Zagreb, 2.12.2009. EIHP Željka Hrs Borković, Margareta Zidar, Marina Malinovec Puček
NATIONAL AWARD NATIONAL AWARD
CEREMONYCEREMONY
PromotionPromotion of of energyenergy efficiencyefficiency and use of and use of
renewablerenewable energyenergy sourcessources in in
nonnon--residentialresidential buildingsbuildings
GreenBuilding Partner University of Split
Building type university library
Location (city, country) Split/Croatia
Year/period of construction 2008
Year/period of refurbishment -
Building area 14.611 m² (gross floor area)
Points quantitative criteria 60
NB_HR_01
University library in Split
2
The heat energy demand for heating is 46 % lower than required by the
Croatian building code.Energy savings
and basis of
calculation (eg. building
code, final energy consumption according to
bills, etc.)
Heat energy is produced by heat pumps integrated in air-condition system
using exhaust air and air from underground levels. Maximum heating and
ventilation capacity is 400 kW. Average COP level is 2.8. Heat energy for
cooling is supplied by adiabatic process, air-condition integrated mechanical
cooling and compact cooling device. Total cooling capacity is 1068 kW.
Average COP level is 4.1. Through integrated design concept high percentage
of energy recuperation is achieved – 80 to 92%.
Building services
- HVACeg. short description, key figures
External envelope – double skin ventilated facade 80 cm, external pane with
reflective coating + internal pane double insulating glass with lowe coating – 1,3
W/m²K; Roof – 0.27 W/m²K; Basement – 0.45 W/m²K; Optimisation of the
building envelope (insulation, airtightness, windows, thermal bridges).
Building envelopeeg. short description, U-values
28,5 kWh/m²a heat energy demand for heating
or 418340 kWh/a primary energy for heating
19,5 kWh/m²a heat energy demand for cooling
or 195475 kWh/a primary energy for cooling
Energy indices (per
m² or m³)
NB_HR_01
University library in Split
Renewable energyeg. short description, key figures
High energy efficient public building – role model for
further public building projects in mediterranean climateReplication and
innovation (description)
CSMS coordinates performance of air-condition system, heat
energy production for heating and cooling and individual space
regulation. DMS is used for performance control, system
surveillance and cost analysis.
Energy management (description)
External shades in ventilated space are automated taking into
account insolation and internal climate parameters. Additional
internal screens are manualy adjusted for optimal light and
insolation conditions.
Other measures (description)
NB_HR_01
University library in Split
3
GreenBuilding Partner City of Labin
Building type Kature - multiresidential buildings with
business units
Location (city, country) Labin/Croatia
Year/period of construction development of design documentation
Year/period of refurbishment -
Building area 1.625 x 3 m² (gross floor area)
Points quantitative criteria 49,5
NB_HR_02
MRB Kature
The heat energy demand for heating is 64,7 % lower than required by the
Croatian building code.Energy savings
and basis of
calculation (eg. building
code, final energy consumption according to
bills, etc.)
Air heat pumps (40 kW) will be used for centralized heating, cooling and DHW
energy production. Floor and wall panel heating and cooling. Ventilation for
kitchen and bathroom spaces.
Building services
- HVACeg. short description, key figures
External wall – 0,25 W/m²K; internal wall to unheated area – 0,3 - 0,25 W/m²K;
ceiling toward attick– 0.13 W/m²K; basement ceiling – 0.15 W/m²K; Windows –
0,9 W/m²K. Optimisation of the building envelope (insulation, airtightness,
windows, heat bridges).
Building envelopeeg. short description, U-values
24,82 kWh/m²a heat energy demand for heating
or 35741 kWh/a primary energy for heatingEnergy indices (per
m² or m³)
NB_HR_02
MRB Kature
4
Renewable energyeg. short description, key figures
High energy efficient building – role model for further building
projects in mediterranean climateReplication and
innovation (description)
Each residential and business unit will be able to optimize internal
temperature conditions and manage own energy expenses.Energy management (description)
Heat exchanger for every unit for energy supply and preparation.Other measures (description)
NB_HR_02
MRB Kature
GreenBuilding Partner PHOENIX PARK d.o.o.
Building type supra regional shopping centre, mega mixed use
Location (city, country) Sesvete/Croatia
Year/period of construction in preparation of design documentation
Year/period of refurbishment -
Building area 70.948 m² (gross floor area)
Points quantitative criteria 51
NB_HR_04
Phoenix Plaza
5
The heat energy demand for heating is 71 % lower than required by national
code.Energy savings
and basis of
calculation (eg. building
code, final energy consumption according to
bills, etc.)
Large shopping, entertainment and communication areas are heated by
centralized air conditioning system consisting of ventilation chambers with heat
exchangers (summer - adiabatic cooling 60%, 1570 kW + external cooling
devices 40%, 1500 kW) and heat recovery (winter 75-85%, 4300 kW, COP 2,8
+ additional heating 1330 kW).
Heating system of retail area (60%) consists of heat pumps (air-water)
recovering waste heat of cooling system and additional heat (if needed) is
supplied by gas boiler (600 kW). Cooling energy is produced in external cooling
system. Fan coils are used for heat energy supply (heating and cooling).
Building services
- HVACeg. short description, key figures
External concrete envelope 15 cm with 18 cm of thermal insulation – 0,30
W/m²K; Optimisation of the building envelope (insulation, airtightness,
windows, thermal bridges).
Building envelopeeg. short description, U-values
8,98 kWh/m³a heat energy demand for heating
or 2.991.955,14 kWh/a primary energy for heating
Energy indices (per
m² or m³)
NB_HR_04
Phoenix Plaza
Renewable energyeg. short description, key figures
Unique example of intergrated design and energy concept.Replication and
innovation (description)
All energy system are integrated with the digital regulation
which combines them into one energy efficient system. This is
achieved with free programmable control units, which allow
every function of the building being easily accommodated.
Digital regulation gets the final touch with the BMS, which
combines controlling, alarming, reporting and many other
complex components of the integrated system, with simple and
user friendly operating, from one or more places, also provides
excellent possibilities for data analyzing and optimizing and
rational use of enegy.
Energy management (description)
All relevant energy processes are supervised and controlled by
CMCS.Other measures (description)
NB_HR_04
Phoenix Plaza
6
GreenBuilding Partner HEP (Croatian utility company) Distribution
system operator - Elektra Koprivnica
Building type office building
Location (city, country) Koprivnica/Croatia
Year/period of construction 1968
Year/period of refurbishment 2005
Building area 1.542 m² (gross floor area)
Points quantitative criteria 54,5
EB_HR_03
Office building HEP DP Elektra Koprivnica
70 kWh/m²a heat energy demand for heating
92.048,88 kWh/a primary energy for heating
The heat energy demand for heating is 70,8 % lower than before the
refurbishment.
Energy savings
and basis of
calculation (eg. building
code, final energy consumption according to
bills, etc.)
For heat energy production existing centralised system is used consisting of 2
boilers of 580 kW (existing) using natural gas. Heating and cooling distribution
system is reconstructed to 4 pipe fan coil system. Air conditioning system is
added using heat from centralised system. DHW is produced in centralised
system. Kitchen area is mechanically ventilated.
Building services
- HVACeg. short description, key figures
External wall – 0,30 (0,34) W/m²K; ceiling toward attick– 0.25 W/m²K; Windows
– 1,4 W/m²K. Optimisation of the building envelope (insulation, airtightness,
windows, heat bridges).
Building envelopeeg. short description, U-values
240 kWh/m²a heat energy demand for heating
or 315.596,16 kWh/a primary energy for heatingEnergy indices (per
m² or m³)
EB_HR_03
Office building HEP DP Elektra Koprivnica
7
Renewable energyeg. short description, key figures
Refurbishment model of existing office buildings
Use of energy efficient energy 4 pipe distribution systemReplication and
innovation (description)
Energy management (description)
On the window frame micro switches for local control of
heating/cooling system are installed contributing energy
consumption reduction.
Other measures (description)
EB_HR_03
Office building HEP DP Elektra Koprivnica
GreenBuilding Partner VALAMAR TURISTIČČČČKI PROJEKT d.o.o.Building type auto camp sanitary block
Location (city, country) Krk/Croatia
Year/period of construction
Year/period of refurbishment 2006
Building area -
Points quantitative criteria 45
RB_HR_05
Autocamp Politin
8
The electricity consumption of heat pumps is 80,6 % lower than by use of
electricity boilers.Energy savings
and basis of
calculation (eg. building
code, final energy consumption according to
bills, etc.)
The main system uses condensing potential of the heat pump of 115 kW for
SHW preparation. Waste water from the sanitary block is used for the
evaporation. The waste sanitary water has sufficient thermal potential and in
energy balance gives about 80-90% of energy recovery.
Building services
- HVACeg. short description, key figures
Building envelopeeg. short description, U-values
24.699 kWh/a electricity demand for SHW
Total primary energy consumption is 103.994 kWh/a. Yearly CO2 emission
savings are 165,35 t.
Energy indices (per
m² or m³)
RB_HR_05
Autocamp Politin
GreenBuilding Endorser HEP Esco d.o.o.
Buildings assisted Primary education school Duga Resa,
High school Duga Resa
Grammar school in Ogulin
Location (city, country) Karlovaččččka County/CroatiaYear/period of construction
Year/period of refurbishment 2005 - 2008
E_HR_05
HEP ESCO d.o.o.
9
THANK YOU FOR YOUR ATTENTIONTHANK YOU FOR YOUR ATTENTION !!
Margareta Zidar
Željka Hrs Borković
www.eu-greenbuilding.org
www.greenbuilding-hr.com
Marina Malinovec Puček