February 2010 - KKS Wire Numbering Convention

Embed Size (px)

DESCRIPTION

KKS wire numbering

Citation preview

  • WPMidas00053 February2010GuidebyMilesNicholson

    KKSWireNumberingConventionAllAutoCADElectricalUsersApopularwirenumberingsysteminthepowergenerationindustryandindeedgenerallyinGermanownedcompaniesistoadopttheKKSwirenumberingconvention.ThisbasicallymeansthatawireconnectingfromtwocomponentswillhavethewirenumberannotatedwiththeFROMpin/TOpindetails.Asadefault,thisisnotafeatureofAutoCADElectricalbutitisavailablefromtheeXtrasribboninstalledfromtheUKEireNordicsLocalisationCDwhichispartofyourmaintenancesubscriptioncontract.TherearesomechangestotheProjectParametersthatneedtobedoneinordertoallowAutoCADElectricaltoadoptawirenumberingconventiononaperphysicalwirebasisratherthanthenormofaperequipotentialbasis.Tochangethesetupoftheproject,rightclickovertheactiveprojectandselectProperties.SelectWireNumberstabUnderthesectionWireNumberOptionsSelect OnaperwirebasisSelectOKCreateanewdrawingcopyingtheprojectsettingsNormallya3devicecircuitwouldbedrawnwithTconnectionsbutthisdoesnotshowhowthe3devicesareactuallywiredandthereforeconnected(typicalstyle).Thereforeinordertogetuniquenumberingoneachphysicalwire,wedrawthewiredirectlyoutoftheconnectingpin(newstyle)

  • TypicalStyle NewStyle

    SelecttheeXtrasribbonSelect KKSWireNumbers

    Ifyouhavethe2010LocalisationCDinstalledwithservicepack1,thecommandwillupdatetheentiredrawing.Withoutservicepack1,itwillupdateonewireatatime.Tip:Ifyouwishthewirenumberstobeinlinewiththewireratherthanat0fortheverticalwirenumbers,thenopentheWD_WNV.dwgintheIEC2libraryandchangethepropertiesoftheattributeWIRENO.