ESSER Honeywell Cat2011 008-030 Iq8control Centrale

Embed Size (px)

Citation preview

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    1/23

    The IQ8Control C as an efficient fire alarm control panel for the property supervision ofsmall to mid-sized objects facilitates simultaneous detection, control and alarm signaling

    both on the analogous ring as well as on the spur.Within the multifunctional IQ8Control C panel, the operation type (powered-loop or non-powered-loop) can be selected via a jumper located on the control panel power supply unit.

    Depending on which loop operation type has been selected, the respective loop module/modules are required.

    Control Panels IQ8Control

    IQ8Control C/Intelligent Addressable

    VdS, CNBOP, BOSECApproval:

    Management SystemWINMAG

    Repeater

    Fibre optic converter

    esserbus transponder

    IQ8Control C

    IQ8Control C

    essernetLoop length max. 1 km(with repeater max. 3 km) esserbus

    Loop length max. 3.5 km-PLus

    external equipment

    12V DC

    Connection example

    Technical Data

    Rated voltage 230 V ACRated frequency 50 ... 60 HzRated current 0.35 A (standard); 0,7 A (powered loop)Quiescent current approx. 215 mA (basic configuration without operating

    unit)approx. 230 mA (basic configuration with operatingunit)

    Current consumption for ext. devices 2 ABattery capacity 2 x 12 Ah, 2 x 24 Ah in extension housingAmbient temperature -5 C ... 45 CStorage temperature -5 C ... 50 CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 6.5 kgDimensions W: 450 mm H: 320 mm D: 185 mmCE certificate 0786-CPD-20827

    Features

    Max. two micromodules

    Max. two esserbus analog loop modules

    Short circuit and open circuit resistant loop opera-tion

    Loop installation with I-Y(ST)Y 0.8 mm cable for amaximum length of 3.5 km

    Up to 127 esserbus devices (fire detectorsrespectively manual call points)/detector zonesper loop

    Up to 32 esserbus transponders per loop/operation of wireless components (see chapter10)

    Operation types TM and PM as per DIN VDE 0833- 2 to avoid unwanted alarms being triggered

    Fire brigade operating panel and alarm transmis-sion unit interface on the peripheral module

    Three common relays, freely programmable,

    monitored, floating for up to 24 V DC/1A (on theperipheral module)

    TTY or RS 485, RS 232 interface

    Integration in the short circuit and open circuitresistant essernet network with up to 31 firedetection panels depends on transmission rate

    Connection to graphical supervisor WINMAG viaserial essernet interface (SEI)

    Operating panel with alphanumerical display

    2 x 20 backlit LCD display

    Event memory for up to 10,000 events

    All System 8000 micromodules are compatible

    Printer interface for internal printer

    Two batteries with monitoring circuit

    Monitored input for external power supply unit

    Additional features for powered loop

    Max. 2 analog powered loop modules

    BUS powered, synchronously controlled, acousticalarm signalling devices as per DIN EN 54-3 withalarm tone as per DIN 33404

    Up to 48 powered loop base sounders (series9200) per loop

    Up to 32 powered loop IQ8Alarm per loop

    Up to 48 IQ8Quad with alarm device per loop

    - The IQ8Control fire detection panels are fully compatible with FACP 8000 panels withinessernet applications

    - FACP 8000 micromodules are also compatible with IQ8Control devices

    - Housing form and colour comply with the FACP 8000 generation

    - The IQ8Control panels can only be programmed with the tools 8000 software solution (part no.789861) and the field bus interface (part no. 789862.10) or directly via USB with the RS-232interface (part no. 769828), with the field bus interface or the RS232 interface.

    Combined with 808619 or 808619.10 FSA transponders, the control panel can be used tocontrol automatic door arrester systems in compliance with the German institute forconstruction engineering (DIBt: Deutsches Institut fr Bautechnik).

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    2/23

    IQ8Control C Design and Order Diagram

    1.Choice of thehousing type

    2.Choice of thecontrol panel

    modules(only 1 module at a time)

    3.Choice of themicromodules

    4.

    Choice of theoperating

    module frontlanguage codes available:

    5.Choice of an

    extension housing(optional)

    IQ8ControlC standard housing 808003 IQ8ControlC for 19 cabinet 808139

    All operating fronts, except SZI 192 detector zones are suitable for both housing types

    *Space for only 1 battery **Requires an additional extension housing

    Slot for one micromodule as standard

    7860_ _Operating front

    7864_ _

    Operating front with1/4 VGA display

    7868_ _Operating front withprinter,w/o take-up reel*

    7869_ _Operating front w. 1/4 VGA

    display, printer , w/o take-up reel

    7861_ _Operating front w.SZI f. 64 detectorzones

    7865_ _Operating front w.

    1/4 VGA display &SZI for 64 zones

    7863_ _Operating front forprinter,w. take-up reel**

    786000SZI front for 192detector zones

    788093

    19 rack mounting kit forSZI 192 detector zones

    786100Filler panel front,neutral forIQ8Control C/M

    789300

    Battery extension housing

    789301

    Extension housing for batteries and

    SZI 192 detector zones

    789302

    Extension housing for SZI

    192 detector zones

    Please notice the control panel packages available!

    01 Germany02 England03 Italy04 Portugal05 Poland06 Spain07 Austria08 Netherlands09 Czech Republic10 Russia11 Hungary12 Denmark13 Sweden14 Croatia15 France16 Slovakia18 Romania19 Slovenia20 Turkey21 Greek22 Flemish23 Walloon25 Arabic / English

    772477

    Peripheral module with

    one additional micromodule slot

    772478

    Extension module with

    one additional micromodule slot

    772479

    Peripheral module

    784382.D0Analog loop module

    784385Master box interfacemodule

    804382.D0Analog loop module powered loop

    784842RS 232/TTYserial interface module

    7875304-relay module

    784840.10essernet module 62,5kBd

    784841.10essernet module 500kBd

    7875313-relay module

    7875323-relaycommon fault module

    Control Panels IQ8Control

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    3/23

    qq$N

    qrHU

    808003

    808139

    Fire alarm panel IQ8Control C

    Fire alarm panel IQ8Control C for 19" cabinet

    Basic design.

    As 808003 but 19" version (7 HU) for upright cabinet installation.

    Control Panels

    Control Panels IQ8Control

    Housing with standard rear panel and front frame for operating panel fronts, interface board,power supply module, system software.

    FACP 808003 IQ8Control C, including 19" installation frame and flat cable for 19" installation750707.

    The operating front must be ordered separately and is not included in the price.

    The operating front must be ordered separately and is not included in the price.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    4/23

    o~!]

    o~"`

    789300

    789301

    Battery extension housing

    Extension housing for batteries and SZI 192 detector zones

    Extension housing for additional batteries.

    Accessories FACP IQ8Control C

    Control Panels IQ8Control

    Housing complete with battery rear panel, connecting cable for battery, mounting positions for 2x 12V/24Ah batteries. Neutral front and material for attaching to the existing panel housing,battery connecting cables, 800 mm.

    Housing complete with battery rear panel, connecting cable for batteries, mounting positions for2 x 12V/24Ah batteries, single zone indicator front for 192 detector zones and material forattaching to the existing panel housing.

    1. 2. 3.

    Assembling the housing parts IQ8Control

    Take off the4 standard covers.

    Insert the2 connecting elements.

    Put the 2 housingson top of each otherand push them together.

    Connection between the central housing and the extension housing

    Technical Data

    Ambient temperature -5 C ... 45 CStorage temperature -10 C ... 50 CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Weight approx. 5 kg (without battery)Dimensions W: 450 mm H: 320 mm D: 185 mm

    Technical Data

    Quiescent current approx. 5 mACurrent consumption 1.5 mA when LED activatedAmbient temperature -5 C ... 45 CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538

    Weight approx. 5.5 kg (without battery)Dimensions W: 450 mm H: 320 mm D: 185 mm

    Batteries are not included and must be ordered separately.

    This housing cannot be used if an operating module front with single zone indicator unit for 64zones is already fitted. Batteries are not included and must be ordered separately.

    A single zone indicator unit can only be used in connection with an operating module front.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    5/23

    o~#c

    qq5

    789302

    808020

    Extension housing for SZI 192 detector zones

    Package IQ8Control C with two slots for micromodules

    The housing can be used to mount additional modules, e.g. an esserbus transponder.

    Control Panel Packages IQ8Control C

    Control Panels IQ8Control

    Housing complete with standard rear panel, single zone indicator front for 192 detector zonesand material for attaching to the existing panel housing.

    1 x control panel 808003

    1 x extension module 772478

    Technical Data

    Quiescent current approx. 5 mACurrent consumption 1.5 mA when LED activated

    Ambient temperature -5 C ... 45 CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 5 kgDimensions W: 450 mm H: 320 mm D: 185 mm

    This housing cannot be used if an operating module front with single zone indicator unit for 64zones is already fitted. A SZI unit can only be used in combination with an operating modulefront.

    The operating front must be ordered separately.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    6/23

    The IQ8Control M as an efficient fire alarm control panel for the property supervision ofmid-sized to large objects, facilitates simultaneous detection, control and alarm signallingboth on the analogous ring as well as on on the spur.

    The loop operation type of the panel (powered-loop or non-powered-loop) can be selectedvia a jumper located on the power supply card.

    Depending on which loop operation type has been selected, the respective analog module/modules should be used.

    Control Panels IQ8Control

    IQ8Control M/Intelligent Addressable

    VdS, CNBOP, BOSEC

    VdS-system recognition: S 294050

    Approval:

    ManagementsystemWINMAG

    Repeater

    Fibre optic converter

    esserbus transponder

    IQ8Control C

    IQ8Control M

    essernet

    Loop length max. 1 km(with repeater max. 3 km)

    esserbusLoop length max. 3.5 km

    -PLus

    external equipment

    12V DC

    Application example

    Technical Data

    Rated voltage 230 V ACRated frequency 50 ... 60 HzRated current 0.35 A (standard); 0,7 A (powered loop)Output voltage 12 V DCQuiescent current approx. 215 mA (basic configuration without operating

    unit)approx. 230 mA (basic configuration with operatingunit)

    Current consumption for ext. devices 2 ABattery capacity max. 2 x 12 V/24 AhAmbient temperature -5 C ... 45 CStorage temperature -10 C ... 50 CType of protection IP 30Housing ABS, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 11.5 kgDimensions W: 450 mm H: 640 mm D: 185 mmCE certificate 0786-CPD-20827

    Features

    Max. five micromodules, with peripheral module772477

    Max. seven esserbus analog loops, with extensionmodule 772476 Short circuit and open circuit tolerant loop opera-

    tion

    Loop installation with I-Y(ST)Y 0.8 mm cable for amaximum length of 3.5 km

    Up to 127 esserbus devices (fire detectorsrespectively manual call points)/detector zonesper loop

    Up to 32 esserbus transponders per loop/operation of wireless components (see chapter10)

    Operation types TM and PM as per DIN VDE 0833- 2 to avoid unwanted alarms being triggered

    Fire brigade operating panel and transmissioninterface on the peripheral module

    Three common relays, freely programmable,monitored, floating for up to 24 V DC/1A (on theperipheral module)

    TTY or RS485 or RS 232 interface

    Integration in the short circuit and open circuitresistant essernet network with up to 31 firedetection panels depends on transmission rate

    Connection to graphical supervisor WINMAG viaserial essernet interface (SEI)

    Operating panel with alphanumerical display

    2 x 20 backlit LCD display

    Event memory for up to 10,000 events

    All Systems 8000 micromodules are compatible

    Printer interface for internal printer

    Two batteries with monitoring circuit Monitored input for external power supply unit

    Additional features for powered loop

    Max. 6 analog powered loops and expandable upto 124 power loops

    BUS supplied, synchronously controlled, acousticalarm signalling devices as per DIN EN 54 - 3 withalarm tone as per DIN 33404

    Up to 48 powered loop base sounders (series9200) per loop

    Up to 32 powered loop IQ8Alarm per loop

    Up to 48 IQ8Quad with alarm device per loop

    - The IQ8Control fire detection panels are fully compatible with FACP 8000 panels

    - FACP 8000 micromodules are also compatible with IQ8Control devices

    - Housing form and colour comply with the FACP 8000 generation- The IQ8Control generation can only be programmed with the tools 8000 software solution (partno. 789861) and the field bus interface (part no. 789862.10) or directly via USB with the RS-232interface (part no. 769828), with the field bus interface or RS232 interface.

    Combined with the 4 zone/2 relay-transponder 808619 or 808619.10, the control panel can beused to control automatic door arrester systems in compliance with the German institute forbuilding technology (DIBt: Deutsches Institut fr Bautechnik).

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    7/23

    IQ8Control M Design and Order Diagram (Basic Design)

    1.Choice of thehousing type

    2.Choice of thecontrol panel

    modules2 Extension modules

    or

    1 Extension module+

    1 Peripheral module

    3.Choice of themicromodules

    5.Choice of an

    extension housing(optional)

    Wall housing

    808004

    772477

    Peripheral module

    with one additional

    micromodule slot

    772476

    Extension module with

    three additional

    micromodule slots

    772478

    Extension module

    with one additional

    micromodule slot

    772479

    Peripheral module

    7860xx

    Operating front

    7864xx

    Operating frontwith 1/4 VGAdisplay

    7868xxOperating frontwith printer

    7869xx

    Operating front w. 1/4 VGAdisplay, printer , w/o take-up reel

    7861xxOperating front w.SZI f. 64 detectorzones

    7865xx

    Operating front w.1/4 VGA display &SZI for 64 zones

    7863xxOperating front forprinter,w. take-up reel**

    786000SZI front for 192detector zones

    78809319 rack mounting kit forSZI 192 detector zones

    786100Filler panel front,neutral

    789303

    Extension housing f. additional modules

    789304

    Extension housing incl. printer

    with paper take-up reel

    Please notice the control panel packages available!

    IQ8Control M for 19" cabinet

    808219

    All operating fronts, except SZI 192 detector zones are suitable for both housing types

    *Requires an additional extension housing

    Slot for one micromodule as standard

    4.Choice of the

    operatingmodule front

    language codes available:

    01 Germany02 England03 Italy04 Portugal05 Poland06 Spain07 Austria08 Netherlands09 Czech Republic10 Russia11 Hungary12 Denmark13 Sweden14 Croatia15 France16 Slovakia

    17 Switzerland (French)18 Romania19 Slovenia20 Turkey21 Greek22 Flemish23 Walloon25 Arabic / English

    784382.D0Analog loop module

    784385Master box interfacemodule

    804382.D0Analog loop module powered loop

    784842RS 232/TTYserial interface module

    7875304-relay module

    784840.10essernet module 62,5kBd

    784841.10essernet module 500kBd

    7875313-relay module

    7875323-relaycommon fault module

    Control Panels IQ8Control

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    8/23

    qq%Q

    qs4

    qs/s

    qs0v

    808004

    808219

    808214

    808215

    FACP IQ8Control M

    FACP IQ8Control M for 19" cabinet

    Package 1 of FACP IQ8Control M

    Package 2 of FACP IQ8Control M

    Basic design.

    As 808004 but 19" version (7HU) for upright cabinet installation.

    With 4 micromodule slots.

    With 4 micromodule slots and 64 single zone indicator units.

    Control Panels

    Control Panel Packages IQ8Control M

    Control Panels IQ8Control

    Housing with rear panel and front frame for operating panel fronts, interface board, powersupply module and system software.

    FACP IQ8Control M 808004, including 19" mounting frame and flat cable for 19" installation750707.

    1 x control panel 808004

    1 x operating panel front 7860xx

    1 x neutral front 786100

    1 x extension module 772476

    1 x control panel 808004

    1 x operating panel front 7861xx

    1 x neutral front 786100

    1 x extension module 772476

    The operating front must be ordered separately and is not included in the price.

    The operating front must be ordered separately and is not included in the price.

    Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).

    The operating front must be ordered separately and is not included in the price.

    Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).

    The operating front must be ordered separately and is not included in the price.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    9/23

    qs1y

    qs2|

    qs3

    o~%i

    808216

    808217

    808218

    789304

    Package 3 of FACP IQ8Control M

    Package 4 of FACP IQ8Control M

    Package IQ8Control M black box

    Extension housing for Package Part No. 808218 IQ8Control M

    With 4 micromodule slots and integrated printer without paper take-up reel.

    With 4 micromodule slots and 192 single zone indicator units.

    With 4 micromodule slots without operating front.

    Control Panels IQ8Control

    1 x control panel 8080041 x operating panel front 7868xx

    1 x neutral front 786100

    1 x extension module 772476

    1 x control panel 8080041 x operating panel front 7860xx

    1 x single zone indicator unit front 192 (Part No.) 786000

    1 x extension module 772476

    1 x control panel 8080041 x neutral front 786100

    1 x extension module 772476

    1 x essernet micromodule: 62.5 kBd (Part No. 784840.10) or 500 kBd (Part No. 784841.10)option

    1 x operating panel front 7863xx

    1 x printer

    1 x paper take-up reel

    Technical Data

    Ambient temperature -5 C ... 45 CStorage temperature -10 C ... 50 CType of protection IP 30Housing ABS plastic, 10% glass fibre reinforced, V - 0

    Color grey similar to Pantone 538Weight approx. 6 kgDimensions W: 450 mm H: 320 mm D: 185 mm

    Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).

    The operating front must be ordered separately and is not included in the price.

    Space for up to 2 x 12V / 24Ah batteries (Part No. 018006).

    The operating front must be ordered separately and is not included in the price.

    Space for up to 2 x 12V / 24Ah batteries (Part No. 018006). The essernet micromodule must beordered separately.

    The operating front must be ordered separately and is not included in the price. The extensionhousing must always be mounted on top of the double housing of the IQ8Control M (Part No.808218). For expanding the IQ8Control M fire alarm panel by an integrated printer with papertake-up reel, the extension housing (Part No. 789304) must be mounted above the fire alarmpanel.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    10/23

    qq?8

    qq@;

    808030

    808031

    Package IQ8Control M with four slots for micromodules

    Package IQ8Control M with seven slots for micromodules

    Control Panels IQ8Control

    1 x control panel 808004

    1 x extension module 772476

    1 x control panel 808004

    2 x extension modules 772476

    The operating front must be ordered separately.

    The operating front must be ordered separately.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    11/23

    o]"786001 Operating front - Esser, German

    Control Panels IQ8Control

    IQ8Control C/M

    IQ8Control C/M operating fronts

    Technical Data

    Quiescent current approx. 45 mA

    Features

    alphanumerical display

    2 x 20 backlit LCD display

    ESSER - front (786001, 786101, 786301, 786401, 786501, 786801 and 786901) is alsoavailable with the respective country specification - except the special versions. When ordering,please fill in the last two digits with the specific language code.

    Example:

    The German version of the standard operating front C/M would have the part no. 7860-01.

    For the Dutch version, the number would have to be changed to 7860-08.

    Specific language code:

    (Not all variants are available in all languages. Please contact your sales representative fordetails)

    01 German (Germany)

    02 English

    03 Italian

    04 Portuguese

    05 Polish

    06 Spanish

    07 German (Austria)

    08 Dutch

    09 Czech

    10 Russian

    11 Hungarian

    12 Danish

    13 Swedish14 Croat

    15 French (France)

    16 Slovak

    17 French (Switzerland)

    18 Romanian

    20 Turkey

    21 Greece

    22 Flemish (Belgium - Dutch)

    23 Walloon (Belgium - French)

    25 Arabic / English

    52 Chinese

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    12/23

    o^"

    oe".

    o`"$

    oa"&

    oaUX

    786101

    786801

    786301

    786401

    786452

    Operating front w. single zone indication 64 - ESSER, German

    Operating front with printer, w/o take-up reel - ESSER, German

    Operating front for printer w. take-up reel - ESSER, German

    Operating front with 1/4 VGA display - ESSER, German

    Operating front with 1/4 VGA display - ESSER, Chinese

    Two-line additional text can be programmed using the programming software package.

    Control Panels IQ8Control

    The printer kit with paper take-up reel (Part No. 784892) must be ordered separately.

    Technical Data

    Quiescent current approx. 50 mACurrent consumption single zone indication: per activated LED 1.5mA

    Technical Data

    Quiescent current approx. 45 mA

    Technical Data

    Quiescent current approx. 45 mA

    Technical Data

    Quiescent current approx. 170 mAResolution 320 x 240 pixels

    This operating module front can only be used on IQ8Control M and a separate extension housingPart No. 789304 must be ordered separately.

    Remote diagnosis is not possible if a two-line extra text is programmed.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    13/23

    ob"(

    obUZ

    of"0

    ofUb

    o]!

    o^!

    786501

    786552

    786901

    786952

    786000

    786100

    Operating front w. 1/4 VGA display & SZI for 64 zones - ESSER,German

    Operating front 1/4 VGA and SZI for 64 zones - ESSER, Chinese

    Operating front w. 1/4 VGA display, printer - ESSER, German

    Operating module front with 1/4 VGA display + printer - ESSER,

    Chinese

    SZI front for 192 detector zones

    Filler panel front, neutral for IQ8Control C/M

    Two-line additional text can be programmed using the programming software package.

    Two-line additional text can be programmed using the programming software package.

    Control Panels IQ8Control

    Including insertable foils with country-specific versions

    Technical Data

    Quiescent current approx. 170 mA

    Current consumption single zone indication: per activated LED 1.5mAResolution 320 x 240 pixels

    Technical Data

    Quiescent current approx. 170 mACurrent consumption printer: 45mAResolution 320 x 240 pixels

    Technical Data

    Quiescent current approx. 5 mACurrent consumption single zone indication: per actuated LED 1.5mA

    Remote diagnosis is not possible if a two-line extra text is programmed.

    Remote diagnosis is not possible if a two-line extra text is programmed.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    14/23

    oq~%

    o_^o

    o__r

    o_`u

    788093

    786261

    786262

    786263

    19 rack mounting kit for SZI 192 detector zones

    IQ8Control C/M operating unit front with FBOIU-ESSER, German/Switzerland

    IQ8Control C/M operating unit front with FBOIU-ESSER, Italian/Switzerland

    IQ8Control C/M operating front with FBOIU-ESSER, French/Switzerland

    7 HU for upright cabinet mounting.

    With integrated Swiss fire department operating and indicating unit (FBOIU) - Germanlettering

    As 786261, but with Italian lettering

    As 786261, but with French lettering

    Control Panels IQ8Control

    772445 mounting frame

    786000 SZI front for 192 detector zones, including insertable foils with country-specific versions

    Technical Data

    Quiescent current approx. 5 mACurrent consumption 1.5 mA per actuated LED

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    15/23

    n9pX

    n9nR

    n9oU

    n9mO

    qQq'

    772479

    772477

    772478

    772476

    804880

    Peripheral module

    Peripheral module with one additional micromodule slot

    Extension module with one additional micromodule slot

    Extension module with 3 additional micromodule slots

    Kit DCF77 radio time module for IQ8Control & FlexES control

    The peripheral module contains a fire brigade operating panel interface as well as a alarmtransmission unit interface and three freely programmable, optionally monitored or up to

    24V DC floating common relays. The peripheral module can only be used on systemterminal 1 of the control panel interface board.

    As 772479 but with one additional micromodule slot. The peripheral module can only beused on system terminal 1 of the control panel interface board.

    The extension module is plugged onto the interface board of the control panel. The exten-sion module can only be used on system terminal 1 of the control panel interface board.

    The extension module is plugged onto the interface board of the control panel. This exten-sion module can be used on plug connectors 1 and 2 of the basic control panel module.

    Used in conjunction with the Kit DCF77 allows radio reception of the DCF77 time signal(CET and CEST time). The DCF77 time signal is sent from a German central transmissionpoint in Frankfurt/Main and Mainflingen and can be received at a distance of up to approx.2.000 km.

    By connecting the Kit DCF77 to the fire alarm system IQ8Control or FlexES control, thesystem time will be automatically set to this time signal. This applies to stand-alone firealarm control panel.

    Accessories for IQ8Control C/M

    Control Panels IQ8Control

    Control Panel Modules for IQ8Control C/M

    Technical Data

    Quiescent current approx. 15 mA

    Technical Data

    Quiescent current approx. 15 mA (without micromodule)

    Technical Data

    Quiescent current approx. 5 mA (without micromodule)

    Technical Data

    Quiescent current approx. 10 mA (without micromodule)

    Only one 772477/78/79 module can be plugged onto the interface board.

    Only one 772477/78/79 module can be plugged onto the basic module.

    Only one 772477/78/79 module can be plugged onto the interface board.

    The 772476 extension module can only be used in the IQ8Control C/M fire alarm panel.

    Each fire alarm control panel (FACP) or essernet network must only be connected to a singleDCF77 time master.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    16/23

    oQI

    j_D

    o~$f

    784892

    736235

    789303

    Printer kit with paper take-up reel for IQ8Control C/M

    Printer paper for printer 736233/736234

    Extension housing

    40 characters, printer with fixed print head.

    Printer paper for part no. 736233 printer without paper take-up reel and for part no.736234 printer with take-up reel.

    The standard extension housing can be used to mount additional modules, e.g. esserbustransponders.

    Control Panels IQ8Control

    Mounting frame complete with Part No. 736234 plain text thermal printer including winder andend-of-paper recognition.

    Housing complete with standard rear panel, neutral front and material for attaching to theexisting control panel housing.

    Accessories

    736235 Printer paper for printer 736233 / 736234

    1. 2. 3.

    Assembling the housing parts IQ8Control

    Take off the4 standard covers.

    Insert the2 connecting elements.

    Put the 2 housingson top of each otherand push them together.

    Connection between the central housing and the extension housing

    Technical Data

    Dimensions L: 2500 mm W: 58 mm

    Technical Data

    Ambient temperature -5 C ... 45 CStorage temperature -10 C ... 50 CType of protection IP 30Housing ABS plastic, 10% glass fibre reinforced, V - 0Color grey similar to Pantone 538Weight approx. 5 kgDimensions W: 450 mm H: 320 mm D: 185 mm

    Features

    For the installation of up to 10 transponders andFO converters with installation kit 788650.

    When the printer is installed in the FACP IQ8Control C, the battery case, including toroidaltransformer, must be replaced by the mounting rack. The batteries and the toroidal transformermust be installed in an additional extension housing, either 789300 or 789301.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    17/23

    n9NY

    o~+

    772445

    789310

    Mounting frame 19" IQ8Control C/M

    Intermediate distribution frame for IQ8Control C

    The mounting box assembly (part no. 789310) is a first fix component for the installationof the 8000 C/M or IQ8Control C/M fire alarm control panel and is specially designed toallow termination of fire cables.

    Control Panels IQ8Control

    Mounting frame with 6 HU for mounting of operating front and printer.

    5DLOZLWKERUHKROHVIRUFDEOHFRQQHFWLRQDQGHDUWKFRQQHFWLRQSRLQW

    &RYHU&DEOHHQWU\

    3(FRQQHFWLRQIRUEDVLVPRGXOH

    [)L[LQJVFUHZ

    IRUKRXVLQJFRYHU[:DOODGMXVWHOHPHQWV

    Mounting example

    Technical Data

    Ambient temperature -5 C ... 45 CStorage temperature -10 C ... 50 CType of protection IP 31Color similar Pantone 538 light-greyWeight approx. 1.1 kgDimensions W: 450 mm H: 320 mm D: 35 mm

    Features

    Allows termination of fire cables

    Ten cable entry points

    Wall adjust elements for panel installation onuneven surface

    Simple installation

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    18/23

    oLs/E1n

    qLs/E1p

    oLv*

    oQK

    ol?,

    ol@/

    olA2

    784382.D0

    804382.D0

    784385

    784842

    787530

    787531

    787532

    Analog loop module

    Analog loop module powered loop

    Master box interface module

    RS 232/TTY serial interface module

    4-relay module

    3-relay module

    3-relay common fault module

    Single loop circuit module for up to 127 Series 9200/IQ8Quad intelligent fire detectors or

    bus devices, divisible into 127 zones.

    Single loop circuit module for up to 127 bus devices. Series 9200/IQ8Quad intelligent firedetectors and esserbus transponders (part no. 80xxxx) or addressable sounders andpowered loop base sounders.

    Single master box interface module for activating and processing acknowledgementsignals from master boxes; programmable as constant or pulsed master box activation.

    Serial interface module with optional RS 232 or TTY typ, for operating external devicessuch as external printers, printers, modems for remote diagnosis.

    4-relay module with freely programmable output functions, each of which can operate asan NC or NO contact (not monitored) for potential-free activation.

    3-relay module with output functions which can be programmed either as NC or NOcontacts, 3 x latching "monitored" relay outputs.

    3-relay module with pre-set functions such as common fault, 2 x freely programmablemonitored relay outputs.

    Control Panels IQ8Control

    Micromodules for IQ8Control C/M

    Technical Data

    Quiescent current approx. 25 mA

    Technical Data

    Quiescent current approx. 15 mA

    Technical Data

    Quiescent current approx. 35 mA (RS 232)approx. 55 mA (TTY)

    Technical Data

    Quiescent current approx. 10 mAContact load relay max. 30 V DC / 1 A

    Technical Data

    Quiescent current approx. 5 mAContact load relay max. 30 V DC / 1 A

    Technical Data

    Quiescent current approx. 15 mAContact load relay max. 30 V DC / 1 A

    Powered loop compatible only with IQ8Control.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    19/23

    oQK/G1s

    Accessories for System 8000 and IQ8

    784842.F0 Module dinterface srie RS 232/TTY

    Control Panels IQ8Control

    Technical Data

    Quiescent current approx. 35 mA (RS 232), approx. 55 mA (TTY)

    kA-j743212 Spare key 1D009 for FACPFor upright cabinets 769163 and 769164.

    Two keys

    kANf743245 Lever lock - type 17 for key no. 801

    Two keys and one cylinder lock.

    m/*769914 Spare key 801 for FACPFor fire alarm panels 2001, IQ8Control C/M, 8000 M/C, 8007, 8008, for operating panel,printer and housing.

    Two keys.

    kAQo743248 Lever lock - type for key no. 901Two keys and one cylinder lock.

    m0-769915 Spare key 901 for FACPFor fire alarm panels 2001, IQ8Control C/M, 8000 C/M, 8008 for operating panel, printerand housing.

    Two keys.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    20/23

    kI?I

    kIF

    744030

    744027

    744028

    744029

    Dummy cover 19", 2 HU

    Dummy cover 19", 3 HU

    Dummy cover 19", 5 HU

    Dummy cover 19", 9 HU

    For covering free installation space in upright cabinets and wall cabinets, 2 HU.

    As 744030, but 3 HU.

    As 744030, but 5 HU.

    As 744030, but 9 HU.

    IQ8Control

    Technical Data

    Material sheet steelColor grey similar to Pantone 538

    Technical Data

    Color grey similar to Pantone 538

    One height unit (HU) covers 44.45 mm.

    Control Panels

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    21/23

    o^P

    o]/21(

    789861

    789860.10

    tools 8000 programming software

    tools 8000 PLus equipment starter kit

    Convenient Windows programming software CD for programming the fire alarm panelsbelonging to Series 8000 C/M, 8008, IQ8Control, Gateway, extended supplementary text in VGA display and ABIGA.

    For programming, the 789862.10 field bus interface is required.

    Complete package for programming of the fire alarm control panels 8007, 8000C/M, 8008,gateway, ABIGA and IQControl via PC or Notebook.

    Maintenance and Test Equipment

    Control Panels IQ8Control

    789861 Programming software for system 8000 and IQ8Control

    789862.10 Field bus and control panel interface PLus

    789863 USB cable

    789864 Serial Connecting Cable

    Accessories

    BME2Z002 Switched-mode power supply with cylindrical plug

    esserbus-PLusLoop length max. 3,5 km

    esserbus-transponder

    Control Panel

    Field bus interface

    USB

    Application example

    This software is also to be used for the LCD panels 785101 and 785103.

    System requirements:

    - FACP 8000 C/M, FACP 8008 or IQ8Control C/M as of software version V2.20

    - PC/Notebook as of Windows 98 SE, but no Windows NT (no USB support)

    - Recommended configuration: 128 MB RAM, 500 MHz CPU

    The field bus interface is used as a programming interface between the FACP and the PC/notebook.

    Furthermore the field bus interface facilitates the direct connection of a r ing bus to theconvenient monitoring of a finished installation and the elimination of possible cabling mistakes.

    www.esser-systems.com

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    22/23

    o_/21.

    o`V

    789862.10

    789863

    Field bus interface PLus

    USB cable A/B for 789862 field bus & panel interface

    Interface for the programming of the fire alarm control panels 8007, 8000C/M, 8008,gateway, ABIGA and IQ8Control or for the direct field-side connection of a single installedanalog loop. With the optional switched-mode power supply BME2Z002, bus-suppliedalarm signaling equipment can be tested independently from the control panel via thedirect connection to the field bus interface 789862.10. (V1.12 or above of programming

    software tools 8000 is required)

    For connecting service PC / laptop with the tools 8000 field bus and panel interface.

    Control Panels IQ8Control

    One interface and two 6-pin plugs.

    Accessories

    BME2Z002 Switched-mode power supply with cylindrical plug

    esserbus-PLusLoop length max. 3,5 km

    esserbus-transponder

    USB

    Power supply for bus suppliedalarm signalling devices

    Field bus interfaceEFI-Plus

    Application example

    Technical Data

    Ambient temperature 5 C ... 45 CStorage temperature 0 C ... 50 CType of protection IP 40Housing plastic, PS (Polystyrene)Color white, similar to RAL 9010 / grey, similar to RAL 7035Weight approx. 300 gDimensions W: 68 mm H: 30 mm D: 135 mm

    Technical Data

    Cable length 1.8 m

    Connecting cables 789863 and 789864 are not included in delivery.

    Windows NT does not support any USB interface. Therefore the use of the programmingsoftware tools 8000 is possible under Windows NT only with the usage of programming

    interface RS 232 (part no. 769828).

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    17

    16

    13

    14

    15

    1

  • 8/22/2019 ESSER Honeywell Cat2011 008-030 Iq8control Centrale

    23/23

    oaY

    oc_

    CNF3[1138

    789864

    789866

    BME2Z002

    Serial connecting cable for 789862

    USB programming cable for panel 8010

    Switched-mode power supply with cylindrical plug

    For connecting the field bus interface to panels 8007, 8000C/M, 8008, Gateway, ABIGA andIQ8Control. With 4-pin special plug for the control panel.

    Connecting lead for programming the extinguishing control panel 8010.

    Control Panels IQ8Control

    Connecting cable, Part-No. 789866

    Extinguishing panel 8010

    Fieldbus interface

    esserbus

    USB

    Technical Data

    Cable length 1.9 m

    Technical Data

    Output voltage 12 V DC