NUCLEAR POWER CORPORATION OF INDIA LTD.
127744024.xls
DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)
Building Name
Footing Number:
Node number
COLUMN/PEDESTAL
Length (l, dim. || Z axis ) = 700 mmBreadth (b, dim. || X axis) = 600 mm
Height of pedestal = 1 m Breadth 6.5 m
Weight of pedestal/column = 10.50 KN
FOOTING
Foot length (L, dim. || Z axis) = 6.75 m
Foot Breadth (B, dim. || X axis) = 6.5 m
Thickness of footing (t) = 750 mm
Clear cover to Reinforcement = 75 mm
Main bar dia of footing = 16 mm
Effective depth of footing = 667 mm Length 6.75 m
Selfweight of the footing = 822.66 KN
Area of Footing(A) = 43.88
Sect mod of foot about Z axis (Zz) = 47.53
Sec mod of foot about X axis (Zx) = 49.36
MATERIALS OF CONSTRUCTION
20
415
CHECK FOR GROSS BEARING PRESSURE
1650
Safe gross bearing pr. = 1702.25 (net pr. + depth of foot * soil unit wt)
215Axial load from output (P1) = 721.07 KN
200 KN-m
2000 KN-m
Depth of top of foot. from ground = 2 m
Unit wt of soil = 19
Weight of soil retained above foot = 1651.29 KN
P = (P1+soil+pedestal+foot selfwt) = 3205.52 KN
Maximum bearing pressure = 117.79
Minimum bearing pressure = 28.33
Hence footing is safe against max gross bearing pr.
DESIGN FORCESFactored load comb. no. 18
100 KN
100 KN-m
5 KN-m
( Pu/Area+ Muz/Zz + Mux/Zx) = 4.48
( Pu/Area - Muz/Zz - Mux/Zx) = 0.07
Design of footing is done using above maximum effective soil pressure
m2
m3
m3
Grade of concrete fck
= N/mm2
Grade of steel fy= N/mm2
SafeNET bearing pressure = KN/m2
KN/m2
Unfactored load case number =
Moment about Z axis (Mz) =
Moment about X axis (Mx) =
KN/m3
KN/m2
KN/m2
Axial load:(Pu) =
Moment about Z axis (Muz
) =
Moment about X axis (Mux
) =
Maximum effective soil pressure pe max
KN/m2
Minimum effective soil pressure pe min
KN/m2
P
A
My
Zy
Mx
Zx
globalZ
globalX
globalX
globalZ
Footing Dimensions
7/29/2019 footing biaxial
2/25
NUCLEAR POWER CORPORATION OF INDIA LTD.
127744024.xls
CALCULATION FOR BOTTOM STEEL
20.52 KN-m per meter
Mulimit = 1228.80 KN-m per meter
The section is singly reinforced
Hence, Ast = 85.468Min Ast = 800.400 (0.12 % for slab, cl 26.5.2.1)
Spacing = 251.20 mm (considering max of above two calculated values of Ast)
pt provided = 0.12 %
Hence provide 16 mm dia bar @ 251 mm c/c parellel to length of footing ( || to Z)
19.51 KN-m per meter
Calc. Ast = 81.272 The section is singly reinforced
Min Ast = 800.4 (0.12 % for slab, cl 26.5.2.1)
Spacing = 251.20 mm (considering max of above two calculated values of Ast)
pt provided = 0.12 %
Hence provide 16 mm dia bar @ 251 mm c/c parellel to breadth of footing ( || to X)
Arrangement of bottom reinforcement as per above design is shown below
16 mm dia bar @ 251 mm c/c
16 mm dia bar @ 251 mm c/c
1 1
Footing Length 6750 mm Breadth 6500 mm
Sec 1-1
1367 600
1267
L1
a a
Z Z
N1 N1
a a
L2 L2
2358
L1 Breadth 6500 mm
700
Footing Length 6750 mm 2283
PLAN
Mu about X1 X1 = ( pe max x length2/2)=
mm2
mm2
Mu about N1 N1 = ( pe max x length2/2)=
mm2
mm2
X1 X
X1 X
Ast=
0.5fck
fy [1 1
4.6Mu
fckbd2 ] bd
7/29/2019 footing biaxial
3/25
NUCLEAR POWER CORPORATION OF INDIA LTD.
127744024.xls
CHECK FOR ONE WAY SHEAR :
One way shear at critical section L1- L1
Distance of critical sec. from edge of footing = 2.36 m
Shear force Vs =pe max x 2.358 x 1m width of footing = 10.574 KN
Shear stress 0.016
0.26
tv < tc hence O.K.
One way shear at critical section L2- L2
Distance of critical sec. from edge of footing = 2.28 m
Shear force Vs =pe max x 2.283 x 1m width of footing = 10.238 KN
Shear stress 0.015
0.26
tv < tc hence O.K.
CHECK FOR TWO WAY SHEAR
Ref. cl 34.2.4 and cl.31.6.3 of IS 456 : 2000
1.54 >1
1
1.12
1.12
Shear force Vs = 4.484 ( 6.75 x 6.5 - 1.367 x 1.267) = 188.99 KN
Length of critical section = 2 x ( 1367 + 1267) = 5268 mm
Area of the critical section (length of critical sec x eff. d ) = 3513756
0.054
tv < allowable hence O.K.
tv= Vs/bd = N/mm2
tc
= N/mm2
tv= Vs/bd = N/mm2
tc
= N/mm2
Allowable shear stress tv allowable
= ks
tc
ks= ( 0.5 + bc) =
Hence, ks=
tc= 0.25 (fck)0.5 = N/mm2
tv allowable
= ks
x c
= N/mm2
mm2
Hence shear stress v= N/mm2
7/29/2019 footing biaxial
4/25
DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)
Project name
Building name
Breadth 6.5 m
Length 6.75 m
Column/Pedestal Footing size
mm mm m KN m m mm
500 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
700 600 0 0 6.75 6.5 750
Length (l,dim. || Z
axis )
Breadth(b, dim. ||
X axis)
Height ofPedestal
Weight ofpedestal
Footlength (L,
dim. || Zaxis)
FootBreadth
(B, dim. ||X axis)
Thicknessof footing
(t)
globalZ
globalX
globalX
globalZ
Footing Dimensions
Z and X axis are ass
as two horizontal Gloaxis of building.
Hence, input the
dimensions of footin
easily b y inputing folength parallel to glo
and footing breadthparallel to global X.
7/29/2019 footing biaxial
5/25
16 mm dia
16 mm dia
1
Footing Length 6
7/29/2019 footing biaxial
6/25
Sec 1-1
1167
L1
a a
Z
N1
a a
L2 L2
2458L1
500
Foot ing Length 6750 mm PLAN
X1 X
X1 X
7/29/2019 footing biaxial
7/25
NUCLEAR POWER CORPORATION OF INDIA LTD.
127744024.xls
DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)
Building Name
Footing Number:
Node number
COLUMN
Length (l, dim. || Z axis ) = 700 mm
Breadth (b, dim. || X axis) = 600 mm
Height of pedestal = 1 m Breadth 3 m
Weight of pedestal/column = 10.50 KN
FOOTING
Foot length (L, dim. || Z axis) = 5 m
Foot Breadth (B, dim. || X axis) = 3 m
Thickness of footing (t) = 750 mm
Clear cover to Reinforcement = 75 mm
Main bar dia of footing = 16 mm
Effective depth of footing = 667 mm Length 5 m
Selfweight of the footing = 281.25 KN
Area of Footing(A) = 15.00Sect mod of foot about Z axis (Zz) = 7.50
Sec mod of foot about X axis (Zx) = 12.50
MATERIALS OF CONSTRUCTION
20
415
CHECK FOR GROSS BEARING PRESSURE
1650
Safe gross bearing pr. = 1702.25 (net pr. + depth of foot * soil unit wt)
215
Axial load from output (P1) = 10 KN
500KN-m
450KN-m
Depth of top of foot. from ground = 2 m
Unit wt of soil = 19
Weight of soil retained above foot = 554.04 KN
P = (P1+soil+pedestal+foot selfwt) = 855.79 KN
Maximum bearing pressure = 159.72
Minimum bearing pressure = -45.61
Recalculation of max pressure done below as min pressure is negative.
Recalculated max bearing press. = 170.76 Max bearing pressure is safe
Minimum bearing pressure = 0
DESIGN FORCES
Factored load comb. no. 18
150 KN
150 KN-m
150 KN-m
( Pu/Area+ Muz/Zz + Mux/Zx) = 42.00
( Pu/Area - Muz/Zz - Mux/Zx) = -22.00
Recalculation of maximum effective pressure done below as min pressure is negative.
75.15
0
m
2
m3
m3
Grade of concrete fck
= N/mm2
Grade of steel fy= N/mm2
SafeNET bearing pressure = KN/m2
KN/m2
Unfactored load case number =
Moment about Z axis (Mz) =
Moment about X axis (Mx) =
KN/m3
KN/m2
KN/m2
KN/m2
KN/m2
Axial load:(Pu) =
Moment about Z axis (Muz
) =
Moment about X axis (Mux
) =
Maximum effective soil pressure pe max
KN/m2
Minimum effective soil pressure pe min
KN/m2
Maximum effective soil pressure pe max
KN/m2
Minimum effective soil pressure pe min KN/m2
P
A
My
Zy
Mx
Zx
globalZ
globalX
globalX
globalZ
Footing Dimensions
7/29/2019 footing biaxial
8/25
NUCLEAR POWER CORPORATION OF INDIA LTD.
127744024.xls
CALCULATION FOR BOTTOM STEEL
173.68 KN-m per meter
Mulimit = 1228.80 KN-m per meter
The section is singly reinforced
Hence, Ast = 738.53Min Ast = 800.40 (0.12 % for slab, cl 26.5.2.1)
Spacing = 251.20 mm (considering max of above two calculated values of Ast)
pt prov