Upload
lvsaru
View
220
Download
0
Embed Size (px)
Citation preview
7/28/2019 lightening effects and protection.pps
1/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Welcome to the expert seminar on
"Surge protection in electrical energy technique
Presented by: S. Gopakumar, Director, Cape Electric Corporation
7/28/2019 lightening effects and protection.pps
2/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
7. Applications
2. How lightning discharges arise
1. Introduction
3. The causes and effects of surge voltages
4. Protection against lightning discharges
6. Type of arresters and selection
5. International Standards
8. Summary / Question and Answers!
Seminar contents and sequences
7/28/2019 lightening effects and protection.pps
3/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
1.0 Introduction
Lightning protection systems
External lightning
protection
Air Termination
Down Conductor
Earth Termination
Room shielding
Internal lightning
protection Surge protection
The measures taken toensure surge protection,are separate from theinstallation of a lightningprotection system.
However, they must becoordinated with theinternal lightning protection.
Lightning equipotential
bonding
Room shielding
Safety Distance
Internal lightning
protection Surge protection
The measures taken toensure surge protection,are separate from theinstallation of a lightningprotection system.
However, they must becoordinated with theinternal lightning protection.
Lightning equipotential
bonding
7/28/2019 lightening effects and protection.pps
4/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Chapter 2
How lightning discharges arise
7/28/2019 lightening effects and protection.pps
5/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
2.2.1 How is a Lightning Current Waveform
-40
-20
0
0 200 400 600 800 1000
s
kA
100 300 500 700 900
Period between the discharges,up to a few milliseconds
Note: The energy effects of all lightning discharges within an ionisation channel are simulated
by the test waveform 10/350 s in IEC 61024-1, Protection of structures against lightning
and IEC 61312-1, Protection against lightning electromagnetic impulse (LEMP).
Main discharge
Secondary dischargei
7/28/2019 lightening effects and protection.pps
6/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
2.2.2 Frequency of lightning strikes
0
5
10
15
20
25
0-10
10-2
0
20-3
0
30-4
0
40-5
0
50-6
0
60-7
0
70-8
0
80-9
0
90-10
0
100-110
110-120
120-13
0
130-140
140-150
150-160
160-170
170-180
180-190
190-200
Lightning amplitude [kA], positive and negative lightning strikes
Lightningfrequency,%
7/28/2019 lightening effects and protection.pps
7/108
7/28/2019 lightening effects and protection.pps
8/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Chapter 3
The causes and effects of surge voltages
7/28/2019 lightening effects and protection.pps
9/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.1.1 A direct strike on a building without anexternal lightning protection installation
7/28/2019 lightening effects and protection.pps
10/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.1.2 Effects (direct strike)
A direct strike on a building without
external lightning protection system
If an electric current flows as a consequence ofa lightning strike to a building, energy isconverted, heating the part of the buildingthrough which the current is conducted to earth.
In addition, material may be melted or ejectedat the foot of the strike.
0
2dtiRW
Effects: fire hazardDue to: specific energy,charge
0
idtQ
7/28/2019 lightening effects and protection.pps
11/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.2.1 Direct strike on an overhead high-voltage line
7/28/2019 lightening effects and protection.pps
12/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.2.2 Effects
Direct strike on an overhead
high-voltage line
For a lightning strike on an overhead line, theimpedance at the first moment is determinedby the surge impedance of the line.
This impedance (ZW) is usually in the regionof 400 to 500 ohms for a single conductor.
2Z IU W
Effects: Overvoltages (voltage surges)
Due to: Maximum lightning impulse current
7/28/2019 lightening effects and protection.pps
13/1089,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.3.1 Direct strike on a low-voltage overhead line
7/28/2019 lightening effects and protection.pps
14/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.3.2 Effects
Direct strike on a low-voltage
overhead line
The preconditions of a direct strike on a low-voltage overhead line are not the same as fordirect strikes on high-voltage overhead lines.
The fundamental difference is in the proximityto the building through which the conduction
of partial lightning currents is possible.
Effects: Overvoltages (surges) in the low-voltage network, partial lightning current
due to: Maximum lightning impulse current
Source: Kopecky/Aachen
7/28/2019 lightening effects and protection.pps
15/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.4.1 A direct strike on a building with an externallightning protection installation
7/28/2019 lightening effects and protection.pps
16/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
L1L2L3
PEN
3.4.2 Effects
A direct strike on a building with an
external lightning protectionbut without equipotential bonding
If the lightning current from a lightning strike isdiverted to earth, there will be a voltage rise atthe earthing point of the installation. This will becarried into the house via the equipotentialbonding system.The equipotential bonding for lightning protection(lightning arresters / class B) prevents damage tothe electrical installations.
earthoninstallatiRiU
Effects: Overvoltages, insulation breakdownDue to: Maximum lightning impulse current
7/28/2019 lightening effects and protection.pps
17/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.5.1 Lightning strike to a tree (close strike)
7/28/2019 lightening effects and protection.pps
18/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.5.2 Effects
Lightning strike to a tree (close strike)
If current flows as a result of a lightning strike to atree, energy is converted (fire hazard).
In addition, the current diverted to earth can becoupled into the earth lines or the nearby building.
Also the electromagnetic field could destroyelectronic equipments inside the building.
Effects: Coupling of the lightning current into earthlines, inductive and galvanic coupling,fire hazard.
7/28/2019 lightening effects and protection.pps
19/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.6.1 Inductive coupling
7/28/2019 lightening effects and protection.pps
20/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.7.1 Switching actions
7/28/2019 lightening effects and protection.pps
21/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.7.2 Effects
Switching actions
Switching actions occur almost everywherewhere work is done with electrical energy.
Especially are areas in which large inductiveloads are switched, for example:
MotorsTransformersChokes
Welding equipmentLong runs of fluorescent tubes
Effects: Overvoltages (surges) on network linesDue to: Energy being returned to the network
Source: Kopecky/Aachen
7/28/2019 lightening effects and protection.pps
22/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.8 Transient overvoltages
Voltage- disturbances in low-voltage networks
30
26
22
18
10
6
2
14
Overvoltage factor / K
1500(I)
2500II
4000(III)
6000(IV)
rv
Lightning surges
Switching surges
Temporary voltage rises
Harmonics and
slow and fast voltage fluctuations
Voltage breakdown
Short interruptions
7/28/2019 lightening effects and protection.pps
23/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3.9 History of EMC
1950 1960 1970 1980 1990
Disturbance variables
Time
Immunity to interferenc
Now
Vacuum tubes
Transistors
Integrated circuits
7/28/2019 lightening effects and protection.pps
24/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
4.3 IEC 60364-4-443 Insulation coordination
6000 V4000 V
2500 V1500 V
IV III II I
Lift
Staircase lighting
Apartments
400 V 230/400 V 230 V 230 V
Surge withstand voltage of insulation
Installation category
7/28/2019 lightening effects and protection.pps
25/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
4.2 Lightning protection zone concept accordingIEC 61312-1
B Lightning arrestersto VDE 0675 Part 6 (A1, A2)Requirement class B (
7/28/2019 lightening effects and protection.pps
26/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
4.1 Equipotential bonding for lightning protectionaccording IEC 61024-1 and IEC 61312-1
The 100% of lightning energy breaks downas follows:
a) 50% of the lightning current will flow through
the ground
b) 50% of the lightning current will flow over the
connected metal parts out of the building:
about 10% to the water pipe (metal)
about 10% to the gas pipe (metal)
about 10% to the oil pipe (metal tank)
about 10% to the sewage pipe
about 10% to the power suppliers incoming feed
max. 5% or 5 kA shared across all data lines
50 %
50 %
7/28/2019 lightening effects and protection.pps
27/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Chapter 5
International Standards
5 1 N ti l d i t ti l t d d
7/28/2019 lightening effects and protection.pps
28/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
5.1 National and international standards(lightning protection)
IEC 61024-1
External lightning
protectionInternal lightning
protection
Lightning protection System (LPS)
Air
TerminationDown
ConductorEarth
TerminationRoom
ShieldingSafety
DistancesLightning
Equipotential
Bonding
7/28/2019 lightening effects and protection.pps
29/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
5.2 Different Standards for lightning protection
Protection of structures against lightning
European StandardCENELEC
ENV 61024-1
International StandardIEC
IEC 61024-1 General Principles IS
IEC 61024-1-1 Guide A: Selection of
IS protection levels for LPS
IEC 61024-1-2 Guide B: Design,IS installation, maintenance
and inspection of LPS
IEC 61663-1 Fibre optic installations IS
IEC 61663-2 Lines using metallic conductors IS
Lightning protection - Telecommunication lines
7/28/2019 lightening effects and protection.pps
30/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
5.3 Different Standards for LEMP
Protection against lightning
electromagnetic impulse (LEMP)
European StandardCENELEC
prEN 61312-1
International StandardIEC
IEC 61312-1 General Principles IS
IEC 61312-2 Shielding, bonding and
TS earthing inside structures
IEC 61312-3 Requirements of surge
TS protective devicesIEC 61312-4 Protection of equipment
TR in existing structures
7/28/2019 lightening effects and protection.pps
31/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Chapter 6
Types of arrester and typical applications
7/28/2019 lightening effects and protection.pps
32/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.1.1 Spark gap technology
Metallic Conductors
Air Gap
The operating voltage can be determined by the distances between the electrodes.Spark gaps are arresters in which two or more electrodes in series are opposed to each other. Theelectrodes consist of incombustible material ( metal, carbon, etc).If a spark gap fires, the operating voltage collapses to the anode-cathode drop voltage.
7/28/2019 lightening effects and protection.pps
33/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Conducting
Materiel
Air Gap
6.1.1 Spark gap technology
Blow out / Exhausting Hole
7/28/2019 lightening effects and protection.pps
34/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.1.1 Spark gap technology
During a Lightning
current admission, thespark gap blows hot
ionized gases through
the holes provided in the
arrester. Ionized gases
are good conductors of
electricity. Hence Blowout type arresters
should be connected
away from live parts.
These devices should be
installed in pressure
releasing typeenclosures
6 1 1 S k h l E l d
7/28/2019 lightening effects and protection.pps
35/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.1.1 Spark gap technology Encapsulated
Output impulse
4
2
1 S
U(kV)
t/(s)Input impulse
(kV)
1
0,5
1 S
U
t/(s)
ElectrodesSpacers made frominsulating material
High Follow Current extinguishing capacity is achieved by connecting Spark Gaps in series,
There by splitting the arc.
6 1 2 V i t t h l
7/28/2019 lightening effects and protection.pps
36/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.1.2 Varistor technology
Intermediate phase
ElectrodesEpoxy resin
sintered zinc oxide grains withadditives of other metallic oxides
Zinc oxideMicro-varistor
= 10 m
tinned copper wire
1) Source: Siemens DruckschriftMetalloxid-Varistor SIOV
t/(ns)Output impulse
U(V)
Input impulse
U
t/(ns)
(V)
Varistors are voltage-dependent resistors with a highly non-linear U/I characteristic.
The electrical properties arise from a large number of micro-varistors connected in paralleland in series.The transitions between the micro-varistors age under the influence of overvoltages.
6 1 3 Di d t h l
7/28/2019 lightening effects and protection.pps
37/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.1.3 Diode technology
Input impulse
U
t/(ps)
(V)
Output impulse
U
t/(ps)
(V)
Voltage(V)
Current
(A)UC UB UR
UCUBUR
Transzorb diodes (also known as suppresser diodes) are diodes that limit both positive
and negative voltage.They switch in the picosecond region and are especially well suited for use in data lineprotection devices.
6 1 4 Arrester technologies
7/28/2019 lightening effects and protection.pps
38/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.1.4 Arrester technologies
How to limit big lightning currents
and surge overvoltages!
Spark gaps
High-performancespark gaps have avery high dischargecapacity, which is whythey are used aslightning arresters.
Varistors
Varistors are used insurge arrestersand fineprotection devices.Unlike other types ofarrester, their ability tocarry lightning current
is limited.
Diodes
Transzorb diodes, alsoknown as suppresserdiodes, are used as diodearresters only in fineprotection devices.They are characterised by
a fast response, but theirdischarge capacity islimited.
6 2 1 Arrester Standardisation
7/28/2019 lightening effects and protection.pps
39/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.2.1 Arrester Standardisation
IEC 61643-1/ (VDE 0675, P.6/A1/A2)Surge Protective Devices Connected to Low-Voltage Power Systems:
Performance requirements and testing methods
IEC 61643-12Surge Protective Devices Connected to Low-Voltage Power Systems:
Selection and application principles
IEC 61643-21Surge Protective Devices Connected to telecommunication and signalling networks.
Performance requirements and testing methods
IEC 61643-22Surge Protective Devices Connected to telecommunication and Signalling Networks
Selection and application principles
6 2 2 Arrester Standardisation
7/28/2019 lightening effects and protection.pps
40/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
6.2.2 Arrester Standardisation
IEC 61643-1:1998 / VDE 0675, P.6/A1/A2Surge Protective Devices Connected to
Low-Voltage Power Systems
Type 1 / B
Arrester for lightning
equipotential bonding.
Tested: Iimp (10/350)
In (8/20)
Type 2 / C
Arrester for Overvoltage
surge protection.
Tested: Imax (8/20)
In (8/20)
Type 3 / D
Fine protectors for mobile
use and for the top-hat rail.
Tested: Uoc (1,2/50)
(8/20)
6.3.1 Types of SPDs IEC 61643-12
7/28/2019 lightening effects and protection.pps
41/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Examples of one-port SPDs
aKey
a. One-port SPDs
U
U
Ub b. One-port SPD with separate input and
output terminals
SPDcc. Generic symbol for a one-port SPD
6.3.2 Types of SPDs IEC 61643-12
7/28/2019 lightening effects and protection.pps
42/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Figure 2 :- Examples of two-port SPDs
a. Three-terminal two-port SPDa
U
Z
bU
Z
Z b. Four-terminal two-port SPD
c SPD
c. Generic symbol for a two-port SPD
ZSeries impedance between input andoutput terminals
6.4.3 Types of SPDs IEC 61643-12I
7/28/2019 lightening effects and protection.pps
43/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Response of one-port and two-port
SPDs to a combination wave impulse
aa. Applied current
waveform0 t s
Ip
820
b U
0 t
U
b. Response of voltage
limiting type SPD
c
0 t
U
c. Response of voltage
switching type SPD
6.4.4 Types of SPDs IEC 61643-12
Figure 3 :- Response of one-port and two-port
7/28/2019 lightening effects and protection.pps
44/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
f. Response of two-port
voltage limiting type SPD
with filteringf
0 t
U
U
Z
NOTE : The voltage levels are only representative and not an indication of actual values.
g p p p
SPDs to a combination wave impulse
d
0 t
U
U
d. Response of one-portcombination type SPD
e
0 t
U
U
Z
e. Response of two-port
combination type SPD
6.5 Types of SPDs IEC 61643-12
7/28/2019 lightening effects and protection.pps
45/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Single voltage limiting component: Limiting type SPD
Single voltage switching component: Switching type SPD
U
Combination of voltage limiting and switching components:
Combination type SPD
6.6.1 IEC 61643 12: Coordination Rules and Principals
7/28/2019 lightening effects and protection.pps
46/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
1. Between two ZnO Varistor based SPDs: Possible only for one port
limiting type SPDs
2. Between a gap based arrester (One port switching type) and a ZnO
Varistor based arresters (One port limiting type).
Coordination between Gap based arrester with voltage protection level of < 4KV and aresponce time of 200 ns with a ZnO based arrester with a Nominal Discharge Current In of5 KA requires approximately 27.2 H inductor or 27.2 meter cable for a perfectcoordination
6.6.2 Coordination.
7/28/2019 lightening effects and protection.pps
47/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Class C arrester starts discharging. Voltage V1 drops at Class C. Corresponding to di/dt
V2 drops at inductor. When V1+V2 = Voltage protection level of Class B arrester, it starts
conducting.
4 KV
I
V
3.2 KV
V 800 V
V
t
4 KV
Class CSingle Port
Voltage Clamping TypeRated for 8/20 s
Class BSingle Port
Voltage Switching TypeRated for 10/350 s
V1
V2
6.6.3 Response of Class B , C and Inductor for a low voltage High Energy Surge.
7/28/2019 lightening effects and protection.pps
48/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Class C arrester starts discharging and will clamp the voltage to V1. Inductor starts clamping the
voltage. Since di/dt is very low, voltage V1 comes to minimum after the initial rise. Complete energypasses through Class C.
I f Class B arrester has a low v ol tage protect ion level , i t has more con trol on th is kind o f surge.
4 KV
6.6.4 Class B & Class C arresters without proper coordination
7/28/2019 lightening effects and protection.pps
49/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Class B arrester never operates since Class C arrester clamps the voltage at less than 2 KV at 40
KA. The entire current flows through Class C arrester resulting in the failure of Class C
4 KV
Low Inductor / Low Distance
V 1.75 KV at40 KA
6.7 Follow Current
7/28/2019 lightening effects and protection.pps
50/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Once Class B arrester is switched on, it shorts the Line and Neutral (or Line and Earth). After the surge current,
short circuit current of the network starts flowing through the arrester. Finally the backup fuse F1 or F2 interruptsthe short circuit current. Short Circuit current following the surge current is called as follow current. Class B
arrester should be capable of extinguishing this follow current without the help of fuse F1 or F2.
Class CSingle Port
Voltage Clamping Type
Rated for 8/20 s
Class BSingle Port
Voltage Switching Type
Rated for 10/350 s
4 KV
F1
F2
Sub StationTransformer
6.8.1 Selection Of Class B arresters for Power Line Protection
7/28/2019 lightening effects and protection.pps
51/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
1. Enclosure
Exhausting / Encapsulated
Special Fireproof / Explosion
proof Enclosure required
Special enclosures with spring
loaded doors are generally used.
The purpose of spring loaded doors
is to open automatically in case of
high pressure inside the enclosure
due to a Blowout
No Special requirements
Can be mounted in
ordinary Metallic/ PP
enclosures
6.8.2 Selection Of Class B arresters for Power Line Protection
2. Coordination2. Coordination: If Coordination Distance/Inductance Value is not properly maintained
7/28/2019 lightening effects and protection.pps
52/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Voltage Protection Level of Class B
arresters
Minimum Coordination Distance / Inductance
Value required
Line to Neutral 4 KVNeutral to Earth 4 KV
15 meter cable or 15 H Inductor
Line to Neutral 2 KVNeutral to Earth 2.5 KV
5 meter cable or 5 H Inductor
Line to Neutral 1.5 KVNeutral to Earth 1.5 KV
Coordination not required
Line to Neutral 1.5 KVNeutral to Earth 4 KV
15 meter cable or 15 H Inductor
Line to Neutral 4 KVNeutral to Earth 1.5 KV
15 meter cable or 15 H Inductor
2. Coordination2. Coordination: If Coordination Distance/Inductance Value is not properly maintained
Class B arrester will not operate resulting the failure of Class C arrester.
6.8.3 Selection Of Class B arresters for Power Line Protection
7/28/2019 lightening effects and protection.pps
53/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
3. Follow Current.
What happened on a spark gap during a surge current?
The spark gap will make an equipotential bonding between line and earth, or line and neutral.
That depends where the gap has been installed. So the spark gap will make a short circuit during the
surge.What happened during a shortcircuit?
During the whole time, the nominal voltage of 230V is still on our spark gap. So this nominal
voltage pushes now a short circuit current over your shorted spark gap arrester.
What happened after the surge?If the surge current is over, the spark gap is still in the same condition, that it is like a shortcircuit and the short circuit current from the main line is still going over the spark gap. Now the spark
gap must be able, to cut off this short circuit current by itself, before the fuse will cut off the current.
Follow Current
The short circuit current following the surge current is called as Follow Current. Follow current is equal to
the peak short circuit capacity of the network. The class B arrester should eliminate (cut off) this shortcircuit current without the help of Back up Fuse. Short circuit value can be calculated based on the
transformer capacity and the distance between the transformer and installation. Approximately 10 to 15KA
will be ideal for telecom installations. Otherwise this will blow the fuses in case of a Lightning
4 Follow current: Fuse Selection of Class B Arrester
6.8.4 Selection Of Class B arresters for Power Line Protection
7/28/2019 lightening effects and protection.pps
54/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
4. Follow current: Fuse Selection of Class B Arrester
Short Circuit at installation Point
in KA
Fuse selection of Class B Arrester with
Short Circuit extinguishing capacity of
4KA
5,6,10 &25 Higher values of short circuit current
will cause the backup fuse to blow.
Use of backup fuse higher than 125 Amps will cause the surgearrester to fail due to excessive follow through current
1.5 50
2 63
2.5 80
3 1003.5 100
4 125
1 35
6.9.1 Type of arrester / Lightning arrester class B
7/28/2019 lightening effects and protection.pps
55/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Requirement class : B according VDE 0675, part 6Requirement class : Type 1 according IEC 61643-1
Principle of operation : Spark gap / Exhausting(Blow out type)
Impulse current Iimp : 60 kA(10/350) per pole for LA60-B100 KA (10/350) for LA100-B
Protection level Up : < 4 kVResponse time : < 100 ns
Series fuse : separate backup fuse required
Lightning Arrester LA60-B and LA 100-B
Application: Where there is an external lightning protectioninstallation, overhead line feed and high networkavailability.
6.9.2 Type of arrester / Lightning arrester class B
7/28/2019 lightening effects and protection.pps
56/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Requirement class : B according VDE 0675, part 6Requirement class : Type 1 according IEC 61643-1
Principle of operation : Spark gap / Multi-Carbon-Technology(encapsulated)
Impulse current Iimp : 50 kA(10/350) per pole Discharge current Imax : 120 kA(8/20) per pole
Protection level Up : < 2 kV Response time : < 100 ns Series fuse : no separate series fuse in
installations up to 500 A Mark of conformity : VDE, VE, KEMA, EZU, MEEI
LightningController MC 50-B VDE
Application: Where there is an external lightning protection installation, overhead
line feed and high network availability.In industrial plants and for high lightning protection classes.
6.9.3 Type of arrester / Lightning arrester class B
7/28/2019 lightening effects and protection.pps
57/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Requirement class : B according VDE 0675, part 6Requirement class : Type 1 according IEC 61643-1
Principle of operation : Spark gap / Multi-Carbon-Technology(encapsulated)
Impulse current Iimp : 125 kA(10/350) per pole Discharge current Imax : 200 kA(8/20) per pole Protection level Up : < 2,5 kV Responce time : < 100 ns Mark of conformity : VDE, VE, KEMA, EZU, MEEI
LightningController MC 125-B/NPE
Application: Where there is an external lightning protection installation, overhead
line feed and high network availability.Lightning arrester for the installation between N and PE.
6.9.4 Application advantage / Encapsulated ArresterLightningController MC
7/28/2019 lightening effects and protection.pps
58/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
g g
Advantage for the installer by using
the OBO LightningControllerMC 50-B VDE and MC 125-B/NPE
No special housing necessary!
No minimum distances through
other electrical installations!
6..9.5 LightningController MC
7/28/2019 lightening effects and protection.pps
59/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
LightningController MC
MC 50-B VDE
MC 125-B/NPE
Tested according:
E DIN VDE 0675
Teil 6 + A1 + A2
IEC 61643-1 +37 A/95/CDV
6.9.5 Coordinated LightningController MCD
7/28/2019 lightening effects and protection.pps
60/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Improvement of the
protection level to < 1,3 kV
Advantage for the builder of the control cabinet: No need of LightningCoordinator LC 63
2,5 kV
2,0 kV
Direct parallel connection betweenLightningController MCD // SurgeController V20-C is possible!
Important for mobile transmitter stations and industrial distribution!
6.9.6 LightningController MCD // SurgeController V20-C
7/28/2019 lightening effects and protection.pps
61/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Direct parallel connection betweenLightningController MCD // SurgeController V20-C
No decoupling element and no C25-B+C/NPE
is necessary!
6.9.7 Class B & Class C together Grid Surge
Applicable only for Class B
arrester with a response time
less than 100 nano sec
7/28/2019 lightening effects and protection.pps
62/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
MCD50-B arresters switches at a low voltage of 700 volt if the energy content is more.Initially Class C arrester starts discharging when the voltage V1 continues for more time,
Class B arrester switches at a low voltage thereby reduces the stress on Class C arrester.
1.3 KV
700 V 1.3 KV
No Inductor / Distance
1.3 KV at InMCD 50-B
V20-C
less than 100 nano sec
6.9.8 Type of arrester / Lightning + surge arresterclass B + C
7/28/2019 lightening effects and protection.pps
63/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Requirement class : B + C according VDE 0675Requirement class : Type 1 + 2 according IEC
Principle of operation : Varistor technology Impulse current Iimp : 25 kA(10/350) per 4-pole block Discharge current Imax : 200 kA(8/20) per 4-pole block
Protection level Up : < 2 kV Series fuse : no separate series fuse in
installations below 160 A Mark of conformity : EZU, MEEI, VdS- approved
Application: Where there is an external lightning protection installation, overheadline feed and high network availability.VdS-approved.
CombiController V25-B+C
6.9.9 Type of arrester / Surge arrester class C
7/28/2019 lightening effects and protection.pps
64/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Requirement class : C according VDE 0675, part 6Requirement class : Type 2 according IEC 61643-1
Principle of operation : Varistor technology Discharge current Imax : 40 kA(8/20) per pole Nom. discharge current In : 20 kA(8/20) per pole
Protection level Up : < 1,3 kV Series fuse : no separate series fuse in
installations below 125 A Mark of conformity : VE, UL, KEMA, EZU, MEEI
SurgeController V20-C
Application: Surge arrester for the installing in the main- and sub- distribution
boards.
6.9.10 Further surge products / Main lines
7/28/2019 lightening effects and protection.pps
65/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Audible signallingdevice AS forV 25-B+C and V20-C
Remote signallingdevice FS forV 25-B+C and V20-C
Fine protectiondevice KNS-D
Fine protectiondeviceVF 230-AC-FS
Checking systemISOLAB
Decoupling element LC 63
7/28/2019 lightening effects and protection.pps
66/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
7. Application
7.1 Procedure for selecting surge arresters
7/28/2019 lightening effects and protection.pps
67/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Buildinglightning protection installation?
overhead line?
lightning current coupling possible?
Lightning arresters(Requirement class B)
Installation as close as possible tothe entrance of the building
Surge protection(Requirement class C)
Installation in sub-distribution board
Surge protection
(Requirement class D)Installation as close as possible tothe device to be protected
yes
Surge protection
(Requirement class D)Installation as close as possible to thedevice to be protected
Surge protection(Requirement class C)
Installation In sub-distribution board
Coordinationbetween B and Carresters for line
lengths below 5metres
Coordinationbetween C and D
arresters
no
Class 1(B) and Class 2(C) protectionfor Lightning & Surge Voltage Protection Equipment in TT System
RRF1
(As per IEC 61024-1, IEC 61312-1, VDE V0100-534)
ENT
7/28/2019 lightening effects and protection.pps
68/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
SPD1
SPD3
SPD2
SPD4
R
Y
B
N
R
Y
B
N
PE
ACCOMMERC
IALMAINS
ACDISTRIBUTIONPANEL
INPOWER
ROOM
EARTH
F2
F3
SPD5
SPD7
SPD6
SPD8
F4 F5 F6
(Class 1 / B) (Class 2/ C)
Note : The above system is forthree phase configuration. For
single phase one phase
conductor and one neutral
wire shall be used
PE -: Protective Earth
F1, F2, F3, F4, F5, F6 -: Fuses of Proper Rating
SPD1, SPD2, SPD3 -: Surge Protection Devices of rating Iimp 50KA, 10/350s
SPD4 -: Surge Protection Devices of rating Iimp 100KA, 10/350sSPD5, SPD6, SPD7 -: Surge Protection Devices of rating Iin 10KA, 8/20s
SPD8 -: Surge Protection Devices of rating Iin 20KA, 8/20s
LV / HV -: Low / High Voltage Disconnector
Iimp -: Value of Lightning Impulse Current 10/350s
Iin -: Value of Nominal Discharge Current 8/20s
-: Co-ordination cable element
TOEQUIPME
7.1.1 Installation example
7/28/2019 lightening effects and protection.pps
69/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
-- Building without external lightning protection --
1. Overvoltage arrester class C
2. Overvoltage arrester class Cin the sub- distribution board
3. Overvoltage arrester class Cfor photovoltaic- facilities
4. Overvoltage arrester class D
7.1.2 Installation example
7/28/2019 lightening effects and protection.pps
70/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
-- Building with external ligtning protection --
1. Lightning Arrester class Bor the CombiController
2. Overvoltage arrester class C
3. Overvoltage arrester class D
7.1.3 Installation example
7/28/2019 lightening effects and protection.pps
71/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
-- Office building with external lightning protection --
1. Lightning arrester class B
4. Overvoltage arrester class D
3. Overvoltage arrester class C
2. Lightning arrester class Bor CombiController
7.1.4 Installation example
7/28/2019 lightening effects and protection.pps
72/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
-- Industrial building with external lightning protection --
1. Lightning arrester class Bor CombiController
2. Overvoltage arrester class C
3. Overvoltage arrester class D
ENT
R1
Class 1 and Class 2 arresters in enclosure with standard inductor. Suitable for small and medium exchanges in TTnetwork
7/28/2019 lightening effects and protection.pps
73/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
AC
COMMERCIAL
M
AINS
TO
EQUIPM
Body earthing of all electronic equipments in the
exchange.
Direct earth connection from the body of equipment
to outside earth pit is not permitted.
EBB
To earth pit
Y
B
N
PE
2
3
456
7 8 9
10
11 12 13
14
PE -: Protective Earth
1,2,3,4,5,6 -: Fuses of Proper Rating
7,8,9 -: Surge Protection Devices of rating Iimp >50KA, 10/350s10 -: Surge Protection Devices of rating Iimp > 100KA, 10/350s
11,12,13 -: Surge Protection Devices of rating In > 10KA, 8/20s
14 -: Surge Protection Devices of rating In > 20KA, 8/20s
Iimp -: Value of Lightning Impulse Current 10/350s
In -: Value of Nominal Discharge Current 8/20s
EBB -: Equipotential bonding bar
: Inductor (made by the SPD manufacturer
Earthing
7/28/2019 lightening effects and protection.pps
74/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Incomingpanel
Surgearresters
Powerplant
Exchange
Battery
+_
Other RFdevices
TelephoneLines
PE
PE
Earthing Schematic for exchanges
Earthing
7/28/2019 lightening effects and protection.pps
75/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Incomingpanel
Surgearresters
Powerplant
Exchange
Battery
+_
Other RFdevices
TelephoneLines
PE
PE
Earthing Schematic for exchanges: Wrong connection
Earthing
7/28/2019 lightening effects and protection.pps
76/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Incomingpanel
Surgearresters
Powerplant
Exchange
Battery
+_
Other RFdevices
TelephoneLines
PE
P
E
Earthing Schematic for exchanges: Bonding of different earthings
PE
B1
B1-Special bonding device to bond different earthnigs, 100KA with voltage protection level 1300 V
Railways Application : Token less Block Instrument
7/28/2019 lightening effects and protection.pps
77/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Used for signaling / train movement
between station. Stations are interconnected either byoverhead line or by UG cable.
20 to 35 volt signals are transmittedfrom the stations depending upon thedistance between stations.
12 volt signal is received at thestations.
Transmission and reception is donethrough the same lines. The same lineis also used for voice conversation.
Railways Application : Token less Block Instrument
7/28/2019 lightening effects and protection.pps
78/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
The input wires are connected to the blockinstrument via spark gaps.
These wires are connected parallely to thecoil of pick up relays, contact oftransmission relays and telephone device.
During lightning season, over voltagechances are high in places where overheadline are used.
If the over voltage occurs when the signal
lines are transmitting, chances of fusefailures are more due to the follow currentcreated by the spark gap during adischarge.
Even though spark gaps are installed in theline, failures are occuring in the blockinstrument may be because of the high
voltage protection level.
Railways Application : Token less Block Instrument
7/28/2019 lightening effects and protection.pps
79/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
These arrester were burnt during the lightningas well as it was not capable of protecting theinstrument. (A number of pieces burnt. Mightbe all the devices installed)
The failure of the arrester may be due to highdischarge current (more than 20 KA) enteringthrough the overhead lines.
Surge arresters with a discharge capacity of
20 KA were installed in Castle rock railwaystation which has a high lightning prone place.
Arrester with a high discharge current handling
capacity is required for this application
Railways Application : Token less Block Instrument
A two stage protection is recommended for thistype of devices
7/28/2019 lightening effects and protection.pps
80/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Stage 2
type of devices. MOV based arrester with a maximum
discharge current handling capacity of 40
KA per pole with in built thermaldisconnector and dynamic disconnector isrecommended on stage1 as per thedrawing.
Class D type arrester designed for 12V DCshould be used in the line connected to thecoil of pickup relay.
Class D type arrester designed for 48V DCshould be used in the line connected to thecontact of transmission relay.
We recommend to install these devices in 2stations most proven for lightning for at least 6months.
Stage 1
Railways Application : Token less Block Instrument
7/28/2019 lightening effects and protection.pps
81/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Stage 1
Stage 2
Line 1Line 2
In stage 1 protection, 2 devices are connectedto each line. Hence the total discharge capacityis 80 KA.
Stage 1 protection is required only in placeswhere over head lines are used.
For places where UG cables are used, only
stage 2 protection is required. If the installation is in places where lightning'sare very less, only one Class D type arrester 48V DC can be used for the complete BlockInstrument.
Specification of each devices is as below.
Stage 1 Protection (Only required if over head lines are used)
Railways Application : Token less Block Instrument
7/28/2019 lightening effects and protection.pps
82/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Stage 1 Protection: (Only required if over head lines are used)
Class II Type surge arrester single port MOV based with in built Thermal disconnector and
Dynamic disconnector as well as visual indication to determine faulty arresters withfollowing specification.
1. Maximum Discharge current operating voltage DC 100V
2. Nominal discharge current of Single block : 15KA for 8/20s wave form
3. Maximum Discharge current for 8/20s : 40KA
4. Response time < 25ns.5. Test standard : Class II type SPD as per IEC 61643
6. Voltage protection level at 1KA (8/20s ) : 300 V
7. Fixing : Rail mounting type.
8. Connection wires : 2.5 to 6 Sq.mm.
9. Enclosure : Arrester should be installed in polypropylene enclosure with Transparent coverso that inside devices are visible.
Railways Application : Token less Block Instrument
Stage 2 Protection : For input to the coil of pickup relay.
Surge arrester based on MOV, spark gap and tranz abzob diode with following rating should bei t ll d t th Bl k i t t ith th f ll i ifi ti
7/28/2019 lightening effects and protection.pps
83/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
installed very near to the Block instrument with the following specifications.
Rated current : : 1Amps Nominal Voltage : 12 V Maximum continuous operating voltage : 13.5Volt Nominal discharge current : 10 KA Voltage protection level : 29V
Series Inductance per path : 100H Connection wires : 0.14 to 2.5 mm 2 Fixing : Rail mounting type.
Stage 2 Protection : For output to the contact of transmission relay as well as for the
input and output of telephone .
1. Rated current : : 1Amps2. Nominal Voltage : 48 V3. Maximum continuous operating voltage : 53 Volt
4. Nominal discharge current : 10 KA5. Voltage protection level : 100V6. Series Inductance : 100H7. Connection wires : 0.14 to 2.5 mm 28. Fixing : Rail mounting type.
Railways Application : Token less Block Instrument
Coordination between Stage 1 and 2 Protection.
Distance of 3 meters (or 3 H inductor) should be provided between stage 1 and 2 protection.
7/28/2019 lightening effects and protection.pps
84/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Connection diagram as follows.
Stage 2 SPD :
12V DC
Stage 2 SPD :
48V DC
To Output of block
instrument as well as
to telephone
12V input signal to
block instrument
Interconnection
Stage 1
Protection in
enclosure
3 meter cable length is required between Stage 1 and Stage 2
L1
L1
L2
L2
L1 L2
Railways Application : Token less Block Instrument
Bonding of Input DC supplies
7/28/2019 lightening effects and protection.pps
85/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Equipotentialisation of Input DC supplies to be done with Class D arresters of suitable
voltages.
Nominal Discharge current In: 10 KA
Bonding
Local Equipotentialisation bonding has to be done by connecting the body of Blockinstrument, earth terminal of all class D arresters (stage 2 protection as well as devices
connected to the DC input to of block instrument.
Earthing
Earthing has to be done as per the drawing.
Railways Application : Token less Block Instrument
7/28/2019 lightening effects and protection.pps
86/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
PE
DC inputs to Block instrument
Less than 0.5 meter
EBB
PE Local bonding bar
EBB- Equipotential bonding bar of the room
1. Stage 1 protection
2. Stage 2 protection
3. Arresters for the DC input to Block instrument
Earth wire to the building ground
1 2
2
33
SSI: Gidhni site plan (Existing)
Axle Counter
IPS Room
B tt R
TVSS
7/28/2019 lightening effects and protection.pps
87/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
SSI
Rack1 Rack2 Relay
panel
TreeTree
EP1 EP2 EP3
EP4 EP5 EP6
EP-Earth pit
Battery Room
1. Body of all devices in the SSI room is connected via
metallic cable trays.
2. Body of SSI and relay panels are connected to thecommon bonding bar with copper cables.
3. Body earthing of axle counter is connected
separately on the backside of the room
4. Common bonding bar is connected to earth pits in
front of the room via copper cables.
5. Body of all devices in IPS room are interconnected
through metallic cable trays.
6. Body of IPS and change over panels are connected to
bonding bar in the room via copper cable.
7. Bonding bar in the IPS room is connected to earth
pits via copper cables.
ASM
ROOMDC
Panel
ACPanel 2
ACPanel 1
SMRPanel C/O
Panel
Axle Counter
Relays
SSI
7/28/2019 lightening effects and protection.pps
88/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Rack1 Rack2 Relay panel
P
C
24 V DC from IPS
12 V DC from IPS
RS485 ports
(To SM Room)
230 V ACRS485 port
PAS or Common Bonding/Earthing Bar
From IPS
Inter
connections
1 . DC and AC Power for SSI as well as PC is
received from IPS
2. Interconnections between SSI main rack and
control panel situated in the nearby building
and routed through metallic pipes.
3 . AC and DC power for control panel and
control PC are routed through metallic pipes.
4. RS485 interconnecting wires are routedthrough metallic pipes connected between
the 2 buildings.
From SM
Room
Gidhni site plan:Possible chances of Coupling of partial Lightning Currents through metallic pipes
connected between two buildings. Power and data cables are routed through these pipes
Axle CounterIPS roomSM
RoomTVSS
7/28/2019 lightening effects and protection.pps
89/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
TreeTree
EP1 EP2 EP3
EP4 EP5 EP6
Note: It is clear that there are no lightning and
transient protection devices provided at the SSI
end to protect the inputs (or outputs) against any
surge coming from outside source.
Rack1 Rack2Relay
panel
Battery
Room
PC Control Panel
RS485/232 port PC to SSI
32 pairs of I/O Nonvital
C/O PanelSMR
PanelAC
Panel
AC
Panel
DC
Panel
24V DC
12V DC
230V AC230V AC
Metallic Pipes
connected to
ground
PC
Problem of safety distance.Lightning strike on the wall of the buildings or on the nearby objects can create Inductive coupling of the metallic parts inside the buildings due to thehigh potential created during the current flow.
wall General
7/28/2019 lightening effects and protection.pps
90/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
1. Example of problems with
safety distance on a wall
wall
Electronic
installation
R
L
2. Example of problems with
safety distance on a flat roof
R
L
Electronic
installation
TallObjects
General
SSI: Gidhni site planPossible chances of Coupling of partial Lightning Currents due
to spread of radiation if a lighting strikes very close to the building.
Axle CounterIPS room
Battery
7/28/2019 lightening effects and protection.pps
91/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
EP1
EP-Earth pit
SSI
Rack1 Rack2 Relay
panel
TreeTree
EP2 EP3
EP4 EP5 EP6
y
Room
Note: Drg. Shown above is schematic for explanation of radiation caused due to lightning and does not include
all the elements (cabinets) of site.
Over Voltage in the ground created a high potential in the body of all devices connected to ground. The devices
which are having the lowest breakdown voltages will damage immediately. If the voltage is so high,
splashovers will happen. Probably the Lightning arrester connected in IPS room must have operated at 2 KV
and diverted the current to the power source. Otherwise there would have been flashes on PCBs.
7/28/2019 lightening effects and protection.pps
92/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Battery
Room
Axle Counter
SSI
Rack1 Rack2 Relay
panel
IPS room
EP2 EP3
TreeTree
EP4 EP5 EP6
Rack1 Rack2 Relay
panel
IPS room
EP2 EP3
Tree
EP4 EP5 EP6
Note: Red colour shows how the radiation
starting ground EP2, EP3 and EP5, moves to throom and affects all equipments connected.
Gidhni site plan-Explanation as what could have happened.
Chance no.1. Ground potential increases due to a discharge either on ground or on the tree (existing outside the building) or any of the nearby objects. Potentialof all the devices connected to earth increases. ( Axle counter body is separately grounded on the backside of building). Chances of failure of all devices due tothe coupling of surge. Failures expected on the non vital I/Os, PCs, SSI main rack PCBs, 12 V & 24 V Power inputs of SSI, IPS inputs and outputs.
Axle CounterIPS roomSM
RoomTVSS
7/28/2019 lightening effects and protection.pps
93/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
EP6
TreeTree
EP1 EP2 EP3
EP4 EP5
Actual following was found at site :
Failure occurred on both PCs, Control panel, SSI main rack PCBs, one output of IPS.
No failure on the IPS Inputs, Lightning and Surge arresters are installed.
No failure on output of IPS, SPDs installed on all outputs.
Recommendations. (Surge arresters should be installed in the following places)
Power supply of PC affected. Recommended device 3. VF 230 AC
24 V and 12 V DC Power supply inputs to SSI. Recommended Device. VF24 DC for 24 Vand VF12 DC for 12 V
RS485 ports affected. Recommended Device 2. SD25 V11 / 25
230 V AC output from IPS No failure occurred. May be due to the presence of SPD
RS 485 ports of Monitoring PC also require protection. Recommended Device 2. SD25V11 / 25
Non Vital inputs Recommended device 1. LSA-BF-24
Rack1 Rack2Relay
panel
Battery
Room
PC Control Panel
RS485/232 port PC to SSI
32 pairs of I/O Nonvital
C/O PanelSMR
PanelAC
Panel
AC
Panel
DC
Panel
24V DC
12V DC
230V AC230V AC
Metallic Pipes
connected to
ground
PC
Gidhni site plan-Explanation as what could have happened.
Chance No2. Lightning/Radiation in the metalic pipes can create over voltage on all the conductors passing through the metalic pipes. Chances of failure of PCBs
connected to Nonvital inputs in controller as well as SSI, RS485 ports connected to both PC and SSI, Power supply to control PC, 230 Volt Inverter output of IPS.
Axle CounterIPS roomSM
RoomTVSS
7/28/2019 lightening effects and protection.pps
94/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
TreeTree
EP1 EP2 EP3
EP4 EP5 EP6
Non Vital inputs affected. Recommended device 1. LSA-BF-24
RS485 ports affected. Recommended Device 2. SD25V11 / 25
Power supply of PC affected. Recommended device 3. VF 230 AC
230 V AC output from IPS No failure occurred. May be due to the presenceof SPD
RS 485 ports of Monitoring PC also require protection. Recommended
Device 2. SD25V11 / 25
Rack1 Rack2Relay
panel
Battery
Room
PC Control Panel
RS485/232 port PC to SSI
32 pairs of I/O Nonvital
C/O PanelSMR
PanelAC
Panel
AC
Panel
DC
Panel
24V DC
12V DC
230V AC230V AC
Metallic Pipes
connected to
ground
PC
SSI - Recommendation
Axle CounterIPS roomSM
RoomTVSS
7/28/2019 lightening effects and protection.pps
95/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
TreeTree
EP1 EP2 EP3
EP4 EP5 EP6
Rack1 Rack2Relay
panel
Battery
Room
PC Control Panel
RS485/232 port PC to SSI
32 pairs of I/O Nonvital
C/O PanelSMR
PanelAC
Panel
AC
Panel
DC
Panel
24V DC
12V DC
230V AC230V AC
Metallic Pipes
connected to
ground
PC
Earthing directly from SSI to
earth pit is not recommended
Earth busbar fro SSI room has to be
connected through the common earth bus
bar in the IPS room.
Arresters to the Dc input of SSI
SUMMARY
Electrical Connections to Microlok and Computers from IPS
1. 24 V DC
7/28/2019 lightening effects and protection.pps
96/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
2. 12 V DC
3. 230 V AC (for PC)
Other Inputs and Outputs
1. Vital inputs from relay panel
2. Non Vital inputs from Station control room
3. RS485 ports from PCs
4. RS 485 ports to PCs
5. Separate earthing done for SSI room and IPS room
Probable Chance of Over Voltage
1. Over Voltage on the body of all devices
2. Induced EMF on the cables connected between two buildings through
metalic pipes3. Difference in potential rise of SSI room and IPS room earth may create
flash over.
Recommended SPDs
24V DC - VF24 DC
12V DC - VF12 DC
7/28/2019 lightening effects and protection.pps
97/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
230 V ACVF230 AC on the input of PCs
RS485 PortsSD25V11 / 25
All non vital inputs and outputs from the Microlok to the control panel.. LSA-
BF-24
LSA-BF-24 device for Control panel inputs and outputs
One no spark gap between the two earth so that in case of excess voltage rise in
one earth, the effect is neutralized.
I tem no 1 to 4 can be implemented in the f irst phase and i tem no. 5 and 6
can be implemented on the next phase.
7.7 Additional installation guidance
Installations should be based on IEC 60364-5-534 Where lightning arresters are
7/28/2019 lightening effects and protection.pps
98/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
The lines to the arrester elements should not be more than 0.5 metres long, so thatno excessive voltage rise can take place in serious cases.
Installations should be based on IEC 60364 5 534. Where lightning arresters areused before the meter, for Germany the TAB (Technische Anschlu Bedingungen)
conditions of the VDEW must be observed.
The earth of the arrester must always be bonded with the earth of the consumerinstallation. If the PE busbar of a distribution board are used, the PE busbar must be
connected to the installation earthing point by a connection which is capable to carrythe lightning current (16 mm to the equipotential bonding bar).
Parallel installation between unprotected conductors (eg to the meter) and protectedconductors (eg supply voltage) must be avoided.
7.8 Connecting wires
If it is not possible to apply the recommended line length ( 0 5m) the surge protection
7/28/2019 lightening effects and protection.pps
99/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
If it is not possible to apply the recommended line length ( 0.5m), the surge protectiondevices should not be connected with a spur line, but in a V-shape.
Take care to run the outgoing and return lines as far apart as possible.
Main equipotential
bonding busbar
Bonding busbar
Main equipotential
bonding busbar
0.5 m
0.5 m
7.9 Application example / Wrong Installation
7/28/2019 lightening effects and protection.pps
100/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
UL = L * di/dt
UL = 3H * 1kA/s
UL = 3kV
7.10 Application example / Correct Installation
7/28/2019 lightening effects and protection.pps
101/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
IN OUT
Loping of Wires
Wiring
7/28/2019 lightening effects and protection.pps
102/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Input and output wires to the arrester
box should be clearly separated.
7/28/2019 lightening effects and protection.pps
103/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Quality of earthing has to be
improved
Chapter 8
7/28/2019 lightening effects and protection.pps
104/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Summary
8.1 Product Guarantee
7/28/2019 lightening effects and protection.pps
105/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
OBO- Bettermann gives a 5 years product guarantee of allovervoltage protection devices
8.2 TBS Construct
7/28/2019 lightening effects and protection.pps
106/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
OBO CONSTRUCT TBS
Planning software for the construction
of surge protection concepts in TN, TT
and IT network systems in a building.
including: Texts for use in tenders, Technical information on the products
circuit diagrams product overviews calculation of lightning protection class
The program is designed to be clear andeasy to use.
8.3 The concept of overvoltage protection
Energy supply Telecommunications
7/28/2019 lightening effects and protection.pps
107/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
All protectors for the different kind of applications you
find in the OBO Bettermann TBS product range!
Energy supply
Measurement and
control lines
Telecommunications
Other data lines
The best lightning and surge protection
will be ineffective unless
every incoming line to the building
is included!
That is the end of our seminar!
7/28/2019 lightening effects and protection.pps
108/108
9,2, Vanchiadithan New Street, Vadasery, Nagercoil 629001. Ph. 04652 277079 / 275197. fax. 04652 274352
Now we are ready to answeryour questions!
Thank you for your
attention!