Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
February 2015
ECOsine® active Harmonic Filters
Manual AHF Viewer (V02)
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 3
© All rights reserved, even and especially in cases of proprietary rights applications.
We also retain sole power of disposal, including all rights relating to copying, transmission
and dissemination.
Revision: 02 (February 2015)
The most current edition of these instructions (PDF format) can be obtained from your
contact of the Schaffner sales organization and on the Internet at www.schaffner.com or
www.myecosine.com
Other technical documentation of our products is also available in the download area of our
website.
Valid for firmware version:
From V02.08.17 on
(For firmware version, see parameter P010)
Meaning of firmware version number:
V XX.xx.xx – hardware release, downwards incompatible
V xx.XX.xx – function version
V xx.xx.XX – small compatible changes
Document name:
Manual AHF Viewer Rev02.pdf
Version history
Revision Date Description
2 February 2015 Minor corrections and updates
1 February 2014 Initial version
4 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Table of Contents
1 General Safety Instructions 8
1.1 Intended use 9
1.2 Personnel qualification 10
1.3 Environmental conditions / Exclusion of warranty 11
2 Introduction 13
2.1 Principle of operation 14
2.2 About these instructions 15
2.3 Type plate 16
2.4 Type code 17
3 Welcome 18
3.1 About this manual 19
3.2 Who should read this guide 20
3.3 Get help 21
3.4 Get training 22
3.5 Contact us 23
4 Installation 24
4.1 Download AHF Viewer software 25
4.2 Minimum system requirements 26
4.3 Features of the software 27
4.4 AHF Viewer installation procedure 28
4.5 USB – RS485 adapter installation procedure 30
5 Overview window 32
5.1 General 33
5.2 Connection settings 35
5.2.1 Setting a Modbus TCP connection: 35
5.2.2 Setting the Modbus RTU connection 35
5.3 Connecting to the ECOsine® active 38
6 Parameter 39
6.1 Changing parameters 40
6.2 Reading and writing parameter files 42
6.2.1 Reading a parameter file from the device 42
6.2.2 Sending a parameter file to the device 42
6.3 Structure of the parameter files 44
6.4 Opening a parameter file 45
7 Oscilloscope 46
7.1 Single measurement 47
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 5
7.1.1 Toolbar 47
7.1.2 Measurement settings 49
7.1.3 FFT analysis 51
7.2 Continuous measurement 52
7.2.1 Toolbar 52
7.2.2 Measurement settings 54
8 Language 56
9 Log file 58
10 Firmware update 60
6 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Index of Tables
Table 1: Use of symbols, terms, and designations 15
Table 2: Type code 17
Table 3: Minimum system requirements 26
Table 4: ECOsine® active RS485 interface pinout 30
Table 5: AHF Viewer toolbar icons 34
Table 6: Modbus RTU settings 37
Table 7: Toolbar icons single measurement 49
Table 8: Properties single measurement 50
Table 9: Channel settings single measurement 51
Table 10: Toolbar icons single measurement 54
Table 11: Continuous measurement values 54
Table 12: Channel settings continuous measurement 55
Table 13: Event log functionality 59
Index of Figures Fig. 1: Principle of operation of the ECOsine® active filter 14
Fig. 2: Folder properties 28
Fig. 3: Security tab 29
Fig. 4: Setting permissions 29
Fig. 5: Device manager – USB Serial Port 31
Fig. 6: Overview screen AHF Viewer 33
Fig. 7: Ethernet communication settings 35
Fig. 8: Serial communication settings 36
Fig. 9: Parameter definition file download 38
Fig. 10: Restart system message window 38
Fig. 11: Connection error system message 38
Fig. 12: Device parameters 40
Fig. 13: Editing parameters 40
Fig. 14: Date parameter 41
Fig. 15: Setting date and time 41
Fig. 16: Sending data to the device 42
Fig. 17: Data transfer failed system message 43
Fig. 18: Possible structure of a parameter file 44
Fig. 19: Parameter file list 45
Fig. 20: Single measurement 47
Fig. 21: Single measurement settings 49
Fig. 22: Single channel settings 50
Fig. 23: FFT analysis 51
Fig. 24: Continuous measurement 52
Fig. 25: Continuous measurement settings 54
Fig. 26: Single channel settings 55
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 7
Fig. 27: Event log 59
Fig. 28: Starting firmware update 61
Fig. 29: Choosing firmware file 61
Fig. 30: Safety prompt before firmware download 62
Fig. 31: Download duration system message 62
Fig. 32: Firmware update completed system message 62
Fig. 33: Firmware update unsuccessful 62
Fig. 34: Restarting firmware update 63
8 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
1 General Safety Instructions
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 9
1.1 Intended use The ECOsine® active harmonic filter is used for active compensation of reactive power and
harmonic content and for load balancing.
Please ensure that no compensation systems, which are not detuned, are connected to the
same grid. Otherwise interactions between ECOsine® active and these compensation
systems may occur.
DANGER
Dangerous voltage
Risk of death due to short circuits and electric shock if the
active filter is opened improperly. The discharge time of
the intermediate circuit after disconnecting from the
mains can be more than 5 minutes.
All interventions involving opening the device cover or
removing or installing the connection cable may only be
performed by qualified personnel.
WARNING
High-frequency interferences
In a residential environment, high-frequency interferences
could occur, which necessitate interference suppression.
Note
Please note that there are additional manuals for some product variants. For the latest
versions of these manuals go to www.schaffner.com
It particularly applies to types FN3420-100/120-400-3-GL, please observe the special
EMC-Filter Manual for these types (ECOsine® EMC Filters for Applications with GL)
10 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
1.2 Personnel qualification Installation of the ECOsine® active filter, inspections for proper operation, and certain
troubleshooting measures may only be performed by qualified personnel. All other
measures may be performed by people who have read these instructions.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 11
1.3 Environmental conditions / Exclusion
of warranty This document classifies groups of environmental parameters and their severities to which
ECOsine® active harmonic filters are subjected when mounted for stationary use at weather
protected locations under use conditions, including periods of erection work, down time,
maintenance and repair. The lifetime of electronic equipment is depending on the
environmental conditions they are exposed to. Especially in harsh environments lifetime is
reduced due to the corrosiveness of the atmospheric environment. Generally corrosion in
micro or power electronics depends on several variants such as the package type, materials
involved, assembly processes, moisture, inorganic and organic contaminants, atmospheric
pollutants, temperature, thermal stress and electrical bias. To increase the lifetime
Schaffner provides all ECOsine® active filters with the ability to work within pollution degree
2 (PD2) and does use coated PCB’s according to IEC61721-3-3. Schaffner standard PCB
construction complies with class 3C2. Please carefully read the provided information and
check if your application fulfills the required specifications as Schaffner expressly points
out that the manufacturer's warranty shall lapse with immediate effect if ECOsine®
active harmonic filters are transported, stored, installed or operated outside their
published specifications.
Important
ECOsine® active harmonic filters (AHF) listed below are IP20 or IP54
devices to be installed in an environment in compliance with the
requirements named in this document.
All AHF must be installed in a clean, dry location, e.g. in sufficiently
ventilated or air conditioned electric cabinets or closed electric rooms.
Contaminants such as oils, liquids, corrosive vapors, abrasive debris,
dust and aggressive gases must be kept out of the filter enclosure.
WARNING: Conductive dust may cause damage to ECOsine®
active harmonic filters. Ensure that installation site of ECOsine®
active is free of conductive dust.
Products
FN3420 series, 3-wire filters, models 30…300A
FN3430 series, 4-wire filters, models 30…300A
Overvoltage class
(EN50178)
ECOsine® active are designed according to EN 50178 overvoltage
class III
12 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Storage environmental
specifications
(IEC 60721-3-1, EN50178)
Climate conditions for storage class 1K3:
Temperature range: -25°C to +55°C
Relative humidity: < 95%, no condensation
Atmospheric pressure: 70KPa to 106KPa
Transportation
environmental
specifications
(IEC 60721-3-2, EN50178)
Climate conditions for transport class 2K3:
Temperature range: -25°C to +70°C
Relative humidity: < 95%, no condensation
Atmospheric pressure: 70KPa to 106KPa
Operation environmental
specifications
(IEC 60721-3-3, EN50178)
Climate conditions for operation class 3K3:
Temperature range: 0°C to +40°C
Relative humidity: < 95%, no condensation
Atmospheric pressure: 70KPa to 106KPa
Degree of pollution
(IEC 61010, EN50178)
Pollution conditions for operation class PD2
Corrosive levels
(IEC 60721-3-3)
Corrosive levels for storage, transport and operation Class 3C2(3)
:
Applies to locations with normal levels of contaminants,
experienced in urban areas with industrial activities
Levels:
Environmental parameter Units(1)
Class 3C2(2)
Mean value Max value
Sea salt Salt mist
Sulphur dioxide ppm
cm3/m
3
0.3 0.11
1.0 0.37
Hydrogen sulphide ppm
cm3/m
3
0.1 0.071
0.5 0.36
Chlorine ppm
cm3/m
3
0.1 0.034
0.3 0.1
Hydrogen chloride ppm
cm3/m
3
0.1 0.066
0.5 0.33
Hydrogen fluoride ppm
cm3/m
3
0.01 0.012
0.03 0.036
Ammonia ppm
cm3/m
3
1.0 1.4
3.0 4.2
Ozone ppm
cm3/m
3
0.05 0.025
0.1 0.05
Nitrogen oxides ppm
cm3/m
3
0.5 0.26
1.0 0.52
(1)
The values given in cm3/m3 have been calculated from the values given in mg/m3
and refer to a temperature of 20 °C and a pressure of 101,3 kPa. The table uses rounded values. (2)
Mean values are expected long-term values. Maximum values are limit or peak
values, occurring over a period of time of not more than 30 min per day. (3)
IEC 60721-3-3 is only applied to the coated PCB covered areas and not the entire
device. The unprotected areas, such as connections, terminations and exposed magnetics, may not survive these exposure levels over time.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 13
2 Introduction
14 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
2.1 Principle of operation The ac mains current, which is drawn by a non-linear load, is measured by ECOsine® active
either directly or indirectly via external current transformers. The harmonic content and
reactive power components are detected and processed in a digital control structure. The
active filter continually generates a compensating current that offsets the harmonic content
and reactive current in the load, so the ac mains only has to provide the minimum
fundamental in phase current.
Compensating current
Mains supply
Load
Neutral
Fig. 1: Principle of operation of the ECOsine® active filter
The active filter instantly adapts to all changes in the load and the systems harmonic
content spectrum, in order to be able to optimally respond at any time.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 15
2.2 About these instructions The following symbols, terms and designations are used in these operating and installation
instructions:
Description
NOTICE Notice Follow these instructions to avoid damages to the unit.
CAUTION
Caution Follow these instructions to avoid damages to the unit or injuries of personnel.
WARNING
Warning Follow these instructions to avoid situations which may cause severe or deadly
injuries.
DANGER
Danger Follow these instructions to avoid situations which may cause severe or deadly
injuries.
DANGER
Dangerous voltage Follow these instructions to avoid situations which cause severe or deadly
injuries due to dangerous electrical voltage.
NOTE
Note text
Note Please observe these notes..
➩
1.
2.
Operation steps Complete the operation described (multiple steps are numbered, arrow indicates
a single step).
Table 1: Use of symbols, terms, and designations
16 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Serial number
WO 1234567 + S/N 00001
Date of manufacture (year (yy) + calendar week)
WO number
Part number
2.3 Type plate
Type code
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 17
2.4 Type code The type designations of all ECOsine® active have the following structure:
FN34TT-AAA-VVV-W-CC
Variable Description
TT Type:
20 – 3-wire device
30 – 4-wire device
AAA Rated current
VVV Rated voltage
W Number of compensated conductors
CC Certificates and variants (optional)
Table 2: Type code
18 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
3 Welcome
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 19
3.1 About this manual This manual is meant to provide comprehensive information on AHF Viewer Software - the
tool for communication and parameterization of ECOsine® active harmonic filters. The
issues discussed in this guide cover the necessary theoretical conceptions as well as
practical aspects of working with the AHF Viewer software. The guide will familiarize you
with the way to use and check settings and to employ the software interface for having the
filters performing various tasks.
20 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
3.2 Who should read this guide The primary audience for this book is anyone interested in or responsible for administering
ECOsine® active harmonic filters. To fully understand the guide, you should have some
basic computer system and power quality habits. Attending Schaffner International training
courses might be helpful. Still, no more than basic knowledge of internet browser
technology and power networks is required in order to comprehend the major AHF Viewer
functionality and learn to perform basic operations.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 21
3.3 Get help In-tool help is always at your fingertips! Schaffner incorporates the latest in help features,
including dialogs and context sensitive help on system messages. This user manual is
included in the help section of the AHF Viewer software and thus available at a click.
22 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
3.4 Get training Do you need training? Schaffner can offer a training course comprised of lecture and
hands-on workshops designed to introduce you to the fundamental concepts of power
quality, ECOsine® harmonic filters and AHF Viewer software.
We also offer customized training courses designed to meet your specific needs. Please
contact your local Schaffner representative or the Schaffner business unit power quality
directly to discuss how we can help you achieve success in your power quality efforts.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 23
3.5 Contact us Schaffner – More than just filters. Schaffner is in the unique position of being able to support
the user with problem analyses, engineering advice, testing and measurement support,
custom products, and a worldwide customer service organization. Our goal is to ensure that
you obtain the level of support you actually need. Toward this objective, we invite you to
contact your local Schaffner sales office or Schaffner representative at any time that we
may be of service to you. You can find out more about us and your local contact on our
corporate website or you may contact us via email:
Corporate URL: www.schaffner.com
Corporate E-mail: [email protected]
24 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
4 Installation
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 25
4.1 Download AHF Viewer software
Schaffner’s library of documents and software downloads encompasses all the essential
data and programs you could ever need for working with ECOsine® active harmonic filters.
To download your version of AHF Viewer please go to www.schaffner.com and open the
download section. AHF Viewer is listed under software:
26 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
4.2 Minimum system requirements
Processor 1 Gigahertz (GHz) 32-bit (x86) or 64-bit (x64)
Operating System Windows XP, Windows 7, Windows 8
Memory
256 MB for 32-bit editions of Windows XP
512 MB for 32-bit and 64-bit editions of Windows 7, Windows 8
Hard disk space 120 MB
Screen resolution
800x640
Table 3: Minimum system requirements
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 27
4.3 Features of the software
The AHF Viewer is a software tool for communication with Schaffner ECOsine® active
harmonic filters. It can be used for commissioning and monitoring ECOsine® active filters via
a serial RS485 connection or via Ethernet connection with Modbus TCP.
Features:
Reading and setting of device configurations I
Detecting of the current device status I
Visualization of measurement values, e.g. line voltage and current in an oscillogram I
FFT signal analysis I
Trend recording of RMS values I
Reading measured RMS values I
Reading the event log I
Firmware update I
28 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
4.4 AHF Viewer installation procedure
For installing AHF viewer software please use the downloaded installation file which will
start an installation wizard guiding you through the setup. For Windows 7 and 8 it is
recommended to not use the default programs installation directory but create an dedicated
folder like C:/AHF_Viewer.
If the default directory is used for installation and you encounter any issues with the AHF
Viewer after installation into the standard programs folder of your Windows 7 or Windows 8
you might need to apply the following settings:
Please make sure to remove write protection of the AHF Viewer installation folder.
To do so please follow steps 1-3:
Note
Please note that administrator rights might be needed for applying these settings!
1. Right click the AHF Viewer folder and choose properties
Fig. 2: Folder properties
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 29
2. Switch to the Security tab and click on Advanced
Fig. 3: Security tab
3. Select ‘Users’ and click on ‘Edit’ to open a new window. Then tick the checkboxes as displayed and confirm all settings by clicking OK.
Fig. 4: Setting permissions
30 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
4.5 USB – RS485 adapter installation
procedure Please follow the manufacturer's installation instructions. They can be downloaded from the
manufacturer's website: www.cti-lean.com.
Pin Function
1 Ground
2 +5V
3 NC
4 NC
5 Line B
6 NC
7 NC
8 NC
9 Line A
Table 4: ECOsine® active RS485 interface pinout
Data transmission lines should always be terminated and stubs should be as short as
possible to avoid signal reflections on the line. Proper termination requires the matching of
the terminating resistors, RT, to the characteristic impedance, Z0, of the transmission cable.
Because the RS-485 standard recommends cables with Z0 = 120 , the cable trunk is
commonly terminated with 120-resistors, one at each cable end. The last bus participant
must have a termination resistor in the connector.
The COM port used for the USB–RS485 interface adapter can be identified in the device
manager. The device manager can be accessed via the Control Panel System Device
Manager.
The USB-RS485 interface adapter can be found by selecting 'Ports (COM & LPT)'. Device
name in Windows is 'USB Serial Port‘.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 31
Fig. 5: Device manager – USB Serial Port
32 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
5 Overview window
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 33
5.1 General
The overview window will be displayed when starting the AHF Viewer. Once a connection to
any ECOsine® active is established, this window will display the most important data of the
connected filter, such as status of the device, measurement values, trigger status, or
currently running measurements (in the status bar).
Fig. 6: Overview screen AHF Viewer
The program features a menu bar and a quick selection bar. The icons of the quick
selection bar have the following functions:
34 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Icon Function
Connect to ECOsine® active
Disconnect from ECOsine® active
Open connection settings
Open parameter window
Read measurement values and parameters. (This will only be
necessary if the “Modem” checkbox of the communication settings is
ticked, preventing the values from being updated automatically)
Table 5: AHF Viewer toolbar icons
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 35
5.2 Connection settings The connection settings window can be opened via the menu ‘ConnectionSettings’ or by
clicking in the quick selection bar.
The “Connection to filter” dialog box is used to set the communication parameters. Two
options are provided: Modbus TCP via Ethernet and Modbus RTU via serial RS485
interface.
5.2.1 Setting a Modbus TCP connection:
If a Modbus TCP connection type is used, only the IP address of the ECOsine® active need
to be set. To establish a connection between the PC/laptop and the ECOsine® active, an
Ethernet connection must exist between the two devices. This could be a point to point
Ethernet cable connection or a routed connection. If you encounter any issues with
establishing a point to point connection Schaffner can offer a knowledge base information
“Direct PC – AHF connection via Ethernet cable (TCP/IP)“.
Fig. 7: Ethernet communication settings
5.2.2 Setting the Modbus RTU connection
To establish a serial connection to the ECOsine® active, the PC/laptop must have an RS485
interface or more likely the use of an USB to RS485 converter would be needed.
36 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
CAUTION
Do not use RS232 adapters or interfaces for connecting to the
ECOsine® active as this may damage the device!
If a Modbus RTU connection type is used, settings set in the AHF Viewer have to match the
ones in the ECOsine® active; respectively they have to be identical.
Fig. 8: Serial communication settings
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 37
Parameter Function Default Value
Slave ID Used to distinguish between devices if more than one device
is used on the same RS485 bus
1
Port Definition of the used COM port for the serial interface. Only
interfaces in use are displayed.
To find out the allocated adapter interface, please refer to the
Device Manager as described in chapter 4.5
Baudrate Serial communication baud rate 38400
Data Bits Serial communication number of data bits 8
Stop Bits Serial communication number of stop bits 1
Parity Parity bits setting (yes/no) No
Modem This parameter prevents automatic updating of measurement
values at a one-second interval to minimize the data rate for
remote connections. Within AHF Viewer you have the option
to obtain current values from the filter by the use of the
update button .
No
Table 6: Modbus RTU settings
38 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
5.3 Connecting to the ECOsine® active
Once the communication settings have been made, a connection to the ECOsine® active
can be established. This is possible via ‘ConnectionConnect to device’ or using the
symbol. An established connection will be visible in the status bar at the bottom of the
window. After establishing a connection to a new AHF, the AHF Viewer may need to
download the parameter definition file from that device. This will be displayed in a system
message and will need to be confirmed with ‘OK’. This procedure is only necessary if a new
parameter setting of ECOsine® active has been detected. Having downloaded the new
parameter definition file from the device, the software has to be restarted. This is also
displayed in a system message and has to be confirmed with ‘OK’. The software will shut
down automatically and needs to be restarted manually.
Fig. 9: Parameter definition file download
Fig. 10: Restart system message window
If it is not possible to establish a connection to an ECOsine® active harmonic filter, a
connection error system message will appear. In that case, please re-check connection and
connection settings of AHF Viewer and ECOsine® active filter.
Fig. 11: Connection error system message
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 39
6 Parameter
40 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
6.1 Changing parameters All parameters can be displayed in the Device parameters window which can be opened via
‘ParameterDevice parameters’ or by clicking the symbol.
Fig. 12: Device parameters
The left part of the window displays the different menu levels which are described in detail
in the ECOsine® active user manual (www.schaffner.com -> Downloads). Changing
parameters can be done by double-clicking on a parameter name. This will open a drop-
down list where you can choose the appropriate value. It is also possible to enter individual
values if necessary and permitted. By clicking ‘OK’, the new value is transferred, applied
and saved in the device. By clicking ‘Cancel, the entry will be discarded.
Fig. 13: Editing parameters
To change date and time settings of the ECOsine® active, please go to base settings and
choose date.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 41
Fig. 14: Date parameter
Double clicking will open a window with an additional ‘PC time’ button, allowing you to
transfer the date and time settings of the PC to the input box. By clicking ‘OK’, these values
will be applied to the ECOsine® active.
Fig. 15: Setting date and time
42 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
6.2 Reading and writing parameter files
6.2.1 Reading a parameter file from the device
To read and save a complete parameter file from an ECOsine® active filter please use
‘FileRead parameter set from device’. The parameter set can only be read from the
device if no long-term measurement is running and no single-measurement trigger is active.
Such a parameter file can be saved on your PC/laptop and could be displayed in the AHF
Viewer or uploaded to an ECOsine® active filter. This functionality helps to ensure a proper
backup of parameters of a device as well as it could be used to simplify parameterization of
several ECOsine® active filters of the same setup, e.g. several filters connected in parallel.
6.2.2 Sending a parameter file to the device
To send a (saved) parameter file into a connected ECOsine® active filter, use ‘FileSend
parameter set to device’. The chosen parameter file setup will be displayed in an extra
window for checking the parameters before uploading them into the filter by clicking OK.
Parameters set to read only are not changed while a new file is uploaded.
Fig. 16: Sending data to the device
In case one or several parameters failed to be uploaded a system message window will tell
about it. In such case all displayed parameters need to be checked manually and need to
be adjusted manually.
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 43
Fig. 17: Data transfer failed system message
44 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
6.3 Structure of the parameter files Parameter files (.btp) are handled as text files which can be opened using a text editor. The
structure of these files is as following:
Param <<number>> = <<parameter number>> = <<value>> ; <<comment>>
Please note that the first number is an order number of the file and does not rely to the
parameter number itself.
The parameter file set itself is also divided into three parts:
DeviceData (filter information)
MeasuredValues (measured values at the moment of data withdrawal)
Commissioning (ECOsine® active settings)
Fig. 18: Possible structure of a parameter file
[DeviceData]
Param0=2=30
Param1=3=60
Param2=4=400
Param3=8=00:22:22:00:0A:C6
Param4=9=10523
Param5=10=V02.08.17
Param6=11=41
Param7=12=2;ready for oper. LTC
Param8=13=0
Param9=14=6
Param10=15=1
Param11=16=0,00
Param12=17=0,00
Param13=18=0,00
Param14=20=4;full load
Param15=21=0;
Param16=30=21,571
[MeasuredValues]
Param0=100=50,08
Param1=101=11,28
Param2=102=0,96
Param3=103=820
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 45
6.4 Opening a parameter file To open a parameter file in the AHF Viewer, select ‘FileOpen parameter set’. Having
chosen the parameter file and opened it, a window will appear displaying the parameters.
By clicking ‘OK’, the window is closed without changing any parameter in the connected
ECOsine® active.
Fig. 19: Parameter file list
46 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
7 Oscilloscope
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 47
7.1 Single measurement To open or start a single measurement, select ‘OscilloscopeSingle measurement’. Within
single measurement it is possible to view the internal trace memory of the connected
ECOsine® active. Measurement channels can be individually activated or deactivated. This
allows comparing different measurement values and hiding those that are not needed.
By means of the two cursors C1 and C2, the current values of all measurement channels at
a certain moment can be displayed at the right side of the window. The time frame in
between the two cursor positions is also displayed. Additionally, measurement trigger
settings, time and date are displayed.
Fig. 20: Single measurement
7.1.1 Toolbar
The icons on the toolbar can be used to quickly control single measurements. Functionality
of the icons is as following:
48 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Icon Function
Connect to ECOsine® active
Disconnect from ECOsine® active
Open connection settings
Open parameter window
Open a saved measurement file
Saves the current measurement to the hard disk, with the following
possible formats.
.nbts (single measurement file)
.bmp
.jpg
.xls
Prints the current measurement on the standard printer
Information about AHF Viewer (Version)
Measurement settings
Start measurement
Stop measurement
Scroll left within measurement
Scroll right within measurement
Scroll upwards within measurement
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 49
Scroll downwards within measurement
Zoom in
Zoom out
Fit zoom to window
Table 7: Toolbar icons single measurement
7.1.2 Measurement settings
Trace channels and trigger for a measurement can be set via the AHF Viewer. If a trigger is
set and measurement is started using the button, the AHF Viewer can be disconnected
again. The measurement recording will be initialized as soon as the chosen trigger condition
arises. The measured values will only be stored in the internal RAM of the ECOsine® active
as long as voltage is applied to the device. When the connection is re-established and the
"Single measurement' window of the AHF Viewer is open, measurement will automatically
be loaded from the ECOsine® active memory.
Fig. 21: Single measurement settings
The following values can be set:
50 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Parameter Function
Trigger This parameter is used to select the measurement value for triggering.
In the dropdown menu all available parameters are displayed.
Trigger Level This is the trigger threshold; for binary signals it is only possible to set
them to 0 and 1.
Mode This defines whether the trigger is activated in case of exceeding or
falling below the trigger level.
Sample Rate Defines the sample rate as a multiple of 0.03125ms. The resulting
sample rate [ms] is calculated and displayed.
Delay
Indicates the pre-trigger history. This allows, for example, using half of
the trace memory for measurement values before trigger activation in
order to include the cause of the trigger in the measurement.
Channels This parameter defines the measurement values to be recorded. A
maximum of 10 different values are possible at the same time.
Table 8: Properties single measurement
By clicking on one of the channels curves, a pop-up will open, offering additional settings for
every channel.
Fig. 22: Single channel settings
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 51
Parameter Function
Gain Gain for the measurement value
Offset Offset to the measurement value
Axis This is to switch scaling of the channel to the left or right axis.
FFT (50Hz) FFT analysis of this channel at 50Hz line frequency
FFT (60Hz) FFT analysis of this channel at 60Hz line frequency
Table 9: Channel settings single measurement
7.1.3 FFT analysis
The FFT analysis functionality of a chosen channel can be done for 50 or 60Hz. The blue
cursor can be used to show amplitudes for every harmonic frequency. All values are peak
values of the selected frequency (RMS value = peak / √2). The ‘Print’ button can be used to
print the graph. By clicking ‘Save as’, the graph can be saved as a picture or table of values.
Fig. 23: FFT analysis
52 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
7.2 Continuous measurement
To open or start a continuous measurement, select ‘OscilloscopeContinuous
measurement’. A continuous measurement allows for recording of slowly changing values
like RMS values or digital values at a sample rate of at least 1 second. The values are
derived from the ECOsine® active filter and are displayed in line charts. For this kind of
measurement connection between PC/laptop and filter has to remain online. The maximum
duration of a continuous measurement is only limited by the available memory on
PC/laptop. Each measurement has to be stored prior starting a new one; otherwise the
measured values will get lost. Measurement channels can be individually activated or
deactivated. This allows comparing different measurement values and hiding those that are
not needed.
By means of the two cursors C1 and C2, the current values of all measurement channels at
a certain moment can be displayed at the right side of the window. The time frame in
between the two cursor positions is also displayed.
Fig. 24: Continuous measurement
7.2.1 Toolbar
The icons on the toolbar can be used to quickly control the continuous measurements.
Functionality of the icons is as following:
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 53
Icon Function
Connect to ECOsine® active
Disconnect from ECOsine® active
Open connection settings
Open parameter window
Open a saved measurement file
Saves the current measurement to the hard disk, with the following
possible formats.
.nbtc (continuous measurement file)
.bmp
.jpg
.xls
Prints the current measurement on the standard printer
Information about AHF Viewer (Version)
Measurement settings
Start measurement
Stop measurement
Scroll left within measurement
Scroll right within measurement
Scroll upwards within measurement
54 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
Scroll downwards within measurement
Zoom in
Zoom out
Fit zoom to window
Table 10: Toolbar icons single measurement
7.2.2 Measurement settings
Trace channels and trigger for a measurement can be set via the AHF Viewer.
Fig. 25: Continuous measurement settings
The following values can be set:
Parameter Function
Interval Interval for recording measurement values by the oscilloscope
Channels This is where you can select the measurement values to be recorded.
A maximum of 10 different values are possible at the same time.
Table 11: Continuous measurement values
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 55
Fig. 26: Single channel settings
By clicking on one of the channels curves, a pop-up will open, offering additional settings for
every channel.
Parameter Function
Gain Gain for the measurement value
Offset Offset to the measurement value
Axis This is to switch scaling of the channel to the left or right axis..
Table 12: Channel settings continuous measurement
56 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
8 Language
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 57
Within the ‘Language’ menu you can set the language of the AHF Viewer software to
German or English. A change of the language requires a restart of the program to be
effective.
58 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
9 Log file
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 59
To open a log file of an ECOsine®, please select ‘EventlogShow eventlog’. A window will
show all status entries with date and time, description, and operating hours.
Fig. 27: Event log
Button Function
Update (latest records) Up to the last 200 entries from the event log of the ECOsine®
active are loaded
Update (all records) All events saved in an ECOsine® active filter are loaded
Open Opens a saved log file
Save Saves a log file
Close Closes the event log window
Table 13: Event log functionality
60 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
10 Firmware update
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 61
CAUTION
During firmware download do not disconnect the RS485
cable or interrupt the power supply of ECOsine® active.
Only authorized Schaffner service staff should perform a
firmware update!
Firmware update is only possible via the RS485 interface!
Set the baud rate of ECOsine® active to 38400 (P231)
When performing a firmware update, please make sure that
All other connections to the device are closed
Parameter P202 is set to ‘direct off’
The firmware update can be started by selecting ‘FileUpdate Device Firmware’. Please
carefully follow the dialog boxes and fill in required information.
1. Choose COM port of RS485 connection and apply with OK
Fig. 28: Starting firmware update
2. Select the appropriate firmware file (*.srec)
Fig. 29: Choosing firmware file
62 ECOsine® active Harmonic Filters – Manual AHF Viewer V02
3. Follow dialog and press ‘OK’ button if to continue
Fig. 30: Safety prompt before firmware download
Fig. 31: Download duration system message
Fig. 32: Firmware update completed system message
If a firmware update was not successful, the following system message will appear.
Fig. 33: Firmware update unsuccessful
ECOsine® active Harmonic Filters – Manual AHF Viewer V02 63
In such case, confirm the message with ‘Yes’ and follow the download instructions. If the
problem consists please recheck all connections and settings.
Fig. 34: Restarting firmware update
To restart a firmware update, disconnect the ECOsine® active from the power supply and
wait until the display is dark. Then reconnect, and wait until the next window appears to
select the firmware file. Select the appropriate file and perform firmware download as
described above.
01
/20
14
EN
Headquarters, global innovation
and development center
Schaffner Group
Nordstrasse 11
4542 Luterbach
Switzerland
T +41 32 681 66 26
F +41 32 681 66 30
www.schaffner.com
To find your local partner within
Schaffner‘s global network, please go to
www.schaffner.com
© 2014 Schaffner Group
The content of this document has been
carefully checked and understood.
However, neither Schaffner nor its
subsidiaries assume any liability
whatsoever for any errors or
inaccuracies of this document and the
consequences thereof. Published
specifications are subject to change
without notice. Product suitability for any
area of application must ultimately be
determined by the customer. In all
cases, products must never be operated
outside their published specifications.
Schaffner does not guarantee the
availability of all published products. This
disclaimer shall be governed by
substantive Swiss law and resulting
disputes shall be settled by the courts at
the place of business of Schaffner
Holding AG. Latest publications and a
complete disclaimer can be downloaded
from the Schaffner website. All
trademarks recognized.
Sales and application centers
China
Schaffner EMC Ltd. Shanghai
T20-3, No 565 Chuangye Road
Pudong New Area
Shanghai 201201
T +86 21 3813 9500
F +86 21 3813 9501 / 02
www.schaffner.com
Finland
Schaffner Oy
Sauvonrinne 19 H
08500 Lohja
T +358 19 35 72 71
F +358 19 32 66 10
France
Schaffner EMC S.A.S.
112, Quai de Bezons
95103 Argenteuil
T +33 1 34 34 30 60
F +33 1 39 47 02 28
Germany
Schaffner Deutschland GmbH
Schoemperlenstrasse 12B
76185 Karlsruhe
T +49 721 56910
F +49 721 569110
Italy
Schaffner EMC S.r.l.
Via Galileo Galilei, 47
20092 Cinisello Balsamo (MI)
T +39 02 66 04 30 45/47
F +39 02 61 23 943
Japan
Schaffner EMC K.K.
Mitsui-Seimei Sangenjaya Bldg. 7F
1-32-12, Kamiuma, Setagaya-ku
Tokyo 154-0011
T +81 3 5712 3650
F +81 3 5712 3651
www.schaffner.jp
Singapore
Schaffner EMC Pte Ltd.
Blk 3015A Ubi Road 1
05-09 Kampong Ubi Industrial Estate
T +65 6377 3283
F +65 6377 3281
Spain
Schaffner EMC España
Calle Caléndula 93
Miniparc III, Edificio E
El Soto de la Moraleja
Alcobendas
28109 Madrid
T +34 618 176 133
Sweden
Schaffner EMC AB
Turebergstorg 1, 6
19147 Sollentuna
T +46 8 5792 1121 / 22
F +46 8 92 96 90
Switzerland
Schaffner EMV AG
Nordstrasse 11
4542 Luterbach
T +41 32 681 66 26
F +41 32 681 66 41
Taiwan
Schaffner EMV Ltd.
6th Floor, No 413
Rui Guang Road
Neihu District
Taipei City 114
T +886 2 87525050
F +886 2 87518086
Thailand
Schaffner EMC Co. Ltd.
Northern Region Industrial Estate
67 Moo 4 Tambon Ban Klang
Amphur Muang P.O. Box 14
Lamphun 51000
T +66 53 58 11 04
F +66 53 58 10 19
UK
Schaffner Ltd.
5 Ashville Way
Molly Millars Lane
Wokingham
Berkshire RG41 2PL
T +44 118 9770070
F +44 118 9792969
www.schaffner.uk.com
USA
Schaffner EMC Inc.
52 Mayfield Avenue
Edison, New Jersey 08837
T +1 732 225 9533
F +1 732 225 4789
www.schaffner.com/us
Schaffner MTC LLC
6722 Thirlane Road
24019 Roanoke, Virginia
T +276 228 7943
F +276 228 7953
www.schaffnerusa.com
Schaffner Trenco LLC
2550 Brookpark Road
44134 Cleveland, Ohio
T +216 741 5282
F +216 741 4860
www.schaffner-trenco.com