December 9, 2008 Sustainability Seminar Energy Plus The successor to DOE 2 Richard D. Hermans, PE HFDP Director of Applications McQuay International

Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Energy Plus

The successor to DOE 2

Richard D. Hermans, PE HFDP

Director of Applications

McQuay International

Page 2: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Acknowledgements• The following organizations have contributed to the development of

this workshop:• U.S. Department of Energy – D.B. Crawley, Program Manager• GARD Analytics – M.J. Witte, T.L. Cornell, R.H. Henninger• University of Illinois at Urbana-Champaign – R.J. Liesen, C.O.

Pedersen, R.K. Strand• U.S. Army Corps of Engineers, Construction Engineering Research

Laboratories – L.K. Lawrie• Lawrence Berkeley National Laboratory – W.F. Buhl, F.C.

Winkelmann• Current funding - National Energy Technology Laboratory (NETL)

under award number DE-FC26-06NT42768 by subcontract through the University of Central Florida/Florida Solar Energy Center

• Prior funding – National Renewable Energy Laboratory (NREL) and Lawrence Berkeley National Laboratory (LBNL)

Page 3: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

EnergyPlus Team• U.S. Department of Energy, DC• Lawrence Berkeley National Laboratory, CA• National Renewable Energy Laboratory, CO• Oak Ridge National Laboratory, TN• Florida Solar Energy Center, FL• GARD Analytics, IL• DHL Consulting, CO• University of Illinois at Urbana-Champaign, IL• COP Associates, MN• Oklahoma State University, OK

Page 4: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

News Media Contact: FOR IMMEDIATE RELEASE

April 12, 2001

(WASHINGTON) Secretary of Energy Spenser Abraham today released a next generation building energy simulation computer program …..

Page 5: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Why Change?• BLAST & DOE2 in

obsolete FORTRAN• “spaghetti” code• Structure precluded

maintenance and additions

• Neither could correctly handle feedback from the HVAC system to the zone conditions

Page 6: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Why Change?

• All three major components: building, system, and plant are solved simultaneously

• In BLAST and DOE2, these are solved sequentially with no feedback between them

Page 7: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Shortcomings

• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface

• EnergyPlus is not fast• EnergyPlus does no design for you• In order to use it effectively, you must be

very well versed in both computer simulation and HVAC design

Page 8: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Strengths

• E+ is extremely flexible• E+ is very precise and the simulations are

close approximations of real world spaces and equipment

• E+ is constantly being updated and improved

• E+ is customizable• Based on best features of BLAST and

DOE-2.1E plus new capabilities

Page 9: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

E+ Highlights

• Windows 2000/XP/Vista, Linux, Mac• Realistic system controls• Moisture adsorption simulation in building

elements• Interzone air flow simulation• Low temp radiant heating/cooling

simulation• Interior surface convection simulation

Page 10: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

E+ Highlights

• Thermal comfort modeling options• Evaporative cooler models• Steam absorption chiller• Air flow sizing based on zone

requirements• Accurate sky illumination model for

daylighting calculations

Page 11: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

E+ Highlights

• Ability to read multiple interval per hour weather data files

• Plenum simulation• Enhanced calculation of return air heat

gain from lights• Flat plate exhaust air heat recovery• Lots of example input files• User-customizable reports

Page 12: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Page 13: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Page 14: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Feedback Simulation

System energy Required is calculated based on

Zone demand at current zone temperature.

The zone demand ispassed to the system and plant

The actual system and plant capacity iscalculated at the current conditions

The resulting newzone temperature

Is calculated.

Page 15: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Realism in Simulation• Simultaneous simulation of loads, systems and

plant• Air and water loops solved iteratively each time

step• Provides tighter coupling between the air and

water-side of the system and plant• Allows capacity limits to be modeled more

realistically• Loads “not met” result in zone temperature and

humidity changes

Page 16: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Version 3.0 released 11/08

• Refrigerant properties added for R404a, R410a and R507c

• New library of compressor performance curves and condensing boiler curves

• Title 24 stuff (if you’re into that…)• Thermal chimney model added• Single speed CT with bypass added• Radiant-convective baseboard added

Page 17: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Version 3.0 released 11/08

• Underground pipe object added• Dry fluid cooler object added• Both mixed and stratified thermal storage

tanks now available• Energy cost calculations now include

option for real time pricing• Additional economic reporting of energy

and demand for each charge

Page 18: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Version 3.0 released 11/08

• This is the seventeenth version• They come out about twice each year

around April and November

Page 19: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

• EISA included work for EUI• DOE used NREL, PNNL to develop

benchmark building• .idf files released in November• SSPC 90.1 has been assisting DOE• Fifteen building types are in the

benchmark• Sixteen weather zones are in the

benchmark

Page 20: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

•Fast Food•Hospital•Large Hotel•Large Office•Medium Office•Outpatient Health Care•Primary School•Restaurant•Secondary School•Small Hotel•Small Office•Stand-Alone Retail•Strip Mall•Supermarket•Warehouse

•Miami•Houston•Phoenix•Atlanta•Los Angeles•Las Vegas•San Francisco•Baltimore•Albuquerque•Seattle•Chicago•Boulder•Minneapolis•Helena•Duluth•Fairbanks

Page 21: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Benchmark EUIChicago kbtu/sqft

0.00

200.00

400.00

600.00

800.00

1000.00

Fast F

ood

Hospital

L Hotel

L Offic

eM O

ffice

Outpatien

tPri S

choo

lResta

urant

2ndys

choo

lSml H

otelSml O

ffice

RetailStrip

MallSup

ermark

etWareh

ouse

Page 22: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Primary School

• E+ produces a standard 3D dwffile

• Some software can produce .idffiles e.g. Google sketch

Page 23: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Air Loop Simulation

Mixed Air

Cooling Coil

Heating Coil

Fan VAV Box

Reheat Coil

Zone

Page 24: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Heating Water Loop

Pump Boiler

Reheat Coil

Page 25: Energy Plus - MN ASHRAE...• EnergyPlus is a stand-alone simulation program without a ‘user-friendly’ graphical interface • EnergyPlus is not fast • EnergyPlus does no design

December 9, 2008 Sustainability Seminar

Take away points

• EnergyPlus is the simulation engine of the future

• EnergyPlus is the most accurate simulation available

• Standard benchmarks are now available