How To Read A Motor Nameplate.docx

Embed Size (px)

Citation preview

  • 7/27/2019 How To Read A Motor Nameplate.docx

    1/8

    http://www.vfds.com/how-to-read-a-motor-nameplate

    How To Read A Motor Nameplate

    CT:VT:

    MODEL NO./SERIAL NO. HZLOW VOLTAGE

    EFF. TYPE S.F. DESIGN

    HP RPM CODE DUTY

    INSL. FRAMEHIGH VOLTAGE

    VOLTS AMPS

    PHASE BEARINGS

    ASSEMBLED IN USA

    The Big Picture

    Reading a motor nameplate can sometimes pose a unique challenge. Most manufacturers display information differently, and nameplatesoften get dirty, damaged, and occasionally are removed. This can make reading a motor nameplate a difficult or frustrating task.

    http://www.vfds.com/how-to-read-a-motor-nameplate#divCtVthttp://www.vfds.com/how-to-read-a-motor-nameplate#divCtVthttp://www.vfds.com/how-to-read-a-motor-nameplate#divCtVthttp://www.vfds.com/how-to-read-a-motor-nameplate#divCtVthttp://www.vfds.com/how-to-read-a-motor-nameplate#divModelhttp://www.vfds.com/how-to-read-a-motor-nameplate#divModelhttp://www.vfds.com/how-to-read-a-motor-nameplate#divHzhttp://www.vfds.com/how-to-read-a-motor-nameplate#divStrappinghttp://www.vfds.com/how-to-read-a-motor-nameplate#divEffhttp://www.vfds.com/how-to-read-a-motor-nameplate#divEffhttp://www.vfds.com/how-to-read-a-motor-nameplate#divTypehttp://www.vfds.com/how-to-read-a-motor-nameplate#divSfhttp://www.vfds.com/how-to-read-a-motor-nameplate#divDesignhttp://www.vfds.com/how-to-read-a-motor-nameplate#divHphttp://www.vfds.com/how-to-read-a-motor-nameplate#divHphttp://www.vfds.com/how-to-read-a-motor-nameplate#divRpmhttp://www.vfds.com/how-to-read-a-motor-nameplate#divCodehttp://www.vfds.com/how-to-read-a-motor-nameplate#divCodehttp://www.vfds.com/how-to-read-a-motor-nameplate#divDutyhttp://www.vfds.com/how-to-read-a-motor-nameplate#divInslhttp://www.vfds.com/how-to-read-a-motor-nameplate#divFramehttp://www.vfds.com/how-to-read-a-motor-nameplate#divFramehttp://www.vfds.com/how-to-read-a-motor-nameplate#divStrappinghttp://www.vfds.com/how-to-read-a-motor-nameplate#divVoltshttp://www.vfds.com/how-to-read-a-motor-nameplate#divAmpshttp://www.vfds.com/how-to-read-a-motor-nameplate#divPhasehttp://www.vfds.com/how-to-read-a-motor-nameplate#divBearingshttp://www.vfds.com/how-to-read-a-motor-nameplate#divBearingshttp://www.vfds.com/how-to-read-a-motor-nameplate#divPhasehttp://www.vfds.com/how-to-read-a-motor-nameplate#divAmpshttp://www.vfds.com/how-to-read-a-motor-nameplate#divVoltshttp://www.vfds.com/how-to-read-a-motor-nameplate#divStrappinghttp://www.vfds.com/how-to-read-a-motor-nameplate#divFramehttp://www.vfds.com/how-to-read-a-motor-nameplate#divInslhttp://www.vfds.com/how-to-read-a-motor-nameplate#divDutyhttp://www.vfds.com/how-to-read-a-motor-nameplate#divCodehttp://www.vfds.com/how-to-read-a-motor-nameplate#divRpmhttp://www.vfds.com/how-to-read-a-motor-nameplate#divHphttp://www.vfds.com/how-to-read-a-motor-nameplate#divDesignhttp://www.vfds.com/how-to-read-a-motor-nameplate#divSfhttp://www.vfds.com/how-to-read-a-motor-nameplate#divTypehttp://www.vfds.com/how-to-read-a-motor-nameplate#divEffhttp://www.vfds.com/how-to-read-a-motor-nameplate#divStrappinghttp://www.vfds.com/how-to-read-a-motor-nameplate#divHzhttp://www.vfds.com/how-to-read-a-motor-nameplate#divModelhttp://www.vfds.com/how-to-read-a-motor-nameplate#divCtVthttp://www.vfds.com/how-to-read-a-motor-nameplate#divCtVt
  • 7/27/2019 How To Read A Motor Nameplate.docx

    2/8

    You will need information from the motor nameplate throughout the life of the motor. If you ever need to size a VFD, repair a motor,replace a motor, connect a motor, correct power factor, purchase parts, or do just about anything with a motor you will need theinformation on the motor nameplate.

    Horsepower

    Horsepower is the mechanical output of a motor. You probably already have a goodunderstanding of what horsepower is, so we wont go into too much detail. However,it is probably important to mention that outside of North America the output rating iscommonly expressed in watts or kilowatts.

    Did you know?Horsepower was a term coined by James Watt. He used this term to helpmarket his steam engine.

    Remember to be conservative. Using anunder powered motor or drive could damageequipment and lead to unnecessarydowntime and expense.

    Voltage

    Motors are designed to run at the voltage listed on their nameplate. Many industrial motors are designed to run at more than one (linepower) voltage. For example, many motors are dual rated and are designed to run at 230V and 460V.

    Typically, motors have an operating tolerance of 10% of the rated voltage on the nameplate (consult your manual). This means that amotor designed to run on 230V can run at 208V (or 240V). Motors should not run outside their designated voltage range, doing so will

    damage your motor and or equipment. When working with a motor rated for dual voltages dont forget to verify the correspondingamperage rating and lead connection.

    Note:Your service factor rating will drop if you utilize your motors voltage tolerance.

    Full Load Amp Rating

  • 7/27/2019 How To Read A Motor Nameplate.docx

    3/8

    The FLA rating is the rate at which a motor will consume power at 100% of rated load and at rated and balanced voltage. This number isextremely important, especially when dealing with electrical components. The wiring, starter, circuit breaker, and thermal overloads are allsized based upon the full load amp rating.

    When it comes to sizing a VFD the FLA rating is a very important piece of information. Learn more about sizing VFDs at ourVFD BuyingGuide.

    Phase

    Unless you have a unique application your motor will be rated for single-phase or three-phase input power.

    RPM (Speed)

    The RPM listed on the nameplate is the shaft speed for the motor. The speed of the motor is directly related to the frequency of the linevoltage and the number of poles in the motor. At 60 Hz, a 4 pole motor will rotate at approximately 1800 RPM (7200/4 poles). However,depending on the amount of rotor slip the motor was designed for you may see the RPM listed as 1775 or 1750, et cetera. This numberrepresents what the manufacturer has engineered the motor will rotate at under full load with the set frequency listed on the nameplate.

    Design Letter

    The design letter provides information about a motors starting torque. B (normal starting torque), C (high starting torque), and D (very highstarting torque) design letters are the most common. A motors starting torque is different than torque during normal operations.

    For example, two motors with similar running torque ratings may have very different starting torque ratings. A motor being used for acentrifugal fan is likely to have different starting torque requirement than a conveyor belt.

    Service Factor

    Motors are often designed to handle a temporary increase in demand. Service factor represents the motors ability to handle thesetemporary demand increases. Think of service factor as an insurance policy. It is designed for ambient temperatures, altitude, high andlow line voltages, and imbalanced voltages. It should not be used as a method of increasing motor horsepower.

    http://www.vfds.com/vfd-buying-guidehttp://www.vfds.com/vfd-buying-guidehttp://www.vfds.com/vfd-buying-guidehttp://www.vfds.com/vfd-buying-guidehttp://www.vfds.com/vfd-buying-guidehttp://www.vfds.com/vfd-buying-guide
  • 7/27/2019 How To Read A Motor Nameplate.docx

    4/8

    The service factor is expressed as a decimal. If you do not see a service factor rating on the motor nameplate the service factor is typically1.00. Additionally, all motors running on a VFD (even at 60 HZ) will lose service factor and be rated at 1.00. Please consult your manualfor more information.

    You can dramatically reduce the life of your motor by consistently running into the service factor rating.

    Frequency

    Frequency is the duration peak to peak of an AC sine wave (60 HZ = 60 cycles per second). Frequency is directly related to the motorsspeed.

    In North America, the standard frequency is typically 60 HZ. Outside North America 50 HZ is often the standard. Some nameplates willhave multiple frequency ratings.

    Code

    AC motors that are started at full voltage will draw a greater current (amps) than during normal operations. This is commonly referred to asinrush current or starting current. These codes represent a range of inrush current.

    Code Letter KVA/HP Approximate Mid-Range Value*

    A 0.00-3.14 1.6

    B 3.15-3.54 3.3C 3.55-3.99 3.8

    D 4.00-4.49 4.3

    E 4.50-4.99 4.7

    F 5.00-5.59 5.3

    G 5.60-6.29 5.9

    H 6.30-7.09 6.7

    J 7.10-7.99 7.5

  • 7/27/2019 How To Read A Motor Nameplate.docx

    5/8

    K 8.00-8.99 8.5

    L 9.00-9.99 9.5

    M 10.00-11.19 10.6

    N 11.20-12.49 11.8

    P 12.50-13.99 13.2

    R 14.00-15.99 15.0

    *To find approximate inrush current for your motor match the code letter on your motor nameplate with the corresponding approximatemid-range value on the chart; multiply the mid-range value and the full load amp rating on your motor nameplate.

    Efficiency

    A motors efficiency rating measures how well the motor converts electrical energy (input) into mechanical energy (output). This is usuallydisplayed as a decimal.

    A motors energy consumption is by far its largest operating expense. As a general rule, a motor that runs 24/7/365 for one year could costthree times more than the purchase price in power consumption. In many applications a VFD can provide considerable savings withregards to operational costs. Centrifugal pumps often have great potential for energy savings. Under some circumstances using a VFD toreduce speed by 20% can result in energy savings of 50%. However, energy savings will vary based upon several factors, such as motorconditions, application, and energy costs in your area.

    Insulation

    The insulation class describes a motors ability to withstand temperatures over time. B, F, and H are commonly used insulation types.Letters occurring later in the alphabet represent insulation that is better able to withstand temperature. So class F can withstandtemperature better than a class B.

    Motor insulation systems that are rated for inverter use will be specified on the motor nameplate (or a sticker). These systems should havewire rated for a minimum of 1600 volt spikes, F or H class insulation, and will be processed with 100% sold resin in a vacuum pressureimpregnation (VPI) system.

    Motors that do not fit this specification can be rewound to meet these requirements.

  • 7/27/2019 How To Read A Motor Nameplate.docx

    6/8

    CT/VT

    CT stands for Constant Torque and VT stands for Variable Torque. If these ratings are on your motor nameplate it typically means yourmotor is rated for inverter use. Consult your manual for more information.

    Duty

    Duty is the length of time a motor can run without a cooling period. Most industrial motors are rated for continuous duty.

    Frame Size

    NEMA frame size outlines motor footprint and shaft dimensions. The first two numbers represent the shaft height from the mounting base.This number divided by four represents the shaft height in inches. The third number is the bolt mounting hole dimensions, some motorsmay have multiple holes for different mounting options.

    The letter is the type of frame, each type is provided below:

    Fractional type motors (frame size 48 and 56)

    C Face mounting (can be round body or footed)

    G Gasoline pump motor

    H Indicates a frame with a larger F dimension

    J Jet pump motor

    Y Special mounting dimensions

    Z All mounting dimensions are standard except shaft extension and or design

    Integral type motors (frame size 143 to 449)

    A DC motor or generator

    C Face mounting (can be round body or footed)

  • 7/27/2019 How To Read A Motor Nameplate.docx

    7/8

    D Flange mounting (can be round body or footed)

    P Vertical hollow and solid shaft with P-base flange

    HP Vertical solid shaft with P-base flange, normal thrust

    JMClosed coupled pump motor with C-face mounting and special shaftextensions

    JPClosed coupled pump motor with C-face mounting and special long shaftextensions

    LP Vertical sold shaft with P- base flange, medium thrust

    S Standard short shaft

    T Standardized shaft (1964 and newer)

    U Standardized shaft (1964 and older)

    V Vertical mounting

    Y Special mounting dimensions

    Z All mounting dimension are standard except shaft extension

    Enclosure Type

    The enclosure type displays information about how well the motor is protected from the environment. The most common enclosure typesare Open Drip-Proof (ODP) and Totally Enclosed Fan Cooled (TEFC).

    ODP An Open Drip-Proof motor is an open enclosure that allows air to flow freely inside around the windings. It is protected from dropsof liquid falling downward from a 0 to 15 degree angle, but is not waterproof.

    TEFC A Totally Enclosed Fan Cooled enclosure prevents air from flowing freely into the motor. The motor is cooled by a fan that blowsair on the outside of the enclosure. A TEFC is not fully air or water tight. Outside contaminants can enter the motor, but this typicallydoesnt interfere with normal operations.

    There are several other enclosure types not listed here.

  • 7/27/2019 How To Read A Motor Nameplate.docx

    8/8

    Bearings

    Your motor nameplate may include bearing information.

    There may be two bearing specifications on a motor nameplate, the drive shaft bearing and the opposite drive shaft bearing. The differentbetween these two are location in the motor. The drive shaft bearing is located close to where the drive shaft extends out of the motor.

    The opposite drive shaft bearing is on the opposite side of the drive shaft.

    Every manufacturer has their own way of displaying bearing information and this can vary widely between manufacturers.

    Consult your manufacturer for more information about bearings.

    Voltage Connection (Strapping) Diagrams

    Connection diagrams display information about connecting your motor to the proper voltage. Some motors are designed to handle multiplevoltages, so there may be more than one diagram.

    Note:Carefully select the correct diagram. Incorrectly connecting wiring will damage your motor.

    Model Number and Serial Number

    The serial number and model number are used to identify the equipment with the manufacturer.