HOCHIKI CORPORATION SINGAPORE BRANCH OFFICE 629 Aljunied Road #03-16 Cititech Industrial Building Singapore 389838 Tel : 65-6841-9728 Fax : 65-6841-9781 Email : [email protected] HEAD OFFICE 10-43 Kamiosaki 2-Chome. Shinagawa-Ku, Tokyo 141-8660, Japan Tel : 81-(3)-3444-4116 Fax : 81-(3)-3444-4167 URL : www.hochiki.co.jp P-2 Type Fire Alarm Control Panel : RPP-EBW Features 1. Easy installation - Wide internal cabinet space for easy wiring - Wiring terminals are vertically arrange to ease installation 2. Simple Configuration -‘Vacant Zone’ and ‘Time Delay’ function are easily established by means of a simple DIL switch inside the panel 3. High reliability - Improved lightning surge protection - Improved noise immunity - Self diagnostic function (Zones open circuit monitored, Battery fault warning, Time delay function, etc.) 4. Light weight, Simple design yet powerful by means of - SMD components, small PCB, compact power unit, etc. 5. Improved local bell control with programmable ‘silence’ timer - If the local bell is put on ‘silence’ mode after an initial alarm signal, any subsequent zone activation immediately re-triggers the local alarm. And should the system be left at ‘silence’ mode without subsequent zone activation, the local alarm will automatically trigger again after a custom preset time period from the first alarm activation. - The custom preset timer can be programmed to reactivate the local alarm after 2,4,6 or 8 minutes from the first alarm activation. 6. New functions - Visual representation of fire alarm status by symbolic indication lamp - Functional test equipped with 2 reset modes for heat and smoke detectors - Identification of first zone alarm by first flashing of zone alarm indicator

P-2 Type Fire Alarm Control Panel : RPP-EBW - ホーチキ · Specifications RPP-EBW Type P Type 2nd Class Fire Alarm Control Panel (with Time Delay Function) Model Name RPP-EBW (03B,

Embed Size (px)

Citation preview

Page 1: P-2 Type Fire Alarm Control Panel : RPP-EBW - ホーチキ · Specifications RPP-EBW Type P Type 2nd Class Fire Alarm Control Panel (with Time Delay Function) Model Name RPP-EBW (03B,

HOCHIKI CORPORATIONSINGAPORE BRANCH OFFICE629 Aljunied Road #03-16 Cititech Industrial BuildingSingapore 389838Tel : 65-6841-9728 Fax : 65-6841-9781Email : [email protected]

HEAD OFFICE10-43 Kamiosaki 2-Chome. Shinagawa-Ku,Tokyo 141-8660, JapanTel : 81-(3)-3444-4116 Fax : 81-(3)-3444-4167URL : www.hochiki.co.jp

P-2 Type Fire Alarm Control Panel : RPP-EBW

Features1. Easy installation -Wide internal cabinet space for easy wiring -Wiring terminals are vertically arrange to ease installation2. Simple Configuration - ‘Vacant Zone’ and ‘Time Delay’ function are easily established by means of a simple DIL

switch inside the panel3. High reliability - Improved lightning surge protection - Improved noise immunity - Self diagnostic function (Zones open circuit monitored, Battery fault warning, Time delay

function, etc.)4. Light weight, Simple design yet powerful by means of - SMD components, small PCB, compact power unit, etc.5. Improved local bell control with programmable ‘silence’ timer - If the local bell is put on ‘silence’ mode after an initial alarm signal, any subsequent

zone activation immediately re-triggers the local alarm. And should the system be leftat ‘silence’ mode without subsequent zone activation, the local alarm willautomatically trigger again after a custom preset time period from the first alarmactivation.

-The custom preset timer can be programmed to reactivate the local alarm after 2,4,6or 8 minutes from the first alarm activation.

6. New functions -Visual representation of fire alarm status by symbolic indication lamp -Functional test equipped with 2 reset modes for heat and smoke detectors - Identification of first zone alarm by first flashing of zone alarm indicator

Page 2: P-2 Type Fire Alarm Control Panel : RPP-EBW - ホーチキ · Specifications RPP-EBW Type P Type 2nd Class Fire Alarm Control Panel (with Time Delay Function) Model Name RPP-EBW (03B,

Specifications

RPP-EBWType P Type 2nd Class Fire Alarm Control Panel (with Time Delay Function)Model Name RPP-EBW� (03B, 05B)(JE)Circuit Type RPP-E24AMains AC220V 50/60HzTransformer Capacity 23VAStand-by-Battery DC12V, 0.6AHBattery Charger Ni-Cd Battery Trickle ChargerMain Sounder Buzzer DC24V 25mAOperating Temperature Range 0°C – 40°CMaterial Self Extinguishing Plastic, 3mmColor Light GrayNumber of Zones 3 Zones & 5 ZonesWeight Approx. 1.7KgDimension 230mm (W) X 330mm (H) X 63mm(D)Made JAPAN

63

20.5

13

21

17

.5

33

0

20 × 150(for DC)

φ20(for AC)

25115

(33

0)

30

5

190(230) 1

5

10

41

18

20

3-mounting hole φ2

φ5

Zone lamp Indication lamp Sounder

Cover

Lock screw

230

Operation switch