P443_en_0817

Embed Size (px)

Citation preview

  • 8/14/2019 P443_en_0817

    1/8

  • 8/14/2019 P443_en_0817

    2/8

    2>3

    Protection Functions Overview

    ANSI FEATURE A Hardware B Hardware

    Optocoupled logic inputs 16 24

    Relay output contacts 24 32

    Dual rated 1A and 5A CT inputs Single and Three Pole Tripping Clockwise and Anticlockwise phase rotation Direct access menu "Hotkeys" Multiple Password access control levels

    21P / 21G Distance Zones - Mho and 5

    quadrilateral full scheme relay

    CVT Transient overreach elimination Load Blinder Easy Setting mode Mutual compensation

    85 Communication-aided schemes, PUTT, POTT, Blocking, Weak Infeed

    Accelerated tripping - Loss of Load, and Zone 1 extension

    50 / 27 Switch on to Fault 68 Power Swing Blocking

    I/V Delta Directional Comparison 67N Directional Earth Fault (DEF) unit protection 50 / 51 / 67 Phase overcurrent stages 4

    50N / 51N / 67N Earth/ground overcurrent stages 4

    67 / 46 Negative sequence overcurrent 46BC Broken conductor 49 Thermal protection 27 Undervoltage protection stages 2

    59 Overvoltage protection stages 2

    59N Residual voltage protection stages 2

    50BF High speed breaker fail

    CTS / VTS Current and Voltage Transformer supervision 79 Autoreclose - shots supported 4

    25 Check synchronism Alternative setting groups 4

    FL Fault Locator Fault Records 5

    SOE Event Records 500

    Disturbance recorder, samples per cycle 48

    Circuit Breaker condition monitor Graphical Programmable Scheme Logic (PSL) IRIG-B time synchronism ()

    InterMiCOM teleprotection ()Key () : denotes optional

    APPLICATION

    > Distance protection

    The MiCOMhoP443 is supplied with a full suite of protection and

    control functions as standard.The configuration column of the menu

    is used to control which functions the user requires in the intended

    application and which may be disabled. Disabled functions are

    completely removed from the menu, to simplify setting.

    The Protection Functions Overview table highlights the functions

    available.

  • 8/14/2019 P443_en_0817

    3/8

    Versatile protection for universal application.

    The simple set mode invokes an inbuilt wizard,to simplify the job of the Protection Engineer.

    X67

    50/2746BC67N CTS

    27/

    59VTS50BF 79 25

    Fault records Disturbance

    Record

    Measurements

    PSL

    Local

    Communication

    2nd Remote

    comm. port

    Remote

    comm. port

    Distance RelayP443

    Inter MiCOM

    LEDs

    conventionalsignalling

    always available

    optional

    protectioncommunication

    Vref

    V

    I

    Self monitoring

    85

    21P 21G 50/51

    FL

    50N/

    51NI/V

    67/

    4668

    59N

    Neutral currentfrom parallel line(if present)

    IM

    49 SOTF/TOR

    1 3

    5

    2

    4

    (Description of ANSI code nos. see protection Functions Overview)

    Figure 1

    User interface

    > Inputs

    AC Current (In)

    1A/5A dual rated ac rms

    AC voltage (Vn)

    100 - 120V nominal phase-phase

    Rated frequency 50/60Hz

    Operative range

    45 - 55Hz at 50Hz

    55 - 65Hz at 60Hz

    > User Interface

    The front panel user interface, as shown in Figure 1

    comprises:

    (1) A back-lit liquid crystal display

    (2) Four fixed function LEDs

    (3) Eight user programmable LEDs

    (4) Menu navigation/data entry keys, and two

    context sensitive hotkeys. Hotkeys can be

    highlighted in vivid green and red colors if

    used for trip/close breaker controls

    (5) "READ" and "CLEAR" keys for view/reset

    of alarms

    FUNCTIONAL OVERVIEW DIAGRAM

  • 8/14/2019 P443_en_0817

    4/8

    4>5

    Figure 5 Quadrilateral characteristics

    Figure 3 Example Min-Max Timing Contour,50Hz, SIR=5

    Figure 2 Mho characteristics

    Zone 3(reverse offset)

    Zone 1

    Zone P

    Zone 2

    Zone 3(without offset)

    Zone P(reverse)

    Directional(reverse)

    Zone 4

    Directional(forward)

    Zone 3

    Zone P (fwd)

    Zone P

    (Reverse)

    Zone 4

    Offset Reverse Z3

    Zone 2

    Zone 1

    Directional

    (forward)

    50Hz, SIR = 5

    50% 70% 80% 90%

    10

    20

    30

    40

    0

    Performance:Subcycle up

    to 75% Reach

    60Hz, SIR = 5

    50% 70% 80% 90%

    10

    20

    30

    40

    0

    Performance:Subcycle up

    to 75% Reach

    Figure 4 Example Min-Max Timing Contour, 60Hz, SIR=5

    MAIN PROTECTION FUNCTIONS

    > Distance Protection

    Five zones of protection are provided as shown in

    Figure 2.

    The relay allows mho and quadrilateral (polygon)

    characteristics to be independently selected for the

    phase and ground distance elements.

    The mho is shown in Figure 2, and uses well-proven

    principles to provide dynamic expansion for faults offthe characteristic angle.

    The quadrilateral characteristics (Figure 5 ) provide

    enhanced fault arc resistance coverage. An adaptive

    technique is used to tilt the reactance reach line of

    each zone and eliminate under/overreaching effects

    due to prefault load flow.

    Blinder characteristics (Figure 6) prevent false tripping

    due to encroachment of heavy loads.

    A superimposed current phase selector detects the

    faulted phase(s) and, controls which of the distanceelements will initiate a trip. Combined with the

    directional decision from a proven delta principle,

    secure operation of distance zones is assured.

    > Power Swing Blocking (PSB)

    The MiCOMhoP443 recognizes power swings quickly,

    by means of the superimposed currents measured by

    the phase selector.

    The PSB does not require any impedance band or

    timers to be set.

    The trip time for faults occurring during a power swing

    remains subcycle.

  • 8/14/2019 P443_en_0817

    5/8

    MiCOMho P443 :

    A full-scheme distance relaywith subcycle technology.

    Operate

    Operate

    RestrainRestrain

    Figure 6 Load blinder

    MAIN PROTECTION SCHEMES

    Pre-configured distance schemes allow single and

    three phase tripping with or without a signalling

    channel.

    Basic scheme logic for stand alone operation

    (without a signalling channel).

    Trip on Close logic allows accelerated tripping to be

    selected following manual, or auto-reclose.

    CARRIER AIDED SCHEMEINCLUDE:

    Direct transfer tripping

    Permissive underreach scheme (PUR)

    Permissive overreach (POR) with open breaker,

    weak infeed echo logic and weak infeed trip feature

    Blocking scheme

    User-defined custom schemes

    The relay provides two independent teleprotection

    schemes each using a separate communication

    channel. The distance, directional and DEF functions

    are thus flexible in configuration, to operate in shared

    channel logic or in discrete modes.

    > Delta Directional Comparison

    Superimposed voltage and current signals are used to

    make highly-secure fault directional decisions.

    The respective forward/reverse decisions at each line

    end can be used in a teleprotection scheme, for full line

    unit protection as proven in the LFDC product.

    The advantage is a channel send even faster than for

    distance aided schemes.

    > Directional Earth Fault (DEF)

    The DEF element can be used within the aided

    schemes to detect high resistance ground faults.

    The innovative "Virtual Current Polarizing" feature even

    ensures correct operation when the fault generates

    negligible zero or negative sequence voltage.

    Traditional relays would have required an extra

    CT input to cover this scenario - not required for the

    MiCOMhoP443.

    > InterMiCOM (optional)InterMiCOM allows high performance permissive and

    blocking type unit protection to be configured, plus

    transfer of any digital status information between line

    ends. Intertripping is supported too, with channel

    health monitoring and cyclic redundancy checks (CRC)

    on the received data for maximum message security.

    InterMiCOM provides eight end-end signals, assignable

    to any function within a MiCOM relay's programmable

    logic. Default failsafe states can be set in case of

    channel outage.

    BACKUP PROTECTION

    > Overcurrent Protection

    Four stages of both phase and earth (ground) fault

    protection are provided with a choice of standard IDMT

    curves (Figure 7). Negative sequence overcurrent is

    also available.

    > Voltage Protection

    Phase under and overvoltage protection functions are

    available in addition to residual overvoltage.

    > Broken ConductorThis protection detects the percentage phase

    unbalance due to an open phase condition.

    > Thermal Overload

    A thermal replica provides alarm and trip stages, to warn

    and protect in the event of prolonged circuit overloading.

  • 8/14/2019 P443_en_0817

    6/8

    6>7

    IEC Standard inverse t = TMSx

    IEC Very inverse t = TMSx

    IEC Extremely inverse t = TMSx

    UK Long time inverse t = TMSx

    IEEE Moderately inverse

    t = TDx

    IEEE Very inverse

    IEEE Extremely inverse

    US CO8 Inverse

    US CO2 Short timeinverse

    t = TDx

    t = TDx

    t = TDx

    t =TD

    x

    0.14

    (IIs -1)0.02

    13.5

    (IIs -1)

    80

    (IIs -1)2

    120

    (IIs -1)

    0.0515

    (IIs -1)0.02

    + 0.114

    19.61

    (IIs -1)2

    + 0.491

    28.2

    (IIs -1)2 + 0.1217

    5.95

    (IIs -1)2 + 0.18

    0.16758

    (IIs -1)0.02 + 0.11858

    IEEE/US curves

    TD = 1

    IEC/UK curves

    TMS = 1

    TD 0.01 to 100TMS 0.025 to 1.2

    IEEE MI

    IEEE VI

    IEEE EI

    US CO8

    US CO2

    100101

    Current (Multiples of Is)

    0.1

    1

    10

    100

    Operating

    time(s)

    UK LTI

    IEC SI

    IEC VI

    IEC EI

    1000

    100

    10

    1

    0.1100101

    Current (Multiples of Is)

    Operating

    time(s)

    Figure 7

    IEC and IEEE/ANSI IDMT

    Figure 8 PSL Editor (MiCOM S1)

    SUPERVISORY FUNCTIONS

    > High speed breaker failure

    Two stage circuit breaker failure protection for

    backtripping upstream circuit breakers, and re-tripping

    of the local circuit breaker if required.

    > VT supervision (fuse fail)

    Voltage transformer supervision is provided to detect

    loss of one, two or three VT signals.

    > CT supervision

    Current transformer supervision is provided to detect

    loss of phase CT input signals.

    CONTROL

    > Hotkey menu

    Trip and close commands are facilitated from front

    panel "hotkeys", to allow direct CB control without the

    need to navigate a menu. Other in/out, on/off and

    enable/disable controls are easily programmed.

    > Autoreclose with check synchronism

    The user may select a single, two, three

    or four shot autoreclose cycle.

    > Programmable scheme logic

    Powerful graphical logic allows the user to customize

    the protection and control functions.

    The gate logic includes OR, AND and majority gate

    functions, with the ability to invert the inputs and

    outputs, and provide feedback. The system is

    optimized to ensure that the protection outputs are not

    delayed by the PSL operation.

    The programmable scheme logic is configured usingthe graphical MiCOM S1 PC software, as shown in

    Figure 8.

    The relay outputs may be configured as latching (eg

    "Lockout") or self-reset.

    > User Interface

    The user interface and menu text are available in

    English, French, German and Spanish as standard.

    The ability to customize the menu text and alarm

    descriptions is also supported.

    > Password Protection

    Password protection may be independently applied

    to the front user interface, front communications

    port and rear communications port. Two levels of

    password protection are available providing access

    to the controls and settings respectively.

    > Measurement and recording facilities

    All event, fault and disturbance records are time

    tagged to a resolution of 1ms. An optional IRIG-B port

    is available for accurate time synchronization.

    > Power system measurementsInstantaneous and time integrated voltage, current and

    power measurements are provided. These may be

    viewed in primary, or secondary values.

  • 8/14/2019 P443_en_0817

    7/8

    A = Clearanceholes

    177.0(4U

    483 (19 rack)

    177.00

    Front

    413.20

    All dimensions in

    157.5 max

    Side30.00

    240.00Incl. wiring

    Secondary cover (when

    74.90

    159.00

    62.00

    168.00

    116.55 142.45

    155.40 129.50

    408.90

    A A A

    A AA

    12 off holes Dia. 3.4

    4.50

    406.90

    Figure 9 Case size MiCOMho P443 (80 TE)

    POST FAULT ANALYSIS

    > Fault location

    A fault location algorithm provides distance to fault in

    miles, kilometres, ohms or percentage of the line length.

    The proven algorithm used tolerates pre-fault loading

    and fault arc resistance.

    > Event records

    Up to 500 time-tagged event records are stored in

    battery backed memory.

    > Fault records

    The last 5 faults are stored :

    Indication of the faulted phase

    Protection operation

    Active setting group

    Fault location (distance to fault)

    Relay and CB operating time

    Pre-fault and fault currents, voltages and frequency

    > Disturbance records

    The oscillography has 8 analog channels, 32 digital and

    1 time channel, all at a resolution of 48 samples/cycle.

    Disturbance records can be extracted from the relay via

    the remote communications and saved in the

    COMTRADE format.

    PLANT SUPERVISION

    > Trip circuit supervision

    Supervision of the trip circuit can be implemented using

    optocoupled inputs and the programmable scheme

    logic.

    > CB State monitoring

    An alarm will be generated if there is a discrepancy

    between the open and closed CB auxiliary contacts.

    > Circuit breaker condition monitoring

    Monitoring the number of breaker tr ip operations

    Recording the sum of broken current quantity

    (interruption duty)

    Ix, 1.0 x 2.0

    Monitoring the breaker operating time

    > Remote auxiliary communications

    Two auxiliary communication ports are available; a rear

    port providing remote communications and a front port

    providing local communications. An additional, second

    rear port can be ordered as an option.

    Any of the following listed rear port protocols can be

    chosen at the time of ordering.

    Courier/K-Bus

    IEC 60870-5-103

    DNP 3.0

    > Second rear Courier port/ InterMiCOM board

    The optional second port is designed typically for dial-

    up modem access by protection engineers/operators,

    when the main port is reserved for SCADA traffic.Selecting this board also ensures that the relay has

    InterMiCOM hardware fitted, as both options reside on

    the same board.

  • 8/14/2019 P443_en_0817

    8/8

    AUTOMATION-L3-P443-BR-01.05-0817-GB

    -

    -AREVA-

    2004

    .AREVA

    ,the

    AREVAlogoan

    danya

    lterna

    tivevers

    ion

    thereo

    fare

    tra

    demarksan

    dserv

    icemarkso

    fAREVA

    .

    M i C O M

    i s a r e g

    i s t e r e

    d t r a

    d e m a r k o

    f A R E V A

    A l l t r a d

    e n a m e s o r

    t r a

    d e m a r k s m e n

    t i o n e

    d h e r e

    i n w

    h e

    t h e r r e g

    i s t e r e

    d o r n o

    t a r e

    t h e p r o p e r t y o

    f t h e

    i r o w n e r s

    3 8 9 1 9 1 9 8 2 R C S P A R I S

    P r i n

    t e d i n F r a n c e

    S O N O V I S I O N I

    T E P

    AREVA T&D Worldwide Contact Centre:

    http://www.areva-td.com/contactcentre/

    Tel.: +44 (0) 1785 250 070

    www.areva-td.com

    AREVA TRACK RECORD -

    HIGH SPEED DISTANCE PROTECTION

    >> Micromho subcycle distance protection deployed on EHV systems

    since 1983 - over 2500 relays supplied.

    Very fast mho characteristic relay.

    >> Quadramho distance protection launched in 1984,

    adding quadrilateral characteristics to the range.

    >> Optimho universal mho and quadrilateral relays launched

    in1989. Over 11500 units delivered.

    >> Numerical implementation and phase selection proven in sub-cycle

    LFDC and LFZR relays.

    >> Over 6500 MiCOM P44x family distance relays delivered

    since launching in 1999

    Our policy is one of continuous development. Accordingly thedesign of our products may change at any time. Whilst everyeffort is made to produce up to date literature, this brochureshould only be regarded as a guide and is intended forinformation purposes only. Its contents do not constitute an offerfor sale or advise on the application of any product referred to init. We cannot be held responsible for any reliance on anydecisions taken on its contents without specific advice.