lightening effects and protection.pps

  • Upload
    lvsaru

  • View
    220

  • Download
    0

Embed Size (px)

Citation preview

  • 7/28/2019 lightening effects and protection.pps

    1/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Welcome to the expert seminar on

    "Surge protection in electrical energy technique

    Presented by: S. Gopakumar, Director, Cape Electric Corporation

  • 7/28/2019 lightening effects and protection.pps

    2/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    7. Applications

    2. How lightning discharges arise

    1. Introduction

    3. The causes and effects of surge voltages

    4. Protection against lightning discharges

    6. Type of arresters and selection

    5. International Standards

    8. Summary / Question and Answers!

    Seminar contents and sequences

  • 7/28/2019 lightening effects and protection.pps

    3/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    1.0 Introduction

    Lightning protection systems

    External lightning

    protection

    Air Termination

    Down Conductor

    Earth Termination

    Room shielding

    Internal lightning

    protection Surge protection

    The measures taken toensure surge protection,are separate from theinstallation of a lightningprotection system.

    However, they must becoordinated with theinternal lightning protection.

    Lightning equipotential

    bonding

    Room shielding

    Safety Distance

    Internal lightning

    protection Surge protection

    The measures taken toensure surge protection,are separate from theinstallation of a lightningprotection system.

    However, they must becoordinated with theinternal lightning protection.

    Lightning equipotential

    bonding

  • 7/28/2019 lightening effects and protection.pps

    4/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Chapter 2

    How lightning discharges arise

  • 7/28/2019 lightening effects and protection.pps

    5/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    2.2.1 How is a Lightning Current Waveform

    -40

    -20

    0

    0 200 400 600 800 1000

    s

    kA

    100 300 500 700 900

    Period between the discharges,up to a few milliseconds

    Note: The energy effects of all lightning discharges within an ionisation channel are simulated

    by the test waveform 10/350 s in IEC 61024-1, Protection of structures against lightning

    and IEC 61312-1, Protection against lightning electromagnetic impulse (LEMP).

    Main discharge

    Secondary dischargei

  • 7/28/2019 lightening effects and protection.pps

    6/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    2.2.2 Frequency of lightning strikes

    0

    5

    10

    15

    20

    25

    0-10

    10-2

    0

    20-3

    0

    30-4

    0

    40-5

    0

    50-6

    0

    60-7

    0

    70-8

    0

    80-9

    0

    90-10

    0

    100-110

    110-120

    120-13

    0

    130-140

    140-150

    150-160

    160-170

    170-180

    180-190

    190-200

    Lightning amplitude [kA], positive and negative lightning strikes

    Lightningfrequency,%

  • 7/28/2019 lightening effects and protection.pps

    7/108

  • 7/28/2019 lightening effects and protection.pps

    8/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Chapter 3

    The causes and effects of surge voltages

  • 7/28/2019 lightening effects and protection.pps

    9/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.1.1 A direct strike on a building without anexternal lightning protection installation

  • 7/28/2019 lightening effects and protection.pps

    10/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.1.2 Effects (direct strike)

    A direct strike on a building without

    external lightning protection system

    If an electric current flows as a consequence ofa lightning strike to a building, energy isconverted, heating the part of the buildingthrough which the current is conducted to earth.

    In addition, material may be melted or ejectedat the foot of the strike.

    0

    2dtiRW

    Effects: fire hazardDue to: specific energy,charge

    0

    idtQ

  • 7/28/2019 lightening effects and protection.pps

    11/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.2.1 Direct strike on an overhead high-voltage line

  • 7/28/2019 lightening effects and protection.pps

    12/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.2.2 Effects

    Direct strike on an overhead

    high-voltage line

    For a lightning strike on an overhead line, theimpedance at the first moment is determinedby the surge impedance of the line.

    This impedance (ZW) is usually in the regionof 400 to 500 ohms for a single conductor.

    2Z IU W

    Effects: Overvoltages (voltage surges)

    Due to: Maximum lightning impulse current

  • 7/28/2019 lightening effects and protection.pps

    13/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.3.1 Direct strike on a low-voltage overhead line

  • 7/28/2019 lightening effects and protection.pps

    14/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.3.2 Effects

    Direct strike on a low-voltage

    overhead line

    The preconditions of a direct strike on a low-voltage overhead line are not the same as fordirect strikes on high-voltage overhead lines.

    The fundamental difference is in the proximityto the building through which the conduction

    of partial lightning currents is possible.

    Effects: Overvoltages (surges) in the low-voltage network, partial lightning current

    due to: Maximum lightning impulse current

    Source: Kopecky/Aachen

  • 7/28/2019 lightening effects and protection.pps

    15/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.4.1 A direct strike on a building with an externallightning protection installation

  • 7/28/2019 lightening effects and protection.pps

    16/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    L1L2L3

    PEN

    3.4.2 Effects

    A direct strike on a building with an

    external lightning protectionbut without equipotential bonding

    If the lightning current from a lightning strike isdiverted to earth, there will be a voltage rise atthe earthing point of the installation. This will becarried into the house via the equipotentialbonding system.The equipotential bonding for lightning protection(lightning arresters / class B) prevents damage tothe electrical installations.

    earthoninstallatiRiU

    Effects: Overvoltages, insulation breakdownDue to: Maximum lightning impulse current

  • 7/28/2019 lightening effects and protection.pps

    17/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.5.1 Lightning strike to a tree (close strike)

  • 7/28/2019 lightening effects and protection.pps

    18/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.5.2 Effects

    Lightning strike to a tree (close strike)

    If current flows as a result of a lightning strike to atree, energy is converted (fire hazard).

    In addition, the current diverted to earth can becoupled into the earth lines or the nearby building.

    Also the electromagnetic field could destroyelectronic equipments inside the building.

    Effects: Coupling of the lightning current into earthlines, inductive and galvanic coupling,fire hazard.

  • 7/28/2019 lightening effects and protection.pps

    19/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.6.1 Inductive coupling

  • 7/28/2019 lightening effects and protection.pps

    20/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.7.1 Switching actions

  • 7/28/2019 lightening effects and protection.pps

    21/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.7.2 Effects

    Switching actions

    Switching actions occur almost everywherewhere work is done with electrical energy.

    Especially are areas in which large inductiveloads are switched, for example:

    MotorsTransformersChokes

    Welding equipmentLong runs of fluorescent tubes

    Effects: Overvoltages (surges) on network linesDue to: Energy being returned to the network

    Source: Kopecky/Aachen

  • 7/28/2019 lightening effects and protection.pps

    22/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.8 Transient overvoltages

    Voltage- disturbances in low-voltage networks

    30

    26

    22

    18

    10

    6

    2

    14

    Overvoltage factor / K

    1500(I)

    2500II

    4000(III)

    6000(IV)

    rv

    Lightning surges

    Switching surges

    Temporary voltage rises

    Harmonics and

    slow and fast voltage fluctuations

    Voltage breakdown

    Short interruptions

  • 7/28/2019 lightening effects and protection.pps

    23/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3.9 History of EMC

    1950 1960 1970 1980 1990

    Disturbance variables

    Time

    Immunity to interferenc

    Now

    Vacuum tubes

    Transistors

    Integrated circuits

  • 7/28/2019 lightening effects and protection.pps

    24/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    4.3 IEC 60364-4-443 Insulation coordination

    6000 V4000 V

    2500 V1500 V

    IV III II I

    Lift

    Staircase lighting

    Apartments

    400 V 230/400 V 230 V 230 V

    Surge withstand voltage of insulation

    Installation category

  • 7/28/2019 lightening effects and protection.pps

    25/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    4.2 Lightning protection zone concept accordingIEC 61312-1

    B Lightning arrestersto VDE 0675 Part 6 (A1, A2)Requirement class B (

  • 7/28/2019 lightening effects and protection.pps

    26/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    4.1 Equipotential bonding for lightning protectionaccording IEC 61024-1 and IEC 61312-1

    The 100% of lightning energy breaks downas follows:

    a) 50% of the lightning current will flow through

    the ground

    b) 50% of the lightning current will flow over the

    connected metal parts out of the building:

    about 10% to the water pipe (metal)

    about 10% to the gas pipe (metal)

    about 10% to the oil pipe (metal tank)

    about 10% to the sewage pipe

    about 10% to the power suppliers incoming feed

    max. 5% or 5 kA shared across all data lines

    50 %

    50 %

  • 7/28/2019 lightening effects and protection.pps

    27/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Chapter 5

    International Standards

    5 1 N ti l d i t ti l t d d

  • 7/28/2019 lightening effects and protection.pps

    28/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    5.1 National and international standards(lightning protection)

    IEC 61024-1

    External lightning

    protectionInternal lightning

    protection

    Lightning protection System (LPS)

    Air

    TerminationDown

    ConductorEarth

    TerminationRoom

    ShieldingSafety

    DistancesLightning

    Equipotential

    Bonding

  • 7/28/2019 lightening effects and protection.pps

    29/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    5.2 Different Standards for lightning protection

    Protection of structures against lightning

    European StandardCENELEC

    ENV 61024-1

    International StandardIEC

    IEC 61024-1 General Principles IS

    IEC 61024-1-1 Guide A: Selection of

    IS protection levels for LPS

    IEC 61024-1-2 Guide B: Design,IS installation, maintenance

    and inspection of LPS

    IEC 61663-1 Fibre optic installations IS

    IEC 61663-2 Lines using metallic conductors IS

    Lightning protection - Telecommunication lines

  • 7/28/2019 lightening effects and protection.pps

    30/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    5.3 Different Standards for LEMP

    Protection against lightning

    electromagnetic impulse (LEMP)

    European StandardCENELEC

    prEN 61312-1

    International StandardIEC

    IEC 61312-1 General Principles IS

    IEC 61312-2 Shielding, bonding and

    TS earthing inside structures

    IEC 61312-3 Requirements of surge

    TS protective devicesIEC 61312-4 Protection of equipment

    TR in existing structures

  • 7/28/2019 lightening effects and protection.pps

    31/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Chapter 6

    Types of arrester and typical applications

  • 7/28/2019 lightening effects and protection.pps

    32/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.1.1 Spark gap technology

    Metallic Conductors

    Air Gap

    The operating voltage can be determined by the distances between the electrodes.Spark gaps are arresters in which two or more electrodes in series are opposed to each other. Theelectrodes consist of incombustible material ( metal, carbon, etc).If a spark gap fires, the operating voltage collapses to the anode-cathode drop voltage.

  • 7/28/2019 lightening effects and protection.pps

    33/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Conducting

    Materiel

    Air Gap

    6.1.1 Spark gap technology

    Blow out / Exhausting Hole

  • 7/28/2019 lightening effects and protection.pps

    34/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.1.1 Spark gap technology

    During a Lightning

    current admission, thespark gap blows hot

    ionized gases through

    the holes provided in the

    arrester. Ionized gases

    are good conductors of

    electricity. Hence Blowout type arresters

    should be connected

    away from live parts.

    These devices should be

    installed in pressure

    releasing typeenclosures

    6 1 1 S k h l E l d

  • 7/28/2019 lightening effects and protection.pps

    35/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.1.1 Spark gap technology Encapsulated

    Output impulse

    4

    2

    1 S

    U(kV)

    t/(s)Input impulse

    (kV)

    1

    0,5

    1 S

    U

    t/(s)

    ElectrodesSpacers made frominsulating material

    High Follow Current extinguishing capacity is achieved by connecting Spark Gaps in series,

    There by splitting the arc.

    6 1 2 V i t t h l

  • 7/28/2019 lightening effects and protection.pps

    36/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.1.2 Varistor technology

    Intermediate phase

    ElectrodesEpoxy resin

    sintered zinc oxide grains withadditives of other metallic oxides

    Zinc oxideMicro-varistor

    = 10 m

    tinned copper wire

    1) Source: Siemens DruckschriftMetalloxid-Varistor SIOV

    t/(ns)Output impulse

    U(V)

    Input impulse

    U

    t/(ns)

    (V)

    Varistors are voltage-dependent resistors with a highly non-linear U/I characteristic.

    The electrical properties arise from a large number of micro-varistors connected in paralleland in series.The transitions between the micro-varistors age under the influence of overvoltages.

    6 1 3 Di d t h l

  • 7/28/2019 lightening effects and protection.pps

    37/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.1.3 Diode technology

    Input impulse

    U

    t/(ps)

    (V)

    Output impulse

    U

    t/(ps)

    (V)

    Voltage(V)

    Current

    (A)UC UB UR

    UCUBUR

    Transzorb diodes (also known as suppresser diodes) are diodes that limit both positive

    and negative voltage.They switch in the picosecond region and are especially well suited for use in data lineprotection devices.

    6 1 4 Arrester technologies

  • 7/28/2019 lightening effects and protection.pps

    38/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.1.4 Arrester technologies

    How to limit big lightning currents

    and surge overvoltages!

    Spark gaps

    High-performancespark gaps have avery high dischargecapacity, which is whythey are used aslightning arresters.

    Varistors

    Varistors are used insurge arrestersand fineprotection devices.Unlike other types ofarrester, their ability tocarry lightning current

    is limited.

    Diodes

    Transzorb diodes, alsoknown as suppresserdiodes, are used as diodearresters only in fineprotection devices.They are characterised by

    a fast response, but theirdischarge capacity islimited.

    6 2 1 Arrester Standardisation

  • 7/28/2019 lightening effects and protection.pps

    39/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.2.1 Arrester Standardisation

    IEC 61643-1/ (VDE 0675, P.6/A1/A2)Surge Protective Devices Connected to Low-Voltage Power Systems:

    Performance requirements and testing methods

    IEC 61643-12Surge Protective Devices Connected to Low-Voltage Power Systems:

    Selection and application principles

    IEC 61643-21Surge Protective Devices Connected to telecommunication and signalling networks.

    Performance requirements and testing methods

    IEC 61643-22Surge Protective Devices Connected to telecommunication and Signalling Networks

    Selection and application principles

    6 2 2 Arrester Standardisation

  • 7/28/2019 lightening effects and protection.pps

    40/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    6.2.2 Arrester Standardisation

    IEC 61643-1:1998 / VDE 0675, P.6/A1/A2Surge Protective Devices Connected to

    Low-Voltage Power Systems

    Type 1 / B

    Arrester for lightning

    equipotential bonding.

    Tested: Iimp (10/350)

    In (8/20)

    Type 2 / C

    Arrester for Overvoltage

    surge protection.

    Tested: Imax (8/20)

    In (8/20)

    Type 3 / D

    Fine protectors for mobile

    use and for the top-hat rail.

    Tested: Uoc (1,2/50)

    (8/20)

    6.3.1 Types of SPDs IEC 61643-12

  • 7/28/2019 lightening effects and protection.pps

    41/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Examples of one-port SPDs

    aKey

    a. One-port SPDs

    U

    U

    Ub b. One-port SPD with separate input and

    output terminals

    SPDcc. Generic symbol for a one-port SPD

    6.3.2 Types of SPDs IEC 61643-12

  • 7/28/2019 lightening effects and protection.pps

    42/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Figure 2 :- Examples of two-port SPDs

    a. Three-terminal two-port SPDa

    U

    Z

    bU

    Z

    Z b. Four-terminal two-port SPD

    c SPD

    c. Generic symbol for a two-port SPD

    ZSeries impedance between input andoutput terminals

    6.4.3 Types of SPDs IEC 61643-12I

  • 7/28/2019 lightening effects and protection.pps

    43/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Response of one-port and two-port

    SPDs to a combination wave impulse

    aa. Applied current

    waveform0 t s

    Ip

    820

    b U

    0 t

    U

    b. Response of voltage

    limiting type SPD

    c

    0 t

    U

    c. Response of voltage

    switching type SPD

    6.4.4 Types of SPDs IEC 61643-12

    Figure 3 :- Response of one-port and two-port

  • 7/28/2019 lightening effects and protection.pps

    44/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    f. Response of two-port

    voltage limiting type SPD

    with filteringf

    0 t

    U

    U

    Z

    NOTE : The voltage levels are only representative and not an indication of actual values.

    g p p p

    SPDs to a combination wave impulse

    d

    0 t

    U

    U

    d. Response of one-portcombination type SPD

    e

    0 t

    U

    U

    Z

    e. Response of two-port

    combination type SPD

    6.5 Types of SPDs IEC 61643-12

  • 7/28/2019 lightening effects and protection.pps

    45/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Single voltage limiting component: Limiting type SPD

    Single voltage switching component: Switching type SPD

    U

    Combination of voltage limiting and switching components:

    Combination type SPD

    6.6.1 IEC 61643 12: Coordination Rules and Principals

  • 7/28/2019 lightening effects and protection.pps

    46/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    1. Between two ZnO Varistor based SPDs: Possible only for one port

    limiting type SPDs

    2. Between a gap based arrester (One port switching type) and a ZnO

    Varistor based arresters (One port limiting type).

    Coordination between Gap based arrester with voltage protection level of < 4KV and aresponce time of 200 ns with a ZnO based arrester with a Nominal Discharge Current In of5 KA requires approximately 27.2 H inductor or 27.2 meter cable for a perfectcoordination

    6.6.2 Coordination.

  • 7/28/2019 lightening effects and protection.pps

    47/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Class C arrester starts discharging. Voltage V1 drops at Class C. Corresponding to di/dt

    V2 drops at inductor. When V1+V2 = Voltage protection level of Class B arrester, it starts

    conducting.

    4 KV

    I

    V

    3.2 KV

    V 800 V

    V

    t

    4 KV

    Class CSingle Port

    Voltage Clamping TypeRated for 8/20 s

    Class BSingle Port

    Voltage Switching TypeRated for 10/350 s

    V1

    V2

    6.6.3 Response of Class B , C and Inductor for a low voltage High Energy Surge.

  • 7/28/2019 lightening effects and protection.pps

    48/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Class C arrester starts discharging and will clamp the voltage to V1. Inductor starts clamping the

    voltage. Since di/dt is very low, voltage V1 comes to minimum after the initial rise. Complete energypasses through Class C.

    I f Class B arrester has a low v ol tage protect ion level , i t has more con trol on th is kind o f surge.

    4 KV

    6.6.4 Class B & Class C arresters without proper coordination

  • 7/28/2019 lightening effects and protection.pps

    49/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Class B arrester never operates since Class C arrester clamps the voltage at less than 2 KV at 40

    KA. The entire current flows through Class C arrester resulting in the failure of Class C

    4 KV

    Low Inductor / Low Distance

    V 1.75 KV at40 KA

    6.7 Follow Current

  • 7/28/2019 lightening effects and protection.pps

    50/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Once Class B arrester is switched on, it shorts the Line and Neutral (or Line and Earth). After the surge current,

    short circuit current of the network starts flowing through the arrester. Finally the backup fuse F1 or F2 interruptsthe short circuit current. Short Circuit current following the surge current is called as follow current. Class B

    arrester should be capable of extinguishing this follow current without the help of fuse F1 or F2.

    Class CSingle Port

    Voltage Clamping Type

    Rated for 8/20 s

    Class BSingle Port

    Voltage Switching Type

    Rated for 10/350 s

    4 KV

    F1

    F2

    Sub StationTransformer

    6.8.1 Selection Of Class B arresters for Power Line Protection

  • 7/28/2019 lightening effects and protection.pps

    51/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    1. Enclosure

    Exhausting / Encapsulated

    Special Fireproof / Explosion

    proof Enclosure required

    Special enclosures with spring

    loaded doors are generally used.

    The purpose of spring loaded doors

    is to open automatically in case of

    high pressure inside the enclosure

    due to a Blowout

    No Special requirements

    Can be mounted in

    ordinary Metallic/ PP

    enclosures

    6.8.2 Selection Of Class B arresters for Power Line Protection

    2. Coordination2. Coordination: If Coordination Distance/Inductance Value is not properly maintained

  • 7/28/2019 lightening effects and protection.pps

    52/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Voltage Protection Level of Class B

    arresters

    Minimum Coordination Distance / Inductance

    Value required

    Line to Neutral 4 KVNeutral to Earth 4 KV

    15 meter cable or 15 H Inductor

    Line to Neutral 2 KVNeutral to Earth 2.5 KV

    5 meter cable or 5 H Inductor

    Line to Neutral 1.5 KVNeutral to Earth 1.5 KV

    Coordination not required

    Line to Neutral 1.5 KVNeutral to Earth 4 KV

    15 meter cable or 15 H Inductor

    Line to Neutral 4 KVNeutral to Earth 1.5 KV

    15 meter cable or 15 H Inductor

    2. Coordination2. Coordination: If Coordination Distance/Inductance Value is not properly maintained

    Class B arrester will not operate resulting the failure of Class C arrester.

    6.8.3 Selection Of Class B arresters for Power Line Protection

  • 7/28/2019 lightening effects and protection.pps

    53/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    3. Follow Current.

    What happened on a spark gap during a surge current?

    The spark gap will make an equipotential bonding between line and earth, or line and neutral.

    That depends where the gap has been installed. So the spark gap will make a short circuit during the

    surge.What happened during a shortcircuit?

    During the whole time, the nominal voltage of 230V is still on our spark gap. So this nominal

    voltage pushes now a short circuit current over your shorted spark gap arrester.

    What happened after the surge?If the surge current is over, the spark gap is still in the same condition, that it is like a shortcircuit and the short circuit current from the main line is still going over the spark gap. Now the spark

    gap must be able, to cut off this short circuit current by itself, before the fuse will cut off the current.

    Follow Current

    The short circuit current following the surge current is called as Follow Current. Follow current is equal to

    the peak short circuit capacity of the network. The class B arrester should eliminate (cut off) this shortcircuit current without the help of Back up Fuse. Short circuit value can be calculated based on the

    transformer capacity and the distance between the transformer and installation. Approximately 10 to 15KA

    will be ideal for telecom installations. Otherwise this will blow the fuses in case of a Lightning

    4 Follow current: Fuse Selection of Class B Arrester

    6.8.4 Selection Of Class B arresters for Power Line Protection

  • 7/28/2019 lightening effects and protection.pps

    54/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    4. Follow current: Fuse Selection of Class B Arrester

    Short Circuit at installation Point

    in KA

    Fuse selection of Class B Arrester with

    Short Circuit extinguishing capacity of

    4KA

    5,6,10 &25 Higher values of short circuit current

    will cause the backup fuse to blow.

    Use of backup fuse higher than 125 Amps will cause the surgearrester to fail due to excessive follow through current

    1.5 50

    2 63

    2.5 80

    3 1003.5 100

    4 125

    1 35

    6.9.1 Type of arrester / Lightning arrester class B

  • 7/28/2019 lightening effects and protection.pps

    55/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Requirement class : B according VDE 0675, part 6Requirement class : Type 1 according IEC 61643-1

    Principle of operation : Spark gap / Exhausting(Blow out type)

    Impulse current Iimp : 60 kA(10/350) per pole for LA60-B100 KA (10/350) for LA100-B

    Protection level Up : < 4 kVResponse time : < 100 ns

    Series fuse : separate backup fuse required

    Lightning Arrester LA60-B and LA 100-B

    Application: Where there is an external lightning protectioninstallation, overhead line feed and high networkavailability.

    6.9.2 Type of arrester / Lightning arrester class B

  • 7/28/2019 lightening effects and protection.pps

    56/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Requirement class : B according VDE 0675, part 6Requirement class : Type 1 according IEC 61643-1

    Principle of operation : Spark gap / Multi-Carbon-Technology(encapsulated)

    Impulse current Iimp : 50 kA(10/350) per pole Discharge current Imax : 120 kA(8/20) per pole

    Protection level Up : < 2 kV Response time : < 100 ns Series fuse : no separate series fuse in

    installations up to 500 A Mark of conformity : VDE, VE, KEMA, EZU, MEEI

    LightningController MC 50-B VDE

    Application: Where there is an external lightning protection installation, overhead

    line feed and high network availability.In industrial plants and for high lightning protection classes.

    6.9.3 Type of arrester / Lightning arrester class B

  • 7/28/2019 lightening effects and protection.pps

    57/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Requirement class : B according VDE 0675, part 6Requirement class : Type 1 according IEC 61643-1

    Principle of operation : Spark gap / Multi-Carbon-Technology(encapsulated)

    Impulse current Iimp : 125 kA(10/350) per pole Discharge current Imax : 200 kA(8/20) per pole Protection level Up : < 2,5 kV Responce time : < 100 ns Mark of conformity : VDE, VE, KEMA, EZU, MEEI

    LightningController MC 125-B/NPE

    Application: Where there is an external lightning protection installation, overhead

    line feed and high network availability.Lightning arrester for the installation between N and PE.

    6.9.4 Application advantage / Encapsulated ArresterLightningController MC

  • 7/28/2019 lightening effects and protection.pps

    58/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    g g

    Advantage for the installer by using

    the OBO LightningControllerMC 50-B VDE and MC 125-B/NPE

    No special housing necessary!

    No minimum distances through

    other electrical installations!

    6..9.5 LightningController MC

  • 7/28/2019 lightening effects and protection.pps

    59/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    LightningController MC

    MC 50-B VDE

    MC 125-B/NPE

    Tested according:

    E DIN VDE 0675

    Teil 6 + A1 + A2

    IEC 61643-1 +37 A/95/CDV

    6.9.5 Coordinated LightningController MCD

  • 7/28/2019 lightening effects and protection.pps

    60/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Improvement of the

    protection level to < 1,3 kV

    Advantage for the builder of the control cabinet: No need of LightningCoordinator LC 63

    2,5 kV

    2,0 kV

    Direct parallel connection betweenLightningController MCD // SurgeController V20-C is possible!

    Important for mobile transmitter stations and industrial distribution!

    6.9.6 LightningController MCD // SurgeController V20-C

  • 7/28/2019 lightening effects and protection.pps

    61/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Direct parallel connection betweenLightningController MCD // SurgeController V20-C

    No decoupling element and no C25-B+C/NPE

    is necessary!

    6.9.7 Class B & Class C together Grid Surge

    Applicable only for Class B

    arrester with a response time

    less than 100 nano sec

  • 7/28/2019 lightening effects and protection.pps

    62/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    MCD50-B arresters switches at a low voltage of 700 volt if the energy content is more.Initially Class C arrester starts discharging when the voltage V1 continues for more time,

    Class B arrester switches at a low voltage thereby reduces the stress on Class C arrester.

    1.3 KV

    700 V 1.3 KV

    No Inductor / Distance

    1.3 KV at InMCD 50-B

    V20-C

    less than 100 nano sec

    6.9.8 Type of arrester / Lightning + surge arresterclass B + C

  • 7/28/2019 lightening effects and protection.pps

    63/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Requirement class : B + C according VDE 0675Requirement class : Type 1 + 2 according IEC

    Principle of operation : Varistor technology Impulse current Iimp : 25 kA(10/350) per 4-pole block Discharge current Imax : 200 kA(8/20) per 4-pole block

    Protection level Up : < 2 kV Series fuse : no separate series fuse in

    installations below 160 A Mark of conformity : EZU, MEEI, VdS- approved

    Application: Where there is an external lightning protection installation, overheadline feed and high network availability.VdS-approved.

    CombiController V25-B+C

    6.9.9 Type of arrester / Surge arrester class C

  • 7/28/2019 lightening effects and protection.pps

    64/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Requirement class : C according VDE 0675, part 6Requirement class : Type 2 according IEC 61643-1

    Principle of operation : Varistor technology Discharge current Imax : 40 kA(8/20) per pole Nom. discharge current In : 20 kA(8/20) per pole

    Protection level Up : < 1,3 kV Series fuse : no separate series fuse in

    installations below 125 A Mark of conformity : VE, UL, KEMA, EZU, MEEI

    SurgeController V20-C

    Application: Surge arrester for the installing in the main- and sub- distribution

    boards.

    6.9.10 Further surge products / Main lines

  • 7/28/2019 lightening effects and protection.pps

    65/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Audible signallingdevice AS forV 25-B+C and V20-C

    Remote signallingdevice FS forV 25-B+C and V20-C

    Fine protectiondevice KNS-D

    Fine protectiondeviceVF 230-AC-FS

    Checking systemISOLAB

    Decoupling element LC 63

  • 7/28/2019 lightening effects and protection.pps

    66/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    7. Application

    7.1 Procedure for selecting surge arresters

  • 7/28/2019 lightening effects and protection.pps

    67/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Buildinglightning protection installation?

    overhead line?

    lightning current coupling possible?

    Lightning arresters(Requirement class B)

    Installation as close as possible tothe entrance of the building

    Surge protection(Requirement class C)

    Installation in sub-distribution board

    Surge protection

    (Requirement class D)Installation as close as possible tothe device to be protected

    yes

    Surge protection

    (Requirement class D)Installation as close as possible to thedevice to be protected

    Surge protection(Requirement class C)

    Installation In sub-distribution board

    Coordinationbetween B and Carresters for line

    lengths below 5metres

    Coordinationbetween C and D

    arresters

    no

    Class 1(B) and Class 2(C) protectionfor Lightning & Surge Voltage Protection Equipment in TT System

    RRF1

    (As per IEC 61024-1, IEC 61312-1, VDE V0100-534)

    ENT

  • 7/28/2019 lightening effects and protection.pps

    68/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    SPD1

    SPD3

    SPD2

    SPD4

    R

    Y

    B

    N

    R

    Y

    B

    N

    PE

    ACCOMMERC

    IALMAINS

    ACDISTRIBUTIONPANEL

    INPOWER

    ROOM

    EARTH

    F2

    F3

    SPD5

    SPD7

    SPD6

    SPD8

    F4 F5 F6

    (Class 1 / B) (Class 2/ C)

    Note : The above system is forthree phase configuration. For

    single phase one phase

    conductor and one neutral

    wire shall be used

    PE -: Protective Earth

    F1, F2, F3, F4, F5, F6 -: Fuses of Proper Rating

    SPD1, SPD2, SPD3 -: Surge Protection Devices of rating Iimp 50KA, 10/350s

    SPD4 -: Surge Protection Devices of rating Iimp 100KA, 10/350sSPD5, SPD6, SPD7 -: Surge Protection Devices of rating Iin 10KA, 8/20s

    SPD8 -: Surge Protection Devices of rating Iin 20KA, 8/20s

    LV / HV -: Low / High Voltage Disconnector

    Iimp -: Value of Lightning Impulse Current 10/350s

    Iin -: Value of Nominal Discharge Current 8/20s

    -: Co-ordination cable element

    TOEQUIPME

    7.1.1 Installation example

  • 7/28/2019 lightening effects and protection.pps

    69/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    -- Building without external lightning protection --

    1. Overvoltage arrester class C

    2. Overvoltage arrester class Cin the sub- distribution board

    3. Overvoltage arrester class Cfor photovoltaic- facilities

    4. Overvoltage arrester class D

    7.1.2 Installation example

  • 7/28/2019 lightening effects and protection.pps

    70/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    -- Building with external ligtning protection --

    1. Lightning Arrester class Bor the CombiController

    2. Overvoltage arrester class C

    3. Overvoltage arrester class D

    7.1.3 Installation example

  • 7/28/2019 lightening effects and protection.pps

    71/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    -- Office building with external lightning protection --

    1. Lightning arrester class B

    4. Overvoltage arrester class D

    3. Overvoltage arrester class C

    2. Lightning arrester class Bor CombiController

    7.1.4 Installation example

  • 7/28/2019 lightening effects and protection.pps

    72/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    -- Industrial building with external lightning protection --

    1. Lightning arrester class Bor CombiController

    2. Overvoltage arrester class C

    3. Overvoltage arrester class D

    ENT

    R1

    Class 1 and Class 2 arresters in enclosure with standard inductor. Suitable for small and medium exchanges in TTnetwork

  • 7/28/2019 lightening effects and protection.pps

    73/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    AC

    COMMERCIAL

    M

    AINS

    TO

    EQUIPM

    Body earthing of all electronic equipments in the

    exchange.

    Direct earth connection from the body of equipment

    to outside earth pit is not permitted.

    EBB

    To earth pit

    Y

    B

    N

    PE

    2

    3

    456

    7 8 9

    10

    11 12 13

    14

    PE -: Protective Earth

    1,2,3,4,5,6 -: Fuses of Proper Rating

    7,8,9 -: Surge Protection Devices of rating Iimp >50KA, 10/350s10 -: Surge Protection Devices of rating Iimp > 100KA, 10/350s

    11,12,13 -: Surge Protection Devices of rating In > 10KA, 8/20s

    14 -: Surge Protection Devices of rating In > 20KA, 8/20s

    Iimp -: Value of Lightning Impulse Current 10/350s

    In -: Value of Nominal Discharge Current 8/20s

    EBB -: Equipotential bonding bar

    : Inductor (made by the SPD manufacturer

    Earthing

  • 7/28/2019 lightening effects and protection.pps

    74/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Incomingpanel

    Surgearresters

    Powerplant

    Exchange

    Battery

    +_

    Other RFdevices

    TelephoneLines

    PE

    PE

    Earthing Schematic for exchanges

    Earthing

  • 7/28/2019 lightening effects and protection.pps

    75/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Incomingpanel

    Surgearresters

    Powerplant

    Exchange

    Battery

    +_

    Other RFdevices

    TelephoneLines

    PE

    PE

    Earthing Schematic for exchanges: Wrong connection

    Earthing

  • 7/28/2019 lightening effects and protection.pps

    76/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Incomingpanel

    Surgearresters

    Powerplant

    Exchange

    Battery

    +_

    Other RFdevices

    TelephoneLines

    PE

    P

    E

    Earthing Schematic for exchanges: Bonding of different earthings

    PE

    B1

    B1-Special bonding device to bond different earthnigs, 100KA with voltage protection level 1300 V

    Railways Application : Token less Block Instrument

  • 7/28/2019 lightening effects and protection.pps

    77/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Used for signaling / train movement

    between station. Stations are interconnected either byoverhead line or by UG cable.

    20 to 35 volt signals are transmittedfrom the stations depending upon thedistance between stations.

    12 volt signal is received at thestations.

    Transmission and reception is donethrough the same lines. The same lineis also used for voice conversation.

    Railways Application : Token less Block Instrument

  • 7/28/2019 lightening effects and protection.pps

    78/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    The input wires are connected to the blockinstrument via spark gaps.

    These wires are connected parallely to thecoil of pick up relays, contact oftransmission relays and telephone device.

    During lightning season, over voltagechances are high in places where overheadline are used.

    If the over voltage occurs when the signal

    lines are transmitting, chances of fusefailures are more due to the follow currentcreated by the spark gap during adischarge.

    Even though spark gaps are installed in theline, failures are occuring in the blockinstrument may be because of the high

    voltage protection level.

    Railways Application : Token less Block Instrument

  • 7/28/2019 lightening effects and protection.pps

    79/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    These arrester were burnt during the lightningas well as it was not capable of protecting theinstrument. (A number of pieces burnt. Mightbe all the devices installed)

    The failure of the arrester may be due to highdischarge current (more than 20 KA) enteringthrough the overhead lines.

    Surge arresters with a discharge capacity of

    20 KA were installed in Castle rock railwaystation which has a high lightning prone place.

    Arrester with a high discharge current handling

    capacity is required for this application

    Railways Application : Token less Block Instrument

    A two stage protection is recommended for thistype of devices

  • 7/28/2019 lightening effects and protection.pps

    80/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Stage 2

    type of devices. MOV based arrester with a maximum

    discharge current handling capacity of 40

    KA per pole with in built thermaldisconnector and dynamic disconnector isrecommended on stage1 as per thedrawing.

    Class D type arrester designed for 12V DCshould be used in the line connected to thecoil of pickup relay.

    Class D type arrester designed for 48V DCshould be used in the line connected to thecontact of transmission relay.

    We recommend to install these devices in 2stations most proven for lightning for at least 6months.

    Stage 1

    Railways Application : Token less Block Instrument

  • 7/28/2019 lightening effects and protection.pps

    81/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Stage 1

    Stage 2

    Line 1Line 2

    In stage 1 protection, 2 devices are connectedto each line. Hence the total discharge capacityis 80 KA.

    Stage 1 protection is required only in placeswhere over head lines are used.

    For places where UG cables are used, only

    stage 2 protection is required. If the installation is in places where lightning'sare very less, only one Class D type arrester 48V DC can be used for the complete BlockInstrument.

    Specification of each devices is as below.

    Stage 1 Protection (Only required if over head lines are used)

    Railways Application : Token less Block Instrument

  • 7/28/2019 lightening effects and protection.pps

    82/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Stage 1 Protection: (Only required if over head lines are used)

    Class II Type surge arrester single port MOV based with in built Thermal disconnector and

    Dynamic disconnector as well as visual indication to determine faulty arresters withfollowing specification.

    1. Maximum Discharge current operating voltage DC 100V

    2. Nominal discharge current of Single block : 15KA for 8/20s wave form

    3. Maximum Discharge current for 8/20s : 40KA

    4. Response time < 25ns.5. Test standard : Class II type SPD as per IEC 61643

    6. Voltage protection level at 1KA (8/20s ) : 300 V

    7. Fixing : Rail mounting type.

    8. Connection wires : 2.5 to 6 Sq.mm.

    9. Enclosure : Arrester should be installed in polypropylene enclosure with Transparent coverso that inside devices are visible.

    Railways Application : Token less Block Instrument

    Stage 2 Protection : For input to the coil of pickup relay.

    Surge arrester based on MOV, spark gap and tranz abzob diode with following rating should bei t ll d t th Bl k i t t ith th f ll i ifi ti

  • 7/28/2019 lightening effects and protection.pps

    83/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    installed very near to the Block instrument with the following specifications.

    Rated current : : 1Amps Nominal Voltage : 12 V Maximum continuous operating voltage : 13.5Volt Nominal discharge current : 10 KA Voltage protection level : 29V

    Series Inductance per path : 100H Connection wires : 0.14 to 2.5 mm 2 Fixing : Rail mounting type.

    Stage 2 Protection : For output to the contact of transmission relay as well as for the

    input and output of telephone .

    1. Rated current : : 1Amps2. Nominal Voltage : 48 V3. Maximum continuous operating voltage : 53 Volt

    4. Nominal discharge current : 10 KA5. Voltage protection level : 100V6. Series Inductance : 100H7. Connection wires : 0.14 to 2.5 mm 28. Fixing : Rail mounting type.

    Railways Application : Token less Block Instrument

    Coordination between Stage 1 and 2 Protection.

    Distance of 3 meters (or 3 H inductor) should be provided between stage 1 and 2 protection.

  • 7/28/2019 lightening effects and protection.pps

    84/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Connection diagram as follows.

    Stage 2 SPD :

    12V DC

    Stage 2 SPD :

    48V DC

    To Output of block

    instrument as well as

    to telephone

    12V input signal to

    block instrument

    Interconnection

    Stage 1

    Protection in

    enclosure

    3 meter cable length is required between Stage 1 and Stage 2

    L1

    L1

    L2

    L2

    L1 L2

    Railways Application : Token less Block Instrument

    Bonding of Input DC supplies

  • 7/28/2019 lightening effects and protection.pps

    85/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Equipotentialisation of Input DC supplies to be done with Class D arresters of suitable

    voltages.

    Nominal Discharge current In: 10 KA

    Bonding

    Local Equipotentialisation bonding has to be done by connecting the body of Blockinstrument, earth terminal of all class D arresters (stage 2 protection as well as devices

    connected to the DC input to of block instrument.

    Earthing

    Earthing has to be done as per the drawing.

    Railways Application : Token less Block Instrument

  • 7/28/2019 lightening effects and protection.pps

    86/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    PE

    DC inputs to Block instrument

    Less than 0.5 meter

    EBB

    PE Local bonding bar

    EBB- Equipotential bonding bar of the room

    1. Stage 1 protection

    2. Stage 2 protection

    3. Arresters for the DC input to Block instrument

    Earth wire to the building ground

    1 2

    2

    33

    SSI: Gidhni site plan (Existing)

    Axle Counter

    IPS Room

    B tt R

    TVSS

  • 7/28/2019 lightening effects and protection.pps

    87/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    SSI

    Rack1 Rack2 Relay

    panel

    TreeTree

    EP1 EP2 EP3

    EP4 EP5 EP6

    EP-Earth pit

    Battery Room

    1. Body of all devices in the SSI room is connected via

    metallic cable trays.

    2. Body of SSI and relay panels are connected to thecommon bonding bar with copper cables.

    3. Body earthing of axle counter is connected

    separately on the backside of the room

    4. Common bonding bar is connected to earth pits in

    front of the room via copper cables.

    5. Body of all devices in IPS room are interconnected

    through metallic cable trays.

    6. Body of IPS and change over panels are connected to

    bonding bar in the room via copper cable.

    7. Bonding bar in the IPS room is connected to earth

    pits via copper cables.

    ASM

    ROOMDC

    Panel

    ACPanel 2

    ACPanel 1

    SMRPanel C/O

    Panel

    Axle Counter

    Relays

    SSI

  • 7/28/2019 lightening effects and protection.pps

    88/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Rack1 Rack2 Relay panel

    P

    C

    24 V DC from IPS

    12 V DC from IPS

    RS485 ports

    (To SM Room)

    230 V ACRS485 port

    PAS or Common Bonding/Earthing Bar

    From IPS

    Inter

    connections

    1 . DC and AC Power for SSI as well as PC is

    received from IPS

    2. Interconnections between SSI main rack and

    control panel situated in the nearby building

    and routed through metallic pipes.

    3 . AC and DC power for control panel and

    control PC are routed through metallic pipes.

    4. RS485 interconnecting wires are routedthrough metallic pipes connected between

    the 2 buildings.

    From SM

    Room

    Gidhni site plan:Possible chances of Coupling of partial Lightning Currents through metallic pipes

    connected between two buildings. Power and data cables are routed through these pipes

    Axle CounterIPS roomSM

    RoomTVSS

  • 7/28/2019 lightening effects and protection.pps

    89/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    TreeTree

    EP1 EP2 EP3

    EP4 EP5 EP6

    Note: It is clear that there are no lightning and

    transient protection devices provided at the SSI

    end to protect the inputs (or outputs) against any

    surge coming from outside source.

    Rack1 Rack2Relay

    panel

    Battery

    Room

    PC Control Panel

    RS485/232 port PC to SSI

    32 pairs of I/O Nonvital

    C/O PanelSMR

    PanelAC

    Panel

    AC

    Panel

    DC

    Panel

    24V DC

    12V DC

    230V AC230V AC

    Metallic Pipes

    connected to

    ground

    PC

    Problem of safety distance.Lightning strike on the wall of the buildings or on the nearby objects can create Inductive coupling of the metallic parts inside the buildings due to thehigh potential created during the current flow.

    wall General

  • 7/28/2019 lightening effects and protection.pps

    90/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    1. Example of problems with

    safety distance on a wall

    wall

    Electronic

    installation

    R

    L

    2. Example of problems with

    safety distance on a flat roof

    R

    L

    Electronic

    installation

    TallObjects

    General

    SSI: Gidhni site planPossible chances of Coupling of partial Lightning Currents due

    to spread of radiation if a lighting strikes very close to the building.

    Axle CounterIPS room

    Battery

  • 7/28/2019 lightening effects and protection.pps

    91/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    EP1

    EP-Earth pit

    SSI

    Rack1 Rack2 Relay

    panel

    TreeTree

    EP2 EP3

    EP4 EP5 EP6

    y

    Room

    Note: Drg. Shown above is schematic for explanation of radiation caused due to lightning and does not include

    all the elements (cabinets) of site.

    Over Voltage in the ground created a high potential in the body of all devices connected to ground. The devices

    which are having the lowest breakdown voltages will damage immediately. If the voltage is so high,

    splashovers will happen. Probably the Lightning arrester connected in IPS room must have operated at 2 KV

    and diverted the current to the power source. Otherwise there would have been flashes on PCBs.

  • 7/28/2019 lightening effects and protection.pps

    92/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Battery

    Room

    Axle Counter

    SSI

    Rack1 Rack2 Relay

    panel

    IPS room

    EP2 EP3

    TreeTree

    EP4 EP5 EP6

    Rack1 Rack2 Relay

    panel

    IPS room

    EP2 EP3

    Tree

    EP4 EP5 EP6

    Note: Red colour shows how the radiation

    starting ground EP2, EP3 and EP5, moves to throom and affects all equipments connected.

    Gidhni site plan-Explanation as what could have happened.

    Chance no.1. Ground potential increases due to a discharge either on ground or on the tree (existing outside the building) or any of the nearby objects. Potentialof all the devices connected to earth increases. ( Axle counter body is separately grounded on the backside of building). Chances of failure of all devices due tothe coupling of surge. Failures expected on the non vital I/Os, PCs, SSI main rack PCBs, 12 V & 24 V Power inputs of SSI, IPS inputs and outputs.

    Axle CounterIPS roomSM

    RoomTVSS

  • 7/28/2019 lightening effects and protection.pps

    93/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    EP6

    TreeTree

    EP1 EP2 EP3

    EP4 EP5

    Actual following was found at site :

    Failure occurred on both PCs, Control panel, SSI main rack PCBs, one output of IPS.

    No failure on the IPS Inputs, Lightning and Surge arresters are installed.

    No failure on output of IPS, SPDs installed on all outputs.

    Recommendations. (Surge arresters should be installed in the following places)

    Power supply of PC affected. Recommended device 3. VF 230 AC

    24 V and 12 V DC Power supply inputs to SSI. Recommended Device. VF24 DC for 24 Vand VF12 DC for 12 V

    RS485 ports affected. Recommended Device 2. SD25 V11 / 25

    230 V AC output from IPS No failure occurred. May be due to the presence of SPD

    RS 485 ports of Monitoring PC also require protection. Recommended Device 2. SD25V11 / 25

    Non Vital inputs Recommended device 1. LSA-BF-24

    Rack1 Rack2Relay

    panel

    Battery

    Room

    PC Control Panel

    RS485/232 port PC to SSI

    32 pairs of I/O Nonvital

    C/O PanelSMR

    PanelAC

    Panel

    AC

    Panel

    DC

    Panel

    24V DC

    12V DC

    230V AC230V AC

    Metallic Pipes

    connected to

    ground

    PC

    Gidhni site plan-Explanation as what could have happened.

    Chance No2. Lightning/Radiation in the metalic pipes can create over voltage on all the conductors passing through the metalic pipes. Chances of failure of PCBs

    connected to Nonvital inputs in controller as well as SSI, RS485 ports connected to both PC and SSI, Power supply to control PC, 230 Volt Inverter output of IPS.

    Axle CounterIPS roomSM

    RoomTVSS

  • 7/28/2019 lightening effects and protection.pps

    94/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    TreeTree

    EP1 EP2 EP3

    EP4 EP5 EP6

    Non Vital inputs affected. Recommended device 1. LSA-BF-24

    RS485 ports affected. Recommended Device 2. SD25V11 / 25

    Power supply of PC affected. Recommended device 3. VF 230 AC

    230 V AC output from IPS No failure occurred. May be due to the presenceof SPD

    RS 485 ports of Monitoring PC also require protection. Recommended

    Device 2. SD25V11 / 25

    Rack1 Rack2Relay

    panel

    Battery

    Room

    PC Control Panel

    RS485/232 port PC to SSI

    32 pairs of I/O Nonvital

    C/O PanelSMR

    PanelAC

    Panel

    AC

    Panel

    DC

    Panel

    24V DC

    12V DC

    230V AC230V AC

    Metallic Pipes

    connected to

    ground

    PC

    SSI - Recommendation

    Axle CounterIPS roomSM

    RoomTVSS

  • 7/28/2019 lightening effects and protection.pps

    95/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    TreeTree

    EP1 EP2 EP3

    EP4 EP5 EP6

    Rack1 Rack2Relay

    panel

    Battery

    Room

    PC Control Panel

    RS485/232 port PC to SSI

    32 pairs of I/O Nonvital

    C/O PanelSMR

    PanelAC

    Panel

    AC

    Panel

    DC

    Panel

    24V DC

    12V DC

    230V AC230V AC

    Metallic Pipes

    connected to

    ground

    PC

    Earthing directly from SSI to

    earth pit is not recommended

    Earth busbar fro SSI room has to be

    connected through the common earth bus

    bar in the IPS room.

    Arresters to the Dc input of SSI

    SUMMARY

    Electrical Connections to Microlok and Computers from IPS

    1. 24 V DC

  • 7/28/2019 lightening effects and protection.pps

    96/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    2. 12 V DC

    3. 230 V AC (for PC)

    Other Inputs and Outputs

    1. Vital inputs from relay panel

    2. Non Vital inputs from Station control room

    3. RS485 ports from PCs

    4. RS 485 ports to PCs

    5. Separate earthing done for SSI room and IPS room

    Probable Chance of Over Voltage

    1. Over Voltage on the body of all devices

    2. Induced EMF on the cables connected between two buildings through

    metalic pipes3. Difference in potential rise of SSI room and IPS room earth may create

    flash over.

    Recommended SPDs

    24V DC - VF24 DC

    12V DC - VF12 DC

  • 7/28/2019 lightening effects and protection.pps

    97/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    230 V ACVF230 AC on the input of PCs

    RS485 PortsSD25V11 / 25

    All non vital inputs and outputs from the Microlok to the control panel.. LSA-

    BF-24

    LSA-BF-24 device for Control panel inputs and outputs

    One no spark gap between the two earth so that in case of excess voltage rise in

    one earth, the effect is neutralized.

    I tem no 1 to 4 can be implemented in the f irst phase and i tem no. 5 and 6

    can be implemented on the next phase.

    7.7 Additional installation guidance

    Installations should be based on IEC 60364-5-534 Where lightning arresters are

  • 7/28/2019 lightening effects and protection.pps

    98/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    The lines to the arrester elements should not be more than 0.5 metres long, so thatno excessive voltage rise can take place in serious cases.

    Installations should be based on IEC 60364 5 534. Where lightning arresters areused before the meter, for Germany the TAB (Technische Anschlu Bedingungen)

    conditions of the VDEW must be observed.

    The earth of the arrester must always be bonded with the earth of the consumerinstallation. If the PE busbar of a distribution board are used, the PE busbar must be

    connected to the installation earthing point by a connection which is capable to carrythe lightning current (16 mm to the equipotential bonding bar).

    Parallel installation between unprotected conductors (eg to the meter) and protectedconductors (eg supply voltage) must be avoided.

    7.8 Connecting wires

    If it is not possible to apply the recommended line length ( 0 5m) the surge protection

  • 7/28/2019 lightening effects and protection.pps

    99/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    If it is not possible to apply the recommended line length ( 0.5m), the surge protectiondevices should not be connected with a spur line, but in a V-shape.

    Take care to run the outgoing and return lines as far apart as possible.

    Main equipotential

    bonding busbar

    Bonding busbar

    Main equipotential

    bonding busbar

    0.5 m

    0.5 m

    7.9 Application example / Wrong Installation

  • 7/28/2019 lightening effects and protection.pps

    100/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    UL = L * di/dt

    UL = 3H * 1kA/s

    UL = 3kV

    7.10 Application example / Correct Installation

  • 7/28/2019 lightening effects and protection.pps

    101/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    IN OUT

    Loping of Wires

    Wiring

  • 7/28/2019 lightening effects and protection.pps

    102/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Input and output wires to the arrester

    box should be clearly separated.

  • 7/28/2019 lightening effects and protection.pps

    103/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Quality of earthing has to be

    improved

    Chapter 8

  • 7/28/2019 lightening effects and protection.pps

    104/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Summary

    8.1 Product Guarantee

  • 7/28/2019 lightening effects and protection.pps

    105/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    OBO- Bettermann gives a 5 years product guarantee of allovervoltage protection devices

    8.2 TBS Construct

  • 7/28/2019 lightening effects and protection.pps

    106/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    OBO CONSTRUCT TBS

    Planning software for the construction

    of surge protection concepts in TN, TT

    and IT network systems in a building.

    including: Texts for use in tenders, Technical information on the products

    circuit diagrams product overviews calculation of lightning protection class

    The program is designed to be clear andeasy to use.

    8.3 The concept of overvoltage protection

    Energy supply Telecommunications

  • 7/28/2019 lightening effects and protection.pps

    107/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    All protectors for the different kind of applications you

    find in the OBO Bettermann TBS product range!

    Energy supply

    Measurement and

    control lines

    Telecommunications

    Other data lines

    The best lightning and surge protection

    will be ineffective unless

    every incoming line to the building

    is included!

    That is the end of our seminar!

  • 7/28/2019 lightening effects and protection.pps

    108/108

    9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352

    Now we are ready to answeryour questions!

    Thank you for your

    attention!