Michael Pacholok, Chief Purchasing Official and Director
Purchasing and Materials Management Division City Hall, 18th Floor, West 100 Queen Street West Toronto, Ontario M5H 2N2
Joanne Kehoe Manager Construction Services
February 24, 2017 Via Website posting (32 pages)
Addendum No. 2 Tender Call No.1 -2017
Closing: 12:00 NOON (LOCAL TIME), March 9, 2017 (REVISED)
FOR: the supply of all materials, equipment, labour and supervision necessary for the construction of the new Block 31 Community Centre/ Child Care Centre/ 2 Elementary Schools (TDSB & TCDSB)
Please refer to the above Tender Call document in your possession and be advised of the following:
1. REVISED Closing Date
The closing date has been extended from March 7 to 12:00 noon, March 9, 2017. The last day for questions is March 3, 2017 at 1:00pm.
2. REVISED - Section 4 - Scope of Work Please refer to attached Addendum #2 from ZAS Architects (25 pages including drawings) dated 17. February, 2017
3. RESPONSES TO QUESTIONS The following are responses to questions received during the bid period.
Q1. Hardware Schedule:There is no hardware schedule. Specification refers to
creating an approved schedule. There is not enough time to prepare, and will not guarantee all bidders will price on the same products, list, etc. A hardware cash allowance should be considered. Please respond.
A1. Hardware supply in the Cash Allowance. A hardware schedule will be issued for information in a subsequent addendum.
Q2. Missing Caisson Information There are 15 caissons and caps not shown on the
S200 series showing founding elevations, caisson marks and cap information (GLs: nH & nJ, n7 east and nG south & n7.2). Please clarify.
A2. Refer to part plan 1/S212 for the caisson type, cap type and founding elevation
Q3. Re: Building Envelope, please clarify the following:
Dwg A002
Re: exterior wall assembly W1A, does the drainage board and waterproofing apply to below grade only per 13/A652?
Please clarify extent of cement parged / cement board. Is the intent to use concrete faced insulation per 11/A652. Also, details 13, 14/A652 does not show cement parging or cement board.
Dwg A319B
roof type in area surrounding planters shows as R2 but hatching indicates R3P
Section 4/A655 shows wood stairs and wood deck. Roof plan shows R1 and R2 (or R3P) roof type.
roof type at perimeter, N, E and W sides surrounding the basketball court shows as R1 in the referenced sections (green per roof types) but there is no hatching indicating green roof. A part of this area shows undefined hatching that suggests R3 gravel ballast roofing.
Roof type west of the basketball court shows roof type R1 with an undefined hatching that suggests R3 gravel ballast roofing.
Section 7/A655 shows roofing in planters appearing as green roofing but is undefined.
Dwgs A600 A605
Are large scale details for conditions on these drawings available? Dwg A656
most details on this drawing are not descriptive. Can descriptive details be provided?
A3. Dwg A002
Drainage board and waterproofing apply to below grade as per 13/A652?
The intent is use concrete faced insulation per 11/A652. As noted on details 13, 14/A652 provide 90mm precast concrete there is no cement parging or cement board in this location.
Dwg A319B
roof type in area surrounding planters is R2
In Section 4/A655 the wood deck would be replaced with concrete pavers under the base price and would be wood deck for the Alternative Price.
The Roof Type at perimeter, N, E and W sides and including the basketball court is R3T (Track and Basketball Ballast Roof) gravel ballast roofing.
14-001 Addendum #02 Page 1 of 5
ADDENDUM # 02
BLOCK 31 DEVELOPMENT, Toronto, Ontario
17 February 2017 Job No. 14-001
1.0 GENERAL 1.1 This Addendum shall form an integral part of the tender documents. The contents of this
Addendum shall be brought to the attention of all concerned. 1.2 Acknowledge receipt of the addendum in the Tender Form. 1.3 All trades shall read the entire Addendum.
2.0 SPECIFICATION
2.1 SECTION 00 01 10 LIST OF CONTENTS
.a Add the following section heading to the List of Contents: 01 32 10 Construction Schedule A 3 VOL 1
2.2 SECTION 01 32 00 PROJECT PROGRESS DOCUMENTATION
.a Delete sub-section 1.1 CONSTRUCTION SCHEDULE in its entirety
2.3 SECTION 01 32 00 PROJECT PROGRESS DOCUMENTATION
.a Delete sub-section 1.1 CONSTRUCTION SCHEDULE in its entirety
2.4 SECTION 01 32 10 CONSTRUCTION SCHEDULE
.a Add attached section 01 32 10 CONSTRUCTION SCHEDULE
2.5 SECTION 09 21 16 GYPSUM BOARD
.a Revise the named products as follows 2.1.4 Tile Backer Board:
Delete CGC Fiberock Aqua Tough Tile Backerboard; Replace with Durock Glass Mat Tile Backer Board
2.1.6 Abuse Resistant Gypsum Board:
Delete Fibre Abuse Resistant by CGC; Replace with Sheetrock Glass Mat Mold Tough Abuse Resistant
2.1.7 Very High Impact (VHI) Abuse Resistant Gypsum Board:
Delete Fiberock VHI Abuse Resistant by CGC; Replace with Sheetrock Mold Tough VHI.
2.1.8 Water (Moisture) and Mould Resistant Wallboard:
Delete Fiberock Brand Aqua-Tough by CGC; Replace with Sheetrock Glass Mat Mold Tough
14-001 Addendum #02 Page 2 of 5
2.6 SECTION 09 54 00 LINEAR WOOD CEILINGS
.a Revise paragraph 2.1.1 to read: 1. Wood Panels: Geopanel Grille Wood Ceiling Panel (WS), SKU: WG-4480-3DWB, Solid
Hemlock, MG, Blade Size; 35mm x 64mm x 305mm (1-3/8 x 2-1/2 x 12), 3 Blades at (4) o.c. Black Acoustic Fabric Backing. Or alternate by 9wood, Atkar Archmill House Inc, Rieger Architectural Products, or Decoustics
2.7 SECTION 11 66 00 GYMNASIUM EQUIPMENT
.a Revise paragraph 2.1.1.2 to read: 2. Or approved alternative product by OES Scoreboards or other manufacturers approved
by consultant
2.8 SECTION 12 12 19 ROLLER BLINDS
.a Revise paragraph 1.2.1 to read:
1. Provide manual sun control fabric roller blinds to interior screens and exterior windows on the following windows: S1.2A TDSB GENERAL OFFICE; S1.2B TDSB VICE PRINCIPAL OFFICE; S1.2C TDSB PRINCIPAL OFFICE; S1.2D TDSB HEALTH RM; S1.3A TCDSB GENERAL OFFICE; S1.3B TCDSB MEETING; S1.3C TCDSB COPY ROOM; S1.3F TCDSB PRINCIPAL OFFICE; S1.3G TCDSB VICE PRINCIPAL OFFICE; S1.5,9,10 TCDSB KINDERGARTEN; S1.11, 12, 14, 15 TDSB KINDERGARTEN; S1.19 PRESCHOOL PLAYROOM 2; S1.24 PRESCHOOL PLAYROOM 1; S1.25A TODDLER PLAYROOM; S1.26A INFANT PLAY ROOM; S1.26C INFANT SLEEP ROOM; S1.28 MEETING; S1.29 RESOURCE OFFICE; S1.30 SUPERVISOR OFFICE; N2.19A TCDSB MULTIPURPOSE; S2.2, 3, 9, 10, 11 TDSB CLASSROOM; S2.5, 6, 8, 30, 31; TDSB CLASSROOM SPEC ED; S2.17, 18, 19, 20, 24, 25 26 TCDSB CLASSROOM; S2.14, 16 TCDSB SPEC ED CLASSROOM; N3.3A STUDIO 1 FITNESS; N3.7, 12 MEETING; N3.13 TEACHING KITCHEN; S3.2, 3, 5, 6, 7, 8, 9, 28,30 TDSB CLASSROOM; S3.11, 12, 13, 14, 15, 16, 17, 18, 23, 24, 25 TCDSB CLASSROOM; S3.34 TDSB CLASSROOM ART; S3.35 TDSB TOOL ROOM; S3.36 TDSB CLASSROOM SCIENCE
2.9 SECTION 12 21 13 MOTORIZED WINDOW SHADES
.a Revise paragraph 1.2.1 to read:
1. Provide electrically operated, interior single solar shade system, with related hardware connected to exterior sensors for automatic opening and closing to complete the installation. Refer to electrical drawings for further information. Provide Motorised Shades to the exterior and interior glazing of School Gym 1 N1.57 and School Gym 2 N1.56. Provide Motorised Shades to the exterior glazing of Multipurpose Room 1 N2.14A; Multipurpose Room 2 N2.12A; Multipurpose Room 3 N2.12; Meeting Room N3.17
14-001 Addendum #02 Page 3 of 5
3.0 ARCHITECTURAL DRAWINGS
3.1 DRAWING A002 CONSTRUCTION ASSEMBLIES
1. Revise Interior Partition Type P1F to read: Materials: 90mm GROUND FINISHED ARCHITECTURAL BLOCK Fire Resistance Rating: 1.1HR
STC Rating: 40 2. Revise Interior Partition Type P1G to read: Materials: 140mm GROUND FINISHED ARCHITECTURAL BLOCK Fire Resistance Rating: 1.5 HR
STC Rating: 43 3. Revise Interior Partition Type P1H to read: Materials: 190mm GROUND FINISHED ARCHITECTURAL BLOCK Fire Resistance Rating: 2.5 HR
STC Rating: 46 4. Revise Interior Partition Type P1I to read: Materials: 240mm GROUND FINISHED ARCHITECTURAL BLOCK Fire Resistance Rating: 3.5 HR
STC Rating: 49
3.2 DRAWING A310 LEVEL 0 SOUTH WING 1. Revise east, west and south walls of S0.2 Solid Waste Area; S0.47 TCDSB
Shipping and Receiving; and S0.48 TDSB SHIPPING AND RECEIVING from P1D to W4A
2. Revise the wording of note ELEVATOR SUMP PIT, COORDINATE WITH MECHANICAL to the following wording 915 X 915 CAST IN PLACE ELEVATOR SUMP PIT 2000 DEEP WITH 915 X 915 RECESSED FLOOR DOOR, REFER TO DETAIL X/A65X
3. Revise north, west and south walls of S0.3 ELECTRICAL; S0.45 ELEV. LOBBY from P1C to W4A
4. Add 90mm Concrete block and 75mm Spray Foam Insulation to the exterior of Partition Type P3B on north and east sides of ELEV. S0.1F
3.3 DRAWING A312 LEVEL SOUTH WING
1. Add Single Door, refer to door schedule, where Door Numbers S1.2.11 is noted. 2. Add Door Number S1.2.12 to door shown between S1.2G TDSB COPY RM and
CORRIDOR S1.1B 3. Revise north and south walls of CORRIDOR S1.1B from P1B to P1G 4. Revise north, east, west and south walls of CORRIDOR S1.1D from P1B to P1G 5. Add note in TCDSB Kindergartens S1.5,7,9 and 10 and TDSB Kindergartens
S1.11,12,13,14 and 15 to C shape P1B wall at cubbies to read P!B to 1500 a.f.f. reinforced refer to detail 9/a809
3.4 A315 LEVEL 3 NORTH WING
1. Revise wording of note GLASS GUARD, REFER TO A340, 5-6 to GLASS GUARD, REFER TO 8/A809
2. Revise wording of note GLASS GUARD, REFER TO A338, 4-5 to GLASS GUARD, REFER TO 8/A809
14-001 Addendum #02 Page 4 of 5
3.5 8/A320 ENLARGED PLAN_WR_NORTH WING LEVEL 2 1. Revise Adult Change Table in BF WR N2.16B to Baby Change Table
3.6 4/A321 ENLARGED PLAN_COMMUNITY CENTRE OFFICE
1. Revise east and south walls of OPEN OFFICE N2.2A from P1B or P1A to P1G
3.7 5/A330 STAIR SW SECTION 1 and 6/A330 STAIR SW SECTION 2 1. Add P4A SHAFT WALL to underside of steel stair flight between Level 1 South
Kindergarten 84.70m and first landing 1750 above Level 1 South Kindergarten. Provide fire sealant at all edges to provide a continuous 1hr fire separation between top and underside of stair.
3.8 6/A331 STAIR SE SECTION 1 and t/A331 STAIR SE SECTION 2
1. Add P4A SHAFT WALL to underside of steel stair flight between Level 1 South Kindergarten 84.70m and first landing 1750 above Level 1 South Kindergarten. Provide fire sealant at all edges to provide a continuous 1hr fire separation between top and underside of stair.
3.9 5/A332 STAIR SN SECTION 1 and 6/A330 STAIR SN SECTION 2
1. Add P4A SHAFT WALL to underside of steel stair flights between Stair Exit South North 83.35m and first landing 3000 above and between first landing and Level 2 South 88.20. Provide fire sealant at all edges to provide a continuous 1hr fire separation between top and underside of stair.
3.10 5/A337 STAIR I - LEVEL 1 SOUTH WING PLAN, 6/A337 STAIR I - LEVEL 2 SOUTH WING PLAN, 7/A337 STAIR SECTION 1 - STAIR I, and 8/A337 STAIR SECTION 2 - STAIR I
1. Revise north and south walls of the stair from P1B where noted to P1G
3.11 DRAWING A403 BUILDING ELEVATIONS (HIDDEN)
1. Replace sheet A403 with A403R2. 3.12 DRAWING A404 BUILDING ELEVATIONS (HIDDEN)
1. Replace sheet A404 with A404R2. 3.13 DRAWING A600 WALL SECTIONS
1. Replace sheet A600 with A600R2. 3.14 DRAWING A601 WALL SECTIONS
1. Replace sheet A601 with A601R2.
3.15 DRAWING A602 WALL SECTIONS
1. Replace sheet A602 with A602R2.
3.16 DRAWING A603 WALL SECTIONS
1. Replace sheet A603 with A603R2.
3.17 DRAWING A604 WALL SECTIONS
1. Replace sheet A604 with A604R2.
14-001 Addendum #02 Page 5 of 5
3.18 DRAWING A605 WALL SECTIONS
1. Replace sheet A605 with A605R2. 3.19 DRAWING A652 WALL SECTION DETAILS
1. Replace sheet A652 with A652R2. 3.20 DRAWING A653 WALL SECTION DETAILS
1. Replace sheet A653 with A653R2. 3.21 DRAWING 51/A700 INDOOR PLAYGROUND WR-NW-L2-NORTH ELEV.
1. Add TL1 finish to wall to 1500 a.f.f.
3.22 DRAWING 53/A700 INDOOR PLAYGROUND WR-NW-L2-SOUTH ELEV.
1. Add TL1 finish to wall to 1500 a.f.f.
3.23 DRAWING A802 LEVEL 1 SOUTH WING REFLECTED CEILING PLAN
1. Add WDC (Linear Wood Ceiling) to soffit east of TCDSB Vice Principal Office 2. Add MP (Metal Panel Soffit) to soffit east of Grid Line s10 sC to sF.1
3.24 DRAWING A809 CEILING DETAILS
.a Replace sheet A809 with A809R2. 3.25 DRAWING A991 WINDOW & CURTAINWALL SCHEDULE
.a Replace sheet A991 with A991R2. 3.26 DRAWING A992 WINDOW & CURTAINWALL SCHEDULE
.a Replace sheet A992 with A992R2.
4.0 ELECTRICAL 4.1 Refer to attached Electrical Addendum# E-1. Dated 15 February 2017 (2 cover pages & 5
drawings, total 7 pages)
End of Addendum # 02 (20 Pages of Attachments)
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
s8s7s4.2 s5.1 s6s5
2
A5012
A503
2
A506
s6.1s4.1
MECH ROOF SOUTH 100.14 m
MP-2
410
43408000x1000
ALUMN. LOUVER2400x1000
ALUMN. LOUVER7200x1000
ALUMN. LOUVER
10000x1000ALUMN. LOUVER
1200
1000
400
2700
1300720020002400180020007602240
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
s8 s7 s4.2s5.1s6 s5
2
A500
2
A506
s6.1 s4.1
MECH ROOF SOUTH 100.14 m
1
A501MP-2
4340
410
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
sA sA.1 sB sC sD sE sE.1 sF
1
A504
1
A506
sGsB.1 sC.1sB.2 sD.1
MECH ROOF SOUTH 100.14 m?
MP-2 MP-1
1600
410
4340
1815
SKYLIGHT, REFER TO A654,3 FOR DETAILS
SOLAR TUBES, REFER TOA654, 11 FOR DETAILS
S4.1.3
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 1 SOUTH KINDERGARTEN 84.70 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
sDsE
LEVEL 0 LOADING AREA 78.20 m
STAIR EXIT S_WEST 83.66 m
1
A506
sC.1sD.1
PR
600
350 735
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 1 SOUTH KINDERGARTEN 84.70 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
sD
LEVEL 0 LOADING AREA 78.20 m
STAIR EXIT S_WEST 83.66 m
sC.1
MP-2
MP-2
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
n6 s3.1 s4
LEVEL 1 SOUTH 84.10 m
MP-2
MP-2
MP-2
MP-2
MP-2
PR
PR-1
S1.26.7 S1.26.6
1
A655
450
3350
650
3150
850
3250
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 1 SOUTH KINDERGARTEN 84.70 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
s3.1 s4
PR
360
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 1 SOUTH KINDERGARTEN 84.70 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
s4.2 s3.1s4
LEVEL 1 SOUTH 84.10 m
s4.1
MP-2
1
A655
850
3160
840
3150
450
600
PERF-M,PERFORATED METAL
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 1 SOUTH KINDERGARTEN 84.70 m
LEVEL 1 SOUTH 84.10 m
SCW19
200
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
s8 s7 s4.2s5.1 s3.1 s3 s2 s1.2s6 s5 s4
2
A500
2
A506
2
A508
s6.1 s4.1 s1.1
1
A501
MP-1 ?
660
1285
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n3
MP-2PR
910
2180PLANTER BOX,
REFER TO ROOFPLAN
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nD.1
LEVEL 5 ROOF NORTH 99.17 m
nD nE
2
A504
nE.1
MP-2PR
1200
3090
PLANTER BOX ,REFER TO ROOFPLAN
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nD.1
LEVEL 5 ROOF NORTH 99.17 m
nE
2
A504
nE.1
MP-2PR
3090
1190
N4.5 N4.4
2025
2005
480 3540
300x300 ALUMN.LOUVER400X350 ALUMN.
LOUVER
O2
2230
110
CJ CONTROL JOINTCONC POURED IN PLACE CONCRETELVR METAL LOUVERM-MESH METAL FABRIC MESHMP-1 METAL PANEL FOR ROOF VALEMP-2 METAL PANEL FOR BUILDING WALLSO1 SURFACE MOUNTED LUMINAIRE WITH TYPE IV LIGHT (REFER TO ELECTRICAL)O2 SURFACE MOUNTED LUMINAIRE (REFER TO ELECTRICAL)PR PRE-CAST CONC. PANEL
*ALL GLASS TO HAVE BIRD FRIT OF 6MM CIRCLES AT 100MM O.C. AS PER CITY OF TORONTO GUIDELINES*ALL GLASS TO BE 6mm INNER GLASS WITH 13mm AIR SPACE AND 6mm OUTER GLASS TO ACHIEVE A 36STC RATING
LEGEND
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
As indicated
2/17/2017 3:32:47 PM
A403R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
BUILDING ELEVATIONS(HIDDEN)
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 1001 SOUTH BUILDING - MECHANICAL PENTHOUSE SOUTH ELEVSOUTH BUILDING - MECHANICAL PENTHOUSE SOUTH ELEV
1 : 1002 SOUTH BUILDING - MECHANICAL PENTHOUSE NORTH ELEVSOUTH BUILDING - MECHANICAL PENTHOUSE NORTH ELEV
1 : 1004 SOUTH BUILDING - MECHANICAL PENTHOUSE WEST ELEVSOUTH BUILDING - MECHANICAL PENTHOUSE WEST ELEV
1 : 1003 SOUTH BUILDING - SW EXIT STAIR EAST ELEVSOUTH BUILDING - SW EXIT STAIR EAST ELEV
1 : 1006 SOUTH BUILDING - SW EXIT STAIR WEST ELEVSOUTH BUILDING - SW EXIT STAIR WEST ELEV
1 : 1007 SOUTH BUILDING - SN EXIT STAIR NORTH ELEV 01SOUTH BUILDING - SN EXIT STAIR NORTH ELEV 01
1 : 1008 SOUTH BUILDING - SN EXIT STAIR NORTH ELEV 02SOUTH BUILDING - SN EXIT STAIR NORTH ELEV 02
1 : 1009 SOUTH BUILDING - SN EXIT STAIR SOUTH ELEV 01SOUTH BUILDING - SN EXIT STAIR SOUTH ELEV 01
1 : 1005 SOUTH BUILDING - KINDERGARTEN ENTRYSOUTH BUILDING - KINDERGARTEN ENTRY
1 2017/01/31 ISSUED FOR TENDER2 2017/02/17 ADDENDUM 2
1 : 10013 SOUTH BUILDING - VEIL NORTH ELEVSOUTH BUILDING - VEIL NORTH ELEV
1 : 10010 NORTH BUILDING - EXIT STAIR NW NORTH ELEVNORTH BUILDING - EXIT STAIR NW NORTH ELEV
1 : 10011 NORTH BUILDING - EXIT STAIR NW WEST ELEVNORTH BUILDING - EXIT STAIR NW WEST ELEV
1 : 10012 NORTH BUILDING - EXIT STAIR NW EAST ELEVNORTH BUILDING - EXIT STAIR NW EAST ELEV
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nC nD.1 nF
LEVEL 5 ROOF NORTH 99.17 m
nD nE nF.1
1
A502
2
A504
nE.1nB nB.1 nC.1
CONC
N4.2.2 NCW49NCW47
N4.1.5
O2
2200
450 450
MP-1 MP-1CONCFOR LIGHTING MOUNTED TOSOFFIT OF ROOF REFER TO E2081
A811R12
A811R1
400
375
300x300ALUMN.LOUVER
O2
2200
1050
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nCnD.1nF
LEVEL 5 ROOF NORTH 99.17 m
nDnEnF.1
1
A502
2
A504
nE.1 nBnB.1nC.1
GL-1 MP-1
NCW45
N4.1.4
GLASS GUARD BEYOND,REFER TO A340,4 SIM.
FOR LIGHTING MOUNTEDTO SOFFIT OF ROOFREFER TO E208
1A811R1
2A811R1
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
n8n7
LEVEL 5 ROOF NORTH 99.17 m
2
A501
n7.2 n8.2
1
A500GL-1CONC
n6.1 n7.1
NCW46NCW48
N4.1.3
MP-1
FOR LIGHTING MOUNTED TOSOFFIT OF ROOF REFER TO E208
O2
MOUNT LIGHTON FRAME
2200
350
505505
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n8 n7
LEVEL 5 ROOF NORTH 99.17 m
n7.2n8.2
1
A500
1
A501
CONC
n6.1n7.1
MP-1
NCW44
N4.1.2
NCW28
FOR LIGHTINGMOUNTED TO
SOFFIT OF ROOFREFER TO E208
750
300
300x300ALUMN.LOUVER
O2
350
2200
8002305525
O2
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n11n10
LEVEL 5 ROOF NORTH 99.17 m
MP-1MP-2
2520
3900 1900 500 1200
1900x1000ALUMN.
LOUVER
1200x1000ALUMN.
LOUVER
2200
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n11 n10
1
A507
MP-1
2225
2305
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nH
nJ
1
A503
MP-1 MP-2
2195
2335
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nH nJ1
A503
MP-1
ROOFACCESSLADDER
193525
20
MP-2
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n8n7.2 n8.2
1
A500
MP-2 ?
1700
1300
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nHnG
1
A503
FOR
CO
MPL
ETE
ELEV
ATIO
NR
EFER
TO
A40
1-3
MP-2
N3.14.2
1300
3035
335
1000
1700
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
MP-1
1755
1410
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nA.4 nC nD.1 nF
LEVEL 5 ROOF NORTH 99.17 m
nD nE nF.1 nG
1
A502
2
A504
nE.1nB nB.1 nC.1
MP-1
2930
1440
550
2350
2400x800ALUMN.
LOUVER
O1
1820
1200
N4.3
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n10 n9 n8
2
A503
1
A507
2
A506
n8.2
1
A500
MP-1
1220
2985
950
1450
1500x1000 ALUMN.LOUVER
CJ CONTROL JOINTCONC POURED IN PLACE CONCRETELVR METAL LOUVERM-MESH METAL FABRIC MESHMP-1 METAL PANEL FOR ROOF VALEMP-2 METAL PANEL FOR BUILDING WALLSO1 SURFACE MOUNTED LUMINAIRE WITH TYPE IV LIGHT (REFER TO ELECTRICAL)O2 SURFACE MOUNTED LUMINAIRE (REFER TO ELECTRICAL)PR PRE-CAST CONC. PANEL
*ALL GLASS TO HAVE BIRD FRIT OF 6MM CIRCLES AT 100MM O.C. AS PER CITY OF TORONTO GUIDELINES*ALL GLASS TO BE 6mm INNER GLASS WITH 13mm AIR SPACE AND 6mm OUTER GLASS TO ACHIEVE A 36STC RATING
LEGEND
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
N3.13BNCW39A
MP-2
3180 37
00
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
PR-1
NCW27
3750
1100
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
LVR MP-2
2310
3305
1100
NCW27
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
As indicated
2/17/2017 3:32:50 PM
A404R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
BUILDING ELEVATIONS(HIDDEN)
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 2017/01/31 ISSUED FOR TENDER2 2017/02/17 ADDENDUM 2
1 : 1001 NORTH BUILDING - ATRIUM PENTHOUSE WEST ELEVNORTH BUILDING - ATRIUM PENTHOUSE WEST ELEV
1 : 1002 NORTH BUILDING - ATRIUM PENTHOUSE EAST ELEVNORTH BUILDING - ATRIUM PENTHOUSE EAST ELEV
1 : 1003 NORTH BUILDING - ATRIUM PENTHOUSE SOUTH ELEVNORTH BUILDING - ATRIUM PENTHOUSE SOUTH ELEV
1 : 1004 NORTH BUILDING - ATRIUM PENTHOUSE NORTH ELEVNORTH BUILDING - ATRIUM PENTHOUSE NORTH ELEV
1 : 1005 NORTH BUILDING - MECHANICAL ROOM PIT SOUTH ELEVNORTH BUILDING - MECHANICAL ROOM PIT SOUTH ELEV
1 : 1006 NORTH BUILDING - MECHANICAL ROOM PIT NORTH ELEVNORTH BUILDING - MECHANICAL ROOM PIT NORTH ELEV
1 : 1007 NORTH BUILDING - MECHANICAL ROOM PIT EAST ELEVNORTH BUILDING - MECHANICAL ROOM PIT EAST ELEV
1 : 1008 NORTH BUILDING - MECHANICAL ROOM PIT WEST ELEVNORTH BUILDING - MECHANICAL ROOM PIT WEST ELEV
1 : 1009 NORTH BUILDING - ROOF BALCONY SOUTH ELEVNORTH BUILDING - ROOF BALCONY SOUTH ELEV
1 : 10010 NORTH BUILDING - ROOF BALCONY WEST ELEVNORTH BUILDING - ROOF BALCONY WEST ELEV
1 : 10011 NORTH BUILDING - VEIL SOUTH ELEVNORTH BUILDING - VEIL SOUTH ELEV
1 : 10012 NORTH BUILDING - VEIL WEST ELEVNORTH BUILDING - VEIL WEST ELEV
1 : 10013 NORTH BUILDING - VEIL NORTH ELEVNORTH BUILDING - VEIL NORTH ELEV
1 : 10014 EXTERIOR BALCONY - SOUTH ELEVEXTERIOR BALCONY - SOUTH ELEV
1 : 10015 EXTERIOR BALCONY - EAST ELEVEXTERIOR BALCONY - EAST ELEV
1 : 10016 EXTERIOR BALCONY - WEST ELEVATIONEXTERIOR BALCONY - WEST ELEVATION
LEVEL 2 NORTH 86.70 m
LEVEL 3 NORTH WING 90.70 m
LEVEL 1 NORTH 83.00 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n2
CW1
CW1
R1
W3A
S2
R1
A653R210
Sim
A6513
Sim
A6516
Sim
A653R210
Sim
3700
4000
4000
A6519
Sim
A65112
Sim
LEVEL 2 NORTH 86.70 m
LEVEL 3 NORTH WING 90.70 m
LEVEL 1 NORTH 83.00 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nFnF.1nG nE.1
W5
W3A
R1
W3A
W3A
S2
A653R22
Sim
A653R21
Sim
A6513
Sim
3720 1130 1815
4000
4000
3700
A656R10
Sim
69.98 m
TEACHINGKITCHEN
N3.13
93.59 m
MULTIPURPOSE3
N2.11
944.46 m
CIRCULATIONN1.1B
14.56 m
PARKING OB12N-P46
A656R14
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 25
2/17/2017 5:03:54 PM
A600R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTIONS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 252 WALL SECTION BWALL SECTION B
1 : 251 WALL SECTION AWALL SECTION A
1 2017/01/31 ISSUED FOR TENDER2 2017/02/17 ADDENDUM 2
LEVEL 2 NORTH 86.70 m
LEVEL 1 NORTH 83.00 m
nA
W3A
R1
W1A
S2
A6516
Sim
A6513
Sim
A653R210
Sim
A6545
Sim
3700
223.55 m
INDOORPLAYGROUND
N2.17A
17.42 m
PARKINGOBP5N-P54
LEVEL 2 NORTH 86.70 m
LEVEL 3 NORTH WING 90.70 m
LEVEL 1 NORTH 83.00 m
nAnA.4
W3A
R1
R1
W3A
W3A
S2
W1A
+2750ACT
+2750ACT
A653R210
Sim
A6516
Sim
A6545
Sim
A6513
Sim
A656R10
Sim
4000
3700
4070
158.10 m
MULTI-USECOMMUNITY
SPACEN3.2A
101.26 m
MULTIPURSPOSEROOM
PRESCHOOLN2.16A
944.46 m
CIRCULATIONN1.1B
17.42 m
PARKINGOBP6N-P53
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 25
2/17/2017 5:04:03 PM
A601R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTIONS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 251 WALL SECTION CWALL SECTION C
1 : 252 WALL SECTION DWALL SECTION D
1 2017/01/31 ISSUED FOR TENDER2 2017/02/17 ADDENDUM 2
LEVEL 2 SOUTH 88.20 m
LEVEL 1 SOUTH KINDERGARTEN 84.70 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
sG
R3
S1
S1
W3A
S1
W1A
W3A
P5C
P5C
P5CW3A
W1B
3800
3800
3500
A6511
Sim
A6514
Sim
104.99 m
TCDSBKINDERGARTEN
S1.9
70.44 m
TCDSBCLASSROOM
S3.13
99.84 m
TCDSB SPECED
CLASSROOMS2.16
A652R213
Sim
LEVEL 2 NORTH 86.70 m
LEVEL 3 NORTH WING 90.70 m
LEVEL 1 NORTH 83.00 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nA.4
LEVEL 5 ROOF NORTH 99.17 m
nB
W3A
R1
S2
W1A
S1
CW1
3630
4465
4000
4000
3700
A653R23
Sim
A653R24
Sim
A6517
Sim
A652R27
Sim
A653R210
Sim
229.12 m
WALKINGTRACKN3.4A
297.08 m
GYM 1 BN2.4A
155.39 m
GENERATORROOMN1.43A
A809R28
Sim
A6545
Sim
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 25
2/17/2017 5:04:13 PM
A602R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTIONS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 252 WALL SECTION FWALL SECTION F
1 : 251 WALL SECTION EWALL SECTION E
1 2016/09/19 ISSUED FOR 50% CD2 2017/01/31 ISSUED FOR TENDER3 2017/02/17 ADDENDUM 2
LEVEL 2 NORTH 86.70 m
LEVEL 3 NORTH WING 90.70 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
n12
Change Rooms 83.00 m
n13
A4236
S2
W1A
LV
CW1
R1
W3A
W3A
3700
4000
4000
750
A6513
Sim
A652R27
Sim
A652R212
Sim
229.12 m
WALKINGTRACKN3.4A
297.08 m
GYM 1 BN2.4A
155.39 m
GENERATORROOMN1.43A
134.46 m
TDSBMULTIPURPOSE
N1.54A
A809R28
Sim
A6545
Sim
A6516
Sim
LEVEL 3 NORTH WING 90.70 m
n12 n13
S1
R1
W3A
W3A
W3B
W2D
W1A
750
A6513
Sim
A6516
Sim
A65111
Sim
517.93 m
MECHANICALN3.14
250.18 m
SCHOOL GYM2
N1.56
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 25
2/17/2017 5:04:21 PM
A603R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTIONS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 251 WALL SECTION GWALL SECTION G
1 : 252 WALL SECTION HWALL SECTION H
1 2016/09/19 ISSUED FOR 50% CD2 2017/01/31 ISSUED FOR TENDER3 2017/02/17 ADDENDUM 2
LEVEL 3 NORTH WING 90.70 m
LEVEL 1 NORTH 83.00 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nJ
W1A
S1
W3B
R1
W3A
W3A
LV
CW1
CW1
S1
4000
7700
A6513
Sim
A656R6
Sim
A656R7
Sim
A652R214
Sim
331.47 m
SCHOOL GYM1
N1.57
331.47 m
SCHOOL GYM1
N1.57
517.93 m
MECHANICALN3.14
LEVEL 2 SOUTH 88.20 m
LEVEL 3 SOUTH 92.00 m
LEVEL 1 SOUTH 84.10 m
W3A
S1
S1
W3A
W3A
W3A
R1
P5C
P5C
+2750ACT
+2750ACT
+3250WDC
4100
3800
A6513
Sim
A652R25
Sim
A652R24
Sim
A652R26
Sim
A6516
Sim
A6515
Sim
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 25
2/17/2017 5:04:28 PM
A604R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTIONS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 252 WALL SECTION JWALL SECTION J
1 : 251 WALL SECTION IWALL SECTION I
1 2017/01/31 ISSUED FOR TENDER2 2017/02/17 ADDENDUM 2
LEVEL 2 NORTH 86.70 m
LEVEL 1 NORTH 83.00 m
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nA
W1A
CW1
W3A
W3A
R1
+2250WDC
944.46 m
CIRCULATIONN1.1B
A6513
Sim
A6545
Sim
8000
3700
300.71 m
COMMUNITYCENTRELOBBYN2.1A
A652R213
Sim
A6516
Sim
LEVEL 0 U.G. PARKING 79.20 m
LEVEL 2 SOUTH 88.20 m
LEVEL 3 SOUTH 92.00 m
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
s3.1s4
LEVEL 1 SOUTH 84.10 m
R1
W3A
W3A
W3A
+2650WDC
+3050ACT
P5C
S1
+3050ACT
P5C
CW1
+2750ACT
P5C
S1
S1
S1
SPW01
SPW01
4900
4100
3800
3800
A6511
Sim
A652R25
Sim
A652R24
Sim
A652R26
Sim
48.92 m
TDSBRESOURCE
S3.29
53.37 m
TDSBRESOURCE
S2.30
53.63 m
PRESCHOOLPLAYROOM 1
S1.24
A652R24
Sim
A6516
Sim
A653R212
Sim
A6545
Sim
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 25
2/17/2017 5:04:30 PM
A605R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTIONS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 251 WALL SECTION KWALL SECTION K
1 : 252 WALL SECTION LWALL SECTION L
1 2016/09/19 ISSUED FOR 50% CD2 2017/01/31 ISSUED FOR TENDER3 2017/02/17 ADDENDUM 2
LEVEL 2 NORTH 86.70 m
n13
CONC. SIDEWALK (REFER TO LANDSCAPE)
80
13mm FIBERBOARD
CONC. FACED INSULATEDPANEL
VAR
IES
(REF
ER T
O G
RAD
ING
PLA
N)
LAP A/V BARRIER ANDWATERPROOFING MIN. 100mm
SEALANT W/ BACKER ROD
3mm ANOD. ALUMN. PLATE SECUREDTO MULLION AND CONC. WALL
A/V BARRIER SECURED TO MULLION
SEALANT W/BACKER ROD
BLADE CWCONNECTION BOLTED
TO CONC. SLAB
64mm x 128 mm x 6.4 STEELANGLE 200mm LONG 600 O.C.
BOLTED TO CONC. SLAB
6mm CONT. BRAKE FORMALUMN. SHAPE FASTENED TO
STEEL ANGLE
STEEL COLUMN BEYOND
335
CW
70
255
FLOATING WOOD FLOOR
LEVEL 3 NORTH WING 90.70 m
n13
ALUMINUM BENT PANEL SECUREDTO ALUMINUM MULLION TO MATCHMULLIONSEALANT WITH BACKER ROD
70DECK CLOSUREANGLE
360
INTERIOREXTERIOR
CW BLADE CONNECTION NOEXPOSED FASTENERS
12mm ABUSE RESISTANT GWB CEILINGAND BULKHEAD ON LIGHT GAUGEFRAMING
LIGHT FIXTURE
7070
40
130
CW
sA
INTERIOREXTERIOR
SEAL WINDOW FRAME TO MEMBRANE WITHONE BEAD OF CONTINOUS SEALANT
LAP AV MEMBRANE OVERTHROUGHWALL FLASHING MEMBRANE
SEALANT WITHBACKER ROD
THROUGHWALL FLASHINGMEMBRANE
SEALANT WITH BACKER ROD-PROVIDE DRAINAGE HOLES AT 400mm O.C.
CONCEALED ROLLER SHADE
ALUMINUM COMPOSITE PANELS ATTACHEDTO THERMALLY-BROKEN SUB-GIRTS
REFER TO REFLECTED CEILINGPLAN FOR CEILING TYPE & HEIGHT
PROVIDE STEEL STUDBRACING TO DECK ABOVEAS REQUIRED
W3A
HEIGHT OF BULKHEAD ABOVEF.F. VARIES: REFER TO R.C.P.
13mm REVEAL MOLDING
BULKHEAD P5B - 16mm GWB ON 92mm STEELSTUD - EXTEND TO U/S STEEL DECK
VAR
IES
PROVIDE PERFORATIONSON U/S W/ INSECT SCREEN, TYPICAL
LEVEL 3 SOUTH92.00 m
sA
16mm GWB ON 152mm STRUCTURALSTUDS @ 400mm O.C.
DRYWALL TRIM PAINTED 16mm REVEAL
CAULKING TO MATCH ALUMINUMCOMPOSITE PANEL
SEAL WINDOW FRAME ON AVB
WINDOW FRAME SECURED TOWINDOW CLIPS
ALUMINUM COMPOSITE PANELSON THERMALLY BROKEN Z-GIRTS
CONCRETE FLOOR SLAB
LAP THROUGHWALL FLASHINGMEMBRANE OVER AV MEMBRANE
FILL GAP WITH SPRAY INSULATION
CLEAR CAULKING
RUBBER BASE
INTERIOREXTERIOR
250
19mm FINISHED PLYWOOD SILLC/W 6mm DIA. RADIUS ONEXPOSED CORNERS
100
38
W3A
20
sA
CONC. SIDEWALK (REFER TO LANDSCAPE)
13mm FIBERBOARD
50mm SEMI RIGID INSULATION W/IMPALE CLIPSDRAINAGE BOARD
WATERPROOFING
LAP WATERPROOFING MIN. 100mmOVER CONC. WALL
BLADE CW CONNECTION CAST IN SLAB
FILL GAP WITH INSULATION
SEALANT W/ BACKER ROD
SEALANT W/ BACKER ROD
MEMBRANE FLASHING
SLOPE 2%
90mm PRE-CAST CONC. PANEL
CAST IN PLATE, FILL IN POCKET AFTERPANEL INSTALATION
350
PRE CAST ANCORS AS REQUIRED BYPRE CAST MANUF.
75mm FOIL FACEDSEMI RIGID
INSULATION ONIMPALE CLIPS
EXTEND DOWNWALL 1200
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
EXTERIOR
FILL CAVITY WITH BATT INSULATION
CONTINUOUS 38x64 PRESSURE TREATEDWOOD BLOCKING
PREFINISHED ALUMINUM COMPOSITE FLASHINGSECURED ONTO WOOD BLOCKING
SLOPE 2%
CONT. 38X64 PRESSURE TREATED WOODBLOCKING
16mm PRESSURE TREATED PLYWOOD SECUREDONTO WOOD BLOCKING
LAP CONTINUOUS SHEET MEMBRANE AIR BARRIER OVERPARAPET AND SEAL ONTO CW FRAME
CONT. 38x64 PRESSURE TREATED WOOD OUTRIGGER @ 600O.C. ON WOOD BLOCKING MECHANICALLY FASTENED TO
STRUCTURAL STEEL STUDS
6mm ALUMN. COMPOSITE PANEL ON STEEL Z GRITS 600mm O.C.50mm SEMI-RIGID INSULATION
16mm GYPSUM SHEATHING ON 152mm STRUCTURAL STEEL STUDS600 O.C. PACKED WITH BATT INSULATION IN-BETWEEN
LAP ROOF MEMBRANE OVERA/V BARRIER MIN. 100mm
WEEP HOLE WITH INSECT SCREEN
PRE-FINISHED FLASHING
Z-GRIT THERMALLY BROKEN
PRE-FINISHED FLASHING
THROUGH WALL MEMBRANEFLASHING
INTERIOR
WALL AIR BARRIER TO OVERLAP ROOFAIR BARRIER MIN. 150mm
EXTEND ROOT BARRIER TO 300 ABOVE ROOFINSULATION
2% SLOPE MINIMUM
STONE BALLAST ON ROOT BARRIER
100mm SOIL DEPTH PLASTIC TRAYGREEN ROOF SYSTEM ON DRAINAGEBOARD AND ROOT BARRIER
PERFORATED GALVANIZEDSTEEL ANGLE
75
25
ALUMN. CURTAIN WALL W/ INSULATED SPANDREL PANEL
STRUCTURAL STEEL ANGLE
115
PROVIDE GUSSET IN MEMBRANE TO ACCOMMODATE CW MOVEMENT
500
CONC. SIDEWALK (REFERTO LANDSCAPE)
13mm FIBERBOARD
50mm SEMI RIGID INSULATIONW/IMPALE CLIPS DRAINAGE BOARD
WATERPROOFING
LAP WATERPROOFING MIN. 100mmOVER CONC. WALL
BLADE CW CONNECTION CAST IN SLAB
FILL GAP WITH INSULATION
SEALANT W/ BACKER RODS ONBOTH SIDES
STEEL COLUMN BEYOND, REFERTO STRUCTURAL
155
50
360 TRENCH HEATER, REFER TO MECHANICAL
6mm S.S. COVER PLATE
MEMBRANE FLASHING
SLOPE 2%
90mm PRE-CAST CONC. PANEL
CAST IN PLATE, FILL IN POCKET AFTERPANEL INSTALATION
350
PRE CAST ANCORS AS REQUIRED BYPRE CAST MANUF.
15
330
grid25 125 125
MAINTAIN MIN. 25mm CLEARANCE BETWEEN ALUMN.CURTAINWALL FRAMING AND STRUCTURAL COLUMN TYP.
LEVEL 2 SOUTH 88.20 mCAULKING TO MATCH ALUMINUM
COMPOSITE PANEL
SEAL WINDOW FRAME ON AVB
WINDOW FRAME SECURED TOWINDOW CLIPS
ALUMINUM COMPOSITE PANELS ONTHERMALLY BROKEN Z-GIRTS
CONCRETE FLOOR SLAB
LAP THROUGHWALL FLASHINGMEMBRANE OVER AV MEMBRANE
FILL VOID WITH SPRAY INSULATION
CLEAR CAULKING
INTERIOREXTERIOR
38
100
W3A
19mm FINISHED PLYWOODJAMB (BEYOND)C/W 6mm DIA. RADIUS ONEXPOSED CORNERS
LEVEL 2 NORTH 86.70 m
n13
CONC. SIDEWALK (REFER TO LANDSCAPE)
80
380
13mm FIBERBOARD
GALV. STEEL ANGLE SECURED TO CONC. WALL
50mm PRE-CAST CONC. PANEL
65VA
RIE
S (R
EFER
TO
GR
ADIN
G P
LAN
)
A/V BARRIER RUN OVER CONC. FOUNDATIONWALL ATTACH TO PRE-CAST
ALUMN. LOUVER
SEALANT W/ BACKER ROD
3mm ANOD. ALUMN. PLATE SECUREDTO MULLION AND CONC. WALL
A/V BARRIERSECURED TO MULLION
SEALANT W/BACKER ROD
STEEL COLUMN BEYOND
360
SEALANT W/ BACKER ROD
LAP A/V BARRIER MIN. 100 OVER FOUNDATIONWATERPROOFING
BLADE CWCONNECTION BOLTED
TO CONC. SLAB
64mm x 128 mm x 6.4 STEELANGLE 200mm LONG 600 O.C.
BOLTED TO CONC. SLAB
6mm CONT. BRAKE FORMALUMN. SHAPE FASTENED TO
STEEL ANGLE
255
FLOATING WOOD FLOOR
30
70 210
LEVEL 2 NORTH 86.70 m
CONC. SIDEWALK, REFER TO LANDSCAPE
13mm FIBERBOARD50mm SEMI RIGID INSULATION W/IMPALE CLIPS
DRAINAGE BOARD WATERPROOFING
LAP WATERPROOFING MIN. 100mmOVER CONC. WALL
BLADE CW CONNECTION CAST IN SLAB
FILL GAP WITH INSULATION
SEALANT W/ BACKER RODS ONBOTH SIDES
STEEL POST BEYOND, REFER TOSTRUCTURAL
9515
5
36012575
TRENCH HEATER, REFER TOMECHANICAL
PRE-FINISHED FLASHING
SLOPE 2%
7575260165
grid
MAINTAIN MIN. 25mm CLEARANCEBETWEEN ALUMN. CURTAINWALL FRAMING
AND STRUCTURAL COLUMN TYP.
30
150
250
200 200 360 80
TO EDGE OF SLAB450
CONT. 64x64mm PRESSURETREATED WOOD BLOCKING
38x290 PRESSURE TREATEDWOOD BLOCKING c/wINSULATION
CONT. 38x89 PRESSURETREATED WOOD BLOCKING
PREFINISHED METAL FLASHING CAPSLOPE 2%
LAP A/V BARRIER OVER GRAVITYCONNECTION
KERF MEMBRANE AND METAL FLASHINGCAP INTO PRECAST AND PROVIDECONTINUOUS SEALANT ALONG JOINT
REGLET TOP OF PRECAST PANEL
FILL CAVITY WITH SPRAY FOAM INSULATION
PRECAST PANEL GRAVITY CONNECTION TOSTEEL BEAM ( BY INSTALLER)
STEEL BEAM (REFER TO STRUCTURAL)
ROOF AIR BARRIER TO OVERLAP WALL AIRBARRIER MIN. 150mm
PRE-FINISHED SHEET STEEL FLASHING
16mm GYPSUM SHEATHING ON 152mmSTRUCTURAL STEEL STUDS 600
O.C.PACKED WITH BATT INSULATION INBETWEEN
WRAP ROOT BARRIER OVER PARAPET
90mm PRECAST PANEL
FILL CAVITY WITH SPRAY FOAM INSULATION
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
PRE-FINISHED FLASHING
INTERIOR EXTERIOR
STRUCTURAL CONCRETE FLOOR SLABS(REFER TO STRUCT. DWGS)
METAL FLASHING OVEREXTENDED ROOFING MEMBRANEON 16mm EXTERIOR SHEATHINGON 65mm RIGID INSULATIONON A/V BARRIERON 16mm EXT. SHEATHINGON 152mm STRUCTURAL STUDS
SEALANT C/W BACKING ROD & W/ WEEP HOLESYSTEM @400mm O.C.
BRING ROOFING MEMBRANE UP MIN. 100mm AND SEALTO A/V BARRIER UNDER METAL FLASHING
400
MIN
.
100
WOOD DECKING ON ADJ. PEDESTALS
WALL TYPE W2A:100mm PRECAST CONCRETE PANELS100mm SPRAY FOAM INSULATION16mm EXTERIOR GYPSUM SHEATHING152mm STRUCTURAL STEEL STUDS16mm GWB
100
LEVEL 2 NORTH 86.70 m
LEVEL 2 NORTH (m.p.) 87.70 m
EXTERIORINTERIOR
PROVIDE DRIP EDGE ATPRECAST RETURN
SEAL THROUGHWALL FLASHING INTO CURTAINWALLHEADER
FILL CAVITY WITH SPRAY FOAM INSULATION
BACKER ROD AND SEALANT
FIXED GLAZING IN ALUMINUM CURTAIN WALL FRAMINGSYSTEM (REFER TO WINDOW SCHEDULE)
EXTEND SPRAY FOAM INSULATION HORIZONTALLY OVER PRECAST
PRECAST CONNECTION SECURE TO STEELHSS
STEEL HSS SECURE TO CONC. SLAB ABOVE
EXTEND CURTAIN WALL MULLION TOCONC. SLAB ABOVE
REFER TO R.C.P. FORCEILING TYPE
WEATHER SEAL, BACKER ROD ANDSEALANT, TYP.
PRECAST PANEL GRAVITY CONNECTIONTO SLAB EDGE (BY INSTALLER)
AIR SEAL, BACKER ROD ANDSEALANT, TYP.
PROVIDE A/V MEMBRANE AT PRECASTCONNECTION, TYP
CAST IN PLACE STEEL ANGLE / ANCHOR(REFER TO STRUCTURAL)
SLOTTED ANCHOR PLATE BETWEENPRECAST PANELS, TYP.
13mm REVEAL MOLDING
P5B BULKHEAD: 16mmGWB ON 64mm STEELSTUDS @ 400mm O.C.
W2A
W2A
S2
ROOF MEMBRANE TOTERMINATE IN REGLET
SLOPE 2%
50
400
20
15
DRIP AT TOP OFCONCRETE
WALL
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 5
2/17/2017 4:35:48 PM
A652R2
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTION DETAILS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 511 CURTAIN WALL BASE WITH OVERHANGCURTAIN WALL BASE WITH OVERHANG
1 : 57 TYPICAL CURTAIN WALL INTERMEDIATE FLOOR INTERFACETYPICAL CURTAIN WALL INTERMEDIATE FLOOR INTERFACE
1 : 54 TYPICAL WINDOW HEADTYPICAL WINDOW HEAD
1 : 55 TYPICAL WINDOW SILL WITH BASE WALLTYPICAL WINDOW SILL WITH BASE WALL
1 : 513 TYPICAL CURTAIN WALL BASE AT PRECAST CONCRETE PANELTYPICAL CURTAIN WALL BASE AT PRECAST CONCRETE PANEL
1 : 51 TYPICAL CURTAIN WALL PARAPETTYPICAL CURTAIN WALL PARAPET
1 : 514 TYPICAL CURTAIN WALL BASE ON CONCRETE CURBTYPICAL CURTAIN WALL BASE ON CONCRETE CURB
1 : 56 TYPICAL FLOOR-LEVEL WINDOW SILLTYPICAL FLOOR-LEVEL WINDOW SILL
1 : 512 CURTAIN WALL BASE WITH OVERHANG & LOUVRECURTAIN WALL BASE WITH OVERHANG & LOUVRE
1 : 510 TYPICAL CURTAIN WALL BASE AT GRADE W/ PERIMETER HEATINGTYPICAL CURTAIN WALL BASE AT GRADE W/ PERIMETER HEATING
1 2016/12/01 ISSUED FOR 90% CD2 2016/12/16 ISSUED FOR BUILDING
PERMIT3 2017/01/31 ISSUED FOR TENDER4 2017/02/17 RE-ISSUED FOR SPA5 2017/02/17 ADDENDUM 2
1 : 52 TYPICAL PRECAST CONCRETE PARAPETTYPICAL PRECAST CONCRETE PARAPET
1 : 53 TYPICAL PRECAST WALL BASE AT ROOFTYPICAL PRECAST WALL BASE AT ROOF
1 : 58 TYPICAL PRECAST CONCRETE WALL AND SOFFITTYPICAL PRECAST CONCRETE WALL AND SOFFIT
1 : 59 TYP. CONCRETE BASE EDGE DETAILTYP. CONCRETE BASE EDGE DETAIL
LEVEL 2 NORTH86.70 m
nA
INTERIOR EXTERIOR
REBAR DOWELS
2% SLOPE
25mm RIGID INSULATION
25
DAMPPROFING
CONCRETE FOUNDATION(REFER TO STRUCTURAL)
ENTRANCEVESTIBULE
N2.1C
FILL GAP WITH INSULATION
SEALANT W/ BACKER ROD
BLADE CW CONNECTION CAST IN SLAB
LEVEL 1 NORTH 83.00 m
nF.1
METAL FABRIC MESH ATTACHMENT
METAL FABRIC MESH
CONC. CURB150
150
LEVEL 2 NORTH 86.70 m
WALL TYPE W3A:COMPOSITE ALUMINUM
PANELS ATTACHEDTO THERMALLY-BROKEN
SUB-GIRTS
THROUGHWALLFLASHING SECURED TO
MULLION
SEALANT W/BACKER ROD
CONCRETE BEAM
INTERIOR
EXTERIOR
210
METAL FABRIC MESHATTACHED TO HORIZONTAL
ANGLE
PROVIDE PERFORATIONSON U/S W/ INSECT
SCREEN, TYP.
METAL FABRIC MESH
150mm SEMI-RIGID INSULATION ATTACHED TOIMPALED CLIPS
A/V BARRIER LAPPEDOVER FORMED METAL
FLASHING
30
0
25mm GAP ENCLOSEDWITH PREFINISHED
ALUMINUM TRIM
FILL CAVITY WITH SPRAY INSULATION
HORIZONTAL 152x152x12 GALV. STEEL ANGLE
VERTICAL 152x152x12 GALV. STEEL ANGLES AT1200mm O.C.
GALV. STEEL BLADES CAST INTO SLAB AT 1200mmO.C.
LEVEL 2 NORTH86.70 m
INTERIOR EXTERIOR
REBAR DOWELS
THERMALLY BROKEN ALUMN.THRESHOLD, PROVIDE MOUNTING CLIPAS REQUIRED
2% SLOPE
25mm RIGID INSULATION
25
DAMPPROFING, LAP AND SEALAGAINST ALUMN. THRESHOLD
CONCRETE GRADE BEAM, REFER TOSTRUCTURAL
ENTRANCE FLOOR GRILLE
LEVEL 4 EXTENSIVE ROOF SOUTH 95.80 m
SOLATUBE -530MM DIAMETER
INTEGRATED FLASHING SYSTEM
EXTEND ROOFING MEMBRANEFLASHING TO UNDERSIDE OF CAP
EXTEND ROOFING PLYS UNDERROOFING FLASHINGTORCH SEAL
HEIGHT OF EXTENSION TUBE VARIESDEPENDING ON ROOF HEIGHT
REFER TO REFLECTED CEILING PLANFOR DIFFUSER REQUIRED:610mm SQUARE FOR SUSPENDED GRIDCEILING; 610mm ROUND FOR GWB
CONTINUOUS SEALANT
25mm x 3mm GALV. METAL FLAT BAR FASTENED TOCOLUMN W/ 2 GALV. SCREWS PER SIDE
16mm SHEATHING ON 38mm x 64mm PT WOODBLOCKING
BOLT TO STEEL BEAM (REFER TOSTRUCT.)
10mm NEOPRENE THERMAL BREAK PAD
10mm DIA. VENT HOLES DRILLED INTO COLUMNS
PRE FINISHEDFLASHINGEXTEND ROOFING MEMBRANE TO BEHIND FLATBAR
135
3900
TO
TO
P O
F M
ETAL
FABR
IC S
CREE
N
4600
TO
TO
P O
FCO
LUM
N
GALV. STEEL STRUCT COLUMN ATTACHED TOSTEEL BEAM (SEE STRUCT)
METAL FABRIC SCREEN (REFER TO SPEC.)
METAL FABRIC ATTACHMENT PLATE (REFERTO SPEC.)
230
GALV. STEEL HSS (SEE STRUCT)
GALV. STEEL STRUCT COLUMN ATTACHED TOSTEEL BEAM (REFER STRUCT)
MOUNT LED LIGHT FIXTURE - (REFER ELECTRICAL)ON HSS BETWEEN POSTS LOCATED 2400 OCC - (REFER STRUCT)
METAL FABRIC SCREEN (REFER TO SPEC.)
METAL FABRIC ATTACHMENT PLATE (REFERTO SPEC.)
220
3900
TO
BO
TTO
M O
F M
ETAL
FAB
RIC
SCRE
EN
4600
TO
CO
NC. R
OO
F SL
AB
HSS - (REFER STRUCT)
WOOD DECKING
ADJ. PEDESTALS
FILL GAP WITH INSULATION
SEALANT W/ BACKER ROD
BLADE CW CONNECTION CAST IN SLAB
PRE-FINISHED FLASHING
LEVEL 4 ACTIVE ROOF NORTH94.70 m
LAP A/V BARRIER OVER ROOFMEMBRANE MIN. 100mm
WEEP HOLE WITH INSECT SCREEN
PRE-FINISHED FLASHING
WOOD DECKING
ADJ. PEDESTALS
Z-GRIT THERMALLY BROKEN
PRE-FINISHED FLASHING
THROUGH WALL MEMBRANEFLASHING
200
LEVEL 1 NORTH STAGE 83.60 m
LEVEL 1 SOUTH 84.10 m
STAIR EXIT S_WEST 83.66 m
CONC. SIDEWALK (REFER TO LANDSCAPE)
13mm FIBERBOARD
50mm SEMI RIGID INSULATION W/IMPALE CLIPSDRAINAGE BOARD
WATERPROOFING
LAP WATERPROOFING MIN. 100mmOVER CONC. WALL
BLADE CW CONNECTION CAST IN SLAB
FILL GAP WITH INSULATION
SEALANT NW/ BACKER ROD
SEALANT NW/ BACKER ROD
PRE-FINISHED FLASHING
SLOPE 2%
50mm RIGID INSULATION
175
WATERPROOFING
75mm FOIL FACED SEMI RIGIDINSULATION ON IMPALE CLIPS
s3.1
LEVEL 1 SOUTH84.10 m
13mm FIBERBOARD
CONC. SIDEWALK (REFER TOLANDSCAPE)
50mm RIGID INSULATION
DRAINAGE BOARD ONWATERPROOFING
WATERPROOFING
SLOPE 2%
SEAL LOUVER FRAME TO AVB WITHONE BEAD OF CONTINUOUS SEALANT
LAP AV MEMBRANE OVERTHROUGHWALL FLASHINGMEMBRANE
THROUGHWALL FLASHINGMEMBRANE
SEALANT WITH BACKER ROD-PROVIDE DRAINAGE HOLES AT400mm O.C.
ALUMINUM COMPOSITE PANELSATTACHED TO THERMALLY-BROKENSUB-GIRTS
ROOF MEMBRANE SECURE TO LOUVERFRAME
76mm FOIL BACKED INSULATION ONIMPALED CLIPS
STRUCTURAL STEEL ANGLES (REFERTO STRUCTURAL)
EXTERIOR GYP. SHEATHING
ALUMINUM LOUVER SECURE TO STEELANGLES ABOVE AND CONCRETE SLABBELOW
SLOPE 2%
50VA
RIE
S: R
EFER
TO
ELE
VATI
ON
S
LEVEL 4 ACTIVE ROOF NORTH 94.70 m
nG
INTERIOR
STRUCTURAL STEEL ANGLES ATTACHED TOCONCRETE SLAB16mm PT PLYWOOD ON 38x89mm WOOD FRAMING
2% SLOPE MINIMUM
ALUMINUM GLAZING CHANNEL SYSTEMMECHANICALLY FASTENED TO STRUCTURAL STEEL
PREFINISHED METAL FLASHINGOVER ROOF MEMBRANE WRAPPED OVER WALLV.B ON SLOPED 16mm PT PLYWOOD
WOOD DECK ONADJUSTABLE PEDASTLES
285
EXTERIOR
76mm FOIL BACKED INSULATION ONIMPALED CLIPS
16mm ABUSE RESISTANT GWBVAPOUR BARRIER152mm STEEL STUD FILL STUD SPACEWITH ROCK WOOL BATT INSULATION300mm CAST IN PLACE CONC. WALL
INTERIOR
ACOUSTIC CEILING TILES
BULKHEAD P5C - 16mm GWBON 64mm STEEL STUD -EXTEND TO U/S STEEL DECK
INSULATED BACK-PAINTED GLAZING
CURTAIN WALL SUPPORT BRACKETATTACHED TO STEEL ANGLE
DECK CLOSURE ANGLE
LINEAR BAR GRILLEREFER TO MECH. DRAWINGS
LINEAR BAR GRILLEREFER TO MECH. DRAWINGS
EXTERIOR
190
P5C
+2750ACT
152mm SEMI-RIGID INSULATION
SEALANT W/ BACKING ROD
SEALANT W/ BACKING ROD
13mm REVEAL MOULDING
350
800
680
CURTAIN WALL SCW-16
FINNED TUBE RADIATORATTACHED TO 38x64mm
UPRIGHTS @ 400mm O.C.
25
A/V BARRIER SEALED TO FRAME
A/V BARRIER
REFER TO 9/A924 FORBENCH CONSTRUCTION
DETAILS
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 5
2/20/2017 10:08:52 PM
A653R1
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
WALL SECTION DETAILS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 : 510 TYPICAL CURTAIN WALL BASE AT GRADETYPICAL CURTAIN WALL BASE AT GRADE
1 : 52 PARKING PERIMETER METAL FABRIC SCREEN BASEPARKING PERIMETER METAL FABRIC SCREEN BASE
1 : 51 PARKING PERIMETER METAL FABRIC SCREEN TOPPARKING PERIMETER METAL FABRIC SCREEN TOP
1 : 511 TYPICAL CURTAIN WALL DOOR THRESHOLD AT GRADETYPICAL CURTAIN WALL DOOR THRESHOLD AT GRADE
1 : 55 TYPICAL SOLATUBE DETAILTYPICAL SOLATUBE DETAIL
1 : 54 ACTIVE ROOF METAL FABRIC SCREEN BASEACTIVE ROOF METAL FABRIC SCREEN BASE
1 : 53 ACTIVE ROOF METAL FABRIC SCREEN TOPACTIVE ROOF METAL FABRIC SCREEN TOP
1 : 57 TYPICAL CURTAIN WALL BASE AT WOOD DECKTYPICAL CURTAIN WALL BASE AT WOOD DECK
1 : 58 TYPICAL COMPOSITE WALL BASE AT WOOD DECKTYPICAL COMPOSITE WALL BASE AT WOOD DECK
1 : 512 CURTAIN WALL BASE OVER VAULT SPACECURTAIN WALL BASE OVER VAULT SPACE
1 : 513 EXTERIOR CONCRETE SLAB OVER VAULT SPACEEXTERIOR CONCRETE SLAB OVER VAULT SPACE
1 : 59 TYPICAL GRADE-LEVEL LOUVRE SECTIONTYPICAL GRADE-LEVEL LOUVRE SECTION
1 : 514 GLASS GUARD BASE AT ROOF WOOD DECKGLASS GUARD BASE AT ROOF WOOD DECK
1 : 515 TYPICAL BELOW-GRADE PERIMETER WALL & EXT. INS. CEILINGTYPICAL BELOW-GRADE PERIMETER WALL & EXT. INS. CEILING
1 2016/12/01 ISSUED FOR 90% CD2 2016/12/16 ISSUED FOR BUILDING
PERMIT3 2017/01/31 ISSUED FOR TENDER4 2017/02/17 RE-ISSUED FOR SPA5 2017/02/17 ADDENDUM 2
1 : 56 CURTAIN WALL SPANDREL - CORRIDOR END WITH BENCHCURTAIN WALL SPANDREL - CORRIDOR END WITH BENCH
51 51
250
2750mmTO T/O F.F.
70
CONT ANOD. ALUMINUM GLAZING CHANNELSECURELY ANCHORED (SEE WINDOW
SCHEDULE)
ONE-HOUR FIRE RATED P2DPARTITION - 16mm TYPE X GWB ON92mm STEEL STUDS @ 400mm O.C.
P5E BULKHEAD: 16mm GWB ON 64mmSTEEL STUDS @ 400mm O.C.
- ANGLED AS SHOWN
WINDOW SPRINKLERS AT 1HRFIRE SEPARATION
(REF MECH. DWGS)
FULL HEIGHT SCREEN SS34 IN ALUM. BASESHOE AND ALUM. U TRACK HEAD SYSTEM
3000mmTO T/O F.F.
120
+2750ACT
BULLNOSE SOLID 140mm CMU BLOCK
1000
BRUSHED STAINLESS STEEL CLADDINGADHERED TO ALUM GLAZING BASE SHOE
ALUM GLAZING SHOE, ANCHORED TOCONCRETE SLAB W/ SS WEDGE ANCHOR
P1B
P2C
STEEL ANGLE BRACING SECURELYANCHORED TO STRUCTURE - SEAL ALL GWB
PENETRATIONS WITH 1 HR FIRE-STOP SEALANT
STRUCT. STEEL SUPPORT C/W WITH HANGERS/BRACING AS REQUIRED AND W/ SPRAY
APPLIED FIRE PROOFING (1HR FFR)
P5E BULKHEAD: 16mm GWB ON 64mmSTEEL STUDS @ 400mm O.C.
- ANGLED AS SHOWN
GROUT BLOCKS SOLID M15 REINFORCING BAR 600mm O.C.
s8
29.04 m
LEARNINGCOMMONS
S3.1F
+2750ACT
CONT ANOD. ALUMINUM GLAZINGCHANNEL SECURELY ANCHORED
STRUCT. STEEL SUPPORT C/W WITHHANGERS/ BRACING AS REQUIRED ANDW/ SPRAY APPLIED FIRE PROOFING (1HRFFR)
FACTORY INSTALLED BLACKPAINTED WOOD DOWEL
WOOD SLAT WALL PANEL
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/WBLACK ACOUSTIC BATTINSULATION INFILL
BLACK SELF-TAPPING SCREWS
FACTORY ATTACHED 32x13mmBLACK WOOD BACKER
6735
5151
164
2030mmTO T/O F.F.
2250mmTO T/O F.F.
40
12 64
2750mmTO T/O F.F.
ONE-HOUR FIRE RATED P2DPARTITION - 16mm TYPE X GWB ON92mm STEEL STUDS @ 400mm O.C.
WINDOW SPRINKLERS AT 1HR FIRESEPARATION (REF MECH. DWGS)
FULL HEIGHT SCREEN SS29 IN ALUM BASESHOE AND ALUM U TRACK HEAD SYSTEM
PREFINISHED ALUM EDGE TRIM, TYP.
120
STEEL ANGLE BRACING SECURELYANCHORED TO STRUCTURE - SEALALL GWB PENETRATIONS WITH 1 HRFIRE-STOP SEALANT
GWB CEILING - TYPE CL-4
P2C
REFER TO 01/A654 FOR SKYLIGHTCURB DETAIL ABOVE
407
s8
FACTORY INSTALLED BLACK-PAINTED WOOD DOWEL
BLACK-PAINTED 92mm STEEL STUDSMOUNTED TO SIDE WALLS TOSUPPORT CURVED BACKERS
35x64mm HARDWOOD SLATS
38x38mm BLACK WOOD BACKERFACTORY-ASSEMBLED TO SUPPORT600mm RADIUS SLATS AS SHOWN
600 R
87.50
35 67
92mm BLACK ACOUSTIC INSULATION
BLACK HEAVY DUTY 24mmMAIN T-BAR @ 610mm O.C(BY INSTALLER)FACTORY ATTACHED 32X13mmBLACK WOOD BACKER
BLACK SELF-TAPPING SCREWS(BY INSTALLER)
12 GA WIRE PAINTED BLACK(BY INSTALLER)
92mm BLACK ACOUSTICINSULATION
64
70
59
P5E 64mm STEEL STUDBULKHEAD
450mm TO U/S STRUCTURALFLOOR SLAB4
50
s5.1
1 HR FIRE STOP SYSTEM
DEFLECTION TRACK, TYP.
CONT ANOD. ALUMINUM GLAZING CHANNELSECURELY ANCHORED (SEE WINDOW SCHEDULE)
ONE-HOUR FIRE RATED P2D PARTITION- 16mm TYPE X GWB ON 92mm STEEL
STUDS @ 400mm O.C.
BULKHEAD P5E: 16mm GWB ON 64mmSTEEL STUDS @ 400mm O.C.
51 51
120
2750mmTO T/O F.F.
WINDOW SPRINKLERS AT 1HRFIRE SEPARATION
(REF MECH. DWGS)
FULL HEIGHT ALL-GLASS SCREEN SS32 INALUM. BASE SHOE AND ALUM. U TRACK
HEAD SYSTEM
PREFINISHED ALUM EDGE TRIM, TYP.
3000mmTO T/O F.F.
+3050ACT
P2CP5C
STRUCTURAL STEEL ROOF DECK
CORRIDORS3.1A
50
250
120
STEEL ANGLE BRACING SECURELY ANCHOREDTO STRUCTURE - SEAL ALL GWB PENETRATIONS
WITH 1 HR FIRE-STOP SEALANT
STRUCT. STEEL SUPPORT C/W WITH HANGERS/BRACING AS REQUIRED AND W/ SPRAY APPLIED
FIRE PROOFING (1HR FFR)
REFER TO 02/A654 FOR SKYLIGHT CURB DETAIL
LEVEL 2 SOUTH 88.20 m
FACTORY INSTALLED BLACK PAINTED WOODDOWEL
35X64mm HW SLAT
BLACK-PAINTED 102mm STEEL STUDS @610mm O.C C/W BLACK ACOUSTIC BATTINSULATION INFILL
BLACK SELF-TAPPING SCREWS
FACTORY ATTACHED 32x13mm BLACK WOODBACKER65
35
164 12 64
WOOD SLAT WALL PANEL
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/WBLACK ACOUSTIC BATTINSULATION INFILL
PRE-FORMED BLACK ANODIZED ALUMINUMCOVER PLATE
PRE-FORMED BLACK ANODIZED ALUMINUMCOVER PLATE
BRUSHED STAINLESS STEEL CLADDINGADHERED TO ALUM GLAZING BASE SHOEALUM GLAZING SHOE, ANCHORED TOCONCRETE SLAB W/ SS WEDGE ANCHOR
ALUM GLAZING SHOE, SECURED TO STEELABOVEGLAZED INTERIOR SCREEN SS21
100
LEVEL 3 SOUTH 92.00 m
s5.1
BRUSHED STAINLESS STEEL CLADDINGADHERED TO ALUM GLAZING BASE SHOE
ALUM GLAZING SHOE, ANCHORED TOCONCRETE CURB W/ SS WEDGE ANCHOR
5150 100
1070
51x19mm PAINTED FLAT BAR STEEL GUARD RAILWITH POSTS @ 1200 O.C.
ALLOW FOR POCKET FOR GUARD RAIL BASEPLATE. FILL POCKET WITH CONCRETE.
P5C FURRING - 16mm GWB ON 92mm STEELSTUDS @ 400mm O.C.
445
10mm J TRIM REVEAL
CONT ANOD. ALUMINUM GLAZINGCHANNEL SECURELY ANCHORED TO
STEEL ABOVE
STEEL SUPPORT C/W WITHHANGERS/ BRACING AS
REQUIRED
35x64mm HW SLAT PANEL
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/W
BLACK ACOUSTIC BATTINSULATION INFILL
2xL-METAL ANGLE BRACKETCONNECTION Z-GRITS PAINTED
BLACK TO MATCH WOODSCREEN ANGLE
51
2280mmTO T/O F.F.
2500mmTO T/O F.F.
40
ONE-HOUR FIRE RATED P2DPARTITION - 16mm TYPE X GWB ON92mm STEEL STUDS @ 400mm O.C.
WINDOW SPRINKLERS AT1HR FIRE SEPARATION
(REF MECH. DWGS)
FULL HEIGHT SCREEN NS42 IN ALUMBASE SHOE AND ALUM U TRACK HEAD
SYSTEM
STEEL ANGLE BRACING SECURELYANCHORED TO STRUCTURE - SEAL
ALL GWB PENETRATIONS WITH 1 HRFIRE-STOP SEALANT
WOOD SLAT WALL PANEL
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/W BLACK
ACOUSTIC BATT INSULATIONINFILL
PRE-FORMED BLACKANODIZED ALUMINUM COVER
PLATE
BRUSHED STAINLESS STEEL CLADDINGADHERED TO ALUM GLAZING BASE SHOE
ALUM GLAZING SHOE, ANCHORED TOCONCRETE SLAB W/ SS WEDGE ANCHOR
51150
51x19mm PAINTED FLAT BAR STEELGUARD RAIL WITH POSTS AT 1200mm O.C.
ALLOW FOR POCKET FOR POST BASEPLATE. FILL POCKET WITH CONCRETE.
P2D PARTITION - 16mm GWB ON92mm STEEL STUDS @ 400mm O.C.
97.45
94.95
1070
220
97.23
92mm BLACK ACOUSTIC INSULATION
BLACK HEAVY DUTY 24mm MAIN T-BAR @ 610mm O.C (BY INSTALLER)
FACTORY ATTACHED 32X13mmBLACK WOOD BACKER
BLACK SELF-TAPPING SCREWS(BY INSTALLER)
12 GA WIRE PAINTED BLACK(BY INSTALLER)
FACTORY INSTALLED BLACKPAINTED WOOD DOWEL35x64mm HW SLAT PANEL
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/WBLACK ACOUSTIC BATTINSULATION INFILL
BLACK SELF-TAPPING SCREWS
FACTORY ATTACHED 32x13mmBLACK WOOD BACKER
3000
720
22MM METAL FURRING CHANNELS
22mm METAL FURRING CHANNEL
2xL-METAL ANGLE BRACKETCONNECTION Z-GRITS PAINTED
BLACK TO MATCH WOOD SCREENANGLE
sC
ONE-HOUR FIRE RATED HOLLOW METALFRAME SECURELY ANCHORED (SCREEN
TYPE SS38 -SEE WINDOW SCHEDULE)
ONE-HOUR FIRE RATED P2D PARTITIONABOVE WINDOW- 16mm TYPE X GWB
ON 92mm STEEL STUDS @ 400mm O.C.
STEEL ANGLE BRACING SECURELYANCHORED TO STRUCTURE - SEAL ALL GWB
PENETRATIONS WITH 1 HR FIRE-STOP SEALANT
STRUCT. STEEL SUPPORT C/W WITH HANGERS/BRACING AS REQUIRED AND W/ SPRAY
APPLIED FIRE PROOFING (1HR FFR)
GWB CEILING - TYPE CL-4
+3400GWB
P1B
ONE-HOUR FIRE RATED WIRED GLASS
95.40
800
94.60
P5D FURRING: 16mm GWB ON92mm STEEL STUDS
SLOPED CAP UNDER SCREENOPENING IN FURRING: 16mm GWB
ON 92mm STEEL STUDS AT400mm O.C.
SLOPE
25
VARIES: REFER TO PLAN
2600mmABOVEFINISHEDFLOOR
35x64mm HW SLAT PANEL
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/WBLACK ACOUSTIC BATTINSULATION INFILL
P2D PARTITION - 16mm GWB ON92mm STEEL STUDS @ 400mm O.C.
STEEL ANGLE BRACING ASREQUIRED FOR SUPPORTSECURELY ANCHORED TOSTRUCTURE
BLACK-PAINTED 102mm STEELSTUDS @ 610mm O.C C/W BLACKACOUSTIC BATT INSULATIONINFILL
PRE-FORMED BLACKANODIZED ALUMINUM COVERPLATE
BRUSHED STAINLESS STEELCLADDING ADHERED TO ALUMGLAZING BASE SHOE
ALUM GLAZING SHOE, ANCHOREDTO CONCRETE SLAB W/ SSWEDGE ANCHOR
P2D PARTITION - 16mm GWB ON92mm STEEL STUDS @ 400mm O.C.
2800mmTO T/O F.F.
2750mmTO T/O F.F.
240
93.50
93.45
90.70
+2750GWB
RADIUS AND GRIND TOP OFGLASS SMOOTH
12mm TEMPERED GLASS
1070
100
2xL-METAL ANGLE BRACKETCONNECTION Z-GRITS PAINTEDBLACK TO MATCH WOOD SCREENANGLE
22mm METAL FURRING CHANNEL
2xL-METAL ANGLE BRACKETCONNECTION Z-GRITSPAINTED BLACK TO MATCHWOOD SCREEN ANGLE
22mm METAL FURRINGCHANNEL
4
35x64mm HW SLATPANEL
BLACK-PAINTED 102mmSTEEL STUDS @ 610mm
O.C C/W BLACKACOUSTIC BATT
INSULATION INFILL
P2D PARTITION - 16mmGWB ON 92mm STEELSTUDS @ 400mm O.C.
P5C
460
DRYWALL TRIM PAINTED 16mm REVEAL
ALUMINUM GLAZING SHOE FOR 6mmGLAZING C/W STAINLESS STEEL COVERSECURED TO WOOD SCREEN STUDSTRUCTURE
SMOKE BAFFLE - 6mm TEMPERED GLASS
89.45
88.99
MATCH BASE OF WOOD SCREENTO BASE OF GLASS BAFFLE -460mm BELOW CEILING LEVEL
P5C BULKHEAD SECURED TO U/S OFSTRUCTURALCONCRETE DECK ABOVE
+2750GWB
90
22mm METAL FURRINGCHANNEL
2xL-METAL ANGLE BRACKETCONNECTION Z-GRITS
PAINTED BLACK TO MATCHWOOD SCREEN ANGLE
LEVEL 3 SOUTH92.00 m
BRUSHED STAINLESS STEEL CLADDINGADHERED TO ALUM GLAZING BASE SHOE
ALUM GLAZING SHOE, ANCHORED TOCONCRETE SLAB W/ SS WEDGE ANCHOR
RADIUS AND GRIND TOP OFGLASS SMOOTH
12mm TEMPERED GLASS
1070
100
LEVEL 3 NORTH WING90.70 m
2x10mm HEAT STRENGTHENED LAMINATEDGLASS (OBC SB-13) GUARD W/ CLEAR FILM (TYP.)C/W POLISHED & BEVELED EDGES EXTENDS TO1500 ABOVE A.F.F..
50mm STAINLESS STEELGLASS FASTENERS C/W GASKETS& 40 mm SPACERS BEHIND SECURED INTOSTEEL ANGLE
FLOOR FINISH (SEE ALSO ROOM SCHEDULE)
LIGHT FIXTUREW/ GWB TRIM
FROSTED FILM BEHIND GLASS
12mm GWB CEILING (REFER TO REFLECTEDCEILING PLANS)
50mm STAINLESS STEELGLASS FASTENERS C/W GASKETS& 40mm SPACERS BEHIND SECURED INTO STEELANGLE BEHIND
40
EXTEND GLASS MIN. 460 BELOW U/S OF CEILING IN MULTI-USECOMMUNITY SPACE N2.15A, END GLASS FLUSH WITH CEILINGIN GYM 1A N2.3A AND GYM 1B N2.4A
LEVEL 2 SOUTH 88.20 m
sC
P1B
P1B
S1
RUBBER COVING
FULLY GROUTED WALL COREM 15 REINFORCING BAR 600
O.C.
REFER TO MILLWORKDRAWINGS (8a/A919) FOR
DESK CONSTRUCTIONDETAILS
140 CMU WALL
140 CMU WALL
HALF-HEIGHT SOLID CAPBLOCK WITH BULLNOSE
EXPOSED CORNERS
13
10
90
ZAS PROJECT NO.:
DATE:
SHEET NUMBER:
SHEET TITLE
SCALE:
DRAWN BY:
REVISIONS
No. Date Description
PROJECT :
CLIENT : - CITY OF TORONTO PARKS FORESTRY & RECREATION
- CITY OF TORONTO CHILDREN'S SERVICES
- TORONTO DISTRICT SCHOOL BOARD
- TORONTO CATHOLIC DISTRICT SCHOOL BOARD
ARCHITECT
KEY PLAN
SEAL
TRUE NORTH CONSTRUCTION NORTH
ISSUED:
No. Date Description
REVIEWED BY:
CLIENTADDRESS :
ARCHITECTUREINTERIORSTRANSPORTATIONPLANNING
GROUP OF COMPANIES
517 Wellington St W. , Suite 404Toronto, OntarioCanada M5V 1G1
T 416 979 9834F 416 979 3763
THIS DRAWING IS NOT TO BE SCALED.
REFER TO APPROPRIATE SURVEY, STRUCTURAL, MECHANICAL,ELECTRICAL, LANDSCAPE, ETC. CONSULTANT DRAWINGS BEFOREPROCEEDING WITH THE WORK.
CONSTRUCTION MUST CONFORM TO ALL APPLICABLE CODES ANDREQUIREMENTS OF AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR WORKING FROM DRAWINGS NOT SPECIFICALLYMARKED "FOR CONSTRUCTION" MUST ASSUME FULLRESPONSIBILITY AND BEAR COSTS FOR ANY CORRECTIONS ORDAMAGES RESULTING FROM HIS WORK.
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS PROVIDED BYAND IS THE PROPERTY OF THE ARCHITECT.
THE CONTRACTOR SHALL VERIFY AND ACCEPT RESPONSIBILITYFOR ALL DIMENSIONS AND CONDITIONS ON SITE AND SHALLNOTIFY THE APPROPRIATE CONSULTANT OF ANY VARIATIONS FROMTHE SUPPLIED INFORMATION.
ZAS ARCHITECTS + INTERIORS 2016 C
ProjectName:
TORONTO CITY HALL4TH FLOOR W, 100 QUEEN ST. W,TORONTO, ONTARIO M5H 2H2
CHILDREN'S SERVICESMETRO HALL,10TH FLOOR, 55 JOHN ST.TORONTO, ONTARIO M5V 3C6
TORONTO DISTRICT SCHOOL BOARD5050 YONGE STREETTORONTO, ONTARIO M2N 5N8
TORONTO CATHOLIC DISTRICTSCHOOL BOARD80 SHEPPARD AVENUE EAST,NORTH YORK, ONTARIO M2N 6E8
1 : 5
2/20/2017 10:26:29 PM
A809R1
14-001
BLOCK 31DEVELOPMENT
Author Checker
2017-01-13
CEILING DETAILS
17 FEB 2017
BLOCK 31 DEVELOPMENT
1 2016/12/01 ISSUED FOR 90% CD2 2016/12/16 ISSUED FOR BUILDING
PERMIT3 2017/01/31 ISSUED FOR TENDER4 2017/02/17 RE-ISSUED FOR SPA5 2017/02/17 ADDENDUM 2
1 : 56 ART ROOM SPRINKLER BULKHEAD AND SILL DETAILART ROOM SPRINKLER BULKHEAD AND SILL DETAIL
1 : 51 SCREEN HEAD SPRINKLERS WITH WOOD SLATSSCREEN HEAD SPRINKLERS WITH WOOD SLATS
1 : 53 WOOD SLAT TRANSITION - VERTICAL TO HORIZONTALWOOD SLAT TRANSITION - VERTICAL TO HORIZONTAL
1 : 54 LEARNING COMMONS SCREEN HEAD WITH SPRINKLERSLEARNING COMMONS SCREEN HEAD WITH SPRINKLERS
1 : 52 GLAZED SCREEN WITH WOOD SLATSGLAZED SCREEN WITH WOOD SLATS
1 : 55 LEARNING COMMON SCREEN BASE WITH GUARD RAILLEARNING COMMON SCREEN BASE WITH GUARD RAIL
1 : 510 ATRIUM WOOD SLAT WITH SPRINKLER HEADATRIUM WOOD SLAT WITH SPRINKLER HEAD
1 : 57 ART ROOM CLERESTORY SCREENART ROOM CLERESTORY SCREEN
1 : 511 ATRIUM WOOD SLAT WITH GLASS GUARDATRIUM WOOD SLAT WITH GLASS GUARD
1 : 513 ATRIUM WOOD SLAT BASEATRIUM WOOD SLAT BASE
1 : 512 TYPICAL GLASS GUARDRAILTYPICAL GLASS GUARDRAIL
1 : 58 COMMUNITY CENTRE GLASS GUARD RAIL ATTACHMENTCOMMUNITY CENTRE GLASS GUARD RAIL ATTACHMENT
1 : 59 LEARNING COMMON CMU BALCONY WALLLEARNING COMMON CMU BALCONY WALL
6570
4320
2250
6630
4380
2250
1200
LV
6645
4395
2250
6705
4455
2250
1200
6795
4545
2250
4570
2250
4580
2250
6830
1200
LV
6860
4610
2250
6880
4630
2250
1200
LV
6900
4650
2250
6920
4670
2250
1200
LV
6925
4675
2250
6945
4695
2250
1200
LV
6985
4735
2250
7005
4755
2250
1200
LV
7030
4780
2250
7050
4800
2250
1200
LV
5100
1300
1400
2400
50251390 1510 1510 615
5100
1300
1400
2400
315
985
3800
59601460150015001500
315
4785
4285
450
1435
24002
745
15451505150515051505
345
2400
7555
10380
1485148514851485148514851485
3165
765
2400
2400
640
10010
02001
00145
ALL
MU
LLIO
NS
TO E
XTEN
D T
O U
/S O
F D
ECK
324951535 1500 1010 1010 1500 1500 1500 1010 1010 1500 1500 1500 1010 1010 1500 1500 1500 1010 1010 1500 1500 1500 2015 1385
N2.15.6 N2.15.7 N2.15.8 N2.15.9 N2.15.10N2.15.8 N2.15.7 N2.15.8 N2.15.9 N2.15.10
EXTENTS OFSOFFIT ABOVE,COORDINATEWITH A400 -A405
EXTENTS OFCURTAINWALL
GLAZING
3595
2400
1195
1400
3370
2400
970
6165
1220 825 2015 1265 385 455
N2.15.1 N2.15.1
1350
1645
3190
6185
2400
2200
1585
213458201500150015008201500150015001500150015001500150015001705
6185
TG
TG TG
23153251990
3750
1350
2400N2.1.3 N2.1.3
TG
2400
2200
1800
200
200
24035
1535150041510851500150015001500150015001500150015001500150015001500
EXTENTS OFSOFFIT ABOVE,COORDINATEWITH A400 -A405
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
SP
TG
SP
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
TG
EXTENTS OFCURTAINWALL
GLAZING
TG TG TG TG TG TG TG TGTGTGTGTGTGTGTG
ALL
MU
LLIO
NS
TO E
XTEN
D T
O U
/S O
F D
ECK
NCW35B135mm CURTAINWALL BACKBOX
NCW35A210mm CURTAINWALL BACKBOX WITH STEEL REINFORCEMENT AS REQUIRED
SP
SP
SP
8030
1605 1605 1605 1605 1605
TG TG TG TG TG
1700
1450
2940980 980 980
ALL
MU
LLIO
NS
TO E
XTEN
D T
O U
/S O
F D
ECK
1940
1760
1740
2260
3630
EXTENTS OF SOFFITABOVE, COORDINATEWITH A400 - A405
1050 1050 1050
3155
1450
1080
1845
108015001500150015001500150015001500150015001500150015001485
TG TG TG TG TGTGTGTGTGTGTGTGTGTG
LV LV LV LV LV LV LV LV LV LV LV
LV LV LV LVLV
TG
GLASS GUARD, REFER TOA340, 4 FOR SIM. DETAIL
1215
235
1080
1845
4370
4370
22065
SLIDING ROOMPARTITION BEHIND,PROVIDE ADDITIONALMULLIONREINFORCEMENT ASREQUIRED
3410
5010
11351070950930930
TG TG TG
N3.13B
TG TG
TG TG TGTG TG
1160
2250
140
22502390
1660