 HBT – Heartbeat supervision sentence .................................. 98

6.5.14 MTW-Water temperature ........................................................ 99

6.5.15 ALR – Set alarm state ............................................................... 99

6.5.16 ACK – Acknowledge alarm .................................................... 99

6.5.17 AKD – Acknowledge detail alarm condition ..................... 100

6.5.18 HDT – Heading true ................................................................ 100

6.5.19 HDG – Deviation and variation ............................................ 100

6.5.20 THS – True heading and status.............................................. 101

6.5.21 ROT – Rate of turn ................................................................... 101

6.5.22 VTG – Course over ground and ground speed ................. 101

6.5.23 GLL – Geographic position latitude/longitude .................. 102

6.5.24 GGA – Global positioning system (GPS) fix data .............. 102

6.5.25 GXP – Transit determined position ....................................... 103

6.5.26 GLP – Loran-C determined position .................................... 103

6.5.27 RMC – Recommended minimum specific GNSS data ..... 103

6.5.28 RMA- Recommended minimum specific Loran-C data .. 105

6.5.29 DDC –Display dimming control ............................................ 106

6.5.30 ZDA – Time and date ............................................................. 106

7 Northern Solutions ................................................................................. 107

7.1 The Company .................................................................................. 107

7.2 Contacting Northern Solutions...................................................... 107

5

About this Manual

1.1 Glossary

Terms used in this manual include:

echo sounder A device that measures the depth of water

under a ship, by measuring the time between

sending a sound pulse and receiving its echo

from the seabed

electromagnetic

log

A type of speed log that uses electromagnetic

measurements to calculate the speed of a

vessel through water. Compare with acoustic

Doppler log, which calculates the speed

through the water or relative to the seabed by

detecting shifts in frequency of acoustic

echoes. EMES60 uses an electromagnetic log.

HMI Human-machine interface: screen units that

give readouts of speed and depth, and allow

the user to control and set up the system

IMO International Maritime Organization

Interface Unit EMES60 electronic unit that connects sensor,

Sensor Power Unit and ship’s power

longitudinal

speed

Speed in the aft-fore direction of the vessel

opto Short for “opto-isolated”

opto-isolated An electrical input that is separated electrically

from the inputting device using an optical

converter circuit

Sensor Power

Unit

EMES60 electronic unit that connects HMI units,

external equipment and Interface Unit

speed log A device that measures the speed of a ship

relative to the water around it and the seabed

under it

transducer A device that converts electrical signals to

sound and back again

6

transverse

speed

Speed in the port-starboard direction of the

vessel

7

1.2 Parts of the Manual

Section 1, About this Manual, introduces this manual.

Section 2, Introduction to EMES60, provides an overview of

the system.

Section 3, Operation, describes the day-to-day operation of

the system, including how to use the information and

control screens.

Section 4, Maintenance, describes the maintenance

procedures that are necessary to keep the system in full

working order, including the regular tests that should be

done.

Section 5, Installation, gives instructions on installing the

system, including fitting the sensor unit in the hull, manual

installation of the other components, running cables

between them, and setting up the system through its control

screens.

Section 6, Technical Details, provides technical details of the

system, including tables of specifications, drawings, output

formats, etc.

Section 7, Northern Solutions, gives more information about

the company, with details of how to contact for more

information.

8

2 Introduction to EMES60

2.1 Summary

EMES60 is a combined electromagnetic speed log and

echosounder navigation system. It is a single sensor with two

transducers in one housing.

Both parts have been designed to meet the relevant international

standards and provide all the modern and legacy input-output

interfaces that are specified by the IMO standards.

As required by the relevant regulations, the two parts are totally

separated internally.

The main advantage of this arrangement is that the system only

needs one hull penetration, and one set of mounting hardware,

thus increasing reliability and reducing costs of installation and

maintenance.

The size and weight of the sensor is significantly less than other

systems on the market, which greatly facilitates installation and

handling.

2.2 Highlights

Only one hull penetration, which increases safety of

navigation

Small overall diameter of sensor, requiring small hull

penetration, which minimizes the risk of mechanical

damage

Sophisticated analog and digital signal processing, which

provides reliable data in any navigation conditions

All modern and legacy input-output interfaces are

supported, including IEC61162-1/1 and IEC61162-450 (Light

Weight Ethernet)

Sound speed calibration based on temperature, which

provides accurate depth measurements in different

conditions without the need for manual adjustments

Includes water temperature sensor, accurate to 1°C

Optimized electromagnetic log operational parameters,

which provides accurate speed through water

measurements in different water conditions, such as sea

water, river water, and brackish water

5

2.3 System Structure

6

3 Operation

3.1 HMI Touch-Screen Controls

Reading the speed and depth information from the system, and

configuring the system for use, is done through the touch-screen

display units, called “human-machine interface” (HMI) units.

Data is also sent to external equipment using a range of standard

communication protocols and data formats.

Two HMI Units are usually fitted, both of which can run both the

echosounder and speed log parts of the system, but typically one

is configured to run the echosounder, and the other is configured

to run the speed log.

The HMI Units use touch-screen technology, so that controlling the

system is done by touching the relevant part of the HMI Unit

screen.

The structure and operation of both HMI units is similar. The

examples below are from the speed log, but the principles are the

same for the echosounder.

3.1.1 Structure of the screen

Summary data: (3.1.2)

Control buttons, time: (3.1.4)

Main window: different for each screen

type

Window navigation: touch a circle to

move to a new screen (3.1.9)

Settings buttons: touch to change

settings, and Home access (0)

7

The exact contents of the parts of the screen are different for

each screen type; see the section for each screen for detailed

information.

3.1.2 Summary data

All the screens show a summary of the data measured by the

system in the top row of the screen, together with GPS position.

The speed log HMI shows:

This section can be enabled or disabled using the GPS Display

on/off button at the top of the Home screens.

3.1.3 Changing display units

To change the units of the displayed values, touch the value

display box in the Summary Data area at the top of the screen. A

menu box appears.

Sp

ee

d: to

uc

h to

ch

an

ge

un

its

He

ad

ing

Po

sition

, No

rthin

g

Po

sition

, Ea

sting

Touch here to change speed units

Touch to enable or disable GPS display

Touch the arrow to see the units options

8

Options for the speed log are:

“mph”: miles per hour

“kn”: knots

“mph” is statute miles per hour (the measure of speed commonly

used for land speeds in some countries). “Knots” are nautical miles

per hour.

Most of the other displayed values have similar controls that are

accessed by touching their display box.

3.1.4 Control buttons

The second row has a set of buttons, which provide numerical

outputs as well as controls for the system. Each screen type is

slightly different, but a typical one is as follows.

3.1.5 Printing and screen snapshots

Touch the Print Screen button to send data

from the screen to a printer.

In Echosounder mode, this will start a

continuous printout of the echogram and the

GPS position data.

In Speed log mode, it makes a copy of the

screen for debug and maintenance purposes.

The function of this button is controlled by the

selection of the Screen copy selection in the

Hardware Interface Selection screen (section

3.1.14).

Win

do

w-sp

ec

ific

co

ntro

l

Prin

t scre

en

Time

disp

lay

: tou

ch

to c

ha

ng

e th

e tim

e

Wa

ter Te

mp

era

ture

disp

lay

: tou

ch

to

ca

libra

te

9

The printer used can be selected from the list

of system printers in the Hardware Interface

Selection screen.

3.1.6 Setting the time

Touch the time display box to open the

time-setting menu. Click on the hours,

minutes or seconds, and use the up and

down arrows to change them. Then touch

the “tick box” to set the new time.

3.1.7 Alarms

If a value goes over a minimum or maximum limit, an alarm can

be triggered. This causes the

following things to happen:

A flashing display is shown in

a prominent position on the

screen

Up to two alarm states are shown in the bottom row of the

screen

The alarm state is logged to an alarm list, with the time of

the alarm

One of the relays in the Interface Unit is switched. These can

be used to trigger audible alarms or set an alarm in other

systems.

To accept an alarm, causing the on-screen warning to disappear,

touch the flashing warning box. More than one alarm condition

could be in place at the same time, so it may be necessary to

repeat this procedure to accept the other alarms.

Some values displayed are colored according to the alarm

condition, even if the alarm has been accepted. For example, the

numerical display of depth will be:

Red in the “too shallow” alarm state

Amber in the “too deep” alarm state

The alarm states are controlled and monitored using the Alarm

screens, see section 3.1.7.

3.1.8 Setting alarm limits

The values at which alarms sound are shown in Alarm Buttons at

the bottom of the screen. There are typically two buttons, one for

the alarm when the value gets too low, and one for when it gets

too high.

10

To change these values, touch

one of the alarm buttons.

A pair of slider bars appears on

the screen; move the low

(“Lo”) and high (“Hi”) sliders to

change the alarm levels.

The alarm values in the alarm

buttons change to show the

new selections.

3.1.9 Window navigation

Use the Window

Navigation part of

the screen to go

directly to a different screen: touch the dot for the required

screen. Alternatively, “swipe” to left or right to move to an

adjacent screen. The current screen is shown as a filled dot.

11

3.1.10 Home screens

Touch the button in the bottom-right of most

screens to access the Home screen.

Also see sections 3.2.2 and 3.3.1.

The Home screens of the Echosounder and Speed Log interfaces

are similar, but a different selection of screens is available for

each.

Date: touch to change; SW Version

Language selection: touch to select the

operating language, and

Password: touch to enter Admin mode

Screen selection: touch to select a

screen type

Window navigation

Control buttons: day/night, default

settings, screen brightness, Return to

Screen, OFF

12

3.1.11 Control buttons

Control buttons at the bottom of the Home windows are:

Day/Night mode: touch to toggle

between Day and Night display modes.

The button shows the current mode. In

night mode, the display is shown in darker

colors, to preserve the night vision of the

user. A sun icon is shown in Day mode,

and a moon in Night mode.

Defaults: sets the system settings to default

values.

You are then presented with the option

of restoring to either the ship’s defaults

(see below) or factory defaults.

An “Are You Sure” screen appears when

the tick button is touched. Touch “OK”

to return all the settings of the system to

the selected set of settings.

Store ship’s default settings: stores the

current settings of EMES60. Also see Saving

Files to USB, section 3.2.1.

Return to Screen: returns the display to the

previous operational screen

OFF: turns the system off. An “Are You

Sure” screen appears when this button is

touched. Touch “OK” to turn the system

off.

13

3.1.12 Brightness control

Double-tap in any screen area, and a brightness

control slider is shown. Slide it up and down to

increase and decrease the brightness of the MMI

screen.

3.1.13 Administrator mode

EMES60 has two input modes: “Normal User” and “Administrator”.

Some operational parameters could prevent correct operation of

EMES60 if they are set incorrectly. These parameters cannot be set

in Normal User mode, and the operator must change to

Administrator mode in order to set them.

The system starts in Normal User mode. To change to Administrator

mode, go to the Home Screen (see sections 3.2.2 and 3.3.1), and

enter the Administrator password in the “Password” section. The

administrator password is supplied with the documentation that is

shipped with the EMES60.

The current input mode is shown at the bottom

of the screen.

14

3.1.14 Hardware interface setup

This screen is used to program the interface box according to the

specific requirements of the installation.

This screen can be accessed from both speed log and

echosounder modes.

The default settings can be restored when necessary.

The following outputs are available:

Relays: these are controlled from

the Alarms screen (see 3.1.7).

Opto outputs: opto-isolated

outputs can be set up to switch

when an event occurs in the

EMES60 system.

Two opto output channels are

provided.

Touch the box next to each opto

channel to set the event that

causes it to trigger. Select “Not

Used” if no action is needed on

that channel.

Opto outputs: touch to select the signals

that drive the Opto output channels

Pulse inputs: touch to select what

happens when a pulse is received on a

pulse input channel

Analog outputs: touch to select the

signals that drive the Analog output

channels

Screen copy: touch to select where

screen copy (print screen) is sent

COM outputs: touch to select the signals

that are provided on the serial data

output channels

15

Pulse inputs: a voltage signal

received from an external system

can be selected to cause an

action in the EMES60 system.

Two pulse input channels are

provided.

Touch the first box to the right of

the channel number (labeled

“Action select” above) next to

the channel to select the action

that is to happen in the system.

Touch the second box (labeled

“Level select” above) to select

which voltage level causes the

action. Options available are:

High Level: the action

happens when the input

channel is a high voltage

Low Level: the action

happens when the input

channel is a low voltage

Low -> High: the action

happens when the input

channel changes from low

to high voltage

High -> Low: the action

happens when the input

channel changes from

high to low voltage

Analog outputs: analog outputs

can be configured to provide a

varying voltage output in

response to a measured value in

the EMES60 system.

Two analog output channels are

provided.

Touch the first box next to the

channel number to switch

between 0 to 10 V voltage

output and 4 to 20 mA current

output.

Action

select Level

select

16

Touch the next button to select

the value output. This is different

for the speed log and the

echosounder. The example

shown is for the speed log, with a

selection between longitudinal

speed, transverse speed, and the

resultant (vector sum) of the two

speeds.

Touch the next box to select the

value that corresponds to the

lowest analogue output. For

example, if ‘5’ is selected for

depth, then the lowest analogue

output (0V or 4mA) is given for

depths of 5m or less. Touch the

next box for the highest value.

For example, if ‘100’ is selected,

then the highest analogue

output (10V or 20mA) is output

for depths of 100m or greater.

Screen copy: this controls what

happens when the Print Screen

button at the top of most

windows is touched

Touch Printer to send screen

copy images to a printer, and

File to send them to a file, stored

in the HMI memory.

Touch the box next to this control

to select the printer from a list of

available system printers.

3.1.15 Demo and Simulation modes

EMES60 can be put into special modes, to help with training and

testing.

17

Select Demo and Simulation modes:

demo and simulation modes are set in

the Home screens; touch the mode

button and select the required mode.

Warning: ensure that the mode is set to

Normal when EMES60 is used for

navigation.

The available modes are:

Normal: the information shown in the screens and the

outputs from the external interfaces are driven by the

measurements made by the speed log and echo sounder

sensors.

Demo: the screens are driven by artificial speed log and

echo sounder data, which is computed inside the EMES60

software. This is useful for training, when real data from the

sensor head is not available.

Simul: simulation mode; in this mode, the screens and

outputs are also driven by data computed by the EMES60

software, but the operator can program the parameters of

the data that is shown and output.

To set the simulation parameters: select simulation mode, then go

back to screen 1. Click in the area of the digital depth (or speed)

indicator.

18

3.2 Echosounder

The echosounder function measures the depth of water under the

vessel.

3.2.1 Saving files to USB key

Data can be transferred to and from the

EMES60 MMI units using the USB Key

control, for maintenance and

troubleshooting.

Remove the MMI unit from the mounting

panel, and insert a USB key drive into the

USB port.

Touch the USB Key button in the Home

screen.

A menu of options is provided:

Upgrade display software: before

inserting the USB key, copy a software

update file to it. These software

updates may be obtained from

Northern Solutions. Select the software

update version to be loaded from the

menu.

Upgrade interface software: as for the

display software, but updating the

interface functions of EMES60

Upgrade sensor software: as for the

display software, but updating the

sensor processing functions of EMES60

Upload ship’s defaults: a set of default

settings for a ship can be saved to

disk, and loaded back to the EMES60

using this option.

Download data: select this option to

copy data from EMES60 to the USB

key. The data can then be sent to

Northern Solutions for diagnostic

purpose.

19

Download data options: the Download

data control allows data to be copied

from the EMES60 MMI units to a USB key.

Select the data type that is to be copied.

The data is copied to a folder called

“EMES60” on the USB key, divided into

sub-folders by data type.

Compress the folders using a tool such as

“zip”, and send them to Northern

Solutions to assist with service and fault-

finding support.

3.2.2 Echosounder Home screen

This screen is used to go to the desired operational screens, and for general

controls.

It is also possible to navigate between different screens by “swiping” sideways, or

by touching the Screen selection buttons at the bottom of the screen.

See section 0 for more on navigating between screens.

Speed; Heading; GPS position

Date: touch to change; SW Version

Language selection, Password

Screen selection: touch to select a

screen type

Window navigation

Control buttons

20

3.2.3 Echosounder main operational screen

This screen is the one that is shown in normal use of the echosounder.

It displays the echogram (a scrolling color-coded view of seabed echoes) and

depth.

Speed, heading and GPS position information is indicated in the top line of the

display.

Image scrolling speed (minutes:seconds per division), time and draft are

indicated in the second line.

The following parameters can be adjusted with this screen:

All transceiver settings (GAIN, TVG, POWER)

Shallow and Deep alarms

Range and picture speed

Ship’s draft

Units of measurement

Alarm settings: touch Alarm to set the

depths that cause an alarm; Home

Scroll speed, touch to change; Print

screen; time: touch to change; draft:

touch to calibrate

Speed: touch to change units; Heading,

GPS position

Transceiver settings: touch Gain, Tvg or

Power to set transceiver parameters

Echogram; Depth scale: touch and drag

the scale bar to change scale

Depth readout

Origin of depth measurement

Location of transducer

21

3.2.4 Changing depth scale

Touch and drag over the depth scale area to change the scale of depth that is

shown in the display.

3.2.5 Changing scroll speed

The right-to-left scroll speed can be changed by either of the following:

Touch the scroll speed indicator to open an adjustment slider

Touch and drag over the time scale area in the top of the echogram

area

3.2.6 Setting the transceiver gain

Touch the Gain button to change the

gain of the sonar receiver. Increase the

gain if the signal appears too weak (for

example, in deep water or over very soft

bottoms), and decrease it if it is too

strong, and seems to be “saturating” (in

shallow water and very hard bottoms).

3.2.7 Setting the time-varying gain

Touch the Tvg button to change the

time-varying gain of the sonar receiver.

This also boosts the receive signal, but

the amount of gain increases with time,

which helps to detect a deep seabed

without increasing the amount of

interference from objects in the water

between the boat and the seabed.

3.2.8 Setting the transmitter power

Touch the Power button to increase the

strength of the pulse of sound energy

from the sonar transmitter. As with the

gain settings, increase this to boost the

signals if they seem to be too weak, or to

reduce it if the signal seems to be

“saturating”.

22

3.2.9 Gain, TVG and Power slider

Touching any of Gain, Tvg or Power

shows a set of slider controls for all three.

Touch and slide the appropriate slider

control to increase and reduce these

settings.

Touch the button below the slider to

revert to factory settings.

3.2.10 Setting the draft offset

The button with a picture of a ship

adjusts the vessel draft offset.

Touch this button, and a slider appears.

Touch and drag to change the draft

offset.

A positive value is the distance between

the transducer and the water surface. A

negative value is the distance between

the transducer and the lowest part of

the keel.

Revert to factory settings

23

3.2.11 Echosounder digital indicator

This screen can be used as a repeater.

The large depth digits are observable

from at least 5m.

The color of the depth digits changes

with alarm states:

Red in the “too shallow” alarm

state

Amber in the “too deep” alarm

state

The text below the numerical readout

shows where the depth is measured

from, and the location of the depth

transducer.

Touch the Digital Indicator screen to

show a control menu, which allows you

to control the values that are shown.

Touch the arrow to the right of each

selection to show a list of available

selections:

Depth reference selections are:

Below transducer: the depth shown is from the sensor to the seabed

Below surface: the depth shown is from the water surface to the seabed

Below keel: the depth shown is from the bottom of the ship’s keel to the

seabed.

Depth units controls the units that the depths are shown in; selections are:

m: meters

ft: feet

Fm: fathoms

Sensor pos control allows the position of the sensor to be shown. Selections are:

Fore ship: the sensor is at the front of the ship

Aft ship: the sensor is at the back of the ship

Starboard: the sensor is on the starboard side

Port: the sensor is on the port side

24

Digit controls the size of the text that shows the depths; selections are:

small: depth is shown in a small font

large: depth is shown in a large font

3.2.12 Echosounder communication screen

This screen is used to verify the incoming and outgoing data through the system

communication lines (NMEA serial and Light Weight Ethernet).

All data can be logged to a file on disk.

It is also used to setup the communication line parameters (UART setting for

NMEA0183, IP address for Light Weight Ethernet)

Message display controls: the input and output message displays can be

controlled separately:

Freeze: touch this to pause new messages being added to the screen

Save to file: touch to send the messages to a file in the HMI memory

Enter file name: touch to enter a name for the file that the messages are

saved to

Input messages: data messages sent to

the system

Output messages: data messages sent

from the system

Message display controls

Message display controls

Horizontal scroll: touch and drag to see

long messages

Communications port controls

25

3.2.13 Saving communications data to file

Input and output data can be saved to

separate files.

In the Communications screen, touch

the “Enter file name” box to select a

name for the log file.

A file name entry box appears.

Touch the name of an existing file to

select it for logging, or touch the file

name entry box to open a touch

keyboard to specify a new name.

The new name will appear in the list

when data has been recorded to it.

To delete a file name from the list, touch

the name to be deleted and then the

Delete key.

Use the touch keyboard to enter the file

name, then touch the Return key

to use this name, or the Esc key to reject

the entered text.

Then touch the “Ok” button to select this

file.

Use the Cancel button to exit the file

name screen without making any

changes.

When a file has been selected for

logging, touch the “Save to file” button.

A tick appears in the button to show that

data is being logged. Touch the button

again to stop logging. The tick

disappears when logging stops.

26

3.2.14 Communications port controls

The parameters of the ports used to send

data to and from EMES60 can be

configured from the Communications

screen. Touch the bottom-left button to

select the port to be set up.

This shows a selection box.

Touch the arrow to the right of the port

name in the selection box. This shows a

list of ports: two serial ports (Port1 and

Port2) and Ethernet (LAN). Touch the one

that you wish to set up.

To change the serial port parameters,

select Port1 or Port2, then touch the

button to the right of the port selection,

which shows the baud rate. A port

settings box opens; touch the small

arrows to the right of the settings values

to change them.

If LAN is selected, the port parameters

change to show the Host IP address and

Port number.

Touch the Host button: A LAN settings

box appears. Use this to set the IP

address of the HMI unit (local host), and

its port number, and the IP address and

port number of the external system that

is connected to over the network.

27

3.2.15 Echosounder alarm configuration screen

This screen allows the system alarms to be configured.

When a value that is measured by the system goes out of limits, an alarm is

issued. This screen allows the alarm limit, and what happens when the alarm is

triggered, to be set.

When an alarm occurs, it is associated

with an ID number.

To set an alarm ID, touch the value box

next to the alarm type text. This opens a

number touch keyboard. Enter the ID

number and touch the “Return” key, or

“Esc” to leave the value unchanged.

Alarm ID and Relay controls

Freeze alarm display and last alarm

Alarm history

Horizontal scroll bar

28

When an alarm is triggered, it is possible

to trigger a relay in the Interface Unit,

which can be used to trigger audible

alarms or set an alarm in other systems.

Touch the “Relay Num” button next to

the relevant alarm type, and select the

number of the relay to trigger, or “Not

Used” to disable relay operation for that

alarm type.

A scrolling history of alarms is shown in the bottom half of the display. Use the

vertical scroll bar to look through all of the alarms in the system memory, and

the horizontal scroll bar to read alarm messages that do not fit in the display

window.

Touch the Freeze button to stop new messages being shown in the window. A

tick appears in the button when the alarm display is frozen.

The shallow and deep alarm depths are

shown in the Alarm button at the bottom

of the screen. If the depth is shallower

than the shallow alarm depth, or deeper

than the deep alarm depth, an alarm is

triggered.

Touch the Alarm button to change the

shallow and deep alarm depths.

This shows a slider control, with Shallow

and Deep settings. Touch and slide to

change the alarm depths.

29

3.2.16 Echosounder hardware Interface screen

This screen controls the hardware inputs and outputs of the echosounder

function. See section 0 for instructions on setting up the hardware interfaces for

the echosounder and speed log.

The analog output can be one of:

DBT: depth below transducer

DBS: depth below surface

DBK: depth below keel

The numbers to the right of this selection show the depth that corresponds to

the lower voltage or current (0V or 4mA), and the depth that corresponds to

the higher (20mA or 10V).

NMEA 0183 messages can be output on three serial ports; use the tick-boxes to

select which messages are sent out on which serial port. Each serial port can

output any number of the available messages. See section 6.5 for a description

of the available NMEA 0183 messages.

Opto outputs: touch to select the signals

that drive the Opto output channels

Pulse inputs: touch to select what

happens when a pulse is received on a

pulse input channel

Analog outputs: touch to select the

signals that drive the Analog output

channels

Screen copy: touch to select where

screen copy (print screen) is sent

COM outputs: touch to select the signals

that are output on the COM serial ports

30

3.2.17 Echosounder history screen

This screen provides a graph of echosounder data against time.

Use the arrows at the bottom of the screen to scroll through the record, and

touch at a point in the graph to show the values at that time; a vertical line

appears at the selected time, and the time box in the second row down shows

the selected time.

The screen shows the echosounder data for one day. To change the day that is

shown, touch the top-left button.

The scale can be changed by touching in the area of the range scale lines.

Touching the upper area changes the upper range, and touching in the lower

area changes the lower range.

The single arrows below the display area move the cursor left and right, and the

double arrows move the entire screen left and right when it is zoomed.

Cursor time and date: time and date of

the cursor line in the history graph.

Touch to select.

History graph: touch to move the

cursor. Touch and drag up and down

to change depth scale.

Navigation: single arrows move cursor,

double arrows move display area when

zoomed in

Data key

31

3.2.18 Echosounder oscilloscope screen

This screen is used for echosounder sensor troubleshooting and setup.

The lower part of the screen indicates the digitized echo-signal, which greatly

facilitates troubleshooting.

GPS information is indicated in the upper line.

Scrolling speed, in minutes and seconds per step, time, and vessel draft are

indicated in the second line.

Echosounder display: shows the echo

signal strength, color-coded

Scroll speed, time and draft

Echosounder signal strength of latest

ping: echo signal strength as a line

graph: time horizontal, signal

strength vertical

Gain controls: see section 3.2.6

32

3.2.19 Echosounder test and troubleshooting screen

This screen shows the results of the self-test functions built in to EMES60.

Self-test measurement results; scroll up

and down to see more results

Troubleshooting output log

33

3.3 Speed log

The speed log measures the speed of the vessel through the

water.

3.3.1 Speed log Home screen

This screen is used to go to the desired operational screens, and for general

controls.

It is also possible to navigate between different screens by “swiping” sideways, or

by touching the Screen selection buttons at the bottom of the screen.

See section 3.1.9 for more on navigating between screens.

See section 3.1.11 for use of the Control buttons.

Date: touch to change; SW Version

Language selection, Password

Screen selection: touch to select a

screen type

Window navigation

Control buttons

34

3.3.2 Speed log main operational screen

This screen is the one that is shown in normal use of the speed log.

It shows the vessel speed through the water in forward and sideways directions,

and the total distance travelled.

Touch the speed and distance display boxes to set the units of measurement.

The alarm limits (low and high speed) are adjustable, using the Alarms screen;

see section 3.1.7.

GPS information is indicated in the upper line.

Time and water temperature are indicated in the second line.

Speed: touch to change units; Heading,

GPS position

Print screen; time; temperature: touch to

calibrate

Transverse speed: sideways speed, as a

number and a bar indicator

Longitudinal speed: forward speed, as a

number and a bar indicator

Total distance travelled

Total distance travelled in this trip: touch

to reset

Alarm speeds: touch to change; Control

screen button; Home access

35

3.3.3 Setting alarm speeds

Alarms are given when the speed is lower

than a low speed limit, and when the

speed is higher than a high speed limit.

See section 3.1.7 for more information on

alarms.

The low speed alarm is

shown in the low speed

alarm button.

The high speed alarm is

shown in the high speed

alarm button.

Touch either of these buttons to show a

pair of sliders that allows you to change

both alarm levels.

3.3.4 Speed log single axis indicator

This screen shows the resultant speed (the

vector sum of forward and lateral speeds)

as a dial and a number.

It also shows the total distance travelled

and the distance in the current trip.

36

3.3.5 Speed log communication screen

This screen is used to verify the incoming and outgoing data through the system

communication lines (NMEA serial and Light Weight Ethernet).

All data can be logged to a file on disk.

It is also used to setup the communication line parameters (UART setting for

NMEA0183, IP address for Light Weight Ethernet).

See section 3.2.13 for details of saving communications data to file.

See section 3.2.14 for details of setting the communications port settings.

Input messages: data messages sent to

the system

Output messages: data messages sent

from the system

Message display controls

Message display controls

Horizontal scroll: touch and drag to see

long messages

Communications port controls

37

3.3.6 Speed log alarm screen

This screen allows the system alarms to be configured.

When a value that is measured by the system goes out of limits, an alarm is

issued. This screen allows the alarm limit, and what happens when the alarm is

triggered, to be set.

See section 3.2.15 for details of setting the alarm ID and relay outputs.

Alarm ID and Relay controls

Freeze alarm display and last alarm

Alarm history

Horizontal scroll bar

38

3.3.7 Speed log hardware interface screen

This screen controls the hardware inputs and outputs of the speed log function.

See section 0 for instructions on setting up the hardware interfaces for the

echosounder and speed log.

The analog output selection can be one of:

Longit: longitudinal speed: speed in the forward direction

of the vessel

Trans: transverse speed: speed in the port-starboard

direction

Resultant: overall speed; the vector sum of the longitudinal

and transverse speeds

The numbers to the right of this selection show the speed that

corresponds to the lower voltage or current (0V or 4mA), and the speed that

corresponds to the higher (20mA or 10V).

NMEA 0183 messages can be output on three serial ports; use the tick-boxes to

select which messages are sent out on which serial port. Each serial port can

output any number of the available messages. See section 6.5 for a description

of the available NMEA 0183 messages.

Opto outputs: touch to select the signals

that drive the Opto output channels

Pulse inputs: touch to select what

happens when a pulse is received on a

pulse input channel

Analog outputs: touch to select the

signals that drive the Analog output

channels

Screen copy: touch to select where

screen copy (print screen) is sent

COM outputs: touch to select the signals

that are provided on the serial data

output channels

39

3.3.8 Speed log history screen

This screen provides a graph of speed data against time.

Use the arrows at the bottom of the screen to scroll through the record, and

touch at a point in the graph to show the values at that time; a vertical line

appears at the selected time, and the time box in the second row down shows

the selected time.

The screen shows the speed data for one day. To change the day that is

shown, touch the top-left button.

The scale can be changed by touching in the area of the range scale lines.

Touching the upper area changes the upper range, and touching in the lower

area changes the lower range.

The single arrows below the display area move the cursor left and right, and the

double arrows move the entire screen left and right when it is zoomed.

Cursor time and date: time and date of

the cursor line in the history graph.

Touch to select.

History graph: touch to move the

cursor. Touch and drag up and down

to change depth scale.

Navigation: single arrows move cursor,

double arrows move display area when

zoomed in

Data key

Zoom buttons; touch to clear the zoom,

and to zoom in and out

40

3.3.9 Speed log oscilloscope screen

This screen is used for speed log sensor troubleshooting and setup.

The raw electromagnetic data from the sensor is shown as three graphs, each

with signal strength in the vertical axis and time in the horizontal axis.

Touch the speed log controls button to

open a control dialog

The controls dialog allows you to set the

paramters of

Raw longitudinal sensor data

Raw transverse sensor data

Raw electromagnetic field data

41

3.3.10 Speed log test and troubleshooting screen

This screen shows the results of the self-test functions built in to EMES60.

Self-test measurement results; scroll up

and down to see more results

Troubleshooting output log

42

3.3.11 Speed log calibration screen

This screen is used for calibrating the speed log.

Make several runs, back and forth, across the same line over the seabed.

Start data collection for each line by touching the left flag, and stop by

touching the right flag. All legs are stored in the Calibration trips table in the

middle of the screen. When enough lines have been run, select the best ones,

and touch them in the Calibration Trips table to transfer them to the Calibration

table in the bottom part of the screen.

See section 5.7.3 for details of the speed log calibration process.

Calibration trip Start, Stop and progress

indicator: touch flags to start and stop

Calibration trip table: touch a column to

select a trip

Calibration trip Use and Delete buttons

Calibration table: shows the trip

information that is used in calibration

Reset and Home buttons

43

4 Maintenance

EMES60 is very simple and robust, and needs very little regular

maintenance. However, the following instructions should help to

keep an EMES60 system accurate and operational.

4.1 Precautions

4.1.1 Operation in Air

The transducer may be damaged by prolonged operation in air.

After the initial dockyard installation tests, and before dry-docking,

make sure that the system is disconnected from the electrical

power supply.

4.1.2 Sensor Head

Do not open the sensor head. There are no user-serviceable parts

inside.

4.2 Tests and Checks

Run the following tests and checks after Installation and at regular

test intervals.

4.2.1 Safety check

Inspect all components of the system for safety, including:

Ensure that all electrical supplies are intact and

undamaged

Ensure that all cables are properly fixed down

Check for water leaks around the valve assembly

4.2.2 Connector checks

Check the state of all cables and connectors. Loose or damaged

cables and connectors are probably the most common source of

system problems.

4.2.3 Electronic Unit Checks

Check the state of the electronic unites.

Ensure that the electronic unites are firmly fixed in place

Check that the cable glands are still holding the cables

firmly and that their rubber seals are intact, undamaged

and not starting to “perish”

Check for corrosion inside and out

Check that all the pluggable terminal blocks are still firmly in

place

Check that all of the terminal block screws that hold the

wires in place are still done up tightly

44

Check and replace if necessary the silica gel packs inside

the electronic unites

4.2.4 Inspect transducer for marine growth

Marine growth on the surface of the transducer will reduce its

efficiency and degrade the accuracy. All such marine growth

should be removed as gently as possible: do not use sharp tools or

mechanical grinders; otherwise, the transducer face can be

damaged.

Pay particular attention to the electromagnetic speed log

electrodes, which are small steel fixings in the face of the

transducer head; they must be clean and untarnished. Carefully

remove any tarnishing, corrosion, or marine growth from these

electrodes using fine abrasive sheet or wire wool, making sure not

to damage the surrounding plastic of the sonar transducer.

4.2.5 Corrosion check

Check all items for corrosion.

4.2.6 Cleaning

Clean the HMI screens and electronics systems:

Electronic unites: use a damp cloth, no solvents.

Display screens: use a soft cloth lightly moistened with a mild

detergent solution, then wipe clean with a soft dry cloth. Do

not use tissue paper, which could scratch the screens.

Sonar assembly: wipe over with a soft cloth lightly moistened

with a mild detergent solution.

4.2.7 Functional checks

The following tests check the function and correct connection of

the EMES60 system.

The LEDs and test points are described in section 6.2.

Test Procedure Checks

for

Expected

Result Sensor Power Unit

Power LEDs

Open the Sensor Power Unit and check

that the power LEDs are lit on both

boards, depending on where the

power source comes from: LD100 (24V

from AC), LD101 (24V from DC). See

section 6.2.2.

Sensor

Power Unit

power

supply

LEDs lit

Sensor Power Unit

Power Test Points

Open the Sensor Power Unit and use a

voltmeter to check the voltage at the

following test points: on both boards:

TP100 (Main 24V Internal Bus), TP10

(Local 5V). See 6.2.3.

Sensor

Power Unit

power

supply

Voltages are

within

permitted

ranges

45

Test Procedure Checks

for

Expected

Result Interface Unit

Power LEDs

Open the Interface Unit and check

that the following LEDs are lit,

depending on which power sources

are connected: LD100 (power from AC

mains), LD101 (power from DC). See

6.2.5.

IU power

supply

LEDs lit

Interface Unit

Power Test Points

Open the Interface Unit and use a

voltmeter to check the voltage at the

following test points: TP100 (24V), TP101

(3.3V), TP102 (5V). See 6.2.6.

Interface

Unit power

supply

Voltages are

within

permitted

ranges

Compass input Start up one of the HMI screens. Look

at the Summary Data items at the top

of the screen (3.1.2). Check that the

heading shown matches the

heading shown by another reliable

heading source on the vessel.

Repeat with the other HMI.

Heading

input

Heading shown

matches that

from another

heading

source within 2°

Position input Start up one of the HMI screens. Look

at the Summary Data items at the top

of the screen (3.1.2). Check that the

position shown matches the

position shown by another reliable

heading source on the vessel.

Repeat with the other HMI.

Heading

input

Heading shown

matches that

from another

heading

source within 2°

4.2.8 Routine Tests

The following tests and observations help you to be confident that

the system is working correctly:

HMI Screens

o Put the system into Demo mode (an option in the

Home screens, section 0), and check that the screens

update regularly with the Demo data. Remember to

disable Demo mode after this test.

NMEA data input

o Input NMEA data is echoed to the communications

screens (3.2.12 and 3.3.5); use this screen to check

that the data is being correctly received.

Echosounder

o Compare the echosounder depth with the depth that

you expect from the chart, accounting for tide

o Look at the Echosounder oscilloscope screen (section

3.2.18) to check that the history of echosounder

values looks reasonable for the seabed type, and the

echo strengths are neither too weak nor too strong.

o Inspect the results of the self-test processes provided

in the Echosounder test and troubleshooting screen,

(3.2.19)

Speed log

46

o Compare the speed log speed with the GPS speed,

which is shown in the top-left corner of most HMI

screens. Any difference in the two speeds should be

related to water currents.

o Check that the history of speeds in the speed log

history screen (3.3.8) matches what you know of the

recent movements of the vessel

o Inspect the results of the self-test processes provided

in the speed log test and troubleshooting screen

(3.3.10).

47

4.3 Troubleshooting

The following suggestions may help to cure any problems with the

system.

Problem Possible

Cause

Test Cure

No GPS or heading

information in the

top bar of the HMI

screens. (No data

from ship’s GPS or

compass).

No output data Inspect communication

screens for input data

(3.2.12).

Turn on ship’s

outputs.

Loose input

wiring

Check input wiring and

ship’s GPS and compass

output

Fix loose cabling.

Input data rate

and format

settings wrong

Check communications

port protocols in

communication screens

(3.2.12 and 3.3.5)

Enter correct

port protocols

Display units are

wrong (e.g. mph

instead of knots)

Wrong units

selected

Touch the value affected

on the screen. A units

selection box should

appear.

Select the

correct units.

False alarms

generated

Alarm limits are

too tight

Check the alarm limits

(3.1.8)

Set correct

alarm limits

HMI displays too dim

or too bright

Day or night

mode selected

at the wrong

time

Go to the Home screen

(0) and select the required

day/night display mode in

the bottom-left corner of

the screen

Correct

day/night mode

used

Can’t set some of

the operation

parameters

Unit is not in

Administrator

mode

Some settings can only be

changed in Administrator

mode. See 3.1.13.

Set Administrator

mode to

change settings.

Echosounder depth

wrong

Wrong depth

origin selected

Check the depth origin

(e.g. “Below Transducer”)

shown in the echosounder

displays. Touch this to

change the origin. See

3.2.11.

Depth origin set

to the value that

you expect.

Draft offset

wrong

See 3.2.10 to inspect and

set the offset

Correct draft

offset used

Transmitter

power and

gains too weak

or strong

See 3.2.9. Correct power

and gains used

for the current

conditions

Sound speed

wrong: sound

speed problem

Check water temperature

in the speed log screens

Problem with

sound speed

identified

Sound speed

wrong: sound

speed not

corrected

Touch the sound speed

display, and use the slider

that appears to enter the

sound speed measured

by another sensor

Sound speed

calibrated

against an

external sensor

Marine growth

on sensor head

Inspect the face of the

sensor (requires dry dock

removal of sensor head, or

diver). See 4.2.4.

Clean sensor

surface gives

best results

Other problem

with the

echosounder

Look at the echosounder

self-test results screen

(3.2.19)

Helps to identify

problems

48

Problem Possible

Cause

Test Cure

Speed log speeds

wrong

Speed log not

calibrated or

calibrated

wrongly

See section for 5.7.3 for

the speed log calibration

process

Speed log is

correctly

calibrated

Other problem

with the speed

log

Look at the speed log self-

test results screen (3.3.10)

Helps to identify

problems

Speed log

electrodes

tarnished or

corroded

Inspect the face of the

sensor (requires dry dock

removal of sensor head, or

diver). See 4.2.4.

Clean

electrodes give

best results

49

5 Installation

5.1 Parts of the System

Qty Image

5.1.1 HMI Units

HMI touch-screen panel 2

HMI panel fixings 8

HMI panel terminal blocks, 3-way 2

5.1.2 Electronic Units and Cabling

Interface Unit 1

Interface Unit pluggable terminal

blocks

Sensor Power Unit 1

Electronic unit fixing lugs 8

Sensor Power Unit pluggable

terminal blocks

50

5.1.3 Sensor Head Assembly

The parts of the sensor head assembly are shown below, in an

“exploded” assembly image. In the left-hand picture, only the

ends of the Installation Pipe are shown; the complete pipe is

shown on the right.

Ref Part name Part number Pcs

1 Sensor housing 1

2 Adapter rubber gasket S_AG 1

3 Adapter, 60mm S_AD60 1

4 Installation pipe washer S_PW 4

5 Installation pipe rubber gland S_PG 2

6 Installation pipe S_IP 1

7 Installation pipe nut S_PN 1

8 Set screw M4x8 mm DIN7991 A4 1

9 Allen screw M5x15 mm DIN912 A4 4

51

5.1.4 Ball Valve Assembly

Ref Part name Specification Part number Pcs

1 Bottom flange, 60mm Custom BV60_BF 1

2 Screw pin Custom BV60_SP 8

3 Bottom flange gasket Custom BV60_BG 1

4 Nut M16 M16 DIN934 A4 BV60_NM16 8

5 Spring washer M16 M16 DIN127B A4 MB60_SW16 8

6 Washer M16 M16 DIN125 A4 MB60_WM16 8

7 Ball valve Custom BV60_BV 1

8 Top flange O-ring BV60_OR 1

9 Top Flange, 60mm Custom BV60_TF 1

10 Top flange rubber gland Custom BV60_RG 2

11 Top flange washer Custom BV60_TW 1

12 Top nut Custom Bv60_TN 1

13 Screw M8 M8 DIN933 A4-80 BV60_SM8 4

52

5.2 Mounting the Sensor on the Vessel

The sensor must be mounted in a water-tight valve or tank, so that

the face of the sensor is flush with the surface of the hull. This is

important in order to minimize turbulence around the sensor face.

The sensor should be mounted:

Where there is space on the inside of the hull to access the

unit for installation and maintenance of the sensor

On a section of the hull that is flat and horizontal, and large

enough to ensure laminar flow over the sensor face

With the transducer face as horizontal as possible: within ±1°

As close to the vessel’s centerline as possible

As far forward on the vessel as possible, ideally just behind

the bulbous bow, and always in the front half of the vessel

As deep as possible, where it remains underwater at all

speeds, conditions and vessel loadings

Away from sources of turbulence or entrained air bubbles in

all weathers, speeds and vessel loadings. Avoid:

o Bow thrusters

o Objects that protrude from the hull

Where risk of damage, for example from anchor chains, is

minimized

It may be necessary to modify the hull to provide a horizontal

mounting surface. If this is done, make sure that any welds are

smoothed off to minimize turbulence.

Make sure that the direction markings on the sensor match the

forward direction of the vessel.

Before any welding:

Remove O-rings and any parts that may be damaged by

heat

After welding:

Grind down to ensure a flush finish

Paint the fitting and hull with anti-corrosion and anti-fouling paint,

but do not paint the active surface of the sensor.

53

5.3 Sensor Deployed and Inboard

When the vessel is afloat, the sensor is deployed below the hull on

the end of the installation pipe. But before the vessel is launched

or dry-docked, the sensor must be brought inboard so that it is not

damaged.

The two states are shown in the images below.

Figure 1 Sensor Deployed (Ball

Valve and Bottom Flange

omitted for clarity)

Figure 2 Sensor Inboard

54

5.3.1 Installing the sensor in the valve

EMES60 is usually mounted in the Sensor Head Assembly, (shown in

5.1.3 above), which is then fitted into the Ball Valve Assembly

(5.1.4).

5.3.2 Cautions

Take care not to damage the inner surfaces of the valve; do

not attempt to lift the valve by passing rope, strops or chain

through the valve.

Do not paint the surface of the sensor.

Any modifications made to the vessel to fit the valve may

require approval of the appropriate classification body.

5.3.3 Fitting the Bottom Flange to the hull

The Bottom Flange is welded to the hull, and the rest of the

assembly is fixed to the Bottom Flange. See section 6.4.1 for a

drawing of the Bottom Flange.

To fit the Bottom Flange to the hull:

Disassemble the Bottom Flange from the valve assembly

Cut a 187mm diameter hole in the hull

Weld the flange to the hull

Grind down the weld to ensure a flush finish

Paint the flange and hull with anti-corrosion and anti-fouling

paint

Check that the inner and top surfaces of the Bottom Flange

are free from dirt, swarf, paint, etc.

Caution: when welding the bottom flange to the hull:

Protect the machined bottom and inner surfaces from

damage and debris. Damaged or dirty surfaces may not

give a good water seal.

55

Do not allow the flange to over-heat; allow cooling time,

particularly when welding to thick hull plates or stainless

steel parts.

Ensure that the welder is suitably qualified and certified.

5.3.4 Assembling the Sensor Head Assembly

The Sensor Head Assembly is deployed inside the Ball Valve

Assembly. The Sensor Head Assembly must be assembled first.

An exploded view of the Sensor Head Assembly is shown in 5.1.3

above, and it is shown in cross-section below.

The Sensor Cable is supplied fixed to the top of the Sensor

Housing. Take care not to damage the seal and connection

56

of the cable to the housing; do not lift the housing by the

cable.

Pass the following components over the length of the Sensor

Cable, in the following order, referring to the diagram

above to check which way round the parts are fitted:

o Adapter Rubber Gasket [2]

o Adapter, 60mm [3]

o Installation Pipe Washer [4]

o Installation Pipe Rubber Gland [5]

o Installation Pipe Washer [4]

o The Installation Pipe [6]

o Installation Pipe Washer [4]

o Installation Pipe Rubber Gland [5]

o Installation Pipe Washer [4]

o Installation Pipe Nut [7]

Place the Adapter Rubber Gasket on top of the Sensor

Housing.

Place the Sensor Head Adaptor (60mm) on top of the

Adaptor Rubber Gasket, and fix it to the Sensor Housing

using 4 M5X15mm socket head screws.

Grease the Installation Pipe Washers with silicone grease

type 6014 or equivalent.

Fit the first Installation Pipe Washer on top of the Sensor

Head Adaptor, then the Installation Pipe Rubber Gland, and

finally another Installation Pipe Washer.

Offer the Sensor Head Adaptor, with Sensor Housing fitted to

it, to the end of the Installation Pipe. Carefully turn the pipe

so that the Sensor Head Adaptor screws into the end of the

Pipe. Note that the top Installation Pipe Washer is pushed

against the step inside the pipe, so that the Adaptor Rubber

Gasket is compressed when the pipe is screwed down onto

the Adaptor, thus causing it to bulge outwards and form a

seal against the pipe. This requires 40-50Nm torque.

When the Installation Pipe is fully screwed home over the

Adaptor, lock it in place with an M4x8 mm Set Screw [8],

using 1.5Nm torque, fixed with Loctite 222.

Grease the remaining two Installation Pipe Washers with

silicone grease type 6014 or equivalent.

At the top of the Installation Pipe, fit the Installation Pipe

Washer, Installation Pipe Rubber Gland and the last

Installation Pipe Washer into the end of the Installation Pipe.

Carefully insert the Installation Pipe Nut into the top of the

Installation Pipe, and rotate it so that it screws into the Pipe

and seals the cable at the top of the pipe.

The Sensor Head Assembly is now ready to be fitted into the Ball

Valve Assembly.

57

5.3.5 Assembling the Ball Valve Assembly

Refer to the images in section 5.3 above to see how the Sensor

Head Assembly is fitted into the Ball Valve Assembly. The parts of

the Ball Valve Assembly are shown below.

Pass the Sensor Cable and Installation Pipe through the Top

Flange (60 mm) [9].

Run the following parts over the length of the Sensor Cable,

and then over the length of the Installation Pipe, in order:

o 2 Top Flange Rubber Glands [10]

o The Top Flange Washer [11]

o The Top Nut [12]

Pull the Installation Pipe back through the Top Flange, so

that the Top Flange Rubber Glands and Top Flange Washer

58

fit inside the top of the Top Flange, and carefully and loosely

screw the Top Nut into the Top Flange. Do not tighten the

Top Nut yet.

Rotate the Installation Pipe so that the Sensor Head will face

forwards when the Top Flange is fitted to the rest of the

assembly. Refer to the alignment marks on the Sensor Head;

see the diagram below.

Push the Sensor Head Assembly fully up through the Top

Flange, so that the Sensor Head is completely inside the Top

Flange.

Tighten the Top Nut to compress the Top Flange Rubber

Glands, and lock it in place using two M8 screws [13]; one

locking the Top Nut into the Top Flange, and the other

locking the Installation Pipe into the Top Nut. Note that

tightening the Top Nut compresses the Top Flange Rubber

Glands, which creates the water seal between the

Installation Pipe and the Top Flange.

5.3.6 Fitting the Assembly to the Bottom Flange

The complete assembly is fitted to the hull using the Bottom

Flange, which has been welded to the hull: see 5.3.3 above.

Screw four Pin Screws [2] into the Bottom Flange [1].

Place the Bottom Flange Gasket [3] on top of the Bottom

Flange.

Place the Ball Valve [7] over the Pin Screws, and fix it in

place using four M16 washers [6], four M16 Spring Washers

[5] and four M16 nuts [4]. Place the Ball Valve so that its

handle is in a convenient orientation for use when installed.

Tighten the nuts on the threaded rods to 90Nm.

59

Screw four Pin Screws [2] into the top of the Ball Valve.

Place the Gasket [3] on top of the Ball Valve

Check that the Sensor Head will face forwards when the

Top Flange is fitted to the Ball Valve; if necessary, loosen the

Top Nut and locking screws to allow the Installation Pipe to

be rotated.

Place the Top Flange, with the Sensor Head Assembly inside

it, over the Pin Screws on the top of the Ball Valve, and fix it

in place using four M16 washers [6], four M16 Spring

Washers [5] and four M16 nuts [4]. Take care not to

damage the sensor’s active surface when lowering the

assembly onto the Ball Valve.

Tighten the nuts on the threaded rods to 95Nm.

Loosen the Top Nut and locking screws to free the Sensor

Head Assembly, but take care that the Sensor Head

assembly does not fall.

Carefully lower the Sensor Head using the Installation Pipe

until it stops. Check that it is flush with the hull, and facing

forwards.

Lift the Installation Pipe again until it stops, so that the Sensor

Head is inside the Top Flange.

Tighten the Top Nut and locking screws to hold the Sensor

Head Assembly in place.

Turn the handle on the Ball Valve to close it. This will protect

the Sensor Head when the vessel is launched.

5.3.7 Checks after assembly

Visually check the assembly for water-tightness.

Check that there are no particles of dirt, metal swarf, etc.,

inside the assembly. These could affect water-tightness.

5.3.8 When the vessel is afloat

Prepare the system for operation when the vessel is afloat after

dry-docking as follows.

Turn the handle on the Ball Valve to open it.

Loosen the Top Nut and locking screws to free the Sensor

Head Assembly. This will also allow any air inside the

assembly to be expelled; look out for water leaking

between the Installation Pipe and Top Nut when the air has

all been driven out; re-tighten the Top Nut a little if

necessary.

Carefully lower the Sensor Head using the Installation Pipe

until it stops. Take care not to rotate the Installation Pipe, so

that the Sensor Head continues to face forwards.

60

Tighten the Top Nut (to 75Nm) and locking screws to hold

the Sensor Head Assembly in place. Use 1.5Nm torque, and

fix with Loctite 222.

5.3.9 Removing the sensor while the vessel is afloat

The sensor can be removed from the valve while the vessel is

afloat, as follows.

Caution: loosen nuts gradually, as water pressure may exert large

forces on the sensor assembly. Proceed carefully and look out for

water leaks.

Loosen the Top Nut and locking screws to free the Sensor

Head Assembly.

Lift the Installation Pipe until it stops, so that the Sensor Head

is inside the Top Flange.

Re-tighten the Top Nut and locking screws.

Turn the handle on the Ball Valve to close it.

Remove the M16 nuts and washers that are holding the Top

Flange to Ball Valve.

Carefully lift the Top Flange, with the Sensor Head inside it,

from the top of the Ball Valve.

The Sensor Head can now be accessed by loosening the

Top Nut and locking screws and pushing on the Installation

Pipe.

5.3.10 Re-fitting the sensor while the vessel is afloat

Re-fitting the sensor is very similar to the initial installation (see 5.3.4

above).

Assemble the Sensor Head to the Installation Pipe and Top

Flange with the Sensor Head fully raised, as described

above.

Fit the Top Flange to the Ball Valve, and tighten the Top Nut

and locking screws.

Make sure that the assembly is re-fitted so that the Sensor

Head faces forwards; check the mark on the Sensor Head.

Use the valve handle to let water into the valve.

Carefully undo the Top Nut until water starts to seep out,

and then fully lower the Sensor Head.

Re-tighten the Top Nut (75Nm) and locking screws.

5.3.11 Preparing for dry dock

If the vessel needs to be dry-docked again, loosen the Top

Nut and locking screws, and lift the Sensor Head by 50mm

to protect its active surface.

61

5.3.12 Cathodic protection

Minimize corrosion of the sensor head by fitting a sacrificial anode.

Suitable anode types include SAF24 and SAF12 on steel hulls, and

AG4 or AG4 MC on aluminum hulls.

Regularly inspect the anode and replace it when necessary.

62

5.4 Mounting Electrical Components

The electrical components of the system are:

Sensor Power Unit

o This supplies power to the sensor head and

communicates with the Interface Unit.

o It should be mounted in the forepeak, close to the

sensor, where the cable lengths are no more than 30

meters from the sensor (40 meter cables are available

on request) and no more than 600 meters from the

Interface Unit.

Interface Unit

o This connects the system to the HMI Units and any

other external equipment that needs the speed log or

echosounder information.

o It should be mounted in the bridge area, where the

cable lengths are no more than 600 meters from the

Sensor Power Unit and no more than 100m meters

from the HMI Units and connected external

equipment.

HMI Units

o These provide graphical and numerical readouts of

the speed and depth information from the sensors,

and allow the user to set the control parameters of

the system.

o Two units are provided, both of which can control

and monitor both echosounder and speed log, thus

providing redundancy.

o The HMI units should be mounted in the bridge or

overhead console, where the cable lengths are no

more than 100 meters from the Interface Unit.

External equipment

o EMES60 can be connected to external equipment,

not supplied by Northern Solutions, using standard

data communications protocols and data formats.

o The maximum distance from the Interface Unit to the

external equipment is 500 meters.

5.4.1 Mounting the HMI units

The HMI units need to be mounted in a panel. Prepare a

rectangular hole 138.0 mm wide and 192.0 mm high. The exterior

dimensions of the unit are 149 x 202mm.

33mm depth is needed behind the panel, plus at least 20mm to

allow for air cooling and for the NMEA Adaptor Board.

Note that the HMI unit is used in “portrait” mode, with the long side

vertical.

63

NMEA communications is made through an NMEA Adaptor Board,

which converts RS422 signals at the 9-way D-type connector on

the HMI unit into NMEA 0183 signals on a screw terminal.

Figure 3 HMI unit dimensions

64

5.4.2 Mounting Electronic Units

Mount the electronic units with the glands facing downwards, to

minimize the risk of water ingress and ease cable routing.

65

5.5 Electrical Installation

5.5.1 Block Diagram

Figure 4 EMES60 Block Diagram

66

5.5.2 Electronic Unit Layouts

In both the Sensor Power Unit and the Interface Unit, the board

handling the echosounder is on the left, and the board handling

the speed log is on the right.

Echo sounder Power Board

Speed log Power Board

Figure 5 Sensor Power Unit boards

Echo sounder Power Board

Speed log Power Board

Figure 6 Interface Unit boards

5.5.3 Cable Diagram

The cables used in the system, with their names, are shown in the

diagram below.

67

The number of cables leading to external equipment depends on

the number of external systems that are required to be connected

to EMES60. In the diagram, IU-Ext1-* means IU-Ext1-1, IU-Ext1-2, IU-

Ext1-3, etc.

Regulations require that the speed log and echosounder sides of

the system must be independent of each other, so they have

separate power and communications connection cables.

HMI 1 HMI 2

Interface Unit

Sensor Power Unit

Sensor

External equipment

External equipment

IU-HMI1 IU-HMI2

IU-Ext1-* IU-Ext2-*SPU-IU

SPU-Sensor

AC PowerSPU-AC-Power1

DC PowerSPU-DC-Power1

AC PowerSPU-AC-Power2

DC PowerSPU-DC-Power2

AC PowerIU-AC-Power1

DC PowerIU-DC-Power1

AC PowerIU-AC-Power2

DC PowerIU-DC-Power2

5.5.4 Cable Types

The types of cable used are: Name Use Construction Supplied

By Power1 Power from ship’s power to

EMES units

Conductor size: 2.5mm2

Configuration: 2 twisted pairs with

individual screens and outer

shield.

Shield type: Overall braided with

drain wire.

Installer

Comms3 Communication signals, 3

twisted pairs

Conductor size: 22 to 18AWG or

0.33 to 0.78mm2 (typical 0.5mm2)

Configuration: 3 twisted pairs with

individual screens and outer

shield.

Shield type: Overall braided with

drain wire.

Capacitance wire to shield <

150pF/m

Installer

Comms4 Communication signals, 4

twisted pairs

As Comms3, but 4 twisted pairs Installer

EMESSensor Custom EMES sensor cable,

supplied with the system

Custom-made

In EMES60

system kit

5.5.5 Cable List

This table lists the cables that are used to connect up the parts of

an EMES60 system.

68

Name From To Cable Max Length

SPU-

Sensor Sensor Sensor Power Unit

EMESSensor: Custom

EMES sensor cable,

supplied with the

system

30m provided as

standard, 40m

available on

request

SPU-DC-

Power1 Power 24VDC

Sensor Power Unit,

side 1 Power1

SPU-AC-

Power1

Power

110/230VAC

Sensor Power Unit,

side 2 Power1

SPU-DC-

Power2 Power 24VDC

Sensor Power Unit,

side 1 Power1

SPU-AC-

Power2

Power

110/230VAC

Sensor Power Unit,

side 2 Power1

SPU-IU Sensor Power

Unit Interface Unit Comms4 600m

IU-DC-

Power1 Power 24VDC Interface Unit, side 1 Power1

IU-AC-

Power1

Power

110/230VAC Interface Unit, side 2 Power1

IU-Ext1-* Interface Unit,

side 1

External equipment

(as many

connections as

required)

Comms4 45m (NMEA 0183

maximum)

IU-Ext2-* Interface Unit,

side 2

External equipment

(as many

connections as

required)

Comms4 45m (NMEA 0183

maximum)

IU-HMI1 Interface Unit HMI unit 1 Comms3 100m

IU-HMI2 Interface Unit HMI unit 2 Comms3 100m

Avoid running communications cables close to electrically noisy

systems and cables.

5.5.6 Pluggable Terminal Block connectors

All cable terminations are made using pluggable

terminal block connectors.

To terminate a cable, simply strip and twist the ends,

insert into the screw terminal, and tighten the screw.

These connectors are supplied with the EMES60 system.

5.5.7 Connection Notes

The following instructions must be followed when connecting up

the EMES60 electronic unites. Failure to do this may reduce the

integrity and robustness of navigation measurements.

69

The sides (echosounder and speed log) must be isolated

from each other: do not connect any signals, grounds or

power wires together.

NMEA outputs from sensor must only be connected to

correct opto-coupled NMEA inputs.

5.5.8 Connecting to Electronic Unites

The EMES60 electronic unites (Sensor Power Unit and Interface

Unit) are connected to each other, other parts of the EMES60

system, and external equipment using cables that are listed in

5.5.2. These cables are provided by the installer, except for the

sensor cable, which is provided as part of the EMES60 kit.

To connect a cable to an electronic unit:

Cut the cable to length

Cut back the jacket to expose the outer screen

Expose the outer screen for the gland connection

Keep twisted pairs together; don’t un-twist them

Strip the insulation on each core to 7mm

Refer to the wiring schedules in section 5.5.9 for each cable

Check where the cable terminates on the boards inside the

electronic unit, and select a gland in the side of the box

that minimises tail length inside the electronic unit. This

information is shown in the wiring tables below and on a

diagram fixed to the inside of the door of the electronic unit.

Loosen the gland

Feed the cable throughthe gland

Ensure the outer screen of the cable is electrically

terminated on the gland (this important for EMC screening

regulations)

Separate one pluggable terminal block from a circuit

board. Remove the blocks one at a time, to help make sure

that the headers go back in the right place on the board.

Match the numbers on the terminal blocks against block

and pin numbers in wiring tables

locations indicated in the pin numbering tables below.

Insert the pluggable terminal into header on board. Make

sure that the terminal goes back into the right part of the

header.

Ensure that cable core functions match the screen-print on

the board.

Seal any un-used glands.

70

5.5.9 Cable Wiring Schedules

Connect the external cables to the Pluggable Terminal Block

Connectors as follows.

SPU-Sensor

Sensor Power Unit Cable

Core Use

Board Header Terminal

Number

Right-

hand J200

7 orange Log power +

8 black Log power -

9 screen

4 blue Log NMEA out +

5 white Log NMEA out -

6 screen

1 brown Log NMEA in +

2 yellow Log NMEA in -

3 screen

Left-

Hand J200

7 red Echosounder power +

8 black Echosounder power -

9 screen

4 green Echosounder NMEA out

+

5 white Echosounder NMEA out

-

6 screen

1 purple Echosounder NMEA in +

2 yellow Echosounder NMEA in -

3 screen

SPU-DC-Power1

Power

Supply

Sensor Power Unit Cable

Core Use

Board Header Terminal

Number

24V + Left-

hand J101

1 1 24V +

24V - 2 2 24V -

Ground None screen screen

There is no distinction made between AC power “live” and

“neutral”; AC power can be connected either way round.

SPU-AC-Power1

Power

Supply

Sensor Power Unit

Cable Core Use Board Header

Terminal

Number

AC Left-

hand J100

1 1 AC power

Ground 2 yellow/green Ground

AC 3 2 AC power

71

SPU-DC-Power2

Power

Supply

Sensor Power Unit Cable

Core Use

Board Header Terminal

Number

24V + Right-

hand J101

1 1 24V +

24V - 2 2 24V -

Ground None screen screen

SPU-AC-Power2

Power

Supply

Sensor Power Unit

Cable Core Use Board Header

Terminal

Number

AC Right-

hand J100

1 1 AC power

Ground 2 green/yellow Ground

AC 3 2 AC power

SPU-IU

Interface Unit Sensor Power Unit Cable

Core Use

Board Header Terminal

Number Board Header

Terminal

Number

Left-

hand J500

1

Left-

hand J201

1 1 a RCV A

2 2 1 b RCV B

3 3 1 scr RCV SCN

4 4 2 a XMT A

5 5 2 b XMT B

6 6 2 scr XMT SCN

IU-DC-Power1

Power

Supply

Interface Unit Cable

Core Use

Board Header Terminal

Number

24V + Left-

hand J101

1 1 24V +

24V - 2 2 0V

Ground None screen screen

IU-AC-Power1

Power

Supply

Interface Unit

Cable Core Use Board Header

Terminal

Number

AC Left-

hand J100

1 1 AC power

Ground 2 green/yellow Ground

AC 3 2 AC power

IU-DC-Power2

Power

Supply

Interface Unit Cable

Core Use

Board Header Terminal

Number

24V + Right-

hand J101

1 1 24V +

24V - 2 2 0V

Ground None screen screen

72

IU-AC-Power2

Power

Supply

Interface Unit

Cable Core Use Board Header

Terminal

Number

AC Right-

hand J100

1 1 AC power

Ground 2 green/yellow Ground

AC 3 2 AC power

IU-HMI1

HMI1 Interface Unit Cable

Core Use

Connector Terminal

Number Board Header

Terminal

Number

Converter

board

Left-hand J400

1 1 a RCVA

2 1 b RCVB

3 1

screen

RCVSCN

4 2 a XMTA

5 2 b XMTB

6 2

screen

XMTSCN

Power

connector

+ 7 3 a +24V

- 8 3 b -24V

9 3

screen

POWSCN

IU-HMI2

HMI2 Interface Unit Cable

Core Use

Connector Terminal

Number Board Header

Terminal

Number

Converter

board

Right-

hand J400

1 1 a RCVA

2 1 b RCVB

3 1

screen

RCVSCN

4 2 a XMTA

5 2 b XMTB

6 2

screen

XMTSCN

Power

connector

+ 7 3 a +24V

- 8 3 b -24V

9 3

screen

POWSCN

73

IU-NMEA1-1 (echosounder NMEA 1)

External NMEA

connection

echosounder 1

Interface Unit Cable

Core Use

Conn-

ector

Terminal

Number Board Header

Terminal

Number

Left-

hand J501

1 1 a RCVA_1

2 1 b RCVB_1

3 1 screen RCVSCN_1

4 2 a XMTA_1

5 2 b XMTB_1

6 2 screen XMTSCN_1

IU-NMEA1-1 (echosounder NMEA 2)

External NMEA

connection

echosounder 2

Interface Unit Cable

Core Use

Conn-

ector

Terminal

Number Board Header

Terminal

Number

Left-

hand J501

7 1 a RCVA_2

8 1 b RCVB_2

9 1 screen RCVSCN_2

10 2 a XMTA_2

11 2 b XMTB_2

12 2 screen XMTSCN_2

IU-NMEA1-1 (echosounder NMEA 3)

External NMEA

connection

echosounder 3

Interface Unit Cable

Core Use

Conn-

ector

Terminal

Number Board Header

Terminal

Number

Left-

hand J501

13 1 a RCVA_3

14 1 b RCVB_3

15 1 screen RCVSCN_3

16 2 a XMTA_3

17 2 b XMTB_3

18 2 screen XMTSCN_3

74

IU-O1 (echosounder output signals)

External

connection

echosounder

Interface Unit Cable

Core Use

Conn-

ector Use Board Header

Terminal

Number

Relay 1

Relay

normally

open

Left-

hand J800

1 RELNC_1

Relay

normally

closed

2 RELNO_1

Relay

common 3 RECLCOM_1

Relay 2

Relay

normally

open

4 RELNC_2

Relay 2

Relay

normally

closed

5 RELNO_2

Relay 2 Relay

common 6 RECLCOM_2

Opto 1 Opto A 7 OPTOA_1

Opto B 8 OPTOB_1

Opto 2 Opto A 9 OPTOA_2

Opto B 10 OPTOB_2

IU-I1 (echosounder input signals)

External

connection

echosounder

Interface Unit Cable

Core Use

Conn-

ector Use Board Header

Terminal

Number

Pulse

out 1

A

Left-

hand J800

11 DIGINA_1

B 12 DIGINB_1

Pulse

out 2

A 13 DIGINA_2

B 14 DIGINB_2

Pulse

ref volt-

age

0V in 15 REFN

15V in 16 REFP

Ana-

log in

0-10V or

4-20mA 17 ANAOP

0V 18 ANAON

75

IU-O2 (speed log output signals)

External

connection speed

log

Interface Unit Cable

Core Use

Conn-

ector Use Board Header

Terminal

Number

Relay 1

Relay

normally

open

Right-

hand J800

1 RELNC_1

Relay

normally

closed

2 RELNO_1

Relay

common 3 RECLCOM_1

Relay 2

Relay

normally

open

4 RELNC_2

Relay 2

Relay

normally

closed

5 RELNO_2

Relay 2 Relay

common 6 RECLCOM_2

Opto 1 Opto A 7 OPTOA_1

Opto B 8 OPTOB_1

Opto 2 Opto A 9 OPTOA_2

Opto B 10 OPTOB_2

IU-I1 (echosounder input signals)

External

connection speed

log

Interface Unit Cable

Core Use

Conn-

ector Use Board Header

Terminal

Number

Pulse

out 1

A

Right-

hand J800

11 DIGINA_1

B 12 DIGINB_1

Pulse

out 2

A 13 DIGINA_2

B 14 DIGINB_2

Pulse

ref volt-

age

0V in 15 REFN

15V in 16 REFP

Ana-

log in

0-10V or

4-20mA 17 ANAOP

0V 18 ANAON

5.5.10 Power

The EMES60 sensor is powered by the EMES60 Sensor Power Supply.

Each subsystem of the sensor consumes 230 or110VAC or 24VDC

(optional) at 6W maximum. Both can be connected at the same

time.

The AC power supply must be between 103.5V and 242V, 47.5Hz

to 63Hz.

DC power, nominally 24V, must be between 21.5V and 31V.

76

The HMI units require DC power, 24VDC at 12.8W maximum each.

The HMI units are powered from the Interface Unit.

The total consumption of each subsystem is 230/110VAC or 24VDC

at 16 W maximum.

5.5.11 Signal Connections

EMES60 supports the following signal output types:

Relay: maximum external connection 30V, 1A

Opto-coupler: maximum external connection 60V, 0.5A

4-20mA: output level 10V, load resistance must be less than

500Ω

0-10V: load resistance must be more than 500Ω

EMES60 supports the following signal input types:

Pulse inputs: 5 to 24V; high- or low-going pulses can be used

A 15V reference voltage is available in the EMES60 terminals for

use with the pulse inputs if required with voltage-free sources.

See section 3.1.3 for instructions on configuring the inputs and

outputs in the HMI interfaces.

5.6 Set-Up

The system is set up using the HMI Units. See section 3 for details of

the HMI screens.

5.6.1 Set Up the Hardware Interface

The Hardware Interface screens of the HMI (see 0) allow you to set

up:

The opto-isolated output channels

The pulse input channels

The analog output channels

The relay switches

The printer

5.7 Calibration

5.7.1 Calibrating the HMI touch-screen

The pointer on the HMI touch screen should appear exactly where

it is touched. If not, run the touch-screen calibration procedure.

77

The HMI unit offers two calibration processes, which are available

through the “PenMount Control Panel” application.

Standard Calibration Click this button and arrows appear, pointing

to red squares. Use your finger or stylus to touch the red squares in

sequence. After the fifth red point calibration is complete, to skip,

press ‘ESC’.

Advanced Calibration Advanced Calibration uses 4, 9, 16 or 25

points to effectively calibrate the touch panel linearity. Click this

button and touch the red squares in sequence with a stylus. To

skip, press ‘ESC’.

5.7.2 Water temperature calibration

Touch the temperature display box in the

speed log main operational screen

(section 3.3.2) to open the temperature

calibration control. This opens a control

slider. This function is used when calibrating

and commissioning the system, and allows the temperature shown

to be adjusted to match the temperature from another, trusted

temperature measurement. This feature is only used when

calibrating the system after installation or if the sensor

configuration parameters are lost. Do not touch this setting in

normal use.

To use this feature, read the current water temperature from, for

example, a thermometer lowered into the water, or the cooling

water inlet temperature sensor. Touch the slider bar, and move left

and right to set the value.

This feature can only be used in Administrator Mode (3.1.13).

5.7.3 Speed log Calibration

The electromagnetic speed log can be affected by magnetic

materials near to the sensor. It is therefore necessary to calibrate

the sensor after it has been installed. This is done by running the

vessel back and forth over the same line on the seabed several

times, and entering the data from these calibration “trips” into a

calibration table. EMES60 uses the data in the calibration table to

correct the speeds measured by the speed log.

See section 3.3.11 for instructions on using the speed log

calibration screen.

Speed log calibration is typically done during vessel sea trials.

A typical calibration sequence is as follows.

78

1. Choose a sea area to run the calibration trips. This needs to

be in open water, where the vessel can run between two

defined points, one nautical mile apart, at a range of

speeds up to 75% of the vessel’s maximum speed. The

effects of wind and tidal currents should be minimized.

2. On the Speed log HMI, open the Speed log Calibration

Screen. See section 3.3.11.

3. Select two points (which we will call point A and point B for

the purpose of this description). The points should be exactly

1 nautical mile apart (although other separations can be

selected if required: touch the distance indicator at the top

of the calibration screen to

enter a new trip distance).

Most users enter these points on the ship’s GPS plotter,

although it is perfectly possible to set up points using transits

by aligning landmarks from a paper chart, and measuring

the distance from the chart.

4. Line up the vessel on a straight course from point A

to point B, travelling at approximately 25% of the

ship’s maximum speed. When point A is reached,

press the trip start button

5. The progress along the first leg of the trip is shown as a

progress bar above the distance indicator. This progress is

derived by integrating the speed log speed, so it might not

be exactly correct yet.

6. When the GPS plotter (or selected external navigation tool)

indicates that point B, the end of the calibration trip,

has been reached, touch the trip stop button.

7. The trip start button will now be flashing, waiting for

the return leg of the trip. Turn the ship around, head back

down the same calibration line at the same speed. Press the

trip start button at point B, and the trip stop button when

point A is reached.

8. The software now gives the prompt message: “Set results in

calibration table?”

9. If you are confident that the results are good, select Ok,

then use the drop-down list to select a column number in

the Calibration table. The Calibration table is shown at the

bottom of the Calibration screen. You can either write to an

empty column, or over-write the data that is already in a

column.

10. Alternatively, you can postpone the entry of the calibration

trip data by pressing Cancel, and then check the trip data

before using it. This method is recommended at least for the

first time that the speed log calibration is done. Look at the

data from the latest trip, which will be shown highlighted in

79

the Calibration trips table. Look at the following values, and

check that they are within the limits of what you would

expect:

a. Trip time and Trip date, which should match the time

that the trip was run

b. Ref. Leg1 shows the speed of the first leg of the trip

(from A to B) calculated from the distance that was

entered in step 3 above and the time taken to run the

leg.

c. Log Leg1 shows the speed of the first leg of the trip as

measured by the speed log.

d. Ref. Leg2 and Log Leg2 show the same information for

the second leg of the calibration trip.

e. Ref. Aver and Log Aver show the reference and

speed log speeds, averaged between the two legs of

the trip

f. Dist Leg1, Dist Leg2, and Dist Aver show the distances

for the two legs, and the average, as computed from

the speed log speed.

g. Drift shows the angle between the forward and

sideways velocity, again for the two legs and the

average between them.

11. If these values all seem to be acceptable,

touch the column to select it, and touch the

Calibration Trip Use button.

12. You will be given the prompt message: “Set results in

calibration table?”, just as in step 8 above. As described in

step 9 above, you can put the values into a selected

column of the Calibration table.

13. Check that the values in the calibration table match what

you expect for the calibration trip:

a. Ref. shows the reference speed for the trip, computed

from time and distance

b. Log shows the speed from the trip as measured by the

speed log before calibration

c. Drift shows the angle between forward and sideways

speed components for the trip.

14. Repeat the process, from steps 4 to 13, A to B and back

again, this time at 50% of the ship’s maximum speed, and

again for 75% of the maximum speed. Enter all of the values

into the Calibration table. The table has five columns,

allowing you to run two more lines at different speeds if you

wish.

The Calibration table shows un-calibrated forward and sideways

speeds on the left of “Calibration table” and the calibrated results

80

on the right, so that you can see what the effect of the table is at

any time during the process.

If one of the calibration trips doesn’t work well, select it

by touching it, and press the Delete button to remove it

from the table.

If one of the columns in the Calibration table is bad, you can:

Over-write it from one of the columns in the Calibration trips

table (see step 9 above), or

Stop is being used in calibration calculations by selecting

any one (or all) of the values in the column by touching it,

and using the “backspace” key to delete the value.

Columns with any one of the three values blank are not

used; or

Touch a value in a table to edit it (see below to see how this

might be used).

When the calibration process is complete, if there is a printer fitted

to the system, use the Print button to make a print-

out of the calibration data as a record of the

process.

It is strongly recommended that the full calibration process is

followed as described above. However, alternative methods are

possible:

One-way trips: if it is certain that there is no effect on water

speed from wind or tide, you can use the results from one

direction only:

o At the end of the first run (A to B) touch the

end run button as usual, and then use the

Calibration Trip Use button to use the data

from the run so far.

o The Start button will now be flashing, waiting for you to

do the return (B to A) trip. You can clear this flashing

as follows: touch it, to start a “dummy” trip, then

touch the End button, and select “Cancel” from the

“Set results in calibration table?” prompt.

Use GPS speed data; this is ground speed, so only matches

the true water speed if there is no tidal current. But if this is

the case, then you could create a column in the Calibration

table as follows:

o Touch the Ref. field and use the keypad to enter the

GPS speed that is shown in the top-left of the window

o Touch the Log field and enter the raw value from the

speed log: this is shown to the left of the Calibration

table header.

81

o Enter zero (or a true value if known) into the Drift field.

Blanks in any of the fields cause the column to be

ignored in the calibration calculations.

82

6 Technical Details

6.1 Specifications

Performance

Echosounder Speed log

Accuracy 0.05m or 0.5% of depth, whatever is

greater 0.1kn or 1% of speed, whatever is greater

Resolution digital out 0.01m 0.01knots

Resolution screen

presentation

Depth < 100m : 0.1mDepth >=100m :

1.0m 0.1knots

Range of measured

values 0.7m-500m +/- 40 knots on all axis

Temperature Accuracy Temperature sensor accurate to 1° C

Display Unit (separate unit for each sub-system)

Resolution 800x480, 7” WVGA

Operator interface Touch screen, tap & swipe operation

Communication line RS422, Optional RS232

Day/Night modes Full range of backlight adjustment day/night color themes selection.

Software upgrade

means USB line, USB flash device, Ethernet

Supported languages English, Norwegian, German, French, Spanish, Russian, Chinese

Calendar, clock Real time clock support or GPS time reference.

Environmental IP68, front panel only

Cutout dimensions 137x185mm, depth 36mm

Operating T° -15 - +55° C (storage -20 -+60°C )

Weight 0.7kg

Echosounder Speed log

Range user adjustable: 0-10m to 0-500m,

auto -5 /+40 knots, +/-5 knots

Presentation units meters, feet, fathoms knots, mi/h

Alarms Shallow and deep alarms adjustable

limits Low and high speed alarms

Interface Unit (separate PCB for each sub-system)

External communication

line

NMEA0183 rev4, /IEC 61162-1/ IEC 61162-2 2inputs/3 outputs,

IEC 61162-4 ( Light Weight Ethernet) 1input/1 output

Analog 1 output, 10Vpp or 4-20mA, fully programmable

Alarm relays 2 Mechanical relays, one dedicated system power failure alarm

General purpose Input 2 digital inputs (for synchronization, slave mode), fully programmable

General purpose Output 2 optocoupler outputs, fully programmable

Software upgrade

means USB line, USB flash device, Ethernet

Environmental IP55

Operating T° -15-+60°

Dimensions, mm 150x300x120

Weight 4kg

Dual Sensor with Cable

Cable length 30m (optional 40m)

Communication link IEC 61162-1/2

Environmental IP68, 6 bar continuous immersion in water

Operating T° -5-+60°

Sensor Dimensions H = 124mm, D = 60.2mm

Weight (with cable) 7kg

83

Hull fitting unit (ball valve)

Hull type Single and double

Body material Stainless steel

Pressure rating 10 bar

Operating T° -5-+60°

Weight 18kg

System Power Requirement

Mains Nominal 115V to 230V:103.5V to 242V, 47.5Hz to 63Hz

DC Nominal 24V: 21.5V to 31V

Power Echosounder: 6W, speed log: 6 W, HMI units: 12.8W maximum each

84

6.2 Circuit board layouts

6.2.1 Power Board Layout

The Interface Unit contains two Power Boards, one for the

echosounder and one for the speed log.

The locations of connectors, LED lights and test points are shown

below. Pin 1 on the connectors is indicated by a mark in the

corner of the connector drawing.

Mains Power connections

Connection to Sensor

Connection to Interface Unit

Test point: Local 5V

Red LED: 24V from AC

Red LED: 24V from DC

Green LED: Local 5V

Red LED: NMEA0183 from Interface

Green LED: NMEA0183 from Sensor

Test point: 24V to Sensor

Test point: NMEA0183 from Interface

Test point: NMEA0183 from Interface

85

6.2.2 Power Board LEDs

LED Color Indicates

LD100 Red 24V from AC

LD101 Red 24V from DC

LD102 Green Local 5V

LD200 Red NMEA0183 from Interface

LD201 Green NMEA0183 from Sensor

6.2.3 Power Board Test Points

Test Point

Function

TP100 Local 5V

TP101 Main 24V Internal Bus

TP200 NMEA0183 from Interface

TP201 NMEA0183 from Sensor

86

6.2.4 I/O Board Layout

The Interface Unit contains two I/O Boards, one for the

echosounder and one for the speed log.

The locations of connectors, LED lights and test points are shown

below. Pin 1 on the connectors is indicated by a mark in the

corner of the connector drawing.

Pin 1

NMEA I/O connections

MISC I/O connections

Display connections

DC Power connections

Mains Power connections

Test point: NMEA0183 from Aux

Input 1

Green LED: NMEA0183 to Aux

Input 1

Red LED: NMEA0183 from Aux Input 1

Green LED: NMEA0183 to Aux

Input 2

Red LED: NMEA0183 from Aux Input 2

Test point: NMEA0183 from Aux

Input 2

Green LED: NMEA0183 to Aux

Input 3

Red LED: NMEA0183 from Aux Input 3

Test point: NMEA0183 from Aux

Input 3

Test point: OptoCoupler Output 1

Test point: OptoCoupler Output 2

Red LED: 24V from AC Red LED: Aux Digital Input 1

Red LED: Aux Digital Input 2

Green LED: Board 3.3V

Green LED: Board 5V

Red LED: 24V from DC

Green LEDs: Special software functions

Test point: OptoCoupler Output 2

Red LED: NMEA0183 to Sensor

Green LEDs: NMEA0183 from Sensor

Test point: NMEA0183 from Display

Red LED: NMEA0183 from Display

Green LED: NMEA0183 to Display

87

6.2.5 I/O Board LEDs

The I/O boards in the Interface Unit contain LED lights, which turn

on to indicate when various signals and power suppliers are

working.

These can be used after installation to check that the power

inputs and communications signals are correctly wired up. They

are also useful for fault-finding.

LED Color Indicates

LD100 Red 24V from AC

LD101 Red 24V from DC

LD102 Green Board 3.3V

LD103 Green Board 5V

LD300 Green Software Function 1

LD301 Green Software Function 2

LD302 Green Software Function 3

LD303 Red Software Function 4

LD400 Red NMEA0183 to Sensor

LD401 Green NMEA0183 from Sensor

LD500 Red NMEA0183 from Display

LD501 Green NMEA0183 to Display

LD502 Red NMEA0183 from Aux Input 1

LD503 Green NMEA0183 to Aux Input 1

LD504 Red NMEA0183 from Aux Input 2

LD505 Green NMEA0183 to Aux Input 2

LD506 Red NMEA0183 from Aux Input 3

LD507 Green NMEA0183 to Aux Input 3

LD800 Red Aux Digital Input 1

LD801 Red Aux Digital Input 2

88

6.2.6 I/O Board Test Points

The following test points on the I/O board can be used to monitor

supply voltages and signals, using a meter or oscilloscope.

Test

Point Function

TP100 Main 24V Internal Bus

TP101 Board 3.3V

TP102 Board 5V

TP400 NMEA0183 from Sensor

TP500 NMEA0183 from Display

TP501 NMEA0183 from Aux Input 1

TP502 NMEA0183 from Aux Input 2

TP503 NMEA0183 from Aux Input 3

TP700 OptoCoupler Output 1

TP701 OptoCoupler Output 2

89

6.3 Wiring Diagrams

6.3.1 EMES Sensor Wiring

6.3.2 Speed Log Sensor Power Unit Wiring

90

6.3.3 Echo Sounder Sensor Power Unit Wiring

6.3.4 Speed Log Interface Unit Wiring

91

6.3.5 Echo Sounder Interface Unit Wiring

92

6.4 System Drawings

6.4.1 Bottom Flange

93

6.5 Data Output and Input Formats

EMES60 outputs and inputs NMEA 0183 format messages to

communicate with external systems. These formats are defined in

standard IEC 61162-1.

6.5.1 NMEA 0183/IEC61162-1 Messages

These messages have a general format that is typified by the

following ASCII string. Each message is called a “sentence”.

$GPGLL,5057.970,N,00146.110,E,142451,A*27

All messages start with a ‘$’ character

Following the $ character are two letters giving a talker identifier

(GP in the example above). EMES60 provides the following talker

identifiers:

SD for the echosounder outputs

VM for the speed log outputs

Next are three characters called a “sentence formatter”, which

define the kind of sentence being used.

The text that follows is specific to each message type, and is

separated by commas ‘,’.

Finally there is a star ‘*’, and a two-character checksum, which is

calculated by exclusive- OR'ing the eight data bits of each

character in the sentence between, but excluding, "$" and "*".

The sentence is terminated with an ASCII carriage return and line

end pair, <CR><LF>, hexadecimal 0D and 0A.

6.5.2 Output Message Summary

Sentence

Formatter

Purpose From See

DPT Water depth relative

to the transducer and

offset of the

measuring transducer.

Echosounder 6.5.4

DBT Depth below

transducer

Echosounder 6.5.9

DBS Depth below surface Echosounder 6.5.10

DBK Depth below keel Echosounder 6.5.11

MTW Water temperature Echosounder 6.5.14

ALR Set alarm state Echosounder

and speed log

6.5.15

ALA Report detailed alarm

conditions

Echosounder

and speed log

6.5.12

94

Sentence

Formatter

Purpose From See

VBW Water-referenced

and ground-

referenced speed

data

Speed log 6.5.5

VLW Dual ground/water

distance

Speed log 6.5.7

VHW Water Speed and

heading

Speed log 6.5.6

HBT Heartbeat supervision Echosounder

and speed log

6.5.13

6.5.3 Input Message Summary

Sentence

Formatter

Purpose To See

ACK Acknowledge alarm Echosounder

and speed log

6.5.16

AKD Acknowledge detail

alarm condition

Echosounder

and speed log

6.5.17

HDT Heading true Echosounder

and speed log

6.5.18

HDG Deviation and

variation

Echosounder

and speed log

6.5.19

THS True heading and

status

Echosounder

and speed log

6.5.20

ROT Rate of turn Echosounder

and speed log

6.5.21

VTG Course over ground

and ground speed

Echosounder

and speed log

6.5.22

GLL Geographic position

latitude/longitude

Echosounder

and speed log

6.5.23

GGA Global positioning

system (GPS) fix data

Echosounder

and speed log

6.5.24

GXP Transit determined

position

Echosounder

and speed log

6.5.25

GLP Loran-C determined

position

Echosounder

and speed log

6.5.26

RMC Recommended

minimum specific

GNSS data

Echosounder

and speed log

6.5.27

RMA Recommended

minimum specific

Loran-C data

Echosounder

and speed log

6.5.28

95

DDC Display dimming

control

Echosounder

and speed log

6.5.29

ZDA Time and date Echosounder

and speed log

6.5.30

6.5.4 DPT – Depth

This gives the water depth relative to the transducer and the offset

of the measuring transducer. Positive offset numbers provide the

distance from the transducer to the waterline. Negative offset

numbers provide the distance from the transducer to the part of

the keel of interest.

$--DPT, x.x, x.x, x.x*hh<CR><LF>

x.x Maximum range scale in use

x.x Offset from transducer, in meters (see Notes 1 and 2)

x.x Water depth relative to the transducer, in meters

6.5.5 VBW – Dual ground/water speed

6.5.6 VHW – Water Speed and heading

96

6.5.7 VLW – Dual ground/water distance

6.5.8 DPT - Depth

6.5.9 DBT – Depth below transducer

6.5.10 DBS – Depth below surface

97

6.5.11 DBK – Depth below keel

98

6.5.12 ALA – Report detailed alarm conditions

This sentence permits the alarm and alarm acknowledges

condition of systems to be reported. Unlike ALR this sentence

supports reporting multiple system and sub-system alarm

conditions.

6.5.13 HBT – Heartbeat supervision sentence

99

6.5.14 MTW-Water temperature

6.5.15 ALR – Set alarm state

6.5.16 ACK – Acknowledge alarm

100

6.5.17 AKD – Acknowledge detail alarm condition

6.5.18 HDT – Heading true

6.5.19 HDG – Deviation and variation

101

6.5.20 THS – True heading and status

6.5.21 ROT – Rate of turn

6.5.22 VTG – Course over ground and ground speed

102

6.5.23 GLL – Geographic position latitude/longitude

6.5.24 GGA – Global positioning system (GPS) fix data

103

6.5.25 GXP – Transit determined position

6.5.26 GLP – Loran-C determined position

6.5.27 RMC – Recommended minimum specific GNSS data

104

105

6.5.28 RMA- Recommended minimum specific Loran-C data

106

6.5.29 DDC –Display dimming control

6.5.30 ZDA – Time and date

107

7 Northern Solutions

7.1 The Company

Northern Solutions AS, based in Norway, is based on a group of

experienced and committed engineers and project managers.

The development team has over 20 years’ experience in

designing and supporting the products for the merchant fleet,

hydrographic market and fisheries. Products developed to date,

including single/dual channel and multi beam echosounders,

acoustic and electromagnetic speed logs, and different kinds of

operator and interfacing units, have an excellent reputation in the

worldwide navigation market.

The main scope of interest of the company is hydroacoustic and

electromagnetic instruments, including sensors, processing units

and man-machine interface for the marine equipment.

The company experience is built not only based on the design “in

front of the drawing board”, but also on many weeks on board

different kind of vessels, ranging from small size fishing boats up to

super tankers and container ships. This allows the designers to listen

to the opinion of a very important group of customers: the end-

users.

The company philosophy is very simple: to supply reliable products

and services at a competitive price, and to provide customers

with slightly more than they expected.

7.2 Contacting Northern Solutions

email [email protected]

web http://www.nor-solutions.com

telephone +47 90 16 72 84

post Northern Solutions AS, Steinalderveien, 2E 1407,

Vinterbro, Norway

108

Northern Solutions

Steinalderveien 2E

1407 Vinterbro

Norway

Org: 912 403 653

[email protected]

+47 90 16 72 84