65
“Lightning Protection” 1 MCPQG/IEEE, May 3, 2011

“Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

  • Upload
    vodang

  • View
    228

  • Download
    4

Embed Size (px)

Citation preview

Page 1: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

“Lightning Protection”

1MCPQG/IEEE, May 3, 2011

Page 2: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

“Lightning Protection”

Presented by,

Mike Puckett, P.E., Puckett Engineering, PLLC

May 3, 2011

Joint meeting of the Music City Power Quality Group and the IEEE Central TN Section

2MCPQG/IEEE, May 3, 2011

Page 3: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

3

OverviewPurposes of Lightning ProtectionLightning StatisticsPhysics of LightningHow does Lightning Damage EquipmentLightning Protection • Grounding and Bonding• Isolation• Surge Protection• Building Envelope

Personal Safety from Lightning

MCPQG/IEEE, May 3, 2011

Page 4: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

4

Purposes of Lightning Protection

Protect PeopleProtect EquipmentProtect Power LinesProtect Structures (Buildings)Protect Storage of Explosive MaterialsProtect Towers and TanksProtect WatercraftProtect Livestock

MCPQG/IEEE, May 3, 2011

Page 5: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

5

Lightning Statistics

30 to 100 Lightning Flashes per Second around the World (Cloud & Cloud-to-Ground)Up to 9 Million Flashes per Day worldwideCloud Discharges account for more Flashes than Cloud-to-Ground Flashes (Intracloud most common)

MCPQG/IEEE, May 3, 2011

Page 6: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

6

Lightning Statistics, cont.Insurance payouts in U.S. 1/3 to 1 Billion/yr.Cost of U.S. Lightning Damage ~ 1 Billion/yr.NFPA reports ~ 30,000 Lightning Caused House Fires each year with cost of $175 Mil.About 30% of all Church Fires are Lightning RelatedLightning is Primary Cause of Fires on Farms and for more than 80% of Livestock LossesIn 1999, Lightning Ignited more than 2000 Forest Fires in Florida alone.

MCPQG/IEEE, May 3, 2011

Page 7: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

7

Physics of LightningTypical 1st Return Stroke near 30,000 Amps but can be as high as 300kA.Subsequent strokes 10,000 to 15,000 Amps.1st Return Stroke Rise Times of 1.8µs to 18µs with 5.5µs being typical for. Equates to 14kHz to 139kHz with 45kHz being typical.Subsequent Return Stroke Rise Times of 0.22µs to 4.5µs with 1.1µs being typical for 1st Return Stroke. Equates to 56kHz to 1.1MHz with 227kHz being typical.Leader Potential of 1,000,000 to 10,000,000 Volts with respect to earth.

MCPQG/IEEE, May 3, 2011

Page 8: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Lightning Stroke

MCPQG/IEEE, May 3, 2011 8

Page 9: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

9

Lightning Stroke

MCPQG/IEEE, May 3, 2011

The shape Represents a

Downward Leader

Leader/Streamer Connection

Page 10: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

10

How does Lightning Damage Equipment

Direct Lightning Strikes.Resistive Coupling.Inductive Coupling.Capacitive Coupling.

MCPQG/IEEE, May 3, 2011

Page 11: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

11

Direct Lightning Strikes

• Strike will cause extensive damage and can also cause damage to equipment inside the building

MCPQG/IEEE, May 3, 2011

Page 12: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

12

Resistive & Inductive Coupling

• Inductive coupling can also induce voltages into nearby equipment.

MCPQG/IEEE, May 3, 2011

Page 13: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

13

Capacitive Coupling

• Transients travelling along circuit conductors will induce voltages into adjacent conductors through mutual capacitance and inductance.

• Similar for cables near objects carrying lightning current.

MCPQG/IEEE, May 3, 2011

Page 14: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

14

Lightning Protection

Grounding and BondingIsolationSurge ProtectionBuilding Envelope

MCPQG/IEEE, May 3, 2011

Page 15: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

15

Grounding and Bonding

Relatively Low Earth ResistanceEquipotential Ground Plane

MCPQG/IEEE, May 3, 2011

Page 16: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

16

Earth Grounding

MCPQG/IEEE, May 3, 2011

Page 17: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

17

Ground Field ConsiderationsThe Ground Rod’s Earth Connection:

“Interfacing Hemisphere”

MCPQG/IEEE, May 3, 2011

Page 18: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

18

Ground Field ConsiderationsInterfacing Hemisphere• The rod’s interfacing hemisphere (IH) has a

radius of approximately 1.0 times the rod’s length. Therefore, it is best to space rods at least twice their length.

• The interfacing hemisphere makes up approximately 94% of the rod’s earth connection (i.e. resistance)

• 25% of the rod’s earth resistance is within the first 1.2 inches of the rod’s IH. Therefore, the first few inches away from the rod are the most important for reducing the earth resistance.

MCPQG/IEEE, May 3, 2011

Page 19: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

19

Ground Field Considerations

Rod, Pipe, and Plate Electrodes with ground resistance greater than 25 ohms must be augmented by one of the following:

» Building steel structure where it is effectively grounded» Concrete encased electrode in foundation or footing» Ground ring encircling the building» Rod or pipe electrode» Plate electrode» Other local underground systems or structures, such as piping

systems and underground tanks• Earth resistivity must be 60 ohm-meters or less for one 8’

rod to achieve 25 ohms (Average soil resistivity in Middle TN is 250 ohm-meters according to Soil Resistivity Map)

• Few areas in U.S. have average soil resistivity less than 60 ohm-meters

MCPQG/IEEE, May 3, 2011

Page 20: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

20

Ground Field Considerations

Ufer Grounds (Encased Electrodes)» Average Soil Resistivity for Middle TN = 250

Ohm-Meters Vs 0.12 Ohm-Meters for Erico’s “GEM”

» Concrete Resistivity is 30 ohm-meters.» Moisture Retention.

Can use Erico’s Calculator for Calculating Earth Resistance with and without GEM or do it manually using the Dwight formulas in the IEEE Green book or other reference. Can calculator download from their website.

MCPQG/IEEE, May 3, 2011

Page 21: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

21

Ground Field ConsiderationsEarth Resistance Guidelines:• Residence – 25 Ohms• Small Commercial – 20 Ohms• Industrial, Large Commercial – 10 Ohms Max.• Substations – 5 Ohms Maximum• With regards to the power system, in general, the

larger the electrical system the lower the earth resistance should be due to the higher fault currents.

• Another reason for lower resistance is for lightning protection. To give lightning the best path possible to earth.

MCPQG/IEEE, May 3, 2011

Page 22: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

22

Ground Field ConsiderationsGrounding Electrode Conductors• Minimize Lengths and sharp bends• Use minimum bending radius of 8 inches• Minimizing length is more important than bends• Conductor Z predominantly inductive reactance at HF

» Z~X=2πfL» L (in µH) =.508l[2.303Log(4l/d) -.75] x 0.01

– l=Length in inches– d=Diameter in inches

» f=Frequency is 45kHz to 227kHz typical (based on 5.5µs and 1.1µs rise times). For IEEE C62.41, 8 x 20µs Waveform, f=32.5 kHz. Lightning can also be in the 1 MHz range or higher.

» VD=Z x I = 163 V/FT. (each way) for 3kA, 8 x 20 µs impulse, using 2 AWG conductor.

» VD=Z x I = 5002 V/FT. (each way) for 3kA, 1 MHz impulse, using 2 AWG conductor.

MCPQG/IEEE, May 3, 2011

Page 23: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

23

Electrical Service Grounding

• With few exceptions, it is imperative to bond everything together to create a virtual “Grounding Grid”

MCPQG/IEEE, May 3, 2011

Page 24: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

24

Ideal Signal (Grounding) Reference Grid

SRG provides equipotential plane between equipment, which minimizes or eliminates potential differences between equipment.The SRG could include a grid of conductors, solid sheet of copper or sheet metal, and/or a building’s steel structure.

MCPQG/IEEE, May 3, 2011

Page 25: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

25

Grounding Grid Considerations

Take a comprehensive approach to grounding/bonding.

MCPQG/IEEE, May 3, 2011

Page 26: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

26

Radio Cable Grounding

Ground Bus

MCPQG/IEEE, May 3, 2011

Page 27: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

27

Radio Cable Bulkhead

MCPQG/IEEE, May 3, 2011

Page 28: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

28

Grounding Grid Considerations, cont.

For steel buildings, take advantage of the building’s structure.• The massive grid of steel can make for a nice

“Grounding Grid” if it is bonded and grounded.• Confirm all bolted connections are continuous. If

not, add jumpers.» The Lightning Protection standards allow using the

steel columns for down conductors but do not require bonding across bolted connections.

• For bar joist construction, confirm whether the metal deck pan is welded to the joists and if the joists are welded together via cross members.

MCPQG/IEEE, May 3, 2011

Page 29: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

29

Grounding Grid Considerations, cont.When bonding to steel, remove primer/paint to ensure a good connection (even if the lug is fastened using a tapped hole).• Advise installer to take necessary precautions if

primer/paint includes lead.• Use lock-washers.• Reapply primer/paint to exposed bare metal.• Apply an antioxidant compound around connection.• Where grounding conductors are installed in metal

conduit, be sure to bond each end of metal conduit to the same grounding point as the ground wire. Otherwise, the conductor and conduit act like a single turn coil.

• Use lugs with two bolt holes to minimize twisting lug where wire or lug could be hit.

MCPQG/IEEE, May 3, 2011

Page 30: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

30

Grounding Grid Considerations, cont.

Bonding Jumper across column and beam connection.Same for the steel purlins that were screwed to beams.

MCPQG/IEEE, May 3, 2011

Page 31: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

31

“Isolation”Minimizing or Eliminating the Adverse Effects of

Potential Differences on the Grounding System

Equipotential Ground Plane (Grounding Grid) (discussed earlier)Ethernet NetworksSignal IsolatorsOptical IsolatorsFiber Optic Cables

MCPQG/IEEE, May 3, 2011

Page 32: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

32

Ethernet Networks

Ethernet networks are more immune to ground loops due to internal isolation on data portsIsolated ground usually not be necessary

MCPQG/IEEE, May 3, 2011

Page 33: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

33

Signal Isolator

This is normally used in process controlsIsolated ground may not be necessary

MCPQG/IEEE, May 3, 2011

Page 34: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

34

Optical Isolator

Optical isolators can provide 2.0kV or more of isolationFor 100% isolation use fiber optic cable between equipment

MCPQG/IEEE, May 3, 2011

Page 35: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

35

Optical Isolator

B&B Electronics offers models for various applicationsFor Ethernet, use Fiber Optic Media Converters.

MCPQG/IEEE, May 3, 2011

Page 36: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

36

Surge ProtectionLocations• Each Electrical Service Entrance• Sub-Panels supplied from transformers, and/or

supplying critical/sensitive equipment.• Each Communications Service (Telephone, Cable

TV, Satellite, etc.)• Each power or communications or data circuit that

extends beyond the building for outdoor equipment or remote buildings.

• Critical/Sensitive utilization equipment. Consider combination units where the equipment is connected to both power and communications/data.

MCPQG/IEEE, May 3, 2011

Page 37: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

37

Surge Protection, cont.SPD Conductor Connections• SPD let-through voltage is insignificant compared to the effect of

conductor lengths• Conductor Z predominantly inductive reactance at high frequency

» L (in µH) =.508l[2.303Log(4l/d) -.75] x 0.01– l=Length in inches– d=Diameter in inches

» f=Frequency is 45kHz to 227kHz typical (based on 5.5µs and 1.1µs rise times). For IEEE C62.41, 8 x 20µs Waveform, f=32.5 kHz. Lightning can also be in the 1 MHz range or higher.

» VD=Z x I = 163 V/FT. (each way) for 3kA, 8 x 20 µs impulse, using 2 AWG conductor.

» VD=Z x I = 5002 V/FT. (each way) for 3kA, 1 MHz impulse, using 2 AWG conductor.

• Consider SPD units integrally-mounted in panels. Be aware if it fails destructively, the panel could also fail.

MCPQG/IEEE, May 3, 2011

Page 38: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

38

Church Case Study

Built in 3 Phases between 1956 and 2008

Wood & ConcreteStructures

1956 & 1992

Steel RoofStructure & Rubber

Roof2001

SteelStructure & Metal

Roof2008

Five Modular Buildings with Steel Floor Joists & Metal

Roof

MCPQG/IEEE, May 3, 2011

Steeple ~110’ above grade

Page 39: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

39

Church Case Study, cont.

Built in 3 Phases between 1956 and 2008

Five Modular Buildings with

Steel Floor Joists & Metal Roof

Wood & ConcreteStructures

1956 & 1992

Steel RoofStructure &

Rubber Roof2001Steel

Structure & Metal Roof

2008

Service #3

Service #2 Service #1

MCPQG/IEEE, May 3, 2011

Annex I Building

Page 40: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

40

Church Case Study, Cont.

MCPQG/IEEE, May 3, 2011

Page 41: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

41

Church Case Study, Systems49 HVAC Units with 26 roof-mounted on 2001 section roof.HVAC DDC Control System.

» This system includes a data cable (RS-485 protocol) that daisy-chains through all HVAC unit controllers.

LAN that originates in 1992 section with fiber optic cables between 1992 section and 2008 section.A/V Control Room in 2008 section for Sanctuary.Video Transmitter in 2008 A/V Control Room with video Receiver in 2001 Café and in 2008 Library. Intercom at main front entrance for communicating with receptionist in front lobby.Access Control System with three card readers.

MCPQG/IEEE, May 3, 2011

Page 42: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

42

Church Case Study, Analysis

Access Control System with three card readers.

MCPQG/IEEE, May 3, 2011

Page 43: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

43

Church Case Study, Lightning Damage

HVAC DDC Control System.» This was the main damage that occurred repeatedly. » It occurred occasionally before the 2008 section but

escalated after the 2008 section.» This system includes a data cable (RS-485 protocol)

that daisy-chains through all HVAC unit controllers.Video Transmitter in 2008 A/V Control Room and video Receiver in 2001 Café. The café receiver had been damaged 2 to 3 times prior to 2010.Intercom and Card reader at main front entrance.

MCPQG/IEEE, May 3, 2011

Page 44: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, Grounding Before

MCPQG/IEEE, May 3, 2011 44

Page 45: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, Grounding After

MCPQG/IEEE, May 3, 2011 45

Page 46: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, Typical Ground Field

MCPQG/IEEE, May 3, 2011 46

Both 8’ rods together yield 21Ω in 150Ω-m soil.

The encased conductor yields 16Ω in 150Ω-m soil.

Each 8’ rod alone yields 38Ω in 150Ω-m soil.

Page 47: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, Ground Field Details

MCPQG/IEEE, May 3, 2011 47

Can download Erico’s Ground Resistance calculator from their

website or calculate manually per IEEE Green book.

Page 48: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, DDC Controls Before

MCPQG/IEEE, May 3, 2011 48

Page 49: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, Ground Differential

MCPQG/IEEE, May 3, 2011 49

Page 50: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, Ground Differential

MCPQG/IEEE, May 3, 2011 50

Page 51: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

Church Case Study, DDC Controls After

MCPQG/IEEE, May 3, 2011 51

Page 52: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

52

Optical Isolator

Optical isolators can provide 2.0kV or more of isolationFor 100% isolation use fiber optic cable between equipment

MCPQG/IEEE, May 3, 2011

Page 53: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

53

Optical Isolator

B&B Electronics offers models for various applicationsFor Ethernet, use Fiber Optic Media Converters.

MCPQG/IEEE, May 3, 2011

Page 54: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

54

Church Case Study, Other Improvements

SPD for all Electrical Services.SPD for all sub-panels that supply rooftop equipment.Bonded the same sub-panels to the building steel.Monitoring system for SPDs to send alarms via the LAN.Improved installation of ac supply SPDs for fire alarm control panels and for low-voltage SPD for fire alarm outdoor circuit to PIV.Installed outdoor exposed DDC data cables in steel conduit.Intercom and Card reader at main front entrance.

MCPQG/IEEE, May 3, 2011

Page 55: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

55

Church Case Study, Lightning Events Since Improvements

As of December 2010, bonding of steel and water pipes were completed.2/24/11 thunderstorm, no damage.2/28/11 thunderstorm, three DDC controllers failed. Several had to be reset.3/23/11 and 4/4/11, Thunderstorms, no damage.Earth Grounding work completed 4/4/11.Optical Isolators installed 4/5/11. Most other work completed by 4/22/11.No problems in recent severe thunderstorms.

MCPQG/IEEE, May 3, 2011

Page 56: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

56

Case Study: “Too Much” Grounding

Metro Emergency Communications CenterMCPQG/IEEE, May 3, 2011

Page 57: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

57

Case Study: “Too Much” Grounding

MCPQG/IEEE, May 3, 2011

UP

STAIR125

CO

RR

IDO

R12

6

911 ROOM

E.O.C.

COORIDOR107

WATCH108

TAP

ES

TOR

.1

12

109

TOIL.

STO.109

CONFEREN

CE10

1

COFFEE

102

MEN

S12

8

TELE

.

TRAN

SMIT

TER

MAI

NT.1

13

UPS

102

LOUNGE1 16

MENS LOCKER RM.

WOMENSLOCKER RM.120

BATT

ERY

GENER

ATOR R

M.

EQUIP.124

SECRETARY106

MENS

WOMENS

ELEVATOR STOR. CORRIDOR

STOR.

MENS WOMEN

JANIT

OR

ELEVATORLOBBY

TRAN

SMIT

TER R

M.

TOIL

.

PASS

AGE

STOR.

STAI

RS

105

ENTRY

110

TVSS

TVSS

TVSS

MANAGER

110911 SUPERVISOR

SECURITYOFFICE

RECEPTION

LOAD

ING

DOCK

117

155

Page 58: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

58

Case Study: “Too Much” Grounding

MCPQG/IEEE, May 3, 2011

Page 59: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

59

Case Study: “Too Much” Grounding

MCPQG/IEEE, May 3, 2011

Page 60: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

60

Personal Safety from Lightning

Safer places include:• Buildings that are protected against lightning.• Large metal frame buildings.• Enclosed automobiles or other vehicles with metal

top and bodies.• Enclosed metal boats or ships.• City streets shielded by nearby buildings.

However, be aware of possible voltage gradients should lightning hit a nearby building.

MCPQG/IEEE, May 3, 2011

Page 61: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

61

Personal Safety from Lightning, cont.If caught in an open area:• Crouch as low as possible,• Keep feet together,• Put hands on knees,• To minimize risk of a direct strike, keep as low as

possible.• To minimize risk of step potential, minimize the

area of the body in contact with the ground. Do not lie flat.

Refer to NFPA 780 and/or other lightning publications for more safety information.

MCPQG/IEEE, May 3, 2011

Page 62: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

62

Personal Safety from Lightning, cont.

Car Protection (Faraday Cage)

MCPQG/IEEE, May 3, 2011

Page 63: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

63

Personal Safety from Lightning, cont.

The Shower Jolt!

MCPQG/IEEE, May 3, 2011

Page 64: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

64

For Effective Lightning Protection

Look at THE BIG PICTURE.Consider all Systems and Equipment Involved.For Personal Safety, Respect Lightning

MCPQG/IEEE, May 3, 2011

Page 65: “Grounding, from the Ground Up” - IEEE Entity Web ... · PDF filePurposes of Lightning Protection ¾Protect People ¾Protect Equipment ¾Protect Power Lines ¾Protect Structures

65

God Bless Americaand Our Troops

MCPQG/IEEE, May 3, 2011