    Precision Cooling forBusiness-Critical Continuity

    Liebert HPMDual Circuit Floor Mount Chilled Water Units for High Redundancy

  • 8/10/2019 Liebert Hpm-r En1

    2/4

    Redundancy To Secure Your Business

    Availability

    100% redundancy CW circuits

    Dual CW circuits with double

    power supply maximize

    availability.

    Flexibility

    Simplified design layout:

    power cables

    condensate drain

    supply/drain for humidifier

    Secondary CW circuit can provideadditional cooling in the event of

    increased heat loads

    Low Total Cost of Ownership:

    Reduced footprint compared to

    two separate units

    Lower investments in air-

    conditioners

    Lower cost for the installation

    Liebert HPM R-type units are

    dual circuit chilled water unitsfor business critical applications.

    Equipped with two independent

    chilled water circuits they are able

    to take cooling fluid from two

    independent sources.

    The models are available in the

    cooling capacity range 24 - 120

    kW for each circuit; each equipped

    with 3 or 2 Port valves. These units

    provide additional security for your

    critical environment. With primaryand secondary chilled water circuits

    the units provide mandatory back

    up in terms of cooling capacit y.

    Liebert HPM Dual CW Circuit

    Hydraulic System Schematic

    Liebert HPM Dual CW Circuit

    units are specifically designed

    for buildings with primary and

    secondary chilled water circuits.

    A typical application is forpolyfunctional buildings where

    a larger cooling source operates

    during the day, serving offices,

    technology and datacentres; while

    at night when cooling is only

    required for the technology and

    datacentres we can use a smaller

    chilled water source, maximizing

    obvious energy savings.

    CW1

    CW2

    2

  • 8/10/2019 Liebert Hpm-r En1

    3/4

    iCOM - Keep it under control

    Control

    The sophisticated control logic of the

    units offers several options to sat-

    isfy the chilled water system require-

    ments and valve management.

    Parallel mode

    The chilled water valve manage-

    ment and positions are the same

    for both CW circuits.

    Safe mode

    First circuit and valve managed

    utilizing 70% of proportional tem-perature band, and then

    second valve starts to open (Re-

    quires same inlet fluid tempera-

    ture on both circuits).

    Alternate mode

    With an external input to the iCOM

    controller it is possible to manage

    which of the two chilled water cir-

    cuits / valves is duty and which is

    standby.

    In parallel and safe modes both CW

    circuits can run together maximizingthe cooling capacity.

    * All the data refer to: one circuit working and G4 air filter* 20 Pa ESP for downward delivery version, 50 Pa ESP for upward delivery version1 Air inlet @ 24 C, 50% RH, water in/out 7/12 C, ESP 20 Pa, G4 air filter2 Air inlet @ 24 C, 45% RH, water in/out 7/12 C, ESP 20 Pa, G4 air filter3 Max. ESP available for the indicated air delivery4 For downward version5 1.5 m height, 2 m front distance; free field; fan (s) working with indicated air delivery, downward delivery version.6 At nominal/indicated air delivery

    Liebert HPM R-type - Technical Data

    ModelM241

    upwarddownward

    M451

    upwarddownward

    M601

    upwarddownward

    L851

    downward

    L111

    downward

    L132

    downward

    Total cooling capacity at max airflow4 kW 24.8 48.4 63.5 86.1 108.1 127.4

    Total cooling capacity4,6 kW 24.2 46.9 60.7 80.3 99.7 118.6

    Sensible cooling capacity4,6 kW 24 43.1 54 68.3 89.1 118.6

    Water flow rate6 l/s 1.15 2.24 2.89 3.83 4.76 5.66

    Number of fans n 1 1 2 2 3 4

    Air delivery m3/h 7050 11500 13900 17150 23900 32700

    Max ESP downward/upward delivery3 Pa 190/210 100/100 120/140 180 210 180

    Sound pressure level5 dB(A) 54.4 65.4 64 64.2 66.1 69.3

    Width mm 1000 1750 1750 2050 2550 3350

    Depth mm 850 850 850 850 850 850

    Height mm 1950 1950 1950 1950 1950 1950

    Net weight kg 335 540 610 640 865 1020

    3

  • 8/10/2019 Liebert Hpm-r En1

    4/4

    Emerson Network PowerTM

    The global leader in Business-Critical Continuity.

    Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of EmersonElectric Co. 2009 Emerson Electric Co.

    AC Power

    Connectivity

    DC Power

    Embedded Computing

    Embedded Power

    Monitoring

    Outside Plant

    Power Switching & Control

    Precision Cooling

    Rack & Integrated Cabinets

    Services

    Surge Protection

    Emerson Network Power, a business of Emerson

    (NYSE:EMR), is the global leader in enabling Business-Critical

    Continuity. The company is a trusted source of custom,

    adaptive and ultra-reliable solutions designed to enable and protect

    its customers business-critical technology infrastructures.

    Backed by the largest global services organization in the industry,

    Emerson Network Power offers a full range of innovative

    power, precision cooling, connectivity and embedded

    products and services for computer, communications, healthcare

    and industrial systems. Key product brands within the

    Emerson Network Power family include Liebert, Knrr, ASCO,

    Astec and Lorain.

    While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and accepts no liability for damages resulting from use ofthis information or for any errors or omissions.

    2008 Liebert CorporationAll rights reserved throughout the world. Specifications subject to changewithout notice.Liebert and the Liebert logo are registered trademarks of LiebertCorporation. All names referred to are trademarksor registered trademarks of their respective owners.

    Ensuring the High AvailabilityOf Mission-Critical Data And Applications.

    Locations

    Emerson Network Power - Headquarters EMEALiebert Business

    Via Leonardo Da Vinci 16/18Zona Industriale Tognana

    35028 Piove di Sacco (PD) ItalyTel: +39 049 9719 111Fax: +39 049 5841 257

    [email protected]

    Emerson Network Power - Service EMEAVia Leonardo Da Vinci 16/18

    Zona Industriale Tognana35028 Piove di Sacco (PD) Italy

    Tel: +39 049 9719 111

    Fax: +39 049 [email protected]

    United States1050 Dearborn Drive

    P.O. Box 29186Columbus, OH 43229

    Tel: +1 614 8880246

    Asia7/F, Dah Sing Financial Centre

    108 Gloucester Road,WanchaiHong Kong

    Tel: +852 2572220

    Fax: +852 28029250