OUTSULATION® MD SYSTEM® An Exterior Wall Insulation and Finish System with
Engineered Moisture Drainage That Incorporates
Continuous Insulation and An Air-Water-Resistive Barrier
Outsulation MD System
Installation Details
DS167
NOTE
DETAIL
TABLE OF CONTENTS
DETAIL
Outsulation® MD System®
OUTSULATION MD SYSTEM OMD 0.0.01BUILDING FACADE OMD 0.0.02DRYVIT VENT ASSEMBLY™ OMD 0.0.03INSULATION BOARD OMD 0.0.04INSULATION BOARD LAYOUT OMD 0.0.05AWRB APPLICATION OMD 0.0.06OPENING PREPARATION- OMD 0.0.07 AQUAFLASH® SYSTEM OPTIONOPENING PREPARATION- OMD 0.0.08 BACKSTOP® NT™ OPTIONOPENING FLASHING INTEGRATION OMD 0.0.09INSIDE/OUTSIDE CORNERS OMD 0.0.10OUTSIDE CORNER - HIGH IMPACT OMD 0.0.11GRADE TERMINATION OMD 0.0.12TERMINATION AT CONCRETE CURB OMD 0.0.13TERMINATION AT OMD 0.0.14 ADA COMPLIANT SIDEWALKEPS PREPARATION AT OMD 0.0.15 WALL PENETRATIONSSTOREFRONT WINDOW SILL - JAMB OMD 0.0.16STOREFRONT WINDOW HEAD OMD 0.0.17TERMINATION AT OMD 0.0.18 WOOD FRAMED DECKTERMINATION AT OMD 0.0.19 WATERPROOF DECKPREPARATION AT PARAPET/ OMD 0.0.20 WALL INTERSECTIONTERMINATION ATPARAPET - OMD 0.0.21 CAP FLASHINGTERMINATION AT FLAT ROOF - OMD 0.0.22 SOLID SUBSTRATETERMINATION AT SLOPED ROOF OMD 0.0.23VERTICAL WALL/ SUSPENDED OMD 0.0.24 SOFFIT TRANSITIONTRANSITION AT SOFFIT/ OMD 0.0.25 FASCIA INTERSECTIONFASCIA/ UNINSULATED SOFFIT OMD 0.0.26 TRANSITIONTERMINATION AT OMD 0.0.27 UNINSULATED SOFFIT VENTHORIZONTAL JOINT AT SLIP TRACK OMD 0.0.28HORIZONTAL JOINT - OMD 0.0.29 SUBSTRATE CHANGEHORIZONTAL TERMINATION OMD 0.0.30 AT STONE VENEER
HORIZONTAL TERMINATION OMD 0.0.31 AT LAP SIDINGVERTICAL EXPANSION JOINT- OMD 0.0.32 EIFSTHROUGH-WALL EXPANSION JOINT OMD 0.0.33VERTICAL EXPANSION JOINT - OMD 0.0.34 FLUSH AND RECESSED OPTIONSVERTICAL EXPANSION JOINT - OMD 0.0.35 DOUBLE SEAL OPTIONVERTICAL TERMINATION OMD 0.0.36 AT STONE VENEERPENETRATIONS OMD 0.0.37SIGN ATTACHMENT OMD 0.0.38AESTHETIC REVEALS OMD 0.0.39RECESSED GRAPHICS OMD 0.0.40PROJECTING GRAPHICS OMD 0.0.41
DRYVIT MAKES NO REPRESENTATION REGARDINGCONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDINGCODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,OR PROJECT LOCATIONS. ALL COMPONENTS INDICATEDIN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BEREQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BEDESIGNED, DETAILED, AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER, ORCONTRACTOR TO BE IN CONFORMANCE WITH MODELCODES, ARCHITECTURAL, AND ENGINEERINGREQUIREMENTS PERTAINING TO SPECIFIC BUILDINGPROJECTS.
DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, ORWORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMSOR PRODUCTS.
THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THEOUTSULATION MD LIMITED COMMERCIAL WARRANTY.CONTACT DRYVIT FOR A FULL AND COMPLETE COPY OFTHE WARRANTY.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OMD 0.0.01
NORMAL IMPACT
HIGH IMPACT
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
FRAMING
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS
DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)
EPS INSULATION BOARD
APPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
FRAMING
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT VENT ASSEMBLY
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)
DRYVIT VENT TRACKDRYVIT BASE COAT
DRYVIT PANZER® REINFORCING MESH
Outsulation® MD System® Outsulation MD SystemNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ OR DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT GRID TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
12" (305 MM) DRYVIT CLOSURE BLOCKS
DRYVIT STARTER STRIP
DRYVIT VENT TRACK™ (SEE NOTE 1)
DRYVIT VENT ASSEMBLY™
DRYVIT TRACK™ (NO VENT HOLES)OVER 6" (152 MM) DRYVIT STARTERSTRIP™
FLOORLINE EXPANSION JOINT(WHEN SPECIFIED)
DRYVIT CLOSURE BLOCKS
OMD 0.0.02
Outsulation® MD System® Building FacadeNOTE:1. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
12" (305 MM)
3/4"(19 MM)
5 5/8" (143 MM)
8" (203 MM)
2"(51 MM)
6" (152 MM)
OMD 0.0.03
Outsulation® MD System® Dryvit Vent Assembly™
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
2"(51 MM) MIN.
2'-0"(610 MM)
1/4" X 1" (6.4 MM X 25 MM) TYP. VERTICALDRAINAGE GROOVE
1/4" X 1/2" (6.4 MM X 12.7 MM)VERTICAL DRAINAGE GROOVEAT BOARD EDGES
4'-0" (1.2 M)
12"(305 MM) TYP.
OMD 0.0.04
Outsulation® MD System® Insulation Board
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
BY OTHERS
OUTSULATION MD SYSTEM
APPROVED SUBSTRATE
VERTICAL DRAINAGE GROOVES
FRAMING
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™
2'-0"(610 MM)
0'-6"(152 MM)
EPS INSULATION BOARD
DRYVIT STARTER STRIP™
Insulation Board Layout
OMD 0.0.05
Outsulation® MD System®
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OMD 0.0.06
Outsulation® MD System® AWRB ApplicationNOTE:1. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER DETAILS, REFER TODRYVIT PUBLICATION DS840.
DRYVIT BACKSTOP® NT™ - TEXTURE
APPROVED SUBSTRATE
FRAMING
DRYVIT BACKSTOP NT - TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT AIR/WATER - RESISTIVEBARRIER COATING
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
STEP #1 STEP #2
STEP #4STEP #3
INSTALL DIAGONAL STRIP OF DRYVITAQUAFLASH MESH AT CORNERSAND EMBED IN AQUAFLASH LIQUID(SEE NOTES 1, 3 AND 4)
APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 1 AND 3)
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 6)
INSTALL DRYVIT AQUAFLASHSYSTEM AT HEADS(SEE NOTES 1 AND 4)
INSTALL DRYVIT AQUAFLASHSYSTEM AT JAMBS(SEE NOTES 1 AND 3)
OMD 0.0.07
Outsulation® MD System® AquaFlash® System Option NOTE:1. DRYVIT AQUAFLASH SHALL EXTEND TOINTERIOR FACE OF OPENING.
2. REFER TO HEAD, SILL AND JAMB DETAILSFOR FLASHING INTEGRATION.
3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS.
5. AQUAFLASH SYSTEM CONSISTS OFAQUAFLASH MESH AND AQUAFLASH LIQUID.
6. FOR ADDITIONAL AIR/WATER- RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.
Opening Preparation -
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
STEP #1 STEP #2
APPLY DRYVIT GRID TAPE™(SEE NOTES 1 AND 2)
TROWEL APPLY DRYVITBACKSTOP NT-TEXTURE(SEE NOTE 2)
6" (152 MM)MIN. (typ)
STEP #3
4" (102 MM) MIN.
APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 2, 3 AND 5)
STEP #4
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING APPLIED TOFACE OF WALL (SEE NOTE 6)
Opening Preparation -Backstop® NT™ Option
OMD 0.0.08
Outsulation® MD System®NOTE:1. APPLY DRYVIT GRID TAPE ON HEAD, JAMB, ANDCORNERS OF OPENINGS AND SHEATHING JOINTS.
2. TROWEL APPLY DRYVIT BACKSTOP NT-TEXTUREOVER THE DRYVIT GRID TAPE ALL THE WAY TOINSIDE FACE OF OPENING. ALL VOIDS MUST BEFILLED; MULTIPLE PASSES MAY BE REQUIRED. ASAN OPTION, DRYVIT GRID TAPE AND DRYVITBACKSTOP NT-TEXTURE MAY ALSO BE APPLIED ATTHE SILL PRIOR TO DRYVIT AQUAFLASH SYSTEMOR FLASHING TAPE APPLICATION.
3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM AT SILL, INCLUDING CORNER SPLICES.
4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTS ANDPROJECT DOCUMENTS.
5. REFER TO HEAD, SILL, AND JAMB DETAILS FORFLASHING INTEGRATION.
6. FOR ADDITIONAL AIR/WATER- RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
STEP #1
REFER TO OMD 0.0.07 & OMD 0.0.08 FORPREPARATION OF OPENING PRIOR TOFLASHING INSTALLATION
STEP #2 STEP #3
REFER TO OMD 0.0.16 FORJAMB DETAIL
INSTALL WINDOW UNIT ANDASSOCIATED FLASHINGS ANDAPPLY DRYVIT AQUAFLASHSYSTEM OVER VERTICAL LEG OFFLASHING (SEE NOTES 1 AND 2)
APPLY DRYVIT AQUAFLASH®SYSTEM SPLICES LAPPING OVERLIP OF SILL PAN FLASHING.(SEE NOTES 1 AND 2)
OMD 0.0.09
Outsulation® MD System® Opening Flashing IntegrationNOTE:1. REFER TO OMD 0.0.16 FORINTEGRATION OF FLASHING.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIER DETAILS, REFER TODRYVIT PUBLICATION DS840.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
8"(203 MM) MIN.
MUST OVERLAP 8" (203 MM) MIN.
SEE NOTE 3
MUST OVERLAP8" (203 MM) MIN.
(SEE NOTES 2, 3 AND 4)
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
8"(203 MM)
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
EPS INSULATION
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT BACKSTOP NT-TEXTUREOVER DRYVIT GRID TAPE
DRYVIT BASE COAT
OMD 0.0.10
Outsulation® MD System® Inside/Outside CornersNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DOUBLE WRAP OUTSIDE CORNERSWITH REINFORCING MESH OR USECORNER MESH™.
3. DO NOT LAP REINFORCING MESHWITHIN 8" (203 MM) OF A CORNER.
4. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
8"(203 MM) MIN.
DRYVIT FINISH
DRYVIT BACKSTOP® NT-TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT PANZER®REINFORCING MESH
DRYVIT STANDARD MESH ORSTANDARD PLUS REINFORCINGMESH OVERLAP MIN. 8" (203 MM)AT CORNER
EPS INSULATION
DRYVIT CORNER MESH™
8" (203 MM) MIN.
DRYVIT BASE COAT
DRYVIT BASE COAT
OMD 0.0.11
Outsulation® MD System® Outside Corner - High ImpactNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
8"(203 MM) MIN.
2'-0"(610 MM) MAX.(SEE NOTE 2)
OUTSULATION MDSYSTEM
BY OTHERS
DRYVIT AIR/ WATER-RESISTIVE BARRIER COATING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
APPROVED SUBSTRATE
EPS INSULATION
DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM(SEE NOTE 4)
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
SLOPE GRADE AWAYFROM FOUNDATION WALL
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BACKSTOP® NT™- TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT VENT ASSEMBLY™™
DRYVIT VENT TRACK™(SEE NOTE 3 & 5)
DRYVIT FINISH
DRYVIT BASE COAT
OMD 0.0.12
Outsulation® MD System® Grade TerminationNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 2'-0" (610 MM)DIMENSION IS EXCEEDED.
3. SLOT IN VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™, OR DRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE, MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM.
5. LIGHTLY SAND SURFACE OF TRACK TOMAXIMIZE ADHESION.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO
BACK OF EPS
APPROVED SUBSTRATE OUTSULATION MDSYSTEM
DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT
GRID TAPE™ (SEE NOTE 4)
DRYVIT VENT ASSEMBLY™
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT BASE COAT
DRYVIT STARTER STRIP™
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP NT-TEXTUREOVER GRID TAPE LAPPED OVERVERTICAL LEG OF DRYVIT VENTTRACK (SEE NOTES 2, 3, AND 4)
3/4" (19 MM) MIN.
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 5)
DRYVIT COMPATIBLE SEALANT,(SEE NOTE 5)
DRYVIT BASE COAT
DRYVIT VENT TRACK™ (SEE NOTES 2 AND 3)
Section A-A
VENT ASSEMBLY LOCATION
CLOSED CELL BACKER ROD,BY OTHERS
SEALANT MATERIAL, BY OTHERS(SEE NOTE 5)
A
A
OMD 0.0.13
Outsulation® MD System® Termination At Concrete CurbNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.
3. SLOT IN VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OR BACKSTOP NT-TEXTURE OVER GRID TAPE.
5. SEALANT SHALL TURN IN AT DRYVITVENT ASSEMBLY LOCATIONS (SEESECTION A-A) TO ALLOW FOR DRAINAGE.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OUTSULATION MD SYSTEM
BY OTHERS
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE APPLIED IN VERTICALNOTCHED TROWEL CONFIGURATION TOBACK OF EPS
APPROVED SUBSTRATE
DRYVIT BASE COAT
3/4" (19 MM) MIN. (SEE NOTE 4)
DRYVIT VENT ASSEMBLY™
DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 7)
DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
METAL PROTECTION SHEET,BY OTHERS
ADA COMPLIANT SIDEWALK SLOPEDAWAY FOR POSITIVE DRAINAGE
2" (51 MM) MAX.OVERLAP
FULLY ADHERED FOUNDATIONWATERPROOFING MEMBRANE,
BY OTHERSCOMPRESSIBLE FILLER BOARD,BY OTHERS
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™-TEXTURE OVER DRYVIT
GRID TAPE™ LAPPED OVER VERTICAL LEG OFDRYVIT VENT TRACK™ (SEE NOTES 5, 6 AND 7)
DRYVIT BASE COAT
DRYVIT VENT TRACK(SEE NOTES 5 AND 6)
OMD 0.0.14
Outsulation® MD System® Termination At ADA Compliant SidewalkNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. USE OF THIS DETAIL IS LIMITED TOSLAB-ON-GRADE APPLICATIONS.
3. INCORPORATE MEASURES TO PROTECTSTRUCTURE FROM MOISTURE INTRUSION,DAMPNESS, AND FROST HEAVE.
4. TO PREVENT DEBRIS ACCUMULATION IT ISRECOMMENDED TO TERMINATE SYSTEM2" (51MM) ABOVE SIDEWALK.
5. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.
6. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
7. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF AQUAFLASHSYSTEM OR BACKSTOP NT-TEXTURE OVERGRID TAPE.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
EPS INSULATION(SEE NOTE 2)
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DETAIL REINFORCING MESH9 1/2" (241 MM) X 12" (305 MM) (TYP.)(SEE NOTE 3)
OMD 0.0.15
Outsulation® MD System® EPS Preparation At Wall PenetrationsNOTE:1. LOCATE INSULATION BOARDS SUCH THATBOARD EDGES DO NOT ALIGN WITH CORNERS OFPENETRATION.
2. APPLY A PIECE OF 9 1/2" (241 MM) X 12" (305 MM)DETAIL REINFORCING MESH DIAGONALLY ATEACH CORNER.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
DRYVIT ADHESIVE INVERTICAL NOTCHED
TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
2 1/2"(64 MM) MIN.
1/2" (12.7 MM)
SILL PAN FLASHINGDETAIL
AIR SEAL PER MANUFACTURER'SREQUIREMENTS, BY OTHERS
DRYVIT COMPATIBLESEALANT, BY OTHERS
WRAP DRYVIT DETAILMESH® 2" (51 MM) MIN.
AT BACKSIDE OF EPS(SEE NOTE 5)
CONTINUOUS FLASHING, BYOTHERS, TURN UP 1/2" (12.7 MM) MIN.AT JAMBS - SEE DETAIL BELOW
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT COMPATIBLE SEALANT,BY OTHERS (SEE NOTE 4)
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2 & 3)
DRYVIT CLOSURE BLOCKDRYVIT BASE COAT
APPROVED SUBSTRATE
DRYVITAIR/WATER-RESISTIVE
BARRIER COATING
WRAP DRYVIT DETAIL MESH®2" (51 MM) MIN. AT BACKSIDE OF EPS
SLOPED SHIM ASREQUIRED, BY OTHERS
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGDRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TO RECEIVESEALANT
DRYVIT BASE COAT
EPS INSULATION BOARD
SEAL PER WINDOW MANUFACTURERREQUIREMENTS, BY OTHERS
OMD 0.0.16
Outsulation® MD System® Storefront Window Sill - JambNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM.
3. DRYVIT BACKSTOP® NT-TEXTURE OVER DRYVITGRID TAPE™ IS AN ALTERNATIVE OPTION AT JAMBAND HEAD CONDITION PER DETAIL OMD 0.0.08.
4. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
5. EDGE WRAPPING METHOD IS ACCEPTABLE ATSILL AND JAMB IN LIEU OF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLY EMBEDDED INDRYVIT BASE COAT AT EPS EDGE AND MUSTEXTEND ONTO SUBSTRATE 2" (51 MM) MIN.
3/4" (19 MM) MIN.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
OUTSULATION MDSYSTEM
BY OTHERS
DRYVIT AQUAFLASH SYSTEM(SEE NOTE 2)
DRYVIT AQUAFLASH SYSTEMOVER CONTINUOUS FLASHINGWITH END DAMS (SEE NOTE 2)
AIR SEAL PERMANUFACTURER'S
REQUIREMENTS,BY OTHERS
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
DRYVIT FINISH
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT AQUAFLASH® SYSTEM, ORDRYVIT BACKSTOP® NT-TEXTURE OVER
GRID TAPE, OVER VERTICAL LEG OFDRYVIT TRACK (SEE NOTES 2 & 4)
DRYVIT TRACK
DRYVIT STARTER STRIP™
3/4" (19 MM) MIN.
DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)
SEALANT AND FLASHING, BY OTHERS
DRYVIT BASE COAT
OMD 0.0.17
Outsulation® MD System® Storefront Window HeadNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
4. LIGHTLY SAND SURFACE OF DRYVITTRACK TO MAXIMIZE ADHESION.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
2" (51 MM) MIN.
FLASHING NO. 2, BY OTHERS
FLASHING NO. 3, BY OTHERS
1" (25 MM) MIN.
2-1/2" (64 MM) MIN.
DRYVIT COMPATIBLESEALANT, BY OTHERS
FLASHING NO. 1,BY OTHERS
DECK BOARD
END JOIST
DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TORECEIVE SEALANT
2" (51 MM) MIN.
DRYVIT COMPATIBLESEALANT WITH BOND
BREAKER, BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT FINISH
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
DRYVIT BASE COATEPS INSULATION BOARD
DRYVIT VENT ASSEMBLY™
DRYVIT AQUAFLASH® SYSTEM OVERCONTINUOUS FLASHING (NOTE 2)
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™(SEE NOTE 2)DRYVIT VENT TRACK™(SEE NOTES 4 & 5)
DRYVIT BASE COAT
OMD 0.0.18
Outsulation® MD System® Termination at Wood Framed DeckNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. DETAIL DOES NOT APPLY TOCANTILEVERED DECKS. CANTILEVEREDDECKS REQUIRE JOB SPECIFICFLASHING DETAILS.
4. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.
5. LIGHTLY SAND SURFACE OF DRYVITTRACK TO MAXIMIZE ADHESION.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS
APPROVED SUBSTRATE
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
FRAMING
SLOPE CONCRETE DECK SURFACEAWAY FROM VERTICAL WALL
2"(51 MM) MIN.
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
COMPATIBLE WATERPROOFDECK COATING, BY OTHERS
CANT STRIP, BY OTHERS
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 4)
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™(SEE NOTES 2 & 3)
DRYVIT BASE COAT
OMD 0.0.19
Outsulation® MD System® Termination at Waterproof DeckNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. SLOT IN VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.
3. LIGHTLY SAND SURFACE OF DRYVITTRACK TO MAXIMIZE ADHESION.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™, OR DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT GRID TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
APPROVED SUBSTRATE
FRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
FLASHING SLEEVE,BY OTHERS
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 1)
8"(203 MM)
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 1)
STEP #1 STEP #2
STEP #3
6"(152 MM)
6"(152 MM)
OMD 0.0.20
Outsulation® MD System® Preparation At Parapet/ Wall IntersectionNOTE:1. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
ROOFASSEMBLY
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
FRAMING,BY OTHERS
2 1/2" (64 MM) MIN.
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
APPROVED SUBSTRATE
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)(SEE NOTE 3)
DRYVIT COMPATIBLE SEALANT,BY OTHERS
DRYVIT FINISH
DRYVIT BASE COAT
OMD 0.0.21
Outsulation® MD System® Termination At Parapet - Cap FlashingNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OR DRYVITBACKSTOP NT-TEXTURE OVER GRID TAPE.
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™(SEE NOTE 2)
METAL CAP FLASHING,BY OTHERS
ROOF ASSEMBLY, BY OTHERS
DRYVIT CLOSURE BLOCK
3. EDGE WRAPPING METHOD ISACCEPTABLE IN LIEU OF BACK WRAPPING.DRYVIT REINFORCING MESH MUST BEFULLY EMBEDDED IN DRYVIT BASE COATAT INSULATION BOARD EDGE AND EXTENDONTO SUBSTRATE 2" (51 MM).
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT FINISH
DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT
DRYVIT BASE COAT
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
EPS INSULATION BOARD
DRYVIT VENT ASSEMBLY™
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT-TEXTUREOVER DRYVIT GRID TAPE™(SEE NOTE 2)DRYVIT VENT TRACK™(SEE NOTES 3 & 4)
ROOF FLASHING ANDCOUNTER FLASHING,
BY OTHERS
DRYVIT COMPATIBLE SEALANT, BYOTHERS (SEE NOTE 5)
8"(203 MM) MIN.
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
ROOF ASSEMBLY,BY OTHERS
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TO
RECEIVE SEALANT
DRYVIT BASE COAT
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER
ROD, BY OTHERS (SEE NOTE 5)
3/4" (19 MM) MIN.
OMD 0.0.22
Outsulation® MD System® Termination At Flat Roof - Solid SubstrateNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.
4. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.
5. DETAIL OMD 0.0.13 SECTION A-A FORSEALANT JOINT CONFIGURATION.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
2"(51 MM)
MIN.
3/4"(19 MM)
MIN.
110
100
ROOF DIVERTER(NOTE 2)
12"(305 MM)
6"(152 MM)
6"(152 MM)
FRAMINGAPPROVED SUBSTRATEDRYVIT AIR/WATER-RESISTIVE BARRIER COATINGDRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
ROOF STEP FLASHING, BY OTHERS
ROOFING SHINGLES
ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)
DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS)
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT
GUTTER SYSTEM SLOPEDAWAY FROM WALL
ROOF DIVERTER FLASHING, BY OTHERS(SEE NOTE 2)
DRYVIT FINISH
EPS INSULATION BOARDDRYVIT BASE COATDRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEMOVER FLASHING (SEE NOTE 8)
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™(SEE NOTES 5 & 6)
DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT GRID
TAPE™ (SEE NOTE 8)
OMD 0.0.23
Outsulation® MD System® Termination at Sloped RoofNOTE:1. EXTEND DIVERTER FLASHING (KICKOUT) AMINIMUM OF 1" (25 MM) BEYOND FACE OF THESYSTEM.
2. ROOF DIVERTER TO BE MADE FROMCORROSION RESISTANT MATERIAL MIN. 24 GAGEWITH WATER TIGHT SEAMS.
3. EXTEND ROOFING UNDERLAYMENT 5" (127 MM)UP VERTICAL WALL BEHIND METAL FLASHING.
4. FOR ADDITIONAL SLOPED ROOF DETAILS,REFER TO DRYVIT PUBLICATION DS106.
5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
6. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.
7. METAL FLASHINGS ARE 10" (254 MM) X 2" (51 MM)LONGER THAN THE EXPOSED PORTION OF THEROOFING SHINGLE AND ARE BENT IN HALFTO ALLOW FOR TWO 5" (127 MM) LEGS. ALTHOUGHNOT SHOWN, METAL FLASHINGS ARE STEPFLASHED (INTERWOVEN) WITH ROOFINGSHINGLES.
8. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
3/4" (19 MM) MIN.
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT
DRYVIT ADHESIVE
DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 4)
APPROVED SUBSTRATE
FRAMING
DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 2 & 3)
DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 5)
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,
BY OTHERS (SEE NOTE 2 & 3)
DRYVIT BASE COAT
DRYVIT CLOSURE BLOCK
APPROVED SUBSTRATE
EPS INSULATION BOARD(SEE NOTE 6)
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION TO BACK OF EPS
OMD 0.0.24
Outsulation® MD System® Vertical Wall/Suspended Soffit TransitionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™ ORSTANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATEDON CONTRACT DRAWINGS.
2. SEALANT JOINT IS REQUIRED FORSUSPENDED SOFFITS. OPTIONAL FORRIGIDLY FRAMED.
3. DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT.
4. DRYVIT AIR/WATER-RESISTIVE BARRIERIS REQUIRED OVER VERTICAL SUBSTRATES.APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESSREQUIRED AS PART OF A CONTINUOUS AIRBARRIER SYSTEM.
5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
6. GROOVED BOARD AND FLAT STOCK EPSARE ACCEPTABLE FOR USE IN HORIZONTALSOFFIT CONDITION.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
FRAMING
APPROVED SUBSTRATE
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT FINISH
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 6)
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT FINISH
DRYVIT ADHESIVE APPLIEDTO BACK OF EPS
DRYVIT DETAIL MESH®
DRIP GROOVE
DRYVIT DETAIL MESH®
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™ -TEXTURE OVER DRYVIT GRIDTAPE™ (SEE NOTE 4)
DRYVIT VENT TRACK™(SEE NOTES 2 AND 3)
DRYVIT VENT ASSEMBLY™
DRYVIT BACKSTOP NT- TEXTUREOVER DRYVIT GRID TAPE
DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION BOARD(SEE NOTE 5)
OMD 0.0.25
Outsulation® MD System® Transition At Soffit/Fascia IntersectionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.
3. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OFAQUAFLASH SYSTEM OR BACKSTOP NT™-TEXTURE OVER GRID TAPE.
5. GROOVED BOARD AND FLAT STOCK EPSARE ACCEPTABLE FOR USE INHORIZONTAL SOFFIT CONDITION.
6. DRYVIT AIR/WATER RESISTIVE BARRIERIS REQUIRED OVER VERTICALSUBSTRATES. APPLICATION OVERHORIZONTAL SOFFIT SUBSTRATE ISOPTIONAL UNLESS REQUIRED AS PART OFA CONTINOUS AIR BARRIER SYSTEM.
1"(25 MM) MIN.
2-1/2"(64 MM) MIN.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
©Dryvit Systems, Inc.Issued: 10/2016
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS 2" (51 MM) MIN.
DRYVIT AQUAFLASH® SYSTEM ORDRYVIT BACKSTOP® NT™ -TEXTURE OVER DRYVIT GRIDTAPE™ (SEE NOTE 4)DRYVIT VENT TRACK™(SEE NOTES 5 & 6)
DRYVIT VENT ASSEMBLY™
DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™
CASING BEAD, BY OTHERS
DRYVIT BASE COAT
FRAMING
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
OMD 0.0.26
Outsulation® MD System® Fascia/Uninsulated Soffit TransitionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.
2. SOFFITS WITHOUT EPS INSULATIONREQUIRE EXPANSION JOINTS EVERY20 FT (6.1 M).
3. REFER TO DRYVIT PUBLICATION DS173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.
4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF AQUAFLASH SYSTEM.
5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
6. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
FRAMING, BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT BASE COAT
SOFFIT VENT, BY OTHERS
DRYVIT FINISH
OMD 0.0.27
Outsulation® MD System® Termination at Uninsulated Soffit VentNOTE:1. CONTROL JOINTS ARE RECOMMENDEDEVERY 20 FT (6.1 M).
2. REFER TO DRYVIT PUBLICATION DS173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.
3. SEAL ALL BUTT JOINTS, INTERSECTIONS,AND ENDS OF VENTS WITH COMPATIBLESEALANT.
4. SEE DRYVIT PUBLICATION DS842 FORADDITIONAL DIRECT APPLIED DETAILS.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
A
DRYVIT AQUAFLASHSYSTEM
(SEE NOTE 7)
SLIP TYPECONNECTION
Section A-A
SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE AT VENTASSEMBLY ONLY (SEE NOTES 5 AND 8)
VENT ASSEMBLY LOCATION
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 7)CLOSED CELL BACKER ROD,
BY OTHERS
SEALANT MATERIAL, BY OTHERS
OMD 0.0.28
Outsulation® MD System® Horizontal Joint at Slip TrackNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TO ABNORMALSTRESS, HIGH TRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BE INDICATED ON CONTRACTDRAWINGS.
2. EXPANSION JOINT IN THE OUTSULATION MD SYSTEM ISNECESSARY WHERE SIGNIFICANT DIFFERENTIALMOVEMENT IS EXPECTED AT FLOOR LINES.
3. LIGHTLY SAND SURFACE OF DRYVIT VENT TRACK TOMAXIMIZE ADHESION.
4. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF BREAK IN SHEATHING.
5. SEALANT SHALL NOT BE IN DIRECT CONTACT WITHASPHALTIC ADHESIVE ON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITH POLYETHYLENE TAPEOR BACKER ROD.
6. SLOT IN DRYVIT VENT TRACK MUST BE POSITIONED OVERDRYVIT VENT ASSEMBLY.
7. DRYVIT FLASHING TAPE SURFACE CONDITIONER ANDDRYVIT FLASHING TAPEMAY BE USED IN LIEU OF DRYVIT AQUAFLASH SYSTEM.
8. SEALANT SHALL TURN IN AT DRYVIT VENT ASSEMBLYLOCATIONS TO ALLOW FOR DRAINAGE. SEE SECTION A-A.
CLOSED CELL BACKERROD, BY OTHERS
(SEE NOTE 4)
DRYVIT VENT TRACK™(SEE NOTES 3 & 6)
DRYVIT VENT ASSEMBLY™
DRYVIT DEMANDIT® OR COLOR PRIME™ ONSURFACES TO RECEIVE SEALANT
SLOPE SURFACE OUTSIDE OF SEALANT1:5 MIN. OUTWARD TO DRAIN
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
WRAP DRYVIT DETAIL MESH® MIN. 2" (51 MM)
EPS INSULATION BOARD
FRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
APPROVED SUBSTRATE
A3/4"
(19 MM) MIN.
DRYVIT COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 5)
DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™ - TEXTURE OVER DRYVITGRID TAPE™ (SEE NOTE 7)
DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS(SEE NOTES 4, 5, AND 8)
DRYVIT CLOSURE BLOCK
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
DRYVIT VENT ASSEMBLY™™
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
SLOPE SURFACE OUTSIDE OF SEALANT1:5 MIN. OUTWARD TO DRAIN
DRYVIT FINISH
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
WRAP DRYVIT DETAIL MESH® MIN. 2" (51 MM)
EPS INSULATION BOARD
FRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATINGDRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
APPROVED SUBSTRATE
A
A3/4"
(19 MM) MIN.
Section A-A
SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE ATVENT ASSEMBLY ONLY (SEE NOTES 3 AND 6)
VENT ASSEMBLY LOCATION
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)CLOSED CELL BACKER ROD,BY OTHERS
SEALANT MATERIAL, BY OTHERS
DRYVIT BASE COAT
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™ - TEXTURE OVER DRYVITGRID TAPE™ (SEE NOTE 5)
DRYVIT COMPATIBLE SEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS (SEE NOTES 3 AND 6)
DRYVIT VENT TRACK™ (SEE NOTES 2 & 4)
WRAP DRYVIT DETAIL MESH® MIN. 2" (51 MM)
DRYVIT CLOSURE BLOCK
DRYVIT COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS (SEE NOTE 3)
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 5)
OMD 0.0.29
Outsulation® MD System® Horizontal Joint - Substrate ChangeNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD™ OR STANDARD PLUS™ MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
3. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
4. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.
5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM.
6. SEALANT SHALL TURN IN AT DRYVIT VENTASSEMBLY LOCATIONS TO ALLOW FORDRAINAGE. SEE SECTION A-A.
DRYVIT STARTER STRIP™
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
SEALANT WITH BOND BREAKER, BY OTHERS
FRAMINGAPPROVED SUBSTRATE
PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT FINISHDRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVE BARRIERCOATING (SEE NOTE 3)
3/4"(19 MM)
MIN.
DRYVIT AQUAFLASH® SYSTEM OR DRYVITBACKSTOP® NT™ - TEXTURE OVER DRYVITGRID TAPE™ (SEE NOTE 2)
CONTINUOUS FLASHING, BY OTHERS
STONE VENEER SYSTEM,BY OTHERS
DRYVIT VENT ASSEMBLY™
DRYVIT VENT TRACK™ (SEE NOTES 4 & 5)
DRYVIT BASE COAT
DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 6)
DRYVIT COMPATIBLE SEALANT WITH BONDBREAKER TAPE, BY OTHERS
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)
Section A-A
SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE ATVENT ASSEMBLY ONLY (SEE NOTE 6)
VENT ASSEMBLY LOCATION
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)
CLOSED CELL BACKER ROD,BY OTHERS
SEALANT MATERIAL, BY OTHERS
A
A
OMD 0.0.30
Outsulation® MD System® Horizontal Termination at Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD™ OR STANDARDPLUS™ MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR INSTALLATION OF DRYVIT AIR/WATER-RESISTIVE BARRIER COATING BENEATHCLADDINGS OTHER THAN DRYVIT EIFS,REFER TO DRYVIT PUBLICATION DS840.
4. LIGHTLY SAND SURFACE OF DRYVIT VENTTRACK TO MAXIMIZE ADHESION.
5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENT ASSEMBLY.
6. SEALANT SHALL TURN IN AT DRYVIT VENTASSEMBLY LOCATIONS TO ALLOW FORDRAINAGE. SEE SECTION A-A.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
FRAMING
DRYVIT AQUAFLASH SYSTEM(SEE NOTE 2)
APPROVED SUBSTRATE
SEALANT WITH BOND BREAKER,BY OTHERS
LAP SIDING, BY OTHERS
CONTINUOUS FLASHING,BY OTHERS
3/4"(19 MM) MIN.
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT FINISH
DRYVIT BASE COATDRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 3)
DRYVIT AQUAFLASH® SYSTEM ORBACKSTOP® NT™-TEXTURE OVERDRYVIT GRID TAPE™ (SEE NOTE 2)
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT VENT TRACK™(SEE NOTES 4 & 5)
DRYVIT BASE COAT
SEALANT WITH BOND BREAKER,BY OTHERS
DRYVIT VENT ASSEMBLY™
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 6)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
Section A-A
SEALANT AGAINST DRYVIT AQUAFLASHSYSTEM WITH BOND BREAKER TAPE ATVENT ASSEMBLY ONLY (SEE NOTE 6)
VENT ASSEMBLY LOCATIONDRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)
CLOSED CELL BACKER ROD,BY OTHERS
SEALANT MATERIAL, BY OTHERS
A
A
OMD 0.0.31
Outsulation® MD System® Horizontal Termination at Lap SidingNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. FOR INSTALLATION OF DRYVITAIR/WATER- RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THANDRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.
4. LIGHTLY SAND SURFACE OF DRYVITVENT TRACK TO MAXIMIZE ADHESION.
5. SLOT IN DRYVIT VENT TRACK MUST BEPOSITIONED OVER DRYVIT VENTASSEMBLY.
6. SEALANT SHALL TURN IN AT DRYVITVENT ASSEMBLY LOCATIONS TO ALLOWFOR DRAINAGE. SEE SECTION A-A.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
3/4" (19 MM) MIN.
FRAMING
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS
EPS INSULATION BOARD
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
2
OMD 0.0.32
Outsulation® MD System® Vertical Expansion Joint - EIFSNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. EIFS EXPANSION JOINTS ARE REQUIREDIN CONTINUOUS ELEVATIONS ATINTERVALS NOT EXCEEDING 75 FT (23 M).
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)
FRAMING
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
EPS INSULATION BOARD
DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
OPTIONAL SECONDARY SEAL, BY OTHERS
DRYVIT DEMANDIT OR COLOR PRIME ONSURFACES TO RECEIVE SEALANT
DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)
DRYVIT DETAIL MESH WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)
OPTIONAL SECONDARY SEAL, BY OTHERS
CLOSED CELL BACKER ROD, BY OTHERS (SEE NOTE 4)DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)
3/4" (19 MM) MIN.
3/4" (19 MM) MIN.
FRAMING
APPROVED SUBSTRATE
DRYVIT FINISH
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
EPS INSULATION BOARD
DRYVIT BASE COAT
DRYVIT BASE COAT
APPROVED SUBSTRATE
OMD 0.0.33
Outsulation® MD System® Through-Wall Expansion JointNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
4. LOCATE EXTERNAL SEALANT JOINTWITHIN 2" (51 MM) OF SUBSTRATE JOINT.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
FRAMING
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)
DRYVIT BACKSTOP® NT™ - TEXTUREOVER DRYVIT GRID TAPE™
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
EPS INSULATION BOARD
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
FLUSH OPTION
RECESSED OPTION
3/4" (19 MM) MIN.
3/4" (19 MM) MIN.
APPROVED SUBSTRATE
OMD 0.0.34
Outsulation® MD System® Vertical Expansion Joint - Flush and Recessed OptionsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
©Dryvit Systems, Inc.Issued: 10/2016
3/4" (19 MM) MIN.
REAR SEAL
FACE SEAL
VENT
APPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD,BY OTHERS (SEE NOTE 3)
REAR SEAL
FACE SEAL
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
EPS INSULATION BOARD
VENT
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
FRAMING
DRYVIT BACKSTOP® NT™ - TEXTUREOVER DRYVIT GRID TAPE™
APPROVED SUBSTRATE
OMD 0.0.35
Outsulation® MD System® Vertical Expansion Joint - Double Seal OptionNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
3/4" (19 MM) MIN.
FRAMINGAPPROVED SUBSTRATE
DRYVIT BASE COAT
DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)
DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT
DRYVIT FINISH
DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS
BEDDING COAT AND STONEVENEER SYSTEM, BY OTHERS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 2)DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS
EPS INSULATION BOARD
DRYVIT REINFORCING MESHEMBEDDED IN BASE COAT
PAPER BACKED EXPANDEDMETAL LATH, BY OTHERS
ANGLE STOP FOR STONEVENEER SYSTEM, BY OTHERS
DRYVIT BASE COAT
OMD 0.0.36
Outsulation® MD System® Vertical Termination At Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIERCOATING BENEATH CLADDINGS OTHERTHAN DRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
3/4"(19 MM)
MIN.
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS
SECONDARY SEAL, BY OTHERS
FRAMING
DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 3)
DRYVIT DEMANDIT OR COLOR PRIMEON SURFACES TO RECEIVE SEALANT
DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)
DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)
DRYVIT BASE COAT
OMD 0.0.37
Outsulation® MD System® PenetrationsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.
3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVEON DRYVIT FLASHING TAPE. COVERDRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
1/2" (12.7 MM) MIN.
FRAMING
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVE BARRIER COATING
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT BASE COAT
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
DRYVIT FINISH
SCREW/BOLT ATTACHMENT TO BUILDINGFRAMING/BLOCKING, BY OTHERS
NEOPRENE WASHER, BY OTHERSSIGN FIXTURE, BY OTHERS
DRYVIT COMPATIBLE SEALANT AND BONDBREAKER TAPE, BY OTHERS (SEE NOTE 2)NON-CORROSIVE PIPE SLEEVE, BYOTHERS, SET IN SEALANT
BLOCKING, SECURED TO FRAMING
DRYVIT BASE COAT
OMD 0.0.38
Outsulation® MD System® Sign AttachmentNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. PERIMETER OF PIPE SLEEVE ISCAULKED TO PREVENT WATER ENTRYINTO WALL.
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT
DRYVIT FINISH
FRAMING
DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS
2" (51 MM) MIN.
DRYVIT DETAIL MESH® EMBEDDED IN DRYVIT BASECOAT. OVERLAP REINFORCING MESH 2 1/2" (64 MM)
DRYVIT BASE COAT
OMD 0.0.39
Outsulation® MD System® Aesthetic RevealsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD™OR STANDARD PLUS™ MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.
2. SLOPE BOTTOM EDGE OF REVEAL FORPOSITIVE DRAINAGE.
2 1/2" (64 MM)
2 1/2" (64 MM)
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
FRAMING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
BY OTHERS
2" (51 MM) MIN.
OUTSULATION MDSYSTEM
OVERLAP 2 1/2" (64 MM)
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
SLOPE GRAPHIC FORPOSITIVE DRAINAGE
DRYVIT BASE COAT
OMD 0.0.40
Outsulation® MD System® Recessed Graphics
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.
Dryvit Systems, Inc.Issued: 10/2016
NOTE:1. MAXIMUM THICKNESS OF EPS BUILTOUT SHAPES SHALL NOT EXCEED13" (330 MM) AT ANY POINT MEASUREDFROM THE SUBSTRATE.
BY OTHERS
OUTSULATION MDSYSTEM
OVERLAP MESH2 1/2" (64 MM)
SLOPE GRAPHIC FORPOSITIVE DRAINAGE
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS
DRYVIT ADHESIVE
EPS SHAPE
EPS INSULATION BOARD
APPROVED SUBSTRATE
DRYVIT AIR/WATER-RESISTIVEBARRIER COATING
DRYVIT BASE COAT
DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT
DRYVIT FINISH
FRAMING
DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION
APPLIED TO BACK OF EPS
DRYVIT BASE COAT
OMD 0.0.41
Outsulation® MD System® Projecting Graphics
©
The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.