10
2009 CAMPUS LIGHTING RETROFIT FORUM Lab Lighting Controls Upgrade Chris Abbamonto, UC Irvine

Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

Embed Size (px)

DESCRIPTION

Laboratory Lighting Controls Retrofit using simplified daylight sensing and occupancy sensing

Citation preview

Page 1: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Lab Lighting Controls Upgrade

Chris Abbamonto, UC Irvine

Page 2: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Laboratory Lighting Controls Upgrade

• New Laboratory Building Biological Sciences 3

• Beat Title 24 Energy Standard by 20%+

• Challenge to reduce annual energy consumption from lighting by ~50%

• Extremely low Lighting Power Density (LPD)

LPD = Lighting Watts / Square Foot

• Lab Environment with ~50 Foot-candle Requirement

• Reducing true LPD not a probable option

Page 3: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

BE

FO

RE Lab Area LPD = 1.1

Lab Prep LPD = 0.9

Corridor LPD = 0.6

Prep Room LPD = 2.0

Page 4: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Manual Switch to Occupancy Sensor

50% Auto On - Manual to 100% - Auto Off

A-B CIRCUITING

Page 5: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Auto on to 50% Light Level

Page 6: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Lower Blinds to Allow for Daylighting

Page 7: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Photocell to Control Window Fixture

BUTTON PHOTOCELLS

Page 8: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Fixture Closest to the Window is OFF

Page 9: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

AF

TE

RLab Area SAVE +50%

Lab Prep SAVE 40%

Corridor SAVE +50%

Prep Room SAVE +50%

Page 10: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Summary

• Project Is Scalable (floors, buildings, campuses)

• Simple Payback Period in the 2.3 to 3.4 year range

• Savings Based on Controls not LPD!

• Consider under cabinet task lighting at the work surface to augment overhead lighting

• Consider perforated blinds to increase light and reduce glare through “views” portion of fenestration

Chris Abbamonto, UC Irvine, [email protected], (949) 285-3172