Upload
ngodang
View
222
Download
0
Embed Size (px)
Citation preview
Materials for fibre optic lines
18/1MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Contents
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Examples of OPGW arrangements . . . . . . . . . . . . . . . . . . . . . . 3
FITTINGS FOR OPGW
C-bracket, welded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
AGS-clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–7
Tension brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Heliformed dead ends . . . . . . . . . . . . . . . . . . . . . . . . . . . 9–10
Thimbles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cone type tension clamps . . . . . . . . . . . . . . . . . . . . . . . . 11
String hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Flexible copper earthbonds . . . . . . . . . . . . . . . . . . . . . . 13
Aluminium-shunts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Parallel groove clamps . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Down lead clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Stockbridge dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Come along spirals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Warning spheres . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
FITTINGS FOR ADSS
Suspension points for light cables . . . . . . . . . . . . . . . . . .
– for short spans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18–19– for long spans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Tension points for light cables
– for short spans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20–22– for long spans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Spiral dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/2
GENERAL Earth wires are for grounding overhead lines and to protect them against atmospheric discharges and lightning strikes. The conductors used vary widely.To cover the permanent growing demand on data-transmission lines, in recentyears, the earth wires of overhead lines include fibre optic elements, which al-low a fast and safe transmission of a large quantity of information. In the verybeginning optical fibres were used in companies mainly for internal data trans-mission and remote control. Nowadays these fibres are also used by externalorganisations for several kinds of transmission. High voltage transmission lineswill not only be used for carrying current, they also play an important part in in-ternational telecommunications and data-transmission.Earth wires with optical fibres are called – OPGW– optical ground wires. Normal types of strain- and supporting-fittings cannot be used here. Theywould result in radial forces too great for this very sensitive type of conductor.For this reason it is necessary to use helical fittings or specially adapted clampse.g. cone type strain clamps. These fittings do not stress the conductor with ex-cessive radial forces. Metal free aerial cables with fibre optics (ADSS), cannot be used as earth ca-bles because of their dielectrical construction. Such types of cables will be in-stalled additionally on overhead lines for data transfer. Basically the same fittings will be used as for OPGW cables except no groun-ding is necessary. Metal free cables installed along railways or short distanceinstallations will be supported by suspension rollers. On the one hand this tech-nique guarantees cost-effective installation, because the suspension rollers willalso be used for pulling through the cable during installation, and on the otherhand they will guarantee safe operation, because the cable can move withinthe rollers in case of contact from falling parts of trees or if there is heavy icing.
Short circuit capability The clamps have a good short circuit capability, which is achieved by asecure encasement of the conductor and by a large contact area. The connec-ting parts such as eyes, bolts etc. are matched to customer requirements.
Standards Connecting bolts acc. to DIN 48073.Split pins are made of stainless steel or tinned copper.Clevis eye connections acc. to DIN 48074 resp. IEC Publication 471.
Hot dip galvanising Steel hardware is hot dip galvanised in Mosdorfer’s own plant.Galvanising can be done in accordance to national and international stan-dards.
abbreviation for boltsS = screw boltN = rivet bolt
18/3
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
FITTINGS FOR OPGW
View of a suspension point with C-shaped bracket
View of a tension point with down lead clamps
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/4
SUSPENSION POINTS
C-brackets welded
This C-shaped suspension bracket, which is „open“ on one side gives excellentaccessibility and movement for the attached suspension clamps. They can beequipped with several types of suspension clamps.
* Special designs for pulling up.
Other designs of the mounting plate are available upon request. If an insulated design is required,please state this separately on your order. Certain dimensions of bolts are also available on re-quest.
Heightfor bolt Hole centres
Shortcircuitcurrent
kAvert.kN
hor.kN
4654.014654.01/24654.034654.01/H4654.04
265265310265310
1919191919
90 x 9090 x 9090 x 9090 x 9090 x 90
M 16M 16M 16M 16M 16
4040404040
3030303030
1515152060
Dimensions in mm max. stat.load
13,00*13,00*18,00*14,50*24,00*
forbolts
Base plate
For special applications, where summer and winter seasons gives dissimilar lo-ads, it is necessary to use a modified type of the standard C-shaped suspensi -on bracket. As shown on the picture beside, the eye-bearing is designed sothat the hinge can move over an angle of >200°. This guarantees, in the pul-ling up of the conductor, that the suspension clamp can move and adjust verti -cally and gives no bending stress to the hinge, the suspension eye or in theworst case to the OPGW-cable.
Standardtype
Type for pulling up
18/5
Materials for fibre optic lines
2MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Armour grip suspension clampstrunnion typefor conductors with aluminium- or aluminium-alloy-outer strands and cables.
With this suspension clamp the conductor will be protected by a neoprene-slee-ve at the point of clamping. The special concave shaped design of the sleevemeans it cannot slip in the event of a one sided load through the conductor. Ar-mour rods made of auminium alloy cover the conductor and the sleeve. The bo-dy of the armour rods will be fastened by an aluminium clamp. This gives themechanical connection to the suspension point. The connection bolts of theclamp are placed near to the conductor axis. Depending on the type of con-ductor it is recommended that reinforcing rods are used. To minimize the ab-
rasion between suspension eye and the connection bolts of the clamp,both are made of steel. AGS-clamps can be used up to a con-
ductor installation angle of 30°. A conductor installationangle of up to 60° can be achieved by using two
AGS-clamps.
WeightkgL.-Nr.
b
25252525252525252525323232323232323232323235353535353535353535
505050505050505050508080808080808080808080
110110110110110110110110110110
Conductor Ø
19,91–10,2810,29–10,6310,64–11,0411,05–11,4511,46–11,9511,96–12,2312,24–12,6912,70–13,0213,03–13,4813,49–13,7813,79–14,1114,12–14,5714,58–15,1015,11–15,4115,42–15,7415,75–16,4016,41–17,1117,12–17,5417,55–18,0518,06–18,5818,59–19,0719,08–19,5219,53–20,2120,22–20,9520,96–21,4821,49–22,1122,12–22,7022,71–23,0523,06–23,3823,39–23,8223,83–24,45
Length ofrods
1800180018001800180018001800180018001800180018001800180018002000200020002000200020002000200020002000200022002200220022002200
808080808080808080809090909090909090909090
120120120120120120120140140140
c
20202020202020202020202020202020202020202020202020202020202020
Connectingbolt
S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19
d
17,33–17,6217,33–18,0518,06–18,4618,47–18,8718,88–19,3719,38–19,6520,72–21,1721,18–21,5021,51–21,9621,97–22,2623,03–23,3523,36–23,8123,82–24,3424,35–24,6524,66–24,9824,99–25,6426,77–27,4727,48–27,9027,91–28,4128,42–28,9428,95–29,4331,78–32,2232,23–32,9132,92–33,6533,66–34,1834,19–34,8134,82–35,4035,41–35,7535,76–36,0836,09–36,5236,53–37,15
1,801,801,801,801,801,801,901,902,002,002,302,302,402,402,402,603,103,103,103,203,204,404,504,504,504,505,005,005,705,705,80
4361.01/14361.02/14361.03/14361.04/14361.05/14361.06/14361.07/14361.08/14361.09/14361.10/14361.11/14361.12/14361.13/14361.14/14361.15/14361.16/14361.17/14361.18/14361.19/14361.20/14361.21/14361.22/14361.23/14361.24/14361.25/14361.26/14361.27/14361.28/14361.29/14361.30/14361.31/1
Breakingstrength
kN
Short cir-cuit current
kA
Dimensions in mm
Material: Clamp: aluminium-alloy, forgedInsert: neopreneRods: aluminium-alloyTrunnion: steel, hot dip galvanisedStraps: steel, hot dip galvanised
AGS-clamps with reinforcing rodsfor conductors with aluminium- or aluminium-alloy outer strands and cables.
WeightkgL.-Nr.
Material: Clamp: aluminium-alloy, forgedInsert: neopreneRods: aluminium-alloyTrunnion: steel, hot dip galvanisedStraps: steel, hot dip galvanised
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/6 2
L. of reinf.rods
323232323232323232323535353535353535353535353535353535353535353535353535353540404040
505050505050505050508080808080808080808080
110110110110110110110110110110110110110110110110110120120120120
Conductor Ø
19,91–10,2610,27–10,5110,52–10,9710,98–11,0911,10–11,4011,41–11,7811,79–11,9111,92–12,4612,47–12,9312,94–13,2513,26–13,3813,39–14,0114,02–14,8114,82–14,8714,88–15,2815,29–15,4115,42–15,6315,64–15,9615,97–16,0216,03–16,4016,41–16,6516,66–17,0317,04–17,2617,27–17,6417,65–17,8717,88–18,1218,13–18,5518,56–18,8118,82–19,0119,02–19,8819,89–20,1320,14–20,2820,29–20,9921,00–21,3521,36–21,4521,46–21,8621,87–22,4422,45–22,8222,83–23,5123,52–24,2524,26–25,0625,07–25,19
Length ofrods
127013701370137013701370137014001420152015201520155016301650165016501680168016801700170017301730175017502030208020802080208020802080208020802080208020802240224022402240
167017701770177017701770177017701820192019201920195019502050205020802080208020802080244024402440244021502480248024802480248024802480248024802480248024802640264026402640
b
9090 90 90 90 90 90 90 90
120120120120120120120120140140140140140140140140140150150150150150150150150150150150150155155155155
Connectingbolt
S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19
d
16,05–16,4016,41–16,6516,66–17,1117,12–17,2317,24–17,5417,55–17,9217,93–18,0518,06–18,6018,61–19,0719,08–19,3919,40–19,5219,53–20,1520,16–20,9520,96–21,0122,30–22,7022,71–22,8322,84–23,0523,06–23,3823,39–23,4423,45–23,8223,83–24,0724,08–24,4524,46–24,6824,69–25,0625,07–25,2925,30–25,5425,55–25,9725,98–26,2326,24–26,4326,44–27,3027,31–27,5527,56–27,7027,71–28,4128,42–28,7728,78–28,8728,88–29,2829,29–29,8629,87–30,2431,31–31,9932,00–32,7333,50–34,3034,31–34,43
2,702,702,802,902,903,003,003,103,204,604,604,70 4,804,804,905,005,106,606,606,606,606,706,806,806,806,40
10,1010,1010,2010,2010,2010,4010,4010,4010,6010,6010,6010,6012,8012,8012,9013,10
4362.00/094362.00/084362.00/074362.00/064362.00/14362.01/14362.02/24362.03/14362.05/14362.04/14362.06/14362.07/14362.08/14362.09/14362.10/14362.11/14362.12/14362.13/14362.16/14362.17/14362.18/14362.14/14362.19/24362.15/14362.21/14362.20/14362.22/14362.23/14362.24/14362.25/14362.26/14362.27/14362.29/14362.28/14362.30/14362.31/14362.32/14362.33/14362.34/14362.35/14362.36/14362.37/1
Breakingstrength
kN
Shortcircuit
current kA
Dimensions in mm
WeightkgL.-Nr.
Material: Clamp: aluminium-alloy, castedInsert: neopreneRods: aluminium-alloyTrunnion: steel, hot dip galvanisedStraps: steel, hot dip galvanised
18/7
Materials for fibre optic lines
1MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
The clevis width is 20 mm. Other dimensions on request.
L.N° refers to right hand lay, for left hand lay please add/L, for example 4361.03/L.Other dimensions on request.AGS clamps for conductors with alumoweld-outer strands on request.
AGS-clamps with fixing bracketTrunnion typefor conductors with aluminium- or aluminium-alloy outer stands.
Dimensions on request.
414141414145454545454545454545
Width ofclevis
25252525252525252525252525252525
Conductor Ø
19,91–10,2810,29–10,6310,64–11,0411,05–11,4511,46–11,9511,96–12,2312,24–12,6912,70–13,0213,03–13,4813,49–13,7813,79–14,1114,12–14,5714,58–15,1015,11–15,4115,42–15,7415,75–16,40
Length ofrods
1800180018001800180018001800180018001800180018001800180018002000
20202020202020202020202020202020
b
145145145145145145145145145145143143143143143143
Connectingbolt
S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19S19
d
17,33–17,6217,33–18,0518,06–18,4618,47–18,8718,88–19,3719,38–19,6520,72–21,1721,18–21,5021,51–21,9621,97–22,2623,03–23,3523,36–23,8123,82–24,3424,35–24,6524,66–24,9824,99–25,64
1,81,81,81,81,91,92,12,12,22,22,42,52,52,52,52,6
4361.01/1/A4361.02/1/A4361.03/1/A4361.04/1/A4361.05/1/A4361.06/1/A4361.07/1/A4361.08/1/A4361.09/1/A4361.10/1/A4361.11/1/A4361.12/1/A4361.13/1/A4361.14/1/A4361.15/1/A4361.16/1/A
Breakingstrength
kN
Shortcircuit
current kA
Dimensions in mm
Armour grip suspension clampsclevis type, with cranced linksfor conductors with aluminium- or aluminium-alloy-outer strands and cables.
With this type of suspension clamp the Armour rods and the neoprene insert are enclosedby a cast aluminium clamp.
The mechanical connection of the clamp to the suspension point is provided by a hot dip galvanised steel clevis eye.
Material: Bracket: steel, hot dip galvanisedPG-clamp: aluminium-alloy
L.-Nr. Weightkg
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/8
forboltsM16M16M16M16M16M16M16M16M16M16M16
Tension brackets weldedfor bolts M16for aluminium-, al-alloy-, ACSR-, AACSR- and alumoweld conductors.
Ground wire brackets are designed so that movement in all directions is gua-ranteed. The conductor will be directed safely by the clamp. The clamps areadjusted to suit the actual conductor diameter.
Other types on request.In case isolation is needed please state in the order.Insulation bolts to be delivered on request.
Conductor Ø
Brea-king
strengthkNHole-
centers
Shortcircuitcur-rentkABoltLink
width4652.02/004652.06/014652.02/104652.03/204652.02/204652.03/304652.03/104652.03/104652.04/104652.06/104652.06/10
without clampwithout clamp
8,2–11,711,8–13,013,1–14,414,5–16,015,9–17,415,9–17,417,5–19,219,1–21,021,1–23,4
100230100100100100100310100230230
90 x 9090 x 9090 x 9090 x 9090 x 9090 x 9090 x 9090 x 9090 x 9090 x 9090 x 90
4040404040404050404050
S19S19S19S19S19S19S19S22S19S19S22
2121212121212121212121
Linkheight
4060404040404060406060
3,607,004,104,104,104,104,108,204,107,807,20
Earth wire bracketswith 3- or 4-hinges
Earth wire brackets with 3 hingesSerial-Nr. 4653…
Earth wire brackets with 4 hingesSerial-Nr. 4653…
Dimensions in mm
TENSION POINTS
18/9
For conductors with aluminium or aluminium-alloy-outer strands
Material: Dead end: alumoweldReinforcing rods: aluminium-alloyThimble: malleable or ductile iron hot dip galvanised
L.-Nr. Weightkg
Materials for fibre optic lines
1MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Heliformed dead endsThe strain-equipment for metal-clad cables consists of reinforcing rods and heli-formed dead ends with strain thimbles, which provide the link between thestring hardware and the dead end sets. The major advantage of this assembly is:l Low tension-stress on the end of the conductor.l Dissemination of the occurring radial forces to a wider surface.l Upgrade of the torsion-factor, thus lower stresses for the sensitive optical
fibres.This strain-equipment is in accordance to VDE 0210, ÖVE L11 and complieswith many other specifications.
a180020002200250025002900300030003000300033003300350035003500350035003500
L.N° refers to right hand lay, for left hand lay please add/L, for example 4480.03/L.Other dimensions on request.The dimension l1 can be elongated in case 2 stockbridge dampers are used.Lay direction: Reinforcing rod – against outer lay of conductor
Dead end – as outer lay of conductor
4480.034480.004480.014480.024480.044480.054480.074480.084480.094480.104480.114480.124480.134480.144480.154480.164480.174480.18
Conductor Ø
08,54–10,4610,47–11,5011,51–12,5012,51–13,2613,27–14,5014,51–15,5015,51–16,8016,81–17,8017,81–18,5018,51–19,7019,71–21,2821,29–22,0022,01–23,0023,01–23,6023,61–24,4024,41–25,3025,31–26,2026,21–27,20
b d2,002,402,803,004,805,105,905,906,207,708,809,80
10,9010,9012,2012,4012,6012,60
ThimbleL-Nr.
4410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.164410.164410.164410.164410.164410.16
90010001200120015001500160016001700190020002200220022002400240024002400
l1430475407573435533514550464550650513645675574608640670
l2705780866
1000845
1160119011801160
96010801040112011001080106010401020
14,68–16,6016,61–17,6417,65–18,6418,65–19,4020,17–21,4021,41–22,4022,41–23,7023,71–24,7024,71–25,4026,99–28,1828,19–29,7630,53–31,2431,25–32,2432,25–32,8432,85–33,6433,65–34,5434,55–35,4435,45–36,44
Dimensions in mm
Material: Thimbles: malleable or ductile iron, hot dip galvanisedBolts: steel, hot dip galvanised
L.-Nr. Weightkg
Material: Dead end: alumoweldReinforcing rods: aluminium-alloyThimble: malleable or ductile iron dip galvanised
L.-Nr. Weightkg
for conductors with alumoweld-outerstrands
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/10 1
BoltsType
4410.021/4410.15/14410.151/4410.16/14410.16/14410.9001
S19S19S22S19S22S22
Clevis width
202222202020
Thimblewidth163232454545
Shortcircuit
current kA284040404042
Breakingstrength
kN100230230230230310
0,80*1,20*1,20*1,50*1,50*4,60*
Strain thimbles
Dimensions in mm
18,25–10,6910,70–11,4711,48–12,4512,46–13,0613,07–13,7713,78–14,4914,50–14,7914,80–15,3015,31–15,8515,86–16,8016,81–18,2418,25–19,0019,01–19,7019,71–21,2821,29–22,56
Conductor Øa b
150015201580164017001750180018501850190020002080208021602240
dThimbleL-Nr.
4410.02/14410.02/14410.02/14410.02/14410.02/14410.02/14410.02/14410.02/14410.02/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/1
189019801270127013901390139013901390157015701570179017901790
l1
200300200200200200200200200250250250250250250
l2
508530397457463513583613619430530610512592672
14,77–17,2117,22–17,9918,82–19,7919,80–20,4021,29–21,9922,00–22,7122,72–23,0123,02–23,5223,53–24,0724,08–25,0225,03–26,4626,47–27,2227,23–27,9227,93–29,5029,51–30,78
4480.194480.204480.214480.224480.234480.244480.254480.264480.274480.284480.294480.304480.314480.324480.33
2,503,003,904,105,105,405,405,505,706,907,207,608,008,108,50
L.N° refers to right hand lay, for left hand lay please add/L, for example 4480.03/L.Other dimensions on request.The dimension l1 can be elongated in case 2 stockbridge dampers are used.Lay direction: Reinforcing rod – against outer lay of conductor
Dead end – as outer lay of conductor
Dimensions in mm
111112
*steel, hot dip galvanised.
Type 1
Type 2
18/11
Material: Clamp: ductile iron, hot dip galvanisedCounter-piece: aluminium-alloyStraps: steel, hot dip galvanisedBolts: steel, 8.8., hot dip galvanised
L.-Nr. Weightkg
Material: Clamp: malleable iron, hot dip galvanisedCounter piece: aluminium-alloyStraps: steel, hot dip galvanisedBolts: steel, 8.8., hot dip galvanised
L.-Nr. Weightkg
Material: Clamp: aluminium-alloyStraps: steel, hot dip galvanisedBolts: steel, 8.8., hot dip galvanised
L.-Nr. Weightkg
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Open cone type tension clamps ductile ironL.-Nr. without cones
Open cone type tension clamps cast aluminiumL.-Nr. without cones
135–264–101135–264–102
Cond. Ø14,9 – 33,814,9 – 33,8
a10001000
b800800
BoltsS19
*
e20
104
f104104
Ratedstrength
kN120120
Shortcircuit
current kA3535
Dimensions in mm
Open cone type tension clamps malleable ironL.-Nr. without cones
9,709,20
Cones to be ordered seperately. Cone diameters will be calculated according to the conductor dimensions. Cones are available with or without jumper connection. Depending upon the construc-tion of the OPGW it can be necessary to use reinforcing rods, especially by using only one layerabove the tube which contains the optical fibres, or if the diameters of the individual wires are smal-ler than 3 mm.Reinforcing rods shall be used on dielectric cables.
*for strain hinges.
135–264–042135–264–043
Cond. Ø10–37,510–37,5
a750950
b550750
BoltsS19S22
e2020
f9494
Ratedstrength
kN180180
Shortcircuit
current kA5050
Dimensions in mm
12,8015,00
135–264–110Cond. Ø10–37,5
a1075
b875
BoltsS22
e20
f110
Ratedstrength
kN280
Shortcircuit
current kA50
Dimensions in mm
18,00Cone for open cone type tension clamps
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
Material: Steel, forged, hot dip galvanised
WeightkgL.-Nr.
L.-Nr. Weightkg
Material: Steel, forged, hot dip galvanised
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/12 1
Twisted eye links
forbolts a b c1 c2
4261.08/104261.08/104261.10/104261.11/104261.12/10
1919192222
70 809090
100
5055606065
1919191919
1919191919
Dimensions in mm
0,530,600,850,850,97
Shortcircuit
current kA
3040404050
Breakingstrength
kN
200200240240320
30323240
160160160230
20202024
19191919
265–405350–490455–775309–441
S 19S 19S 19S 22
50 x 850 x 850 x 860 x 8
4266.304266.334266.384266.53
3,203,805,204,48
Bolts b x s a c d
Breakingstrength
kN
Shortcircuit
current kA
Adjustable extension links straight
Dimensions in mm
Other types see cat. part 3
Type
4268.32/104268.31/104268.02/104268.02/104268.02/20
M20M20M24M24M24
300–420440–690380–505380–505520–770
5050555555
1919191919
ba c
1919192219
forbolts
160160240240240
Breakingstrength
kN
1818252525
1,90*2,90*3,10*3,10*4,50*
Shortcircuit
current kA
Turnbuckles eye-eye
Dimensions in mm
Other types see cat. part 3
Other types see cat. part 3
18/13
Material: Aluminium-conductorCable lug: aluminium
L.-Nr. WeightkgLength Bolts
Short circuitcurrent
kACross section
mm2
Material: Flexible copperCable lug: copper, tinned
L.-Nr. Weightkg
ACCESSORIES
Flexible copper-earthbonds
They are used for additional earthing between the clamp-body of the suspen-sion-clamp and the earthwire suspension equipmentor to the tower.Cu-shunts are regularly equipped with a bent cable lug with a bolt M12 x 20 and a straight cable lug with a fixing consisting of a bolt M12 x 35 with washer and nut.
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Cross sectionmm2
707095
120
Lengthmm
5001000
500500
Short circuitcurrent
kA
14141924
Other lengths on request.Special types: with shrink tubes (connecting the compressed part of the cable lug to the flexible earthbond)L-Nr. + S, f. e.: 4664.03 S
4664.034664.03/14664.31/14664.40/20
0,601,000,800,90
4664.354664.35/14664.35/24664.364664.454664.50
70707095
120150
50010001000100010001000
M12x35 M12x35 M16x35 M12x35 M12x35 M12x35
888
111418
0,200,300,400,400,500,60
Other lengths on request.Special types: with shrinkable tubes (connecting the compressed part of the cable lug to the flexibleearthbond)L-Nr. + S, f. e.: 4664.03 S
Aluminium-shuntsfor additional earthing between OPGW-cable and tower.
Material: Body: aluminium-alloy, forgedBolts: steel, 8.8, hot dip galvanised
L.-Nr. Weightkg
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/14 1
2 x M102 x M102 x M102 x M102 x M123 x M103 x M103 x M103 x M123 x M123 x M123 x M123 x M123 x M123 x M123 x M123 x M123 x M12
170170170170165090090090100100100100120120120120130130
19,0–19,910,0–10,710,8-11,711,8–12,612,7–13,613,7–14,915,0–16,216,3–17,117,2–18,118,2–19,019,1–20,020,1–21,121,2–22,222,3–23,423,5–24,524,6–25,725,8–26,726,8–27,8
Parallel groove clamps, acc. DIN 48075 with serrated grooves. for aluminium-, al-alloy-, ACSR-, AACSR- and alumoweld conductors.
1PA100-020LW1PA100-025LW1PA100-040LW1PA100-055LW1PA100-060LW1PA100-070LW1PA100-095LW1PA100-100LW1PA100-115LW1PA100-140LW1PA100-155LW1PA100-160LW1PA100-165LW1PA100-200LW1PA100-225LW1PA100-230LW1PA100-250LW1PA100-260LW
Conductor Ø LengthBolts
0,300,300,300,300,300,500 500,500,600,600,600,600,800,800,800,800,900,90
Reductions- and bimetallic tubes on request.
Dimensions in mm
Parallel groove clamps are used at the strain-point of metal-clad OPGW-con-ductors / earth-wires, to connect the earth wire with the tower through a fle-xible Al-shunt. The Al-shunt provides an additional earthing-bridge, in order toprotect the OPGW-earth wire in the event of a short circuit.To eliminate stressing of the sensitive fibre optics by radial forces, there are se-veral inner diameters of the clamps available, this means the clamps can beadjusted to the OPGW-conductor diameter.This ensures that, with proper installation of the clamps, the attenuation will bemaintained.
Material: Clamp: extruded aluminium-alloyThreaded parts: steel, hot dip galvanisedFixing bracket: steel, hot dip galvanised
L.-Nr. Weightkg
18/15
Materials for fibre optic lines
1MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Down lead clampsThe down lead clamp is used to attach the OPGW-conductor to the tower andto route the conductor down the tower in a defined way. The down lead clampis designed for installation in a 90° or 0° position. Therefore these clamps canbe used for many applications and can be adjusted quickly and easily to thestipulated requirements, by linesmen.
8,2–11,711,8–13,013,1–14,414,5–15,815,9–17,417,5–19,219,3–21,221,3–22,822,9–24,6
404040404040404040
222222222222222222
M8M8M8M8M8M8M8M8M8
0,400,400,650,650,650,700,700,700,75
4680.274680.27/014680.27/044680.27/14680.27/1/14680.27/24680.27/2/14680.27/2/34680.27/2/2
Conductor Ø LengthWidth ofbracket
Fixing boltsDimensions in mm
On ordering please state exact conductor diameter.
Special types:• one side with packing piece L. Nr. …/F
f. e.: 4680.27/6F
With elongated bolt Type for angles For inside fixing on a tower structure
Material: Weights: cast iron, hot dip galvanisedMessenger cable: steel, hot dip galvanisedClamp: aluminium-alloy, forgedBolt: stainless steel
L.-Nr. WeightkgBolt
TorqueNm
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/16
9301.000/EA19301.010/EA19301.020/EA19301.030/EA19301.040/EA19301.050/EA19301.060/EA19301.070/EA19301.080/EA19301.090/EA19301.100/EA19301.110/EA19301.120/EA19301.130/EA1
9303.000/EA19303.010/EA19303.020/EA19303.030/EA19303.040/EA19303.050/EA19303.060/EA19303.070/EA19303.080/EA19303.090/EA19303.100/EA19303.110/EA19303.120/EA19303.130/EA1
1,601,601,601,601,601,651,651,901,901,901,902,002,002,00
2,102,102,102,102,102,202,202,402,402,402,602,602,602,60
Stockbridge dampers with forged clampsfor aluminium-, al-alloy-, ACSR-, AACSR- and alumoweld conductors.
Weights are cast onto the messenger cable.
Conductor Ø
7,00– 9,009,01–11,00
11,01–14,5014,51–17,0017,01–19,5019,51–22,0022,01–24,5024,51–28,0028,01–31,0031,01–33,0033,01–35,0035,01–38,0038,01–42,0042,01–46,00
7,00– 9,009,01–11,00
11,01–14,5014,51–17,0017,01–19,5019,51–22,0022,01–24,5024,51–28,0028,01–31,0031,01–33,0033,01–35,0035,01–38,0038,01–42,0042,01–46,00
Length
380380380380380385385395395395395395395395
420420420420420425425440440440440440440440
M10M10M10M10M10M12M12M12M12M12M12M12M12M12
M10M10M10M10M10M12M12M12M12M12M12M12M12M12
3030303535353540404545454545
3030303535353540404545454545
Dimensions in mm
Special designs:• Bolts hot dip galvanized L.-Nr. … 1/EA1
f. e. 9304.031/EA1• Weights fixed with cones L.-Nr. … /EA (without 1)
f. e. 9304.030/EAOther types see cat. part 10.
Material: Alumoweld
Weightkg
L.-Nr.
Material: Sphere: glass fibre reinforced polyesterClamps: aluminium-alloy
WeightkgL.-Nr.
18/17
Materials for fibre optic lines
1MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Conductor Ø Length
6,55– 7,367,37– 8,278,28– 9,269,27–10,40
10,41–11,7011,71–13,1213,13–14,6714,68–16,6016,61–18,7918,80–21,2821,29–24,0724,08–27,22
154016201670167017201820187018901980127013901570
0,160,180,240,300,330,500,630,851,172,002,653,59
4781.604781.614781.624781.634781.644781.654781.664781.674781.684781.694781.704781.71
L.N° refers to right hand lay, for left hand lay please add/L, for example 4781.60/L.Other dimensions on request.Lay direction equal to outer lay of conductors.
Dimensions in mm
Warning spheres
Come along spiralsfor conductors with aluminium, aluminium-alloyand alumoweld-outer standsCome along spirals are used forstringing.
ConductorØ SphereØ
9,5–12,012,0–14,514,5–17,017,0–19,519,5–22,022,0–24,524,5–28,028,0–31,531,5–35,0
600600600600600600600600600
5,55,55,55,55,55,55,55,55,5
9220.10 . .9220.11 . .9220.12 . .9220.13 . .9220.14 . .9220.15 . .9220.16 . .9220.17 . .9220.18 . .
Maße in mm
Types: L.-Nr. . . . . . . . OR – orange RAL 2005L.-Nr. . . . . . . . RT – red RAL 3020L.-Nr. . . . . . . . WE – white RAL 9016L.-Nr. . . . . . . . RW – one half red, one half white
Other types on request
Material: Cast aluminium
Weightkg
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
L.-Nr.
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/18
a
140
b
16
F1 kN
12,0
F2 kN
5,0
F3 kN
4,0
Breaking strengthDimensions in mm
5411/1
FITTINGS FOR ADSS
SUSPENSION POINTS FOR LIGHT CABLES WITHSHORT SPANS ON WOODEN OR CONCRETE POLES
The following fixing accessories are designed to allow movement of the clamp inall directions, to prevent any damage.
Eye bolt for wooden or concrete poles
Thread
5050/8/3 M20
a
115
b
260
c
100
d
35
Verticalload kN
4,0 1,50
Hook bolt for wooden or concrete poles
Hook CS140for fixing onto wooden or concrete poles by means of a bolt M14 or stainlesssteel bonds.
0,33
Dimensions in mm
Bolts to be ordered separately.
Thread
5060/21 M16
a
160
b
240
c
150
d
30
Verticalload kN
4,0 0,90
Dimensions in mm
Material: Straps: steel, hot dip galvanisedBolts: steel, hot dip galvanisedRoller: weather resistant plastic
L.-Nr. Weightkg
18/19
Material: Straps: steel, hot dip galvanisedBolts: steel, hot dip galvanisedRoller: glassfibre reinforced plasticRoller insert: neopreneKeeper piece: neoprene
L.-Nr. Weightkg
Materials for fibre optic lines
1MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
Hook bolt M20
Suspension rollers without counter piecefor light cables.
Variation
Hole
Oval hole
Cross slotCross slot
slotslot
Hole
17,5
20x45
2222 ––
RollerØ80
80
80939393
Straps
40 x 5
40 x 3
50 x 450 x 640 x 640 x 6
Height
105
140
160175115225
to be fixed on
Hook bolt M16Hook bolt M16Hook CS140Eye bolt M20Eye bolt M20
Wire upto Ø 6 mmWire upto Ø 6mm
Other variations on request.
0,70
0,50
0,801,301,201,55
5030/29
5030/30
5030/315030/15030/115030/12
Roller suspension clampfor light cables
Cond. Ø
10–25
Hole Ø
24
Roller Øto be fixed on
5170.10 80 1,30
Dimensions in mm
Other fixings see cat. part 19
Suspension roller withflexible wire and slot
Suspension roller with cross slot Suspension roller with hole Suspension roller with slot
Suspension roller with oval hole
Dimensions in mm
b ca
Breaking strengthDim. in mm
Material: Cast aluminium
WeigthkgL.-Nr.
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/20
Thread
M16M16M20M20
a
30303030
b
250380250380
c
100100100100
s
15151515
horizontal kN
5,55,5
13,013,0
vertical kN
5,55,5
13,013,0
0,750,951,281,60
TENSION POINTS FOR LIGHT CABLES WITH SHORTSPANS ON WOODEN AND CONCRETE POLES
Hook bolts
Rated strengthDimensions in mm
5060506150625063
Other dimensions on request.
Eye bolts
Other dimensions on request. Other types see cat. part 19.
100 16 70
Console CS 100For fixing on wooden or concrete poles by means of a bolt M14 or stainlesssteel bonds.
5410/1 25,0 8,0 4,0 0,33
F1 kN F2 kN F3 kN
Bolts are to be ordered separately.
SUSPENSION POINTS FOR ADSSWITH LONG SPANS ON LATICE TOWERS
C-bracketssee page 4
AGS clampssee page 5–7
Thread
M16M16M20M20
a
30303030
b
250350230350
c
100100120120
horizontal kN
40,040,040,040,0
vertical kN
7,07,0
15,015,0
0,800,961,231,56
Rated strengthDimensions in mm
50505051/15050/115050/12
Material: Dead end: alumoweldReinforcing rod: aluminium-alloyThimble: malleable or ductile iron, hot dip galvanised
L.-Nr.Weight
kgDead end
18/21
Material: Steel, hot dip galvanised
L.-Nr. Weightkg
Cond. Ø
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
a b c sBreaking strength
kN
2600.65/12600.66/1
400400
1620
3535
2222
13,020,0
1,101,55
Extension hooks twisted
They will be used to increase the distance between the tower and anchor rod,so that the metal-free aerial cables can be directed around or down the towerwith a greater bending radius.
Straight hooks on request.
4481.094481.004481.014481.024481.034481.044481.054481.064481.074481.08
425450450450500500550550550600
408760920920
1020870970970990
1095
690980950950950
13001300130015001500
a b l1 l2
1500190020002000215021502300230023002450
8,25-10,6910,70-11,4711,48-12,4512,46-13,0613,07-13,7713,78-14,4914,50-15,1715,18-15,8515,86-16,8016,81-18,24
ThimbleL.-Nr.
4410.024410.024410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/14410.15/1
1,802,502,802,903,003,904,004,104,204,35
d
14,39-16,8316,84-17,6118,38-19,3519,36-19,9619,97-20,6721,20-21,9121,92-22,5922,60-23,2723,28-24,2224,23-25,66
Heliformed dead ends
By using an extension-hook, no strain thimble is necessary. The anchor rods will be directly attachedto the extension hook.
Dimensions in mm
Dimensions in mm
L.N° refers to right hand lay, for left hand lay please add/L, for example 4481.09/L.Other dimensions on request.The dimension l1 can be elongated in case 2 stockbridge dampers are used.Lay direction: Reinforcing rod – against outer lay of conductor
Dead end – as outer lay of conductor
LengthConductor Ø
Material: Alumoweld
L.-Nr. Weightkg
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
18/22
Dimensions in mm
Heliformed dead ends without reinforcing rodsDepending upon the type of the aerial cables reinforcing rods may not be necessary. The anchor rods can be directly connected to an extension-hook.Otherwise, a strain thimble will be used.
4781.804781.814781.824781.834781.844781.854781.864781.874781.884781.894781.904781.91
6,55– 7,367,37– 8,278,28– 9,269,27–10,40
10,41–11,7011,71–13,1213,13–14,6714,68–16,6016,61–18,7918,80–21,2821,29–24,0724,08–27,22
430450500570630710730820920
102010501150
0,110,120,140,150,230,260,380,530,721,151,361,48
Extension pointsfor long spans, for lattice towers
•Tension brackets see page 8
•Thimblessee page 10
•String hardwaresee page 12
•Down lead clampssee page 15
•Fixing accessoriessee page 20–21
18/23
Material: Weather resistant plastic
L.-Nr. Weightkg
Spiral dampersFunction: Contrary to the function of a Stockbridge-damper where energy willbe converted, the Spiral vibration damper interrupts the incoming wave andprevents the establishment of a stationary oscillation form.
Materials for fibre optic lines
MOSDORFER Ges. m. b. H. A-8160 WEIZTel. 0 31 72 / 25 0 50, Fax 0 31 72 / 25 05 29, e-mail: [email protected]
9320.049320.059320.069320.07
Conductor Ø6,35– 8,308,31–11,72
11,73–14,3214,33–19,30
Length1240130013451615
0,280,300,320,93
Dimensions in mm