24
03/10 506374−01 *2P0310* *P506374-01* Page 1 E2010 Lennox Industries Inc. Dallas, Texas, USA RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency. IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance. IMPORTANT This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed. WARNING Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes. Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. INSTALLATION INSTRUCTIONS Merit ® Series 13ACX Units AIR CONDITIONER 506374−01 03/10 Supersedes 11/09 TABLE OF CONTENTS Shipping and Packing List 1 . . . . . . . . . . . . . . . . . . . . . . . . General 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Dimensions 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Unit Parts Arrangement 2 . . . . . . . . . . . . . . . . . . . Model Number Identification 3 . . . . . . . . . . . . . . . . . . . . . . General Information 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Gauge Set and Service Valves 3 . . . . . . . . . . . Recovering Refrigerant from Existing System 5 . . . . . . . New Outdoor Unit Placement 6 . . . . . . . . . . . . . . . . . . . . . New or Replacement Line Set 6 . . . . . . . . . . . . . . . . . . . . . Metering Devices and Flushing the System 10 . . . . . . . . Testing for Leaks 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Evacuating the System 13 . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Connections 14 . . . . . . . . . . . . . . . . . . . . . . . . . . Servicing Unit Delivered Void of Charge 16 . . . . . . . . . . . Unit Start−Up 16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Refrigerant 16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing and Installing Louvers 22 . . . . . . . . . . . . . . . . . System Operation 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Start−Up and Performance Checklist 24 . . . . . . . . . . . . . . Shipping and Packing List Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier. 1 ɦ Assembled outdoor unit 1 ɦ Refrigerant flow control kit (Fixed Orifice) 1 ɦ Liquid line filter drier General 13ACX, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox 13ACX Engineering Handbook. This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices: S Thermal expansion valve (TXV) S Fixed orifice Litho U.S.A.

INSTALLATION INSTRUCTIONS · 2017. 4. 13. · 03/10 506374−01 Page 1 2010 Lennox Industries Inc. Dallas, Texas, USA RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • 03/10 506374−01

    �������� ����������Page 1

    �2010 Lennox Industries Inc.Dallas, Texas, USA

    RETAIN THESE INSTRUCTIONSFOR FUTURE REFERENCE

    WARNINGImproper installation, adjustment, alteration, service ormaintenance can cause personal injury, loss of life, ordamage to property.

    Installation and service must be performed by a licensedprofessional installer (or equivalent) or a service agency.

    IMPORTANTThe Clean Air Act of 1990 bans the intentional venting ofrefrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.Approved methods of recovery, recycling or reclaimingmust be followed. Fines and/or incarceration may belevied for noncompliance.

    IMPORTANTThis unit must be matched with an indoor coil asspecified in Lennox Engineering Handbook. Coilspreviously charged with HCFC−22 must be flushed.

    WARNINGElectric Shock Hazard. Can cause injuryor death. Unit must be grounded inaccordance with national and localcodes.

    Line voltage is present at all componentswhen unit is not in operation on units withsingle-pole contactors. Disconnect allremote electric power supplies beforeopening access panel. Unit may havemultiple power supplies.

    INSTALLATIONINSTRUCTIONS

    Merit® Series 13ACX Units

    AIR CONDITIONER506374−01 03/10Supersedes 11/09

    TABLE OF CONTENTS

    Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .

    General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Typical Unit Parts Arrangement 2. . . . . . . . . . . . . . . . . . .

    Model Number Identification 3. . . . . . . . . . . . . . . . . . . . . .

    General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Operating Gauge Set and Service Valves 3. . . . . . . . . . .

    Recovering Refrigerant from Existing System 5. . . . . . .

    New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . . . .

    New or Replacement Line Set 6. . . . . . . . . . . . . . . . . . . . .

    Metering Devices and Flushing the System 10. . . . . . . .

    Testing for Leaks 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Evacuating the System 13. . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Connections 14. . . . . . . . . . . . . . . . . . . . . . . . . .

    Servicing Unit Delivered Void of Charge 16. . . . . . . . . . .

    Unit Start−Up 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    System Refrigerant 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Removing and Installing Louvers 22. . . . . . . . . . . . . . . . .

    System Operation 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Start−Up and Performance Checklist 24. . . . . . . . . . . . . .

    Shipping and Packing List

    Check the unit for shipping damage and listed times beloware intact. If damaged, or if parts are missing, immediatelycontact the last shipping carrier.

    1 � Assembled outdoor unit

    1 � Refrigerant flow control kit (Fixed Orifice)

    1 � Liquid line filter drier

    General

    13ACX, which will also be referred to in this instruction asthe outdoor unit, uses HFC−410A refrigerant. This outdoorunit must be installed with a matching indoor unit and lineset as outlined in the Lennox 13ACX EngineeringHandbook.

    This outdoor unit is designed for use in systems that useone of the following refrigerant metering devices:

    � Thermal expansion valve (TXV)

    � Fixed orifice

    Litho U.S.A.

  • Page 2

    506374−01 03/10

    Unit Dimensions − Inches (mm)

    SIDE VIEW

    SUCTION AND LIQUIDLINE CONNECTION

    DISCHARGE AIR

    SIDE VIEW

    OUTDOORCOIL FAN

    COMPRESSOR

    A

    B

    A

    OPTIONAL UNITSTANDOFF KIT (4)

    (FIELD INSTALLED)

    Model Numbers A B

    −018 24−1/4 (616) 25−1/4 (641)

    −024 24−1/4 (616) 25−1/4 (641)

    −030 24−1/4 (616) 29−1/4 (743)

    −036 24−1/4 (616) 29−1/4 (743)

    −042 28−1/4 (724) 29−1/4 (743)

    −048 28−1/4 (724) 37−1/4 (925)

    −060 28−1/4 (724) 33−1/4 (845)

    Typical Unit Parts Arrangement

    COMPRESSORHARNESS

    LIQUID LINE SERVICE VALVE SUCTION LINE SERVICE VALVE

    OUTDOOR COIL

    DISCHARGE LINE

    HIGH PRESSURESWITCH (S4)

    COMPRESS0R

    GROUND LUG

    CONTACTOR

    CONTROL

    CAPACITOR

    CONTROL WIRELOOP

    CUTOUT FOR HIGHVOLTAGE CONDUIT

    NOTE � PLUMBING LAYOUT AND COMPRESSOR TYPE MAY VARY SLIGHTLY BETWEENMODEL SIZES.

  • Page 3

    13ACX SERIES

    Model Number Identification

    AC X13 024 −

    Unit TypeAC = Air Conditioner

    RefrigerantX = R−410A

    Cooling Capacity − Tons

    018 = 1.5024 = 2030 = 2.5036 = 3042 = 3.5048 = 4060 = 5

    Minor Revision NumberNominal SEER

    2

    Voltage230 = 208/230V−1phase−60hz

    230−−

    WARNINGThis product and/or the indoor unit it is matched with maycontain fiberglass wool.

    Disturbing the insulation during installation,maintenance, or repair will expose you to fiberglass wooldust. Breathing this may cause lung cancer. (Fiberglasswool is known to the State of California to cause cancer.)

    Fiberglass wool may also cause respiratory, skin, andeye irritation.

    To reduce exposure to this substance or for furtherinformation, consult material safety data sheetsavailable from address shown below, or contact yoursupervisor.

    Lennox Industries Inc.P.O. Box 799900Dallas, TX 75379−9900

    CAUTIONPhysical contact with metal edges and corners whileapplying excessive force or rapid motion can result inpersonal injury. Be aware of, and use caution whenworking near these areas during installation or whileservicing this equipment.

    General Information

    These instructions are intended as a general guide and donot supersede local codes in any way. Consult authoritieswho have jurisdiction before installation.

    Operating Gauge Set and Service Valves

    These instructions are intended as a general guide and donot supersede local codes in any way. Consult authoritieswho have jurisdiction before installation.

    TORQUE REQUIREMENTS

    When servicing or repairing heating, ventilating, and airconditioning components, ensure the fasteners areappropriately tightened. Table 1 lists torque values forfasteners.

    IMPORTANTOnly use Allen wrenches of sufficient hardness (50Rc −Rockwell Harness Scale minimum). Fully insert thewrench into the valve stem recess.

    Service valve stems are factory−torqued (from 9 ft−lbs forsmall valves, to 25 ft−lbs for large valves) to preventrefrigerant loss during shipping and handling. Using anAllen wrench rated at less than 50Rc risks rounding orbreaking off the wrench, or stripping the valve stemrecess.

    See the Lennox Service and Application Notes #C−08−1for further details and information.

    IMPORTANTTo prevent stripping of the various caps used, theappropriately sized wrench should be used and fittedsnugly over the cap before tightening.

    When servicing or repairing HVAC components, ensurethe fasteners are appropriately tightened. Table 1 providestorque values for fasteners.

    Table 1. Torque Requirements

    Parts Recommended Torque

    Service valve cap 8 ft.− lb. 11 NM

    Sheet metal screws 16 in.− lb. 2 NM

    Machine screws #10 28 in.− lb. 3 NM

    Compressor bolts 90 in.− lb. 10 NM

    Gauge port seal cap 8 ft.− lb. 11 NM

    USING MANIFOLD GAUGE SET

    When checking the system charge, only use a manifoldgauge set that features low loss anti−blow back fittings.

    Manifold gauge set used with HFC−410A refrigerantsystems must be capable of handling the higher systemoperating pressures. The gauges should be rated for usewith pressures of 0 − 800 psig on the high side and a lowside of 30" vacuum to 250 psig with dampened speed to500 psi. Gauge hoses must be rated for use at up to 800psig of pressure with a 4000 psig burst rating.

  • Page 4

    506374−01 03/10

    OPERATING SERVICE VALVES

    The liquid and vapor line service valves are used forremoving refrigerant, flushing, leak testing, evacuating,checking charge and charging.

    Each valve is equipped with a service port which has afactory−installed valve stem. Figure 1 provides informationon how to access and operating both angle and ball servicevalves.

    (VALVE STEM SHOWNCLOSED) INSERT HEXWRENCH HERE

    VALVE STEMFRONT-SEATED

    TO OUTDOORUNIT

    SERVICE PORTCORE

    TO INDOORUNIT

    SERVICE PORT

    SERVICE PORT CAP

    CLOSED TO BOTHINDOOR AND OUTDOOR

    UNITS

    STEM CAP

    ANGLE−TYPESERVICE VALVE(FRONT−SEATED

    CLOSED)

    SERVICE PORTSERVICE PORT

    CORE

    TO OUTDOOR UNIT

    STEM CAP

    (VALVE STEMSHOWN OPEN)INSERT HEXWRENCH HERE

    SERVICE PORT CAP

    TO INDOORUNIT

    OPEN TO BOTH INDOOR ANDOUTDOOR UNITS

    ANGLE−TYPE SERVICE VALVE(BACK−SEATED OPENED)

    BALL (SHOWN CLOSED)

    SERVICE PORT CORE

    TO INDOOR UNIT

    TO OUTDOOR UNIT

    TO OPEN ROTATE STEMCOUNTERCLOCKWISE 90°.

    TO CLOSE ROTATE STEMCLOCKWISE 90°.

    SERVICE PORT

    SERVICE PORT CAP

    STEM CAP

    VALVE STEM

    WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN TO THELINE SET AND INDOOR UNIT.

    BALL−TYPE SERVICEVALVE

    SERVICE VALVESVARIOUS TYPES

    WHEN SERVICE VALVE IS OPEN, THE SERVICE PORT IS OPEN TO LINE SET,INDOOR AND OUTDOOR UNIT.

    To Access Service Port:

    A service port cap protects the service port core from contamination andserves as the primary leak seal.

    1. Remove service port cap with an appropriately sized wrench.

    2. Connect gauge set to service port.

    3. When testing is completed, replace service port cap and tighten as fol-lows:

    123

    4567

    8910

    11 12

    1/6 TURN

    Operating Angle Type Service Valve:

    1. Remove stem cap with an appropriately sized wrench.

    2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valvesizes) to back the stem out counterclockwise as far as it will go.

    Operating Ball Type Service Valve:

    1. Remove stem cap with an appropriately sized wrench.

    2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.

    Reinstall Stem Cap:

    Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap andtighten as follows:

    � With Torque Wrench: Finger tighten and then torque cap per Table 1.

    � Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turnan additional 1/12 turn clockwise.

    NOTE � A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.

    123

    4567

    8910

    11 12

    1/6 TURN

    � With Torque Wrench: Finger tighten and torque cap per Table 1.

    � Without Torque Wrench: Finger tighten and use an appropriatelysized wrench to turn an additional 1/6 turn clockwise.

    Figure 1. Angle and Ball Service Valves

  • Page 5

    13ACX SERIES

    Recovering Refrigerant from Existing System

    SERVICEDISCONNECT

    SWITCH

    MAIN FUSE BOX/BREAKER PANEL

    Disconnect all power to the existing outdoor unit at the servicedisconnect switch or main fuse box/breaker panel.

    DISCONNECT POWER CONNECT MANIFOLD GAUGE SET

    MANIFOLD GAUGES

    RECOVERY MACHINE

    CLEAN RECOVERYCYLINDER

    OUTDOOR UNIT

    HIGHLOW

    Connect a gauge set, clean recovery cylinder and a recoverymachine to the service ports of the existing unit. Use theinstructions provided with the recovery machine to make theconnections.

    METHOD 1:Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existingHCFC−22 to flush the system.

    Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void ofrefrigerant.

    METHOD 2:Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush thesystem.

    The following devices could prevent full system charge recovery into the outdoor unit:

    � Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.

    � Compressor can stop pumping due to tripped internal pressure relief valve.

    � Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meetsa certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum.Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings andinternal seals.)

    Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the

    main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.

    Perform the following task:

    A. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.

    B. Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unitmain power OFF and use a recovery machine to remove the remaining refrigerant from the system.

    NOTE � It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.

    C. When the low side system pressures reach 0 psig, close the vapor line valve.

    D. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.

    RECOVERINGREFRIGERANT FROM SYSTEM

    Remove existing HCFC−22 refrigerant using one of the following procedures:

    RECOVERING REFRIGERANT

    IMPORTANT � Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,and/or long line sets.

    1 2

    3

  • Page 6

    506374−01 03/10

    New Outdoor Unit Placement

    See Unit Dimensions on Page 2 for sizing mounting slab,platforms or supports. Refer to Figure 2 for mandatoryinstallation clearance requirements.

    *

    * *

    *

    NOTES:

    � Service panel access clearance of 30 in. (762 mm) must bemaintained.

    � Clearance to one of the other three sides must be 36 in. (914mm).

    � Clearance on one of the remaining two sides may be 12 in. (305mm) and the final side may be 6 in. (152 mm).

    � Clearance required on top of unit is 48 in. (1219 mm).

    � A clearance of 24 in. (610 mm) must be maintained between twounits.

    Figure 2. Installation Clearances

    POSITIONING CONSIDERATIONS

    CAUTIONIn order to avoid injury, take proper precaution when lift-ing heavy objects.

    Consider the following when positioning the unit:

    � Some localities are adopting sound ordinances basedon the unit’s sound level registered from the adjacentproperty, not from the installation property. Install the

    unit as far as possible from the property line.

    � When possible, do not install the unit directly outsidea window. Glass has a very high level of soundtransmission. For proper placement of unit in relation

    to a window see the provided illustration in Figure 3.

    INSTALL UNIT AWAYFROM WINDOWS

    TWO 90� ELBOWS INSTALLED IN LINE SETWILL REDUCE LINE SET VIBRATION

    Figure 3. Outside Unit Placement

    PLACING OUTDOOR UNIT ON SLAB

    When installing a unit at grade level, the top of the slabshould be high enough above the grade so that water fromhigher ground would not collect around the unit asillustrated in Figure 4.

    GROUND LEVEL

    MOUNTINGSLAB

    BUILDINGSTRUCTURE

    DISCHARGE AIR

    Figure 4. Typical Slab Mounting at Ground Level

    Slab may be level or have a slope tolerance away from thebuilding of not more than two degrees, or 2 inches per 5feet (51 mm per 1524 mm) as illustrated in Figure 4.

    INSTALLING OUTDOOR UNIT ON ROOF

    Install the unit at a minimum of 4 inches (102 mm) abovethe surface of the roof. Ensure the weight of the unit isproperly distributed over roof joists and rafters. Redwoodor steel supports are recommended.

    New or Replacement Line Set

    This section provides information on installation orreplacement of existing line set. If line set is not beinginstalled or replace then proceed to Brazing Connectionson Page 9.

  • Page 7

    13ACX SERIES

    If refrigerant lines are routed through a wall, seal andisolate the opening so vibration is not transmitted to thebuilding. Pay close attention to line set isolation duringinstallation of any HVAC system. When properly isolatedfrom building structures (walls, ceilings. floors), therefrigerant lines will not create unnecessary vibration andsubsequent sounds.

    Also, consider the following when placing and installing ahigh−efficiency air conditioner:

    REFRIGERANT LINE SET

    Field refrigerant line set consists of liquid and suction linesfrom the outdoor unit to the indoor unit coil. Use LennoxL15 (braze, non−flare) series line set, or field−fabricatedrefrigerant lines that meet the specifications listed below.

    Table 2. Refrigerant Line Set

    Model

    Valve FieldConnections

    Recommended Line Set

    LiquidLine

    SuctionLine

    LiquidLine

    SuctionLine

    L15 LineSet

    −018−024−030

    3/8 in.(10 mm)

    3/4 in.(19 mm)

    3/8 in (10 mm)

    3/4 in.(19 mm)

    L15−4115 ft. − 50 ft.

    (4.6 m − 15 m)

    −036−042−048

    3/8 in.(10 mm)

    7/8 in.(22 mm)

    3/8 in.(10 mm)

    7/8in. (22 mm)

    L15−6515 ft. − 50 ft.

    (4.6 m − 15 m)

    −0603/8 in.

    (10 mm)1−1/8 in.(29 mm)

    3/8 in.(10 mm)

    1−1/8 in.(29 mm)

    FieldFabricated

    NOTE � Some applications may required a field provided 7/8" to1−1/8" adapter

    NOTE − When installing refrigerant lines longer than 50feet, contact Lennox Technical Support ProductApplications for assistance or Lennox piping manual. Toobtain the correct information from Lennox, be sure tocommunicate the following points:

    � Model (13ACX) and size of unit (e.g. −060).

    � Line set diameters for the unit being installed as listedin Table 2 and total length of installation.

    � Number of elbows and if there is a rise or drop of thepiping.

    MATCHING WITH NEW OR EXISTING INDOOR COILAND LINE SET

    The RFC1−metering line consisted of a small bore copperline that ran from condenser to evaporator coil. Refrigerantwas metered into the evaporator by utilizingtemperature/pressure evaporation effects on refrigerant inthe small RFC line. The length and bore of the RFC linecorresponded to the size of cooling unit.

    If the 13ACX is being used with either a new or existingindoor coil which is equipped with a liquid line which servedas a metering device (RFCI), the liquid line must bereplaced prior to the installation of the 13ACX unit.Typically a liquid line used to meter flow is 1/4" in diameterand copper.

    LIQUID LINE FILTER DRIER INSTALLATION

    The filter drier (one is shipped with each 13ACX unit) mustbe field installed in the liquid line between the outdoor unit’sliquid line service valve and the indoor coil’s meteringdevice (fixed orifice or TXV) as illustrated in Figure 5. This

    filter drier must be installed to ensure a clean,moisture−free system. Failure to install the filter drier willvoid the warranty. A replacement filter drier is availablefrom Lennox. See Brazing Connections on Page 9 forspecial procedures on brazing filter drier connections tothe liquid line.

    OUTDOORUNIT

    LIQUID LINESERVICE VALVE

    LIQUID LINEFILTER DRIER

    LINELIQUIDLINE

    BRAZE CONNECTIONPOINTS

    Figure 5. Typical Liquid Line Filter Drier Installation

    CAUTIONBrazing alloys and flux contain materials which arehazardous to your health.

    Avoid breathing vapors or fumes from brazingoperations. Perform operations only in well ventilatedareas.

    Wear gloves and protective goggles or face shield toprotect against burns.

    Wash hands with soap and water after handling brazingalloys and flux.

    IMPORTANTThe Environmental Protection Agency (EPA) prohibitsthe intentional venting of HFC refrigerants duringmaintenance, service, repair and disposal of appliance.Approved methods of recovery, recycling or reclaimingmust be followed.

    IMPORTANTIf this unit is being matched with an approved line setor indoor unit coil which was previously charged withmineral oil, or if it is being matched with a coil whichwas manufactured before January of 1999, the coiland line set must be flushed prior to installation. Takecare to empty all existing traps. Polyol ester (POE) oilsare used in Lennox units charged with HFC−410Arefrigerant. Residual mineral oil can act as aninsulator, preventing proper heat transfer. It can alsoclog the expansion device, and reduce the systemperformance and capacity.Failure to properly flush the system per theinstructions below will void the warranty.

  • Page 8

    506374−01 03/10

    ANCHORED HEAVY NYLONWIRE TIE OR AUTOMOTIVE

    MUFFLER-TYPE HANGER

    STRAP LIQUID LINE TOVAPOR LINE

    WALLSTUD

    LIQUID LINE

    NON−CORROSIVEMETAL SLEEVE

    VAPOR LINE − WRAPPEDIN ARMAFLEX

    AUTOMOTIVEMUFFLER-TYPE HANGER

    REFRIGERANT LINE SET � TRANSITIONFROM VERTICAL TO HORIZONTAL

    Line Set Isolation � The following illustrations areexamples of proper refrigerant line set isolation:

    STRAPPINGMATERIAL (AROUND

    VAPOR LINE ONLY)

    TAPE ORWIRE TIE

    WIRE TIE (AROUNDVAPOR LINE ONLY)

    FLOOR JOIST ORROOF RAFTER

    TAPE ORWIRE TIE

    To hang line set from joist or rafter, use either metal strapping materialor anchored heavy nylon wire ties.

    8 FEET (2.43 METERS)

    STRAP THE VAPOR LINE TO THE JOISTOR RAFTER AT 8 FEET (2.43 METERS)INTERVALS THEN STRAP THE LIQUIDLINE TO THE VAPOR LINE.

    FLOOR JOIST OR

    ROOF RAFTER

    REFRIGERANT LINE SET � INSTALLING HORIZONTAL RUNS

    NOTE � Similar installation practices should be used if line set isto be installed on exterior of outside wall.

    PVCPIPE

    FIBERGLASSINSULATION

    CAULK

    OUTSIDEWALL

    VAPOR LINE WRAPPEDWITH ARMAFLEX

    LIQUIDLINE

    OUTSIDE WALL LIQUID LINEVAPOR LINE

    WOOD BLOCKBETWEEN STUDS

    STRAP

    WOOD BLOCK

    STRAP

    SLEEVE

    WIRE TIE

    WIRE TIE

    WIRE TIE

    INSIDE WALL

    REFRIGERANT LINE SET � INSTALLINGVERTICAL RUNS (NEW CONSTRUCTION SHOWN)

    INSTALLATION

    LINE SET

    NOTE � Insulate liquid line when it is routed through areas where thesurrounding ambient temperature could become higher than thetemperature of the liquid line or when pressure drop is equal to or greaterthan 20 psig.

    NON−CORROSIVEMETAL SLEEVE

    IMPORTANT � Refrigerant lines must not contact structure.

    NON−CORROSIVEMETAL SLEEVE

    8 FEET (2.43 METERS)

    IMPORTANT � Refrigerant lines must not contact wall

    WARNING � Polyol ester (POE) oils used with HFC−410Arefrigerant absorb moisture very quickly. It is very important that therefrigerant system be kept closed as much as possible. DO NOTremove line set caps or service valve stub caps until you are readyto make connections.

    Figure 6. Line Set Installation

  • Page 9

    13ACX SERIES

    CUT AND DEBUR

    CAP AND CORE REMOVAL

    Cut ends of the refrigerant lines square(free from nicks or dents) and debur theends. The pipe must remain round and donot pinch end of the line.

    Remove service cap and corefrom both the vapor and liquid lineservice ports.

    ATTACHED GAUGES

    OUTDOORUNIT

    LIQUID LINE

    VAPOR LINE

    LIQUID LINE SERVICEVALVE

    VAPOR LINESERVICE

    VALVE

    ATTACHGAUGES

    INDOORUNIT

    SERVICE PORT MUST BE OPEN TO ALLOW EXITPOINT FOR NITROGEN

    A. Connect gauge set low pressure side to liquid line servicevalve.

    B. Connect gauge set center port to bottle of nitrogen withregulator.

    NITROGEN

    HIGHLOW

    USE REGULATOR TO FLOWNITROGEN AT 1 TO 2 PSIG.

    WRAP SERVICE VALVE FLOW NITROGEN

    To protect components duringbrazing, wrap a wet cloth aroundthe liquid line service valve bodyand copper tube stub and useanother wet cloth underneath thevalve body to protect the basepaint.

    Flow regulated nitrogen (at 1 to 2 psig) through the refrigerationgauge set into the valve stem port connection on the liquid line servicevalve and out of the valve stem port connection on the vapor servicevalve.

    NOTE � The fixed orifice or checkexpansion valve metering device at theindoor unit will allow low pressurenitrogen to flow through the system.

    NIT

    RO

    GE

    N

    HIGHLOW

    USE REGULATOR TOFLOW NITROGEN AT 1

    TO 2 PSIG.

    BRAZE LINE SET

    INSTALL SERVICE PORT CAPS ONLY

    Braze the liquid line to the liquid lineservice valve. Turn off nitrogen flow.

    After all connections have been brazed, disconnect manifold gaugeset from service ports, cool down piping with wet rag and remove allwrappings. Do not reinstall cores until after evacuation procedure.Reinstall service port caps if desired to close off refrigerant ports.

    IMPORTANT � Connect gauge set low pressure side to vaporline service valve and repeat procedure starting at paragraph 4for brazing the liquid line to service port valve.

    SERVICE PORT CORE

    SERVICE PORT CAPSERVICE PORT

    WARNING � Allow braze joint to coolbefore removing the wet rag from theservice valve. (TEMPERATURES ABOVE250ºF CAN DAMAGE VALVE SEALS

    CONNECTIONS

    BRAZING

    12

    3

    4 5

    6

    7

    B

    A

    POINT FLAME AWAY FROMSERVICE VALVE

    NOTE − Use silver alloy brazing rods with five or six percent minimum silveralloy for copper−to−copper brazing, 45 percent alloy for copper−to−brass andcopper−to−steel brazing.

    Figure 7. Brazing Connections

  • Page 10

    506374−01 03/10

    Metering Devices and Flushing the System

    SENSINGLINE

    TEFLON RING

    FIXED ORIFICE

    (Uncased Coil Shown)

    BRASS NUT

    LIQUID LINE ASSEMBLY(INCLUDES STRAINER)

    LIQUID LINE ORIFICE HOUSING

    DISTRIBUTOR TUBES

    DISTRIBUTORASSEMBLY

    REMOVE AND DISCARDWHITE TEFLON SEAL (IF

    PRESENT)

    A. On fully cased coils, remove the coil access and plumbing panels.

    B. Remove any shipping clamps holding the liquid line and distributorassembly.

    C. Using two wrenches, disconnect liquid line from liquid line orificehousing. Take care not to twist or damage distributor tubes duringthis process.

    D. Remove and discard fixed orifice, valve stem assembly if presentand Teflon washer as illustrated above.

    E. Use a field−provided fitting to temporary reconnect the liquid line tothe indoor unit’s liquid line orifice housing.

    F. Reverse above order to install.

    TYPICAL CHECK EXPANSION VALVEREMOVAL PROCEDURE

    TWO PIECE PATCH PLATE(UNCASED COIL ONLY)

    VAPORLINE

    DISTRIBUTORASSEMBLY

    DISTRIBUTORTUBES

    LIQUIDLINE

    MALE EQUALIZERLINE FITTING

    EQUALIZERLINE

    CHECKEXPANSION

    VALVE

    TEFLONRING

    (Uncased Coil Shown)STUB END

    TEFLONRING

    SENSING BULB

    LIQUID LINEORIFICE

    HOUSING

    LIQUID LINEASSEMBLY WITH

    BRASS NUT

    A. On fully cased coils, remove the coil access and plumbing panels.

    B. Remove any shipping clamps holding the liquid line and distributor as-sembly.

    C. Disconnect the equalizer line from the check expansion valve equaliz-er line fitting on the vapor line.

    D. Remove the vapor line sensing bulb.

    E. Disconnect the liquid line from the check expansion valve at the liquidline assembly.

    F. Disconnect the check expansion valve from the liquid line orifice hous-ing. Take care not to twist or damage distributor tubes during this pro-cess.

    G. Remove and discard check expansion valve and the two Teflon rings.

    H. Use a field−provided fitting to temporary reconnect the liquid line to theindoor unit’s liquid line orifice housing.

    LOW HIGH

    EXISTINGINDOOR

    UNIT

    GAUGEMANIFOLD

    INVERTED HCFC−22CYLINDER CONTAINSCLEAN HCFC−22 TO BEUSED FOR FLUSHING.

    LIQUID LINE SERVICEVALVE

    INLET

    DISCHARGE

    TANKRETURN

    CLOSEDOPENED

    RECOVERYCYLINDER

    RECOVERY MACHINE

    NEWOUTDOOR

    UNIT

    VAPOR LINESERVICE VALVE

    VA

    PO

    R

    LIQ

    UID

    1

    A. Inverted HCFC−22 cylinder with clean refrigerant to the vapor servicevalve.

    B. HCFC−22 gauge set (low side) to the liquid line valve.

    C. HCFC−22 gauge set center port to inlet on the recovery machine withan empty recovery tank to the gauge set.

    D. Connect recovery tank to recovery machines per machineinstructions.

    CONNECT GAUGES AND EQUIPMENT FORFLUSHING PROCEDURE

    A

    B

    CD

    B

    OR

    FLUSHING LINE SET

    A. Set the recovery machine for liquid recovery and start the recov-ery machine. Open the gauge set valves to allow the recoverymachine to pull a vacuum on the existing system line set and in-door unit coil.

    B. Invert the cylinder of clean HCFC−22 and open its valve to allowliquid refrigerant to flow into the system through the vapor linevalve. Allow the refrigerant to pass from the cylinder and throughthe line set and the indoor unit coil before it enters the recoverymachine.

    C. After all of the liquid refrigerant has been recovered, switch therecovery machine to vapor recovery so that all of the HCFC−22vapor is recovered. Allow the recovery machine to pull down to 0the system.

    D. Close the valve on the inverted HCFC−22 drum and the gaugeset valves. Pump the remaining refrigerant out of the recoverymachine and turn the machine off.

    The line set and indoor unit coil must be flushed with at least thesame amount of clean refrigerant that previously charged the sys-tem. Check the charge in the flushing cylinder before proceeding.

    LINE SET AND INDOOR COIL (1 OF 2)

    FLUSHING

    1

    2

    3

    CAUTION �This procedure should not be performed on sys-tems which contain contaminants (Example compressor burnout.

    TYPICAL FIXED ORIFICE REMOVAL ANDREPLACEMENT PROCEDURE

  • Page 11

    13ACX SERIES

    A. Attach the vapor line sensing bulb in the proper orientationas illustrated to the right using the clamp and screws pro-vided.

    NOTE � Confirm proper thermal contact between vapor lineand check expansion bulb before insulating the sensing bulbonce installed.

    B. Connect the equalizer line from thecheck expansion valve to theequalizer vapor port on the vaporline. Finger tighten the flare nutplus 1/8 turn (7 ft−lbs) as illus-trated below.

    The check expansion valve unit can be installed internal orexternal to the indoor coil. In applications where an uncased coilis being installed in a field−provided plenum, install the checkexpansion valve in a manner that will provide access for fieldservicing of the check expansion valve. Refer to belowillustration for reference during installation of check expansionvalve unit.

    TYPICAL CHECK EXPANSION VALVE INSTALLATION PROCEDURE

    TWO PIECEPATCH PLATE

    (UNCASEDCOIL ONLY)

    VAPORLINE

    LIQUID LINEORIFICE

    HOUSINGDISTRIBUTOR

    TUBES

    LIQUID LINE

    MALE EQUALIZER LINEFITTING (SEE

    EQUALIZER LINEINSTALLATION FORFURTHER DETAILS)

    SENSINGLINE

    EQUALIZERLINE

    CHECKEXPANSION

    VALVE

    TEFLONRING

    (Uncased Coil Shown)

    SENSING BULB INSULATION IS REQUIREDIF MOUNTED EXTERNAL TO THE COILCASING. SENSING BULB INSTALLATIONFOR BULB POSITIONING.

    STUBEND

    TEFLONRING

    LIQUID LINEASSEMBLY WITH

    BRASS NUT

    DISTRIBUTORASSEMBLY

    This outdoor unit is designed for use in systems that use check expansion valve metering device. See the Lennox 13ACX Engineering Handbookfor approved check expansion valve kit match−ups and application information.

    A. Remove the field−provided fitting that temporary reconnected the liquidline to the indoor unit’s distributor assembly.

    B. Install one of the provided Teflon rings around the stubbed end of thecheck expansion valve and lightly lubricate the connector threads andexpose surface of the Teflon ring with refrigerant oil.

    C. Attach the stubbed end of the check expansion valve to the liquid lineorifice housing. Finger tighten and use an appropriately sized wrench toturn an additional 1/2 turn clockwise as illustrated in the figure above, or20 ft−lb.

    D. Place the remaining Teflon washer around the other end of the checkexpansion valve. Lightly lubricate connector threads and expose sur-face of the Teflon ring with refrigerant oil.

    E. Attach the liquid line assembly to the check expansion valve. Fingertighten and use an appropriately sized wrench to turn an additional 1/2turn clockwise as illustrated in the figure above or 20 ft−lb.

    ON 7/8" AND LARGER LINES,MOUNT SENSING BULB ATEITHER THE 4 OR 8 O’CLOCKPOSITION. NEVER MOUNT ONBOTTOM OF LINE.

    12

    ON LINES SMALLER THAN 7/8",MOUNT SENSING BULB ATEITHER THE 3 OR 9 O’CLOCKPOSITION.

    12

    BULB

    VAPOR LINE

    VAPOR LINE

    NOTE � NEVER MOUNT ON BOTTOM OF LINE.

    BULB

    BULBBULB

    VAPOR LINE

    FLARE NUT

    COPPER FLARESEAL BONNET

    MALE BRASS EQUALIZERLINE FITTING

    FLARE SEAL CAP

    OR

    123

    4567

    8910

    11 121/2 TURN

    SENSING BULB INSTALLATION

    EQUALIZER LINE INSTALLATION

    123

    45

    678

    910

    11 12

    1/8 TURN

    FLUSHING LINE SET AND INDOOR COIL (2 OF 2)

    4

    A. Remove and discard either the flare seal cap or flare nutwith copper flare seal bonnet from the equalizer line porton the vapor line as illustrated in the figure to the right.

    B. Remove and discard either the flare seal cap or flare nutwith copper flare seal bonnet from the equalizer line port onthe vapor line as illustrated in the figure to the right.

  • Page 12

    506374−01 03/10

    Leak Testing the System

    TO VAPORSERVICE VALVE

    HFC−410A

    MANIFOLD GAUGE SET

    OUTDOOR UNIT

    HIGHLOW

    NITROGEN

    NOTE � Normally, the high pressure hose is connected to the liquid line port. How-ever, connecting it to the vapor port better protects the manifold gauge set from highpressure damage.

    A. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Openthe valve on the HFC−410A cylinder (vapor only).

    B. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount ofHFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve onthe HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.

    C. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

    D. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize theline set and the indoor unit.

    E. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurablewith a leak detector.

    F. After leak testing disconnect gauges from service ports.

    USE REGULATOR TO FLOWNITROGEN AT 1 TO 2 PSIG.

    LINE SET AND INDOOR COIL

    After the line set has been connected to the indoor unit and air conditioner, check the line set connections andindoor unit for leaks. Use the following procedure to test for leaks:

    LEAK TEST

    A. Connect an HFC−410A manifold gauge set highpressure hose to the vapor valve service port.

    B. With both manifold valves closed, connect thecylinder of HFC−410A refrigerant to the center portof the manifold gauge set.

    1CONNECT GAUGE SET

    2TEST FOR LEAKS

    AB

    NOTE � Later in the procedure, the HFC−410Acontainer will be replaced by the nitrogen container.

    WARNINGWhen using a high pressure gas such asdry nitrogen to pressurize a refrigerationor air conditioning system, use aregulator that can control the pressuredown to 1 or 2 psig (6.9 to 13.8 kPa).

    WARNINGRefrigerant can be harmful if it is inhaled. Refrigerantmust be used and recovered responsibly.

    Failure to follow this warning may result in personal injuryor death.

    WARNINGFire, Explosion and Personal SafetyHazard.

    Failure to follow this warning couldresult in damage, personal injury ordeath.

    Never use oxygen to pressurize orpurge refrigeration lines. Oxygen,when exposed to a spark or openflame, can cause damage by fireand/or an explosion, that could resultin personal injury or death.

    IMPORTANTLeak detector must be capable of sensing HFCrefrigerant.

  • Page 13

    13ACX SERIES

    Evacuating the System

    A. Open both manifold valves and start the vacuum pump.

    B. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).

    NOTE � During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressureindicates a relatively large leak. If this occurs, repeat the leak testing procedure.

    NOTE � The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero ofpressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

    C. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuumpump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogencylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum inthe line set and indoor unit. Close the manifold gauge valves.

    D. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release thedry nitrogen from the line set and indoor unit.

    E. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until theabsolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pumpand closing the manifold gauge valves.

    F. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it toan upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set andindoor unit.

    G. Perform the following:

    OUTDOOR

    UNIT

    TO VAPORSERVICE VALVE

    TO LIQUID LINESERVICE VALVE

    MICRONGAUGE

    VACUUM PUMP

    A34000 1/4 SAE TEE WITHSWIVEL COUPLER

    500

    MANIFOLDGAUGE SET

    HFC−410A

    RECOMMENDMINIMUM 3/8" HOSE

    A. Connect low side of manifold gaugeset with 1/4 SAE in−line tee to vapor lineservice valve

    B. Connect high side of manifold gaugeset to liquid line service valve

    C. Connect micron gauge availableconnector on the 1/4 SAE in−line tee.

    D. Connect the vacuum pump (withvacuum gauge) to the center port of themanifold gauge set. The center port linewill be used later for both the HFC−410Aand nitrogen containers.

    HIGHLOW

    123

    45

    678

    910

    11 12

    1/6 TURN

    NITROGEN

    USE REGULATOR TO FLOWNITROGEN AT 1 TO 2 PSIG.

    EVACUATING

    1CONNECT GAUGE SET

    A

    B

    C

    D

    2EVACUATE THE SYSTEM

    � Close manifold gauge valves.

    � Shut off HFC−410A cylinder.

    � Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores withcore tool while maintaining a positive system pressure.

    � Replace the stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn asillustrated.

    LINE SET AND INDOOR COIL

    NOTE � Remove cores from service valves (if not al-ready done).

  • Page 14

    506374−01 03/10

    IMPORTANTUse a thermocouple or thermistor electronic vacuumgauge that is calibrated in microns. Use an instrumentcapable of accurately measuring down to 50 microns.

    WARNINGDanger of Equipment Damage. Avoid deep vacuumoperation. Do not use compressors to evacuate asystem. Extremely low vacuums can cause internalarcing and compressor failure. Damage caused bydeep vacuum operation will void warranty.

    Evacuating the system of non−condensables is critical forproper operation of the unit. Non−condensables are

    defined as any gas that will not condense undertemperatures and pressures present during operation ofan air conditioning system. Non−condensables and watersuction combine with refrigerant to produce substancesthat corrode copper piping and compressor parts.

    Electrical

    In the U.S.A., wiring must conform with current local codesand the current National Electric Code (NEC). In Canada,wiring must conform with current local codes and the currentCanadian Electrical Code (CEC).

    Refer to the furnace or air handler installation instructionsfor additional wiring application diagrams and refer to unitnameplate for minimum circuit ampacity and maximumovercurrent protection size.

    24VAC TRANSFORMER

    Use the transformer provided with the furnace or airhandler for low-voltage control power (24VAC − 40 VAminimum)

    Refer to the unit nameplate for minimum circuit ampacity, and maximumfuse or circuit breaker (HACR per NEC). Install power wiring and properlysized disconnect switch.

    NOTE � Units are approved for use only with copper conductors.Ground unit at disconnect switch or to an earth ground.

    SIZE CIRCUIT AND INSTALL SERVICEDISCONNECT SWITCH

    NOTE � 24VAC, Class II circuit connections are made in the controlpanel.

    Install room thermostat (ordered separately) on an inside wallapproximately in the center of the conditioned area and 5 feet (1.5m) fromthe floor. It should not be installed on an outside wall or where it can beaffected by sunlight or drafts.

    THERMOSTAT

    5 FEET(1.5M)

    INSTALL THERMOSTAT

    SERVICEDISCONNECT

    SWITCH

    MAIN FUSE BOX/BREAKER PANEL

    WARNINGElectric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national andlocal codes.

    Line voltage is present at all components when unit is not in operation on units with single-pole contactors.Disconnect all remote electric power supplies before opening access panel. Unit may have multiple powersupplies.

  • Page 15

    13ACX SERIES

    Any excess high voltage field wiring should be trimmed andsecured away from any low voltage field wiring. To facilitate aconduit, a cutout is located in the bottom of the control panel.Connect conduit to the control panel using a proper conduit fitting.

    ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING

    HIGH VOLTAGEFIELD WIRING

    LOW VOLTAGEFIELD WIRING

    FACTORYWIRING

    WIRE RUN LENGTH AWG# INSULATION TYPE

    LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING

    MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.

    Install low voltage wiring from outdoor to indoor unit and from thermostatto indoor unit as illustrated.

    HIGH VOLTAGE / GROUND WIRES

    CONTROL WIRING

    A. Run 24VAC control wires through hole with grommet and secure withprovided wire tie.

    B. Make 24VAC thermostat wire connections. Locate the two wires from thecontactor and make connection using field provided wire nuts:

    � Yellow to Y1

    � Black to C (common)

    NOTE � For proper voltages, select thermostat wire (control wires)gauge per Table above.

    NOTE � Wire tie provides low voltage control wire strain relief and tomaintain separation of field installed low and high voltage circuits.

    W1

    Y

    G

    C

    R

    Y

    G

    C

    THERMOSTAT INDOOR UNIT

    POWER

    HEAT

    COOLING

    INDOORBLOWER

    COMMON

    OUTDOORUNIT

    Y1

    C

    W

    R

    SINGLE PHASE

    NOTE � Do not bundle any excess 24VAC control wires insidecontrol panel.

    CONTROLWIRING

    HIGH VOLTAGECONNECTIONS(CONTACTOR)

    GROUND

    GROMMETAND WIRE TIE

    HIGH VOLTAGEFLEXIBLE CONDUIT A

    B

    Figure 8. Typical 13ACX Unit Wiring Diagram

  • Page 16

    506374−01 03/10

    TO LIQUIDLINE SERVICE

    VALVE

    TEMPERATURESENSOR

    DIGITAL SCALE

    REFRIGERANT TANK

    TEMPERATURE SENSOR(LIQUID LINE)

    MANIFOLD GAUGE SET

    A. Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.

    B. Connect the manifold gauge set’s low pressure side to the suction line service port.

    C. Connect the manifold gauge set’s high pressure side to the liquid line service port.

    D. Position temperature sensor on liquid line near liquid line service port.

    OUTDOOR UNIT

    CHARGE INLIQUID PHASE

    CONNECTIONS FOR TESTING AND CHARGING

    GAUGE SET

    A

    C

    D

    LOW HIGH

    B SUCTION LINESERVICE PORTCONNECTION

    Figure 9. Gauge Set Setup and Connections

    Servicing Units Delivered Void of Charge

    If the outdoor unit is void of refrigerant, clean the systemusing the procedure described below.

    1. Leak check system using procedure outlined on Page12.

    2. Evacuate the system using procedure outlined onPage 13.

    3. Use nitrogen to break the vacuum and install a newfilter drier in the system.

    4. Evacuate the system again using procedure outlinedon Page 13.

    5. Weigh in refrigerant using procedure outlined underStart−Up and Charging Procedures.

    6. Monitor the system to determine the amount ofmoisture remaining in the oil. It may be necessary toreplace the filter drier several times to achieve therequired dryness level. If system dryness is notverified, the compressor will fail in the future.

    Unit Start−Up

    IMPORTANTIf unit is equipped with a crankcase heater, it should beenergized 24 hours before unit start−up to preventcompressor damage as a result of slugging.

    1. Rotate fan to check for binding.

    2. Inspect all factory− and field−installed wiring for looseconnections.

    3. After evacuation is complete, open the liquid line andsuction line service valves to release the refrigerantcharge (contained in air conditioner) into the system.

    4. Replace the stem caps and tighten to the value listedin Table 1.

    5. Check voltage supply at the disconnect switch. Thevoltage must be within the range listed on the unit’snameplate. If not, do not start the equipment until youhave consulted with the power company and thevoltage condition has been corrected.

    6. Set the thermostat for a cooling demand. Turn onpower to the indoor handler and close the airconditioner disconnect switch to start the unit.

    7. Recheck voltage while the unit is running. Power mustbe within range shown on the nameplate.

    8. Check system for sufficient refrigerate using theprocedures that follow.

    System Refrigerant

    This section outlines procedures for:

    1. Connecting gauge set for testing and charging;

    2. Checking and adjusting indoor airflow;

    3. Adding or removing refrigerant.

  • Page 17

    13ACX SERIES

    ADDING OR REMOVING REFRIGERANT

    This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquidline filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22.This unit is NOT approved for use with coils which use capillary tubes or fixed orifices as a refrigerant metering device.

    Check airflow using the Delta−T (DT) process using the illustration in Figure 10.

    Cº TDrop – DT = ºF ACTION

    53º 19 – 15 = 4 Increase the airflow58º 14 – 15 = −1 (within +3º range) no change62º 10 – 15 = −5 Decrease the airflow

    DT80 24 24 24 23 23 22 22 22 20 19 18 17 16 15

    78 23 23 23 22 22 21 21 20 19 18 17 16 15 14

    76 22 22 22 21 21 20 19 19 18 17 16 15 14 13

    74 21 21 21 20 19 19 18 17 16 16 15 14 13 12

    72 20 20 19 18 17 17 16 15 15 14 13 12 11 10

    70 19 19 18 18 17 17 16 15 15 14 13 12 11 10

    57 58 59 60 61 62 63 64 65 66 67 68 69 70

    Temperature of airentering indoorcoil ºF

    INDOOR COIL

    DRY BULB

    DRYBULB

    WET BULB

    B

    TDrop

    19º

    A

    Dry

    −bu

    lb

    Wet−bulb ºF

    A

    72º

    B

    64º

    C

    53º

    air flowair flow

    All temperatures are expressed in ºF

    1. Determine the desired DT � Measure entering air temperature using dry bulb (A) and wet bulb (B). DTis the intersecting value of A and B in the Table (see triangle).

    2. Find temperature drop across coil � Measure the coil’s dry bulb entering and leaving air temperatures(A and C). Temperature Drop Formula: (TDrop) = A minus C.

    3. Determine if fan needs adjustment � If the difference between the measured TDrop and the desiredDT (TDrop–DT) is within +3º, no adjustment is needed. See example below:

    4. Adjust the fan speed � See indoor unit instructions to increase/decrease fan speed.

    Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:

    AIRFLOW

    Use the following procedure to adjust for optimal air flow across the indoor coil:

    INDOOR COIL

    Changing air flow affects all temperatures; rechecktemperatures to confirm that the temperature dropand DT are within +3º.

    Figure 10. Checking Indoor Airflow over Evaporator Coil using Delta−T (DT) Chart

  • Page 18

    506374−01 03/10

    WHEN TO CHARGE?

    � Warm weather best� Can charge in colder weatherCHARGE METHOD? Determine by:

    � Metering device type� Outdoor ambient temperatureREQUIREMENTS:

    � Sufficient heat load in structure

    � Indoor temperature between 70-80ºF(21−26ºC)

    � Manifold gauge set connected to unit� Thermometers:

    − to measure outdoor ambienttemperature− to measure liquid line temperature− to measure suction linetemperature

    TXV RFC

    APPROACH ORSUBCOOLING

    WEIGH-INSUPERHEAT

    65ºF

    (18.3ºC) and

    Above

    START: Determine how refrigerant is metered

    39ºF

    (3.8ºC) and

    Below

    Whichmeteringdevice?

    WEIGH-IN

    64ºF

    (17.7ºC) and

    Below

    40ºF

    (4.4ºC) and

    Above

    Figure 11. Determining Charge Method

    WEIGH IN TXV

    START: Measure outdoor ambient temperature 1. Check Liquid and suction line pressures2. Compare unit pressures with Table 3,

    Normal Operating Pressures.

    3. Conduct leak check; evacuate aspreviously outlined.

    4. Weigh in the unit nameplate charge plusany charge required for line set differencesover feet.

    Liquid Line

    Set Diameter

    Ounces per 5 feet (g per 1.5 m)adjust from 15 feet (4.6 m) line set*

    3/8" (9.5 mm) 3 ounce per 5’ (85 g per 1.5 m)

    NOTE − *If line length is greater than 15 ft. (4.6 m), add thisamount. If line length is less than 15 ft. (4.6 m), subtract thisamount.

    Refrigerant Charge per Line Set Length

    USE EITHER APPROACHOR SUBCOOLING

    METHOD

    This nameplate is for illustration

    purposes only. Go to actual

    nameplate on outdoor unit for

    charge information.

    ABOVE orBELOW65ºF

    (18.3ºC) and

    Above

    64ºF

    (17.7ºC) and

    Below

    Figure 12. HFC−410A Weigh In TXV Method

  • Page 19

    13ACX SERIES

    DO NOT CHARGE UNIT

    (Results of charging at lowtemperatures not reliable)

    START: Measure outdoor ambient temperature

    USE WEIGH-IN METHOD

    Weigh-in or remove refriger-ant based upon line length

    APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])

    1. Confirm proper airflow across coil using Figure10.

    2. Compare unit pressures with Table 3, NormalOperating Pressures.

    3. Set thermostat to call for heat (must have acooling load between 70-80ºF (21−26ºC).

    4. Connect gauge set.

    5. When heat demand is satisfied, set thermostatto call for cooling.

    6. Allow temperatures and pressures to stabilize.

    7. Record outdoor ambient temperature:

    AMBº =_________

    8. Record liquid line temperature:

    LIQº = __________

    9. Subtract to determine approach (APPº):

    LIQº_____ − AMBº _____ = APPº_____

    10. Compare results with table below.

    Figure 13. HFC−410A Approach TXV Charge

    ABOVE orBELOW

    If value is greater than shown (high approach),

    add refrigerant; if less than shown (liquid

    temperature too close to ambient temperature,

    low approach), remove refrigerant.

    If refrigerant is added

    or removed, retest to

    confirm that unit is

    properly charged.

    ºF (ºC)* −018 −024 −030 −036 −042 −048 −060

    Any 4 (2.2) 8 (4.4) 8 (4.4) 11 (6.1) 9 (5.0) 8 (4.4) 9 (5.0)

    *Temperature of air entering outdoor coil

    64ºF

    (17.7ºC) and

    Below

    65ºF

    (18.3ºC) and

    Above

    DO NOT CHARGE UNIT

    (Results of charging at lowtemperatures not reliable)

    START: Measure outdoor ambient temperature

    USE WEIGH-IN METHOD

    Weigh-in or remove refrigerantbased upon line length

    SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])

    BLOCK OUTDOOR COIL: [sometimes necessarywith lower temperatures] Use cardboard or plasticsheet to restrict the airflow through the outdoor coilto achieve pressures from 325−375 psig(2240−2585 kPa). Higher pressures are needed tocheck charge. Block equal sections of air intakepanels and move coverings sideways until theliquid pressure is in the above noted ranges.

    If value is MORE

    than shown, remove

    refrigerant.

    1. Confirm proper airflow across coil using Figure10.

    2. Compare unit pressures with Table 3, NormalOperating Pressures.

    3. Set thermostat to call for heat (must have acooling load between 70-80ºF (21−26ºC)

    4. Connect gauge set

    5. Measure outdoor ambient temperature

    6. When heat demand is satisfied, set thermostat tocall for cooling

    7. Allow temperatures and pressures to stabilize.

    NOTE − If necessary, block outdoor coil tomaintain 325 − 375 psig.

    8. Record liquid line temperature:

    LIQº = ______

    9. Measure liquid line pressure and use the value todetermine saturation temperature (see Table 4):

    SATº = ______

    10. Subtract to determine subcooling (SCº):

    SATº_____ − LIQº _____ = SCº _____

    11. Compare results with table below.

    Figure 14. HFC−410A Subcooling TXV Charge

    MORE orLESS

    If value is LESS

    than shown, add

    refrigerant.

    If refrigerant is added

    or removed, verify

    charge using the

    Approach Method.

    ABOVE orBELOW

    ºF (ºC)* −018 −024 −030 −036 −042 −048 −060

    Any 10 (5.6) 10 (5.6) 9 (5.0) 12 (6.7) 9 (5.0) 9 (5.0) 7 (3.9)

    *Temperature of air entering outdoor coil

    64ºF

    (17.7ºC) and

    Below

    65ºF

    (18.3ºC) and

    Above

    CARDBOARD ORPLASTIC SHEET

  • Page 20

    506374−01 03/10

    WEIGH IN RFC

    START: Measure outdoor ambient temperature1. Check Liquid and suction line pressures

    2. Compare unit pressures with Table 3,Normal Operating Pressures.

    3. Conduct leak check; evacuate aspreviously outlined.

    4. Weigh in the unit nameplate charge plusany charge required for line set differencesover feet.

    Liquid Line

    Set Diameter

    Ounces per 5 feet (g per 1.5 m)

    adjust from 15 feet (4.6 m) line set*

    3/8" (9.5 mm) 3 ounce per 5’ (85 g per 1.5 m)

    NOTE − *If line length is greater than 15 ft. (4.6 m), add this

    amount. If line length is less than 15 ft. (4.6 m), subtract this

    amount.

    Refrigerant Charge per Line Set Length

    USE SUPERHEAT

    This nameplate is for illustration purposes

    only. Go to actual nameplate on outdoor unit

    for charge information.

    ABOVE orBELOW

    39ºF

    (3.8ºC) and

    Below

    40ºF

    (4.4ºC) and

    Above

    Figure 15. HFC−410A Weigh In RFC Method

    START: Measure outdoor ambient temperature

    NOTE − Do not attempt to charge system where adash appears, system could be overcharged.Superheat is taken at suction line service port.Suction line superheat must never be less than 5ºFat the suction line service port.

    USE WEIGH-IN METHOD

    Weigh-in or remove refrigerantbased upon line length

    SHº (Superheat) Values (+/−5ºF)

    Wet Bulb (air entering indoor coil)

    ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76

    40 15 18 20 23 26 29 32 34 38 41 43 46 48 51

    45 13 16 18 21 24 27 30 33 36 39 41 44 46 49

    50 11 14 16 19 22 25 28 31 34 37 39 42 44 47

    55 9 12 14 17 20 23 27 30 33 36 38 40 42 44

    60 7 10 12 15 18 21 24 27 30 33 35 38 40 43

    65 - 6 10 13 16 19 21 24 27 30 33 36 38 41

    70 - - 7 10 13 16 19 21 24 27 30 33 36 39

    75 - - - 6 9 12 15 18 21 24 28 31 34 37

    80 - - - - 5 8 12 15 18 21 25 28 31 35

    85 - - - - - - 8 11 15 19 22 26 30 33

    90 - - - - - - 5 9 13 16 20 24 27 31

    95 - - - - - - - 6 10 14 18 22 25 29

    100 - - - - - - - - 8 12 16 21 24 28

    105 - - - - - - - - 5 9 13 17 22 26

    110 - - - - - - - - - 6 11 15 20 25

    115 - - - - - - - - - - 8 14 18 24

    * Dry−bulb temperature (ºF) of entering outdoor ambient air.

    1. Confirm proper airflow across coil using Figure10.

    2. Compare unit pressures with Table 3, NormalOperating Pressures.

    3. Use SUPERHEAT to correctly charge unit or toverify the charge is correct.4. Set thermostat to call for heat (must have a coolingload between 70-80ºF (21−26ºC)

    5. Connect gauge set.

    6. When heat demand is satisfied, set thermostat tocall for cooling.

    7. Allow temperatures and pressures to stabilize.

    8. Measure the suction line pressure and use the usevalue to determine saturation temperature (Table4):

    SATº =_________

    9. Record suction line temperature:

    VAPº =_________

    10. Subtract to determine superheat (SHº):

    VAPº − _____ SATº ______ = SHº______

    11. Record the wet bulb temperature (air enteringindoor coil):

    WB =_______

    12. Record outdoor ambient temperature.

    13. Compare results with table to the left.

    If value is MORE

    than shown, then

    ADD refrigerant.

    If value is LESS than

    shown, then REMOVE

    refrigerant.

    If refrigerant is

    REMOVED, retest to

    confirm that unit is

    properly charged.

    MORE orLESS

    If refrigerant is

    ADDED, retest to

    confirm that unit is

    properly charged.

    ABOVE orBELOW39ºF

    (3.8ºC) and

    Below

    40ºF

    (4.4ºC) and

    Above

    Figure 16. HFC−410A Superheat RFC Method

  • Page 21

    13ACX SERIES

    Table 3. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig)

    IMPORTANTUse this table to perform maintenance checks; it is not a procedure for charging thesystem. Minor variations in these pressures may be due to differences in installations.Significant deviations could mean that the system is not properly charged or that aproblem exists with some component in the system.

    13ACX −018 −024 −030 −036 −042 −048 −060

    �F (�C)* Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction

    Expansion Valve (TXV)

    65 (18) 233 / 132 244 / 137 248 / 127 263 / 135 238 /132 235 / 132 241 / 130

    70 (21) 251 / 133 263 / 138 263 / 131 281 / 138 262 / 133 254 / 132 260 / 130

    75 (24) 265 / 133 285 / 139 284 / 132 302 / 140 280 / 134 276 / 134 280 / 132

    80 (27) 292 / 135 307 / 140 307 / 134 325 / 142 301 / 136 298 / 134 299 / 134

    85 (29) 314 / 136 329 / 141 330 / 135 349 / 142 327 / 137 323 / 135 321 / 135

    90 (32) 338 / 137 354 / 142 355 / 136 375 / 143 353 / 138 350 / 137 344 / 134

    95 (35) 362 / 138 379 / 143 380 / 137 404 / 144 377 / 140 377 / 138 371 / 135

    100 (38) 388 / 140 404 / 144 407 / 138 433 / 145 404 / 141 406 / 140 400 / 137

    105 (41) 415 / 141 438 / 145 434 / 139 462 / 147 435 / 142 430 / 141 428 / 139

    110 (43) 444 / 142 464 / 147 465 / 141 494 / 149 465 / 143 464 / 142 458 / 141

    115 (45) 475 / 143 495 / 148 497 / 142 527 / 150 499 / 144 495 / 143 484 / 142

    Fixed Orifice (RFC)

    65 (18) 233 / 121 246 / 126 245 / 123 261 / 134 246 / 126 247 / 125 248 / 124

    70 (21) 250 / 124 265 / 129 265 / 126 281 / 136 263 / 128 266 / 128 266 / 126

    75 (24) 270 / 128 286 / 132 286 / 129 301 / 138 284 / 131 286 / 131 288 / 130

    80 (27) 291 / 131 307 /135 308 / 132 324 / 140 305 / 133 307 / 133 309 / 133

    85 (29) 313 / 134 330 / 137 331 / 135 346 / 142 327 / 135 329 / 135 330 / 135

    90 (32) 335 / 136 353 / 140 355 / 138 371 / 144 350 / 138 353 / 138 354 / 138

    95 (35) 359 / 138 378 / 142 380 / 140 396 / 146 374 / 140 377 / 140 377 / 140

    100 (38) 383 / 140 402 / 143 405 / 142 422 / 148 399 / 142 403 / 142 406 / 142

    105 (41) 409 / 142 428 / 145 431 / 144 448 / 150 424 / 144 428 / 144 431 / 144

    110 (43) 436 / 145 456 / 147 458 / 146 477 / 151 452 / 146 455 / 146 457 / 146

    115 (46) 464 / 147 486 / 149 487 / 148 506 / 153 481 / 148 483 / 147 484 / 148

    *Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary.**Temperature of the air entering the outside coil.

    Table 4. HFC−410A Temperature � Pressure (Psig)

    °F °C Psig °F °C Psig

    −40 −40.0 11.6 60 15.6 170

    −35 −37.2 14.9 65 18.3 185

    −30 −34.4 18.5 70 21.1 201

    −25 −31.7 22.5 75 23.9 217

    −20 −28.9 26.9 80 26.7 235

    −15 −26.1 31.7 85 29.4 254

    −10 −23.3 36.8 90 32.2 274

    −5 −20.6 42.5 95 35.0 295

    0 −17.8 48.6 100 37.8 317

    5 −15.0 55.2 105 40.6 340

    10 −12.2 62.3 110 43.3 365

    15 −9.4 70.0 115 46.1 391

    20 −6.7 78.3 120 48.9 418

    25 −3.9 87.3 125 51.7 446

    30 −1.1 96.8 130 54.4 476

    35 1.7 107 135 57.2 507

    40 4.4 118 140 60.0 539

    45 7.2 130 145 62.8 573

    50 10.0 142 150 65.6 608

    55 12.8 155

  • Page 22

    506374−01 03/10

    Removing and Installing Louvers

    WARNING

    To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:

    While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel,nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).

    While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blownaround and battered.

    WARNING

    PANEL A

    PANEL B PANEL C

    PANEL D

    When removing the unit panels. Remove panel A

    first, then B, C and finally D. When reinstalling pan-

    els, reverse that order starting with panel D, C, B

    and finally A.

    ORDER OF REMOVAL AND REINSTALLATION

    REMOVAL

    REPEAT STEPS 1, 2 AND

    3 TO REMOVE PANELS B,

    C AND FINALLY D.

    STEP 1

    STARTING WITH PANEL D,

    INSERT PANEL UNDER UNIT

    TOP CAP LIP AND LIFT

    SLIGHTLY TO CLEAR SIDE LIP

    OF PANEL FROM BASE.

    PANEL A

    PANEL A

    STEP 2

    INSTALLATION

    REPEAT STEPS 1 AND 2 TO INSTALL PANELS C,

    B AND FINALLY A.

    TO REMOVE PANEL,REMOVE MOUNTINGSCREWS SECURINGPANEL TO THE UNIT.

    SLIGHTLY LIFT PANEL A INORDER TO CLEAR SIDELIPS OF PANEL FROMBASE OF UNIT.

    STEP 3TILT PANEL OUT SLIGHTLYAND PULL DOWNWARDTO REMOVE.

    STEP 1

    STEP 2MOVE PANEL IN TOWARDS UNIT.ALIGN LEFT/RIGHT SIDE LIPS OFPANEL WITH GROOVE INSERTSALONG LEFT/RIGHT SIDE OF UNIT.

    PANEL D

    TOP CAP

    BASE

    SIDE

    GROOVE

    STEP 3

    SECURE PANEL, WITHMOUNTING SCREWS.

  • Page 23

    13ACX SERIES

    System Operation

    The outdoor unit and indoor blower will cycle on and off asdictated by demands from the room thermostat. When thethermostat’s blower switch is in the ON position, the indoorblower will operate continuously.

    HIGH PRESSURE SWITCH

    13ACX units are equipped with a high-pressure switch thatis located in the liquid line of the compressor as illustratedin figure on Page 2.

    The switch is a Single Pole, Single Throw (SPST),manual−reset switch which is normally closed andremoves power from the compressor when discharge

    pressure rises above factory setting at 590 + 10 psi. Themanual−reset switch can be identified by a red cap that ispress to preform the reset function.

    Maintenance

    DEALER

    WARNINGElectric shock hazard. Can cause injuryor death. Before attempting to performany service or maintenance, turn theelectrical power to unit OFF at disconnectswitch(es). Unit may have multiple powersupplies.

    WARNINGImproper installation, adjustment, alteration, service ormaintenance can cause personal injury, loss of life, ordamage to property.

    Installation and service must be performed by a licensedprofessional installer (or equivalent) or a service agency.

    Maintenance and service must be performed by a qualifiedinstaller or service agency. At the beginning of eachcooling season, the system should be checked as follows:

    Outdoor Unit1. Outdoor unit fan motor is pre−lubricated and sealed.

    No further lubrication is needed.

    2. Visually inspect all connecting lines, joints and coils forevidence of oil leaks.

    3. Check all wiring for loose connections.

    4. Check for correct voltage at unit (unit operating).

    5. Check amp draw on outdoor fan motor.

    Motor Nameplate:_________ Actual:__________.

    6. Inspect drain holes in coil compartment base andclean if necessary.

    NOTE - If insufficient cooling occurs, the unit should begauged and refrigerant charge should be checked.

    Outdoor Coil

    Clean and inspect outdoor coil (may be flushed with awater hose). Ensure power is off before cleaning.

    NOTE � It may be necessary to flush the outdoor coilmore frequently if it is exposed to substances which arecorrosive or which block airflow across the coil (e.g., peturine, cottonwood seeds, fertilizers, fluids that may containhigh levels of corrosive chemicals such as salts)

    Sea Coast � Moist air in ocean locations can carry salt,which is corrosive to most metal. Units that are locatednear the ocean require frequent inspections andmaintenance. These inspections will determine thenecessary need to wash the unit including the outdoor coil.Consult your installing contractor for properintervals/procedures for your geographic area or servicecontract.

    Indoor Unit1. Clean or change filters.

    2. Lennox blower motors are prelubricated andpermanently sealed. No more lubrication is needed.

    3. Adjust blower speed for cooling. Measure the pressuredrop over the coil to determine the correct blower CFM.Refer to the unit information service manual for pressuredrop tables and procedure.

    4. Belt Drive Blowers − Check belt for wear and propertension.

    5. Check all wiring for loose connections.

    6. Check for correct voltage at unit. (blower operating)

    7. Check amp draw on blower motor.

    Motor Nameplate:_________ Actual:__________.

    Indoor Coil1. Clean coil if necessary.

    2. Check connecting lines, joints and coil for evidence ofoil leaks.

    3. Check condensate line and clean if necessary.

    HOMEOWNERCleaning of the outdoor unit’s coil should be performed bya trained service technician. Contact your dealer and setup a schedule (preferably twice a year, but at least once ayear) to inspect and service your outdoor unit. Thefollowing maintenance may be performed by thehomeowner.

    CAUTIONPhysical contact with metal edges and corners while applying excessiveforce or rapid motion can result in personal injury. Be aware of, and usecaution when working near these areas during installation or whileservicing this equipment.

    IMPORTANTSprinklers and soaker hoses should not be installedwhere they could cause prolonged exposure to theoutdoor unit by treated water. Prolonged exposure of theunit to treated water (i.e., sprinkler systems, soakers,waste water, etc.) will corrode the surface of steel andaluminum parts and diminish performance and longevityof the unit.

    Outdoor CoilThe outdoor unit must be properly maintained to ensure itsproper operation.

  • Page 24

    506374−01 03/10

    � Please contact your dealer to schedule properinspection and maintenance for your equipment.

    � Make sure no obstructions restrict airflow to theoutdoor unit.

    � Grass clippings, leaves, or shrubs crowding the unitcan cause the unit to work harder and use more

    energy.

    � Keep shrubbery trimmed away from the unit andperiodically check for debris which collects around theunit.

    Routine Maintenance

    In order to ensure peak performance, your system must beproperly maintained. Clogged filters and blocked airflowprevent your unit from operating at its most efficient level.

    1. Air Filter � Ask your Lennox dealer to show youwhere your indoor unit’s filter is located. It will be eitherat the indoor unit (installed internal or external to thecabinet) or behind a return air grille in the wall orceiling. Check the filter monthly and clean or replaceit as needed.

    2. Disposable Filter � Disposable filters should bereplaced with a filter of the same type and size.

    NOTE � If you are unsure about the filter required for yoursystem, call your Lennox dealer for assistance.

    3. Reusable Filter � Many indoor units are equippedwith reusable foam filters. Clean foam filters with amild soap and water solution; rinse thoroughly; allowfilter to dry completely before returning it to the unit orgrille.

    NOTE � The filter and all access panels must be in placeany time the unit is in operation.

    4. Electronic Air Cleaner � Some systems areequipped with an electronic air cleaner, designed toremove airborne particles from the air passing throughthe cleaner. If your system is so equipped, ask yourdealer for maintenance instructions.

    5. Indoor Unit � The indoor unit’s evaporator coil isequipped with a drain pan to collect condensateformed as your system removes humidity from theinside air. Have your dealer show you the location ofthe drain line and how to check for obstructions. (Thiswould also apply to an auxiliary drain, if installed.)

    Thermostat OperationSee the ComfortSense® 7000 thermostat homeownermanual for instructions on how to operate your thermostat.

    Preservice CheckIf your system fails to operate, check the following beforecalling for service:

    � Verify room thermostat settings are correct.

    � Verify that all electrical disconnect switches are ON.

    � Check for any blown fuses or tripped circuit breakers.

    � Verify unit access panels are in place.

    � Verify air filter is clean.

    � If service is needed, locate and write down the unitmodel number and have it handy before calling.

    Accessories

    For update−to−date information, see any of the followingpublications:

    � Lennox 13ACX Engineering Handbook

    � Lennox Product Catalog

    � Lennox Price Book

    Start−Up and Performance Checklist

    Job Name Job no. Date

    Job Location City State

    Installer City State

    Unit Model No. Serial No. Service Technician

    Nameplate Voltage

    Rated Load Ampacity Compressor Outdoor Fan

    Maximum Fuse or Circuit Breaker

    Electrical Connections Tight? � Indoor Filter clean? � Supply Voltage (Unit Off)

    Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.

    Discharge Pressure Suction Pressure Refrigerant Charge Checked? �

    Refrigerant Lines: Leak Checked? � Properly Insulated? � Outdoor Fan Checked? �

    Service Valves: Fully Opened? � Caps Tight? � Thermostat

    Voltage With Compressor Operating Calibrated? � Properly Set? � Level? �