PMAC Catalogue 2012

Embed Size (px)

Citation preview

  • Zhuhai Pilot Technology Co. Ltd.

    Power Meters Catalog V4.0Power metering & energy efficiency management

  • Established in 2000, Zhuhai Pilot Technology Co., Ltd. occupies an area of 20,000 square meters plant with nearly 400 staffs.

    PILOT headquarter in Zhuhai of China, and equipped with a R&D center in Shenzhen NanshanTechnology Park.

    Our business is throughout the world with over 20 branch offices in China, and distribution network in Germany, Romania, Iran, Saudi Arabia, UAE, Pakistan, India, Indonesia, Malaysia, New Zealand, Australia, Canada, Mexico, Colombia, Chile, Brazil etc.

    Our products and services:

    --Digital panel meters--Multifunction power meters--Energy meters--Power Quality Analyzer--Branch circuit monitor--LV motor protection and control devices--Leakage current detectors--Energy efficiency solution

    Additional, our R&D team design customized products to satisfy your special requirements.

  • Certificate 1

    Projects References 2

    Product Selection Guide 4

    Products

    PST700Multifunction Power Meter 5

    PMAC615 Single Phase Digital Panel Meter 8PMAC625 Three Phase Digital Panel Meter 9

    PMAC720 Multifunction Power Meter 11PMAC727 Multifunction Power Meter 14PMAC735 Multifunction Power Meter 17PMAC760 Multifunction Power Quality Analyzer 20

    PMAC901 Single Phase Din-rail Energy Meter 23PMAC903 Three Phase Din-rail Energy Meter 23PMAC905 Multifunction Energy Meter 25PMAC915 Three Phase Multi-tariff kWh Meter 27PMAC921 Single Phase Multi-tariff kWh Meter 29

    CONTENTS

    Page

  • Certificate

    1

  • Projects References

    Projects Abroad

    Hindustan Zinc Limited, the Lead Plant and Silver Plant ( India)IKEA Mega Bangna - IKEA Asias Largest Complex (Thailand)Trekkpje Uranium Plant (South Africa) D.G Khan Cement Plant (Pakistan)Bandung Hydropower Plant (Indonesia)Scotts Feeds Factory Project ( U.K.)Iranian Petrochemical Project ( Iran)

    Olympic Venues

    Beijing Olympic Hockey CenterBeijing Olympic Beach Volleyball CenterBeijing Olympic Shooting RangeQingdao International Sailing CenterBeijing Olympic Basketball Gymnasium

    Municipal Projects

    Shanghai F1 International Circuit Shanghai Pudong Government Processing Center Shanghai World Expo - World Expo Axis Shanghai World Expo Village, Block B/ Block D/E plot Shanghai World Expo-China Pavilion Bank of China Shanghai Information Center Chengdu Commodity Inspection Bureau Guangzhou Baiyun International Convention and Exhibition Centre, Phase I, II, III Guangzhou International Financial Center (also known as Guangzhou West Tower) Handan Wastewater Treatment Plant Hangzhou Nanxing Water Plant Industrial and Commercial Bank of China Head Office Building, Xinjiang Nanjing Jiuhuashan TunnelNew Museum of Nanjing Massacre Memorial Hall Sichuan Cangxi Wastewater Treatment Plant Sichuan Wenjiang Water Plant Urumqi Inspection Centre Xingjiang Radio and Television Building Xinjiang Television Station Building

    Power Plants / Hydropower Plants

    Yunfu Power Plant of Guangdong ElectricXuangxin Power Plant in Inner MongoliaXinjiang Manasi Power Plant, Phase IIIDaihai Power Generation Co. Ltd. 4 600MW project, in Inner Mongolia"Shandong Binzhou Weiqiao Thermoelectric Co., Ltd. Zouping 3rd Thermoelectric Plant: 8 135KW Project"Inner Mongolia Yuanbaoshan Power Plant:2 600MW project Inner Mongolia JingLong (Fengzhen) Power Plant: 2 600MW projectXinjiang Hami Power PlantXinjiang Qiapuqihai Hydropower StationXinjiang Turk Yamaguchi Hydropower Station Xinjiang Karasuk Hydropower StationJilintai Hydropower Station IIExpansion Project of Qinshan Nuclear Power Station Phase II

    Airports / Metro

    Guangzhou New Baiyun International AirportShanghai Pudong International Airport, Phase IIShanghai Hongqiao Airport Reconstruction ProjectQingdao Luiting International AirportWuxi AirportUrumqi Airport Overnight FloorXinjiang Kanas Airport TerminalBeijing Metro Line 4#, 5#Shanghai Metro Line 6#, 7#Dalian Light Rail Line 3#Shenzhen Metro Line 1#Guangzhou Metro Line 2#/ 3#, 4#

    2

  • Telecommunication Porjects

    Shenzhen King Tin Telecommunications RoomShenzhen Fu Yong Telecommunications Room, Phase I,II,& IIIChina Netcom Building in ShanghaiChina Mobile Building in HenanChina Mobile Building in WangjingChina Unicom Building in Zhuhai

    Tobacco Industry

    Hongyun Group, Kunming Cigarette Factory Moving ProjectLongyan Cigarette FactoryGuiyang Cigarette FactoryHongta Group, Yuxi Cigarette FactoryHongyun Group, Honghe Cigarette FactoryShijiazhuang Cigarette Factory

    Hospital / Gym/ School

    Tsinhua University Environmental BuildingPalais Omnisports of Guangzhou Asian Games CityDongguan Changping Chang An HospitalShanghai Nanhui Central Hospital Shanghai Red House HospitalShanghai Donghua University, Songjiang CampusGuangzhou University City Complex Building, Phase I, II & IIIThe New Campus of Sichuan Normal UniversityShanghai StadiumFoshan Century Lotus StadiumFoshan Swimming PoolFoshan Pearl StadiumBeijing Chaoyang Hospital

    Commercial/ Complex Buildings

    TPL National Support Center / ShanghaiGuangzhou Science MeseumGuangdong GSM BuildingShenzhen Ho Shing Commercial CentreShenzhen Hong Long Century PlazaGuangxi TV Station/ Guangxi Science MuseumChongqing Grand TheatreBeijing Yanjing HotelBeijing Big Bell Temple Commercial Plaza Beijing Chang An Grand MallShanghai Gubei Fortune CentreShanghai Tongji Union Square Shangri-La Hotel, QingdaoHanzhong IMC Times Square in Shaanxi

    Oil/ Chemical/ Light Industry

    China Heavy Truck ZF Steering Project Daqing Petrochemical 1.2 million / N delayed coking Daya Bay CNOOC Phase II and petrochemical supporting project Henan Zhongzhou Aluminum Inner Mongolia Yitai Coal Chemical Project New paper mill project in Myanmar Rene Sola project in Sichuan, 3,000 tons of polysiliconShanghai Chlor-Alkali Chemical PVC project Shanghai Huayi Group, 6500 tons / year synthetic camphor agent project Shanghai No. 5 Iron and Steel Plant Shanxi Coking Group, 1 million tons of coking Shihezi Tianye Chemical, 500,000 tons of calcium carbide project Sinopec (GZ) 1 million t catalytic cracker Sinopec East Gas Transmission - Puguang gas field project Sinopec Fujian Petrochemical integration project Sinopec Refining & Chemical Project in Shijiazhuang Xinjiang Tianshan Cement, 2000 tons / D Xinjiang Yili Steel, 300,000 tons of calcium carbide project in Nilka

    Projects References

    3

  • Photo

    SOE event log

    Setpoint alarm

    Data record

    RS485 / Modbus

    The 2nd RS485

    Profibus

    Ethernet or USB

    Infrared COM

    Memory card

    Pulse output

    Other functions

    Communication

    U or F deviation

    Phase angle

    PST700 PMAC615 PMAC625 PMAC720 PMAC735 PMAC727 PMAC760 PMAC901 PMAC903 PMAC905 PMAC915 PMAC921

    Display LCD LED LED LCD LCD LCD LCD LCD LCD LCD LCD LCD

    Single or 3 phase 3 single 3 3 3 3 3 single 3 3 3 single

    Real-time measurement

    U, I, P, Q, kWh

    S

    PF, F

    kvarh

    kVAh

    Demand

    Max./ min. value

    Multi-tariff energy

    Temperature

    Power quality analysis

    Harmonic

    Voltage crest factor

    Current K factor

    Unbalance rate

    Load rate

    DI/ DO

    Status input Relay output

    Analog input

    Analog output

    Product Selection Guide

    ModelFeatures

    standard feature optional feature 4

  • Feature Suit for LV/ HV voltage system

    For low voltage system, PST700 direct connect up to 600VAC

    For high voltage system, PTS700 need to connect with PTs, PT ratio programmable

    New appearance and designLarge LCD display and button, replace AI capacitor by Tam capacitor

    Self-testing phase sequence error In case of error phase sequence input, PST700 will display on LCD

    Real-time measurementTrue-RMS measuring parameters includes:

    U, I, P, Q, S, PF, F, kWh, kvarh, kVAh, demand, max./min. value

    Demand calculation mode is programmable2 kinds of demand modes: fixed mode and slip mode

    Demand cycle programmable: 5/ 10/ 15/ 30/ 60mins

    Slip window programmable: 1/ 2/ 3/ 5mins

    Multi-tariff billing, historical data of 31 days and 12 months2 kinds of setting modes: time zone mode and holiday mode

    Time zone mode: 2 time zones in one year

    Holiday mode: working days ( Mon.- Fri.) and holidays ( Sat.- Sun.)

    There are 2 lists of tariff rate, each list can setup 8 periods of time in 24 hours, 4 tariff rates.

    Power quality analysisHarmonic analysis, crest and K factor, unbalance etc.

    Optional module and upgradeablePluggable in option module, support online upgrade

    Setpoint alarmUnder/ over limit alarm, monitoring objects include: U, I, PF, F, THD, unbalance

    If any parameters is over or under limit and persists over the specified time, PST700 will record the event, and trip relay output signal.

    High accuracyActive energy: according to IEC62053-22, class 0.5s

    Reactive energy: according to IEC62053-23, class 2

    Small size and thin stylePanel: 96x96x13.5mm Cut-out: 90x90mm,

    Depth: 45.1mm (basic unit) + 21.5mm (optional module)

    Standard IEC62053-22/ 23, CE. KEMA

    PST700 Multifunction Power Meter

    Optional module

    Basic unit

    5

  • PST700 Multifunction Power Meter

    2 analog output (4-20mA)

    2 analog input (4-20mA)

    Profibus communication

    AO

    AI

    P

    The 2nd RS485C

    2 relay outputR

    2 pulse outputEp

    U_unbl, I_unblUnbalance

    Max./ min. (U, I, P, Q)Max./ min. value

    Voltage/ frequency deviation, Voltage unbalance record

    THDu, THDi, TOHDu, TOHDi, TEHDu, TEHDi, HRU, RHI

    Voltage crest factor, current K factor, Load rate, Voltage deviation, Frequency deviation

    2 status input S

    SOE (event log), Real-time clock ( yyyy-mm-dd hh:mm:ss)Record function

    Optional Module

    Modbus-RTU protocolRS485

    3 status input + 2 relay output3DI +2 DO

    Harmonic RMS-U, Harmonic RMS-IHarmonic RMS (0-31st )

    Harmonic energy (1st -31st )

    Power quality analysis

    Dmd_I, Dmd_P, Dmd_Q ,Dmd_S

    F

    kWh and kvarh (4 quadrant), kVAh

    PFa, PFb, PFc, PFPa, Pb, Pc, P, Qa, Qb, Qc, Q, Sa, Sb,Sc, SIa, Ib, Ic, In, Iavg

    Ua, Ub, Uc, Uab, Ubc, Uca, UL-L avg, UL-N avg

    Frequency

    Demand & Max. demand

    Multi-tariff energy

    Real time metering

    Harmonic (31st )

    Energy

    Power factor

    Power

    Current

    Over/ under limit alarmSetpoint alarm

    Voltage

    Basic Function

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V

    Direct: 600Vph-ph

    PT primary: 0~999.9kVPT secondary: 100Vph-ph or 110V

    Current 0.2% 0.001ACT primary: 0~49,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/var/ VAeach phase: 0~49994MW/ Mvar/ MVA

    Total: 0~149982MW/ Mvar/ MVA

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 45~ 65 Hz

    Active energy 0.5% 0.1kWh 0~ 99,999,999.9 kWh

    Reactive energy 2.0% 0.1kvarh 0~ 99,999,999.9 kvarh

    THD 1.0% 0.001 0~100.0%

    Individual harmonic 1.0% 0.001 0~100.0%

    Un-balance 1.0% 0.001 0~100.0%

    6

  • PST700 Multifunction Power Meter

    Technical Specification

    50MInsulation resistance

    Pulse output value: 1000~9999imp/ kWh Pulse width: 60~100ms programmable

    Pulse output

    AC 2KV/minutePower frequency withstand voltage

    4kV (peak), 1.2/50uSImpulse withstand voltage

    Metering True RMS, 1 sec refresh time

    Input Rate current: 1A or 5ARate voltage: direct 120 ~277Vph-N, (optional)PT secondary: 100Vph-ph or 110V, (optional)

    Frequency: 50/ 60Hz

    Overload 120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Status input Wet contact, external power supply

    Relay output Node capacity: 250VAC/5A

    Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 3Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

    Dimension & InstallationUnit: mm

    Basic unit: approx 400gr.Weight

    Power supply 86 ~265VAC99~374VDC

    Power loss 2VA

    Communication RS485 serial, support Modbus-RTUBaud rate: 2400, 4800, 9600, 19200, 38400bpsAddress: 1~247

    Dimension(L x W x H)

    Panel: 96 x 96 x 13.5 mmCut-out: 90 x 90 x 45.1 mm (basic)90 x 90 x 66.6 mm (optional module)

    IP index IP52 (front panel) and IP30 (case)

    Environment Operating temperature: -10~ +55 Storage temperature: -40~ +70 Humidity: 5%~95% non-condensing

    Order InformationBasic unit: PST700Note: 1: Current input 5A (optional 1A)

    2: Voltage input: 0~600V.3. Default PT secondary 100Vph-ph. (optional 110V)

    Optional module

    PAIAO

    Profibus communication (under development)2 analog input (under development)2 analog output (under development)

    2 status input, 2 relay outputThe 2nd RS4852 pulse output

    SRC

    Ep

    Note: 1. Max. 3 modules for 1 meter.

    2. Module A can be repeatedly chosen for 1 meter, others can not be repeatedly chosen.

    7

  • Feature Suit for 220V or 240V low voltage system. Simultaneous sampling of Volts and Amps Compact design with all real-time measurement 10 years back-up of integrated energy data LED display, high brightness, auto-scrolling CT ratio programmable Pluggable terminals, easy to install and maintain Panel size: 110 x 65mm Standard: IEC62053-21, CE

    Technical SpecificationMetering True RMS, 1 sec refresh time

    Input Rate current: 5A (optional 1A)Rate voltage: 220V (optional 240V)Frequency: 50 or 60Hz

    Overload 120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Status input 2 channels, external power supply

    Relay output 1 channel, Node capacity: 220VAC/5A, 30VDC/5A

    Power supply 85~265VAC, 80~300VDC

    Power loss 3VA

    Communication RS485 serial, support Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Environment

    Operating temperature: -20~ +60

    Storage temperature: -30~ +70

    Humidity: 5%~95% non-condensing

    Dimension(L x W x H)

    Panel: 110 x 65 x 18 mmCut-out: 90 x 44.5 x 55 mm (+0.5mm)

    IP index IP54 (front panel) and IP20 (case)

    Weight Approx 220gr.

    Power frequency withstand voltage AC 2KV/minute

    Insulation resistance 50M

    Impulse withstand voltage 4kV (peak), 1.2/50uS

    Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

    Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 3Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    PMAC615 Single Phase Digital Panel Meter

    Note: Reactive power and power factor can be read via RS485 COM only

    One RS485

    One relay output

    Two status input (wet contact)

    COM

    DO

    DI

    Optional FunctionMeasuring RangeResolutionAccuracyParameter

    0-99,999,999.9 kWh

    45 ~ 65Hz

    -1.000 ~ +1.000

    0 ~30MW/ Var0 ~ 50,000A

    0 ~ 500Vph-ph

    0.1kWh

    0.01Hz

    0.001

    0.1 MW/ var

    0.001A

    0.01V

    1.0%

    0.01

    0.5%

    0.5%

    0.2%

    0.2%

    Active energy

    Real time metering

    Frequency

    Power factor

    Power

    Current

    Voltage

    Basic Function

    Order Information

    W

    Z

    Voltage + Current + Active Energy

    Voltage + Current + Active Power + Reactive Power + Power Factor + Frequency + Active Energy

    SRCC

    Two External Status Input ( wet contact)One Relay Output + One RS485 COMOne RS485 COM

    PMAC615----

    8

  • Feature Suit for 220V, or 240V (ph-N) low voltage system Simultaneous sampling of Volts and Amps Compact design with all real-time measurement 10 years back-up of integrated energy data LED display, high brightness, auto-scrolling CT primary is programmable Pluggable terminals, easy to install Panel size: 96 x 96mm Password protect Standard: IEC62053-21, CE

    Basic FunctionPMAC625 measures and display one or more parameters listed below:

    VoltageUa, Ub, Uc, Uab, Ubc, Uca, CurrentIa, Ib, Ic, In Active power Pa, Pb, Pc, P Reactive power Qa, Qb, Qc, Q Power factorPFa, PFb, PFc, PF Frequency--F Active energykWh Reactive energy-- kvarh

    Optional Function Two status input ( wet contact) Two relay alarm output One RS485 communication

    Technical Specification

    Metering True RMS, 1 sec refresh time

    Input Rate current: 5A (optional 1A) Rate voltage: 220Vph-N (optional 240V)Frequency: 50/ 60Hz

    Overload 120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Status input 2 channels, external power supply

    Relay output 2 channels, Node capacity: 220VAC/5A, 30VDC/5A

    Power supply 85~265VAC, 80~300VDC

    Power loss 2VA

    Communication RS485 serial, support Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Approx. 350gr.Weight

    Dimension(L x W x H)

    Panel: 96 x 96 x 18 mmCut-out: 89.5 x 89.5 x 65 mm (+0.5mm)

    IP index IP54 (front panel) and IP20 (case)

    Environment Operating temperature: -20~ +60 Storage temperature: -30~ +70 Humidity: 5%~95% non-condensing

    Power frequency withstand voltage AC 2KV/minute

    Insulation resistance 50M

    Impulse withstand voltage 4kV (peak), 1.2/50uS

    Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

    Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 3Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    PMAC625 Three-phase Digital Panel Meter

    9

  • Dimension & Installation

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V 264V(ph-N), 500V (ph-ph)

    Current 0.2% 0.001CT primary: 0~9,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/ var 9,999 kW/ kvar

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 35-65Hz

    Active energy 1.0% 0.1kWh 0-99,999,999.9 kWh

    Reactive energy 2.0% 0.1kvarh 0-99,999,999.9 kvarh

    Order Information

    PMAC625 Three-phase Digital Power Meter

    W

    Z

    Voltage + Current + Active Power + Reactive Power + Power Factor + Active Energy

    Voltage + Current + Active Power + Reactive Power + Power Factor + Frequency + Active Energy + Reactive Energy

    SRC

    Two External Status Input ( wet contact)Two Relay Alarm OutputOne RS485 COM

    PMAC625---

    Note: PMAC625 default rated voltage/ current is 220V/ 5A. Other customized input such as 240V or 1A is available, please mention the requirement before place order.

    Example: Model No. PMAC625-W-C, which indicates the device measures voltage, current, active power, reactive power, power factor, active energy, and provide RS485 communication

    Unit: mm

    10

  • Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Consist of basic unit and optional modules 10 years back-up of integrated energy data Large LCD, high brightness High accuracy, V or I is 0.2%, kWh is class 1 CT and PT programmable Panel size: 96 x 96mm Password protect Standard: IEC62053-21/ 23, CE

    Basic FunctionPMAC720 provides one RS485 communication,

    measures and display real-time parameters:

    VoltageUa, Ub, Uc, Uab, Ubc, Uca, CurrentIa, Ib, Ic, In Active power Pa, Pb, Pc, P Reactive power Qa, Qb, Qc, Q Power factorPFa, PFb, PFc, PF Frequency--F Active energykWh Reactive energy kvarh Optional Module

    4 status input (dry contact) + 4 relay output 8 status input (dry contact) + 2 relay output 4 status input (wet contact) + 4 relay output 8 status input (wet contact) + 2 pulse output 2 pulse output + 2 analog outputStatus input apply to monitoring various kinds of switch status

    Relay output apply to monitoring over limit alarm with setpoint system

    Pulse output apply to exporting pulse signal for active/ reactive energy

    Technical Specification

    Optional Function Up to 31st harmonic analysis Clock and SOE (event log) TOU (multi-tariff) Two RS485 communication port One 4~20mA analog input One 4~20mA analog output

    Basic unit Optional module

    Metering True RMS, 1 sec refresh time

    Input Rate current: 5A (optional 1A)Rate voltage: direct 120 ~277Vph-N, (optional)

    PT secondary 57.7V/ 100V Frequency: 50/ 60Hz

    Overload 120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Status input (optional)

    8 channels, provides 30VDC power if it is dry contact

    Relay output (optional)

    4 channels, Node capacity: 220VAC/5A, 30VDC/5A

    Analog output (optional)

    2 channels, 4~20mA, load resistance: 400

    Pulse output (optional)

    2 channels,48~50VDC for external connection

    Power supply 85~265VAC, 80~300VDC

    Power loss 2VA

    Communication RS485 serial, support Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Dimension(L x W x H)

    Panel: 96 x 96 x 16 mmCut-out: 89.5 x 89.5 x 55 mm (+0.5mm)

    IP index IP54 (front panel) and IP20 (case)

    Weight Approx. 500gr.

    Power frequency withstand voltage AC 2KV/minute

    Insulation resistance 50M

    Impulse withstand voltage 4kV (peak), 1.2/50uS

    PMAC720 Multifunction Power Meter

    11

  • Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2 Edition 2.0 (2008)RF immunity test IEC 61000-4-3 Edition 3.0 (2007)Electrical fast transient/burst immunity test IEC 61000-4-4 Edition 2.0 (2004)Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5 Edition 2.0 (2005) Conducted emissions EN 61326-1:2006, CISPR 11:2004Radiated emissions EN 61326-1:2006, CISPR 11:2004

    Environment

    Operating temperature: -20~ +60 Storage temperature: -30~ +70 Humidity: 5%~95% non-condensing

    PMAC720 Multifunction Power Meter

    One 4~20mA analog outputAOOne 4~20mA analog inputAI

    PMAC-Feature

    720N 720A 720B 720C 720D 720E

    U-LL, U-LN, 3I, In, 3P, P, 3Q, Q,F, 3PF, PF, kWh, kvarh,

    RS485 communication

    4 status input (dry contact) + 4 relay output 8 status input (dry contact) + 2 relay output 4 status input (wet contact) + 4 relay output 8 status input (wet contact) + 2 relay output 2 pulse output + 2 analog output (4~20mA)

    H Up to 31st harmonic analysis T Clock and SOE (event log) function F TOU ( time-of-use) M Two RS485 communication ports

    Apparent power Demand function Remark: = standard feature, =optional function = conditional function1. If select -F, -T should be selected also.2. Analog port-AI and AO are incompatible feature, can not be selected together3. For module PMAC720N-, PMAC720E- , the SOE function is invalid.

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V

    Directly: 300Vph-N, 520Vph-ph

    PT primary: 0~599,999VPT secondary: 57.7Vph-N, 100Vph-ph

    Current 0.2% 0.001ACT primary: 0~49,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/ vareach phase: 0~100 MW/ Mvar

    Total: 0~300 MW/ Mvar

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 45~ 65 Hz

    Active energy 1.0% 0.1kWh 0~ 99,999,999.9 kWh

    Reactive energy 2.0% 0.1kvarh 0~ 99,999,999.9 kVarh

    Individual harmonic 1.0% 0.001 0~100.0%

    Un-balance 1.0% 0.001 0~100.0%

    12

  • Dimension & Installation

    Order Information

    NABCDE

    Basic ModuleBasic Module + 4 Status Inputs (Dry Contact) + 4 Relay Outputs Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Outputs Basic Module + 4 Status Inputs (Wet Contact) + 4 Relay OutputsBasic Module + 8 Status Inputs (Wet Contact) + 2 Relay Outputs Basic Module + 2 Pulse Outputs + 2 Analog Outputs (4-20mA)

    HTFM

    Up to 31st Harmonic AnalysisClock and SOE (Event Log) FunctionTOU (Time- of- Use)Two RS485 Communication Ports

    AIAO

    One 4-20mA Analog InputOne 4-20mA Analog Output

    V1V2V3V4V5V6V7

    57.7/ 100V (via PT), 5A57.7/ 100V (via PT), 1A220/ 380V (direct), 5A220/ 380V (direct), 1A120/ 208V (direct), 5A240/ 415V (direct), 5A277/ 480V (direct), 5A

    PMAC720---- ----

    Example: Model No. PMAC720-A-H-AO-V1, which indicates the device provides basic function + 4 status input + 4 relay output + harmonic analysis + one analog output, rated input 57.7/ 100V, 5A

    unit: mm

    PMAC720 Multifunction Power Meter

    13

  • PMAC727 Multifunction Power Meter

    Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Build-in clock and event logging Phase failure alarm 10 years back-up of integrated energy data Large LCD, high brightness High accuracy, V or I is 0.2%, kWh is class 1 CT and PT programmable Pluggable terminals, easy to install Panel size: 96 x 96mm Password protect Standard: IEC62053-21/ 23, CE

    Basic FunctionPMAC727 provides one RS485 communication,

    measures and display real-time parameters:

    VoltageUa, Ub, Uc, Uab, Ubc, Uca, Voltage unbalance rate UL-L unbal, UL-N unbal CurrentIa, Ib, Ic, In Current unbalance rate I unbal Active power Pa, Pb, Pc, P, power load rate Reactive power Qa, Qb, Qc, Q Power factorPFa, PFb, PFc, PF Frequency--F Active energykWh Reactive energy kvarh 31st harmonic & THD Temperature of switch box/ cable

    Basic Data Recording Function Record data once per hour ( last 24 hours) Record the Avg/ Max./ Min. data of every day (last 31 days) Record energy consumption hourly ( last 24 hours), daily

    (last 31 days), and monthly (last 12 months)

    Record phase failure event, max. 30 events Record over-limit event, max. 200 events

    Metering True RMS, 1 sec refresh time

    Input Rate current: 1A or 5ARate voltage: direct 120 ~277Vph-N, (optional)

    PT secondary 57.7V/ 100V Frequency: 50/ 60Hz

    Overload 120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Power frequency withstand voltage AC 2KV/minute

    Insulation resistance 50M

    Impulse withstand voltage 4kV (peak), 1.2/50uS

    Approx. 500gr.Weight

    Operating temperature: -20~ +60 Storage temperature: -30~ +70 Humidity: 5%~95% non-condensing

    Environment

    Power supply 85~265VAC, 80~300VDC

    Power loss 2VA

    Communication RS485 serial, support Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Dimension(L x W x H)

    Panel: 96 x 96 x 18 mmCut-out: 89.5 x 89.5 x 65 mm (+0.5mm)

    IP index IP54 (front panel) and IP20 (case)

    Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 3Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

    Technical Specification

    14

  • 0~100.0%0.0011.0%THD

    0~100.0%0.0011.0%Un-balance

    0~1501 1Temperature

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V

    Directly: 300Vph-N, 520Vph-ph

    PT primary: 0~499,999VPT secondary: 57.7Vph-N, 100Vph-ph

    Current 0.2% 0.001ACT primary: 0~49,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/ var each phase: 0~100 MW/ Mvar

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 35~ 65 Hz

    Active energy 1.0% 0.1kWh 0~ 99,999,999.9 kWh

    Reactive energy 2.0% 0.1kvarh 0~ 99,999,999.9 kVarh

    Individual harmonic 1.0% 0.001 0~100.0%

    PMAC727 Multifunction Power Meter

    Fundamental RMS voltage

    Harmonic Ratio for Voltage (3-31st)

    Total Harmonic Distortion for Voltage (THDu)

    Total Harmonic Distortion for Current (THDi)Harmonic Ratio for Current (3-31st)Fundamental RMS current

    Frequency

    and daily (last 31 days),monthly (last 12 months)

    Active energy kWh (present & total)Reactive energy kvarh (present & total)

    Power factorPFa, PFb, PFc, PFReactive power Qa, Qb, Qc, QLoad rateActive power Pa, Pb, Pc, P

    I unbal

    CurrentIa, Ib, Ic, InUL-L unbal, UL-N unbalVoltageUa, Ub, Uc, Uab, Ubc, Uca,

    Model PMAC727 Data Record Function

    Measuring Parameters Record data per hour (last 24 hours)

    Record Avg./ Max./ Min. data of every day (last

    31 days)Over-limit record

    15

  • PMAC727 Multifunction Power Meter

    Dimension & Installation

    Order Information

    V1V2V3V4V5V6V7

    57.7/ 100V (via PT), 5A57.7/ 100V (via PT), 1A220/ 380V (direct), 5A220/ 380V (direct), 1A120/ 208V (direct), 5A240/ 415V (direct), 5A277/ 480V (direct), 5A

    PMAC727--

    Example: Model No. PMAC727-V1, which indicates the device provides all basic function, rated input 57.7/ 100V, 5A

    unit: mm

    16

  • Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Consist of basic unit and optional modules 10 years back-up of integrated energy data Large LCD, high brightness High accuracy, V or I is 0.2%, kWh is class 1 CT and PT programmable Pluggable terminals, easy to install Panel size: 96 x 96mm Password protect Standard: IEC62053-21/23, CE

    Basic FunctionPMAC735 provide one RS485 communication,

    measures and display real-time parameters:

    VoltageUa, Ub, Uc, Uab, Ubc, Uca, Voltage unbalance rate UL-L unbal, UL-N unbal CurrentIa, Ib, Ic, In Current unbalance rate I unbal Active power Pa, Pb, Pc, P Reactive power Qa, Qb, Qc, Q Apparent powerSa, Sb,Sc, S Power factorPFa, PFb, PFc, PF Frequency--F Active energykWh (4 quadrant) Reactive energy kvarh (4 quadrant) Demand and Max. record for I, P, Q, S Max./ Min. value

    Optional Module 4 status input + 4 relay output 8 status input + 2 relay output 8 status input + 2 pulse output Profibus communication moduleStatus input apply to monitoring various kinds of switch status

    Relay output apply to monitoring over limit alarm with setpoint system

    Pulse output apply to exporting pulse signal for active/ reactive energy

    Profibus supports high speed bus communication up to 1.5M, and

    Compatible with SIEMENS Profibus communication system.

    2 channels, 4~20mA, load resistance: 400

    Analog output (optional)

    2 channels,48~50VDC for external connection

    Pulse output (optional)

    4 channels, Node capacity: 220VAC/5A, 30VDC/5A

    8 channels, provides 30VDC power if it is dry contact

    120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Rate current: 1A or 5ARate voltage: direct 120 ~277Vph-N, (optional)

    PT secondary 57.7/ 100V Frequency: 50/ 60Hz

    True RMS, 1 sec refresh time

    Overload

    Input

    Relay output (optional)

    Status input (optional)

    Metering

    85~265VAC, 80~300VDCPower supply

    2VAPower loss

    RS485 serial, support Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Communication

    Approx. 500gr.

    IP54 (front panel) and IP20 (case)

    Panel: 96 x 96 x 18 mmCut-out: 89.5 x 89.5 x 65 mm (+0.5mm)

    IP index

    Weight

    Dimension(L x W x H)

    4kV (peak), 1.2/50uS

    Impulse withstand voltage

    50MInsulation resistance

    AC 2KV/minutePower frequency withstand voltage

    Optional Function Up to 31st harmonic analysis, K factor, THD SOE (event log) One 4~20mA analog output

    PMAC735 Multifunction Power Meter

    Technical Specification

    17

  • Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 3Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    Standard (EMC) Environment

    Operating temperature: -20~ +60 Storage temperature: -30~ +70 Humidity: 5%~95% non-condensing

    SOE

    One 4-20mA analog outputRemark: = standard, =optional

    Harmonic analysis, K factor

    4 status input + 4 relay output

    8 status input + 2 pulse output

    8 status input + 2 relay output

    735P

    735E

    735B

    U-LL, U-LN, 3I, In, 3P, P, 3Q, Q, 3S, S, F, 3PF, PF, kWh, kvarh, Demand& maximum recording,Unbalance rate, Build-in clock,Max./min. recording, RS485 communication

    Profibus communication

    735A735NModel PMACFeature

    0~100.0%0.0011.0%THD

    0~100.0%0.0011.0%Un-balance

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V

    Directly: 300Vph-N, 520Vph-ph

    PT primary: 0~499,999VPT secondary: 57.7Vph-N, 100Vph-ph

    Current 0.2% 0.001ACT primary: 0~49,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/ var each phase: 0~100 MW/ Mvar

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 35~ 65 Hz

    Active energy 1.0% 0.1kWh 0~ 99,999,999.9 kWh

    Reactive energy 2.0% 0.1kvarh 0~ 99,999,999.9 kVarh

    Individual harmonic 1.0% 0.001 0~100.0%

    PMAC735 Multifunction Power Meter

    18

  • Order Information

    Example: Model No. PMAC735-A-H-V1, which indicates the device provides basic function + 4 status input + 4 relay output + harmonic analysis, rated input 57.7/ 100V, 5A

    One 4-20mA Analog Output AO

    57.7/ 100V (via PT), 5A57.7/ 100V (via PT), 1A220/ 380V (direct), 5A220/ 380V (direct), 1A120/ 208V (direct), 5A240/ 415V (direct), 5A277/ 480V (direct), 5A

    V1V2V3V4V5V6V7

    SOE (Event Log) FunctionT

    Up to 31st Harmonic Analysis, THD, K FactorH

    NABEP

    Basic ModuleBasic Module + 4 Status Inputs (Dry Contact) + 4 Relay Outputs Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Outputs Basic Module + 8 Status Inputs (Dry Contact) + 2 Pulse OutputsBasic Module + Profibus Module

    PMAC735---- ------

    Dimension & Installation

    AuxiliaryModule

    PMAC735

    unit: mm

    PMAC735 Multifunction Power Meter

    19

  • Feature Suit for LV/ HV voltage system True-RMS measuring parameters Power quality analysis, over limit alarm Integrated measure, analyze, control and protect function Use DSP chip to process voltage and current signal Graphical data, easy and clearly for reading Large and color LCD, high brightness 10 years back-up of integrated energy data High accuracy, V or I is 0.2%, kWh is class 1 Panel size: 126.7 x 126.7mm Password protect Standard: IEC62053-21/ 23, CE

    PMAC760 Intelligent Power Quality Analyzer

    U_unbl, I_unblUnbalance

    Phase angle

    USB

    Ethernet communication port, 10M, UDP/ TCP Server/ TCP Client Ethernet

    USB 2.0 communication port

    Event log and real time clockSOE and Clock

    Optional Function

    Modbus-RTU protocolRS485

    4 status input + 4 relay outputDI/ DO

    THDu, THDi, TOHDu, TOHDi, TEHDu, TEHDi2nd-31st harmonic (display), 32nd -63rd harmonic (COM)

    Voltage deviation

    Harmonic

    Frequency deviation Power quality analysis

    F

    Dmd_I, Dmd_P, Dmd_Q ,Dmd_S

    Max._U, Max._I, Max._P, Max._QMin._U, Min._I, Min._P, Min._Q

    kWh and kvarh (4 quadrant), kVAh

    PFa, PFb, PFc, PFPa, Pb, Pc, P, Qa, Qb, Qc, Q, Sa, Sb,Sc, S

    Ia, Ib, Ic, In, Iavg

    Ua, Ub, Uc, Uab, Ubc, Uca, UL-L avg, UL-N avg

    Max./ Min. value

    Demand

    Frequency

    Real time metering

    Voltage fluctuate

    Energy

    Power factor

    Power

    Current

    Over/ under limit alarmSetpoint alarm

    Voltage

    Basic Function

    20

  • 4 channels, Node capacity: 250VAC/5A, 30VDC/5A

    4 channelsDry contact (internal 30VDC power supply)

    120% of rated, continuouslyInstantaneous current: 10 times/ secInstantaneous voltage: 2 times/ sec

    Rate current: 1A or 5ARate voltage: direct 120 ~277Vph-N, (optional)

    PT secondary 57.7/ 100V Frequency: 50/ 60Hz

    True RMS, 1 sec refresh time

    Overload

    Input

    Relay output

    Status input

    Metering

    85~265VAC, 80~300VDCPower supply

    10VAPower loss

    Approx. 760gr.

    IP54 (front panel) and IP20 (case)

    Panel: 126.7 x 112.7 x 13 mmCut-out: 119 x 105 x 91 mm (+0.5mm)

    IP index

    Weight

    Dimension(L x W x H)

    Voltage wave SOE event log Harmonic Phase vector

    LCD display graphical data

    Multi-communication

    4kV (peak), 1.2/50uS

    Impulse withstand voltage

    50MInsulation resistance

    AC 2KV/minutePower frequency withstand voltage

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 3Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    Standard (EMC) Environment

    Operating temperature: -20~ +60 Storage temperature: -30~ +70 Humidity: 5%~95% non-condensing

    PMAC760 Intelligent Power Quality Analyzer

    Technical Specification

    21

  • Dimension & Installation

    SHLD

    COMSHLD

    Order Information

    57.7/ 100V (via PT), 5A57.7/ 100V (via PT), 1A220/ 380V (direct), 5A220/ 380V (direct), 1A120/ 208V (direct), 5A240/ 415V (direct), 5A277/ 480V (direct), 5A

    V1V2V3V4V5V6V7

    Ethernet port

    USB port

    N

    U

    PMAC760----

    Example: Model No. PMAC760-N-V3, which indicates the device provides basic function + Ethernet communication port, rated input 220/ 380V, 5A

    Unit: mm

    PMAC760 Intelligent Power Quality Analyzer

    0~100.0%0.0011.0%THD

    0~100.0%0.0011.0%Un-balance

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V

    Directly: 300Vph-N, 520Vph-ph

    PT primary: 0~999,999VPT secondary: 57.7Vph-N, 100Vph-ph

    Current 0.2% 0.001ACT primary: 0~49,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/ var each phase: 0~100 MW/ Mvar

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 45~ 65 Hz

    Active energy 1.0% 0.1kWh 0~ 99,999,999.9 kWh

    Reactive energy 2.0% 0.1kvarh 0~ 99,999,999.9 kVarh

    Individual harmonic 1.0% 0.001 0~100.0%

    22

  • PMAC901 Single Phase Din-rail Energy MeterPMAC903 Three Phase Din-rail Energy Meter

    Basic Function Measure and display kWh value One RS485 communication Support Modbus-RTU Other real time data via RS485: V, I, P, Q, S, PF, F

    Feature Suit for 220V AC low voltage system 6 +1 digits LCD display (999999.9 kWh) kWh accuracy class 0.5S LED indicates pulse, reverse energy 3 keys for programming CT programmable, pulse output 35mm DIN rail installing, standard DIN ED5002 High temperature resistant materials Spring type buckle, easy to install Standard: IEC62053-21/ 22/23, CE, KEMA

    Optional Function Multi-tariff Reactive energy measuring Demand analysis

    ParameterAccuracy

    Resolution Measuring RangePMAC901 PMAC903

    Voltage 0.2% 0.2% 0.01V 198V~242V (L-N)

    Current 0.2% 0.2% 0.001A 0.5~4995A

    Active power 0.5% 0.5% 0.1W 0~1MW

    Reactive power No 1.0% 0.1Var 0~1Mvar

    Apparent power 0.5% 0.5% 0.1VA 0~1MvA

    Power factor No 0.5% 0.001 -1.000~+1.000

    Frequency No 0.01 0.01Hz 45Hz~65Hz

    Active energy Class 0.5S Class 0.5S 0.1kWh 0~999999.9 kWh

    Reactive energy No Class 2 0.1kVarh 0~999999.9 kvarh

    2VAInput consumption

    AC 220Vph-N, 50Hz (optional 120V, 60Hz)Rated voltage

    Rated current 10(40)A, 10(60)A, 20(100)A or 5A/ CT

    Overload 115% of rated

    Pulse output 1 or 2 channels

    Pulse output value PMAC901:1000imp/kWhPMAC903: 400imp/ kWh (40A or 60A)

    200imp/ kWh (100A)3600imp/ kWh (5A/ CT)

    PMAC901: 1-phase 2-wirePMAC903: 3-phase 4-wire

    Connection mode

    Operating temperature: -20~ +55 Storage temperature: -20~ +55 Humidity: 5%~95% non-condensing

    Environment

    RS485 serial, Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Communication

    Self supply, 220VAC, 50-60HzPower supply

    80 msImpulse duration

    Com

    mun

    icat

    ion

    data

    Dis

    play

    da

    ta

    Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 4Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

    Technical Specification

    23

  • Dimension

    Order Information

    TOU (Multi-tariff)Reactive energy measuring (only available for PMAC903)Demand analysis (only available for PMAC903)

    FQD

    Rated current: 10 (40)ARated current: 10 (60)ARated current: 20 (100)ARated current: 5A / CT (when In>100A, connect via CT)

    4060

    1005

    C One RS485 communication

    10.5S

    Active energy accuracy: Class 1Active energy accuracy: Class 0.5S

    PMAC901---- ----PMAC903---- ----

    Note: PMAC901, 903 default rated voltage 220V, frequency 50Hz. Other customized input such as120V or 60Hz is available, please mention the requirement before place order.

    Example 1: Model No. PMAC901-C-1-40-F, which indicates the device provides basic function, rated current is 40A (direct), accuracy class 1, and measure multi-tariffExample 2: Model No. PMAC903-C-1-5-Q, which indicates the device provides basic function, rated current is 5A/ CT, accuracy class 1, and measure reactive energy

    PMAC903PMAC901

    75.0mm

    94.0mm

    45.0mm

    50.0mm65.0mm

    35.7mm R PMAC903

    125.5mm

    94.0mm

    35.7mm

    45.0mm

    50.0mm65.0mm

    PMAC901 Single Phase Din-rail Energy MeterPMAC903 Three Phase Din-rail Energy Meter

    24

  • PMAC905 Multifunction Energy Meter

    Feature Suit for LV/ HV voltage system CT and PT programmable kWh accuracy class 0.5S Password protect Panel size: 96 x 96mm Pluggable terminals, easy to install Large high-contrast LCD Two pulse output Standard: IEC62053-22/ 23, CE, KEMA

    Basic FunctionPMAC905 measure and display real-time parameters:

    VoltageUa, Ub, Uc, Uab, Ubc, Uca, CurrentIa, Ib, Ic, In Active power Pa, Pb, Pc, P Reactive power Qa, Qb, Qc, Q Apparent powerSa, Sb,Sc, S Power factorPFa, PFb, PFc, PF Frequency--F EnergykWh, kvarh (4 quadrant)

    Optional Function Statistics of multi-tariff energy: 8 periods of time, 4 different tariff Record historical energy value: (kWh & kvarh) data of last 31 days/ 12

    months

    One RS485 communication (Modbus)

    PT primary: 0~499,999VPT secondary: 57.7Vph-N, 100Vph-ph

    Parameter Accuracy Resolution Measuring Range

    Voltage 0.2% 0.01V

    Directly: 300Vph-N, 520Vph-ph

    Current 0.2% 0.001ACT primary: 0~49,999ACT secondary: 1 A or 5A

    Power 0.5% 0.1W/ Var/ VA 0~100 MW/ MVar/ MVA

    Power factor 0.5% 0.001 -1.000~+1.000

    Frequency 0.01 0.01Hz 35Hz~65Hz

    Active energy Class 0.5S 0.1kWh 0~999999.9 kWh

    Reactive energy Class 2 0.1kVarh 0~999999.9 kvarh

    3-phase 3-wire, 3-phase 4-wireConnection mode

    1A or 5ARated current

    yesCT earth connection (secondary)

    50/ 60HzFrequency

    direct 120 ~277Vph-N, (optional) PT secondary 57.7/ 100V

    Rated voltage

    Power consumption 3VA

    Overload 120% of rated

    Operating temperature: -20~ +60 Storage temperature: -30~ +70 Humidity: 5%~95% non-condensing

    Environment

    50msImpulse duration (width)

    1000~9900 imp/kWh programmablePulse output value

    2 channelsPulse output

    RS485 serial, Modbus-RTUBaud rate: 4800 or 9600bpsAddress: 1~247

    Communication

    85 to 265VAC or 100 to 300VDCPower supply

    Technical Specification

    Surge immunity test (1, 2/50s8/20s) IEC 61000-4-5,Level 4Conducted emissions EN 55022,Class BRadiated emissions EN 55022,Class B

    Standard (EMC)

    Electrostatic discharge immunity test IEC 61000-4-2,Level 4Radiated immunity test IEC 61000-4-3,Level 3Electrical fast transient/burst immunity test IEC 61000-4-4,Level 4

    25

  • 57.7/ 100V (via PT), 5A57.7/ 100V (via PT), 1A220/ 380V (direct), 5A220/ 380V (direct), 1A120/ 208V (direct), 5A240/ 415V (direct), 5A277/ 480V (direct), 5A

    V1V2V3V4V5V6V7

    One RS485 communicationC

    F Statistics of multi-tariff energy

    D Record historical energy value

    PMAC905---- ----

    96mm

    96mm

    89.5

    56.5

    9.0 46.7 18.390mm

    90mm

    Note: Other customized input such as 110V or 1A is available, please mention the requirement before place order.

    Example: Model No. PMAC905-F-D-V3 , which indicates the device provides basic function, auxiliary statistics and record function. Rated input is 220V/380V, 5A.

    PMAC905 Multifunction Energy Meter

    Order Information

    Dimension & Installation

    Unit: mm

    26

  • PMAC915 Three Phase Multi-tariff kWh Meter

    Feature

    LCD display With the DSP technology and the real-time high speed calculation, it guarantees the

    measuring accuracy in the case of big load wave and harmonic waves.

    2MB large data storage, can be extended to 4MB Keep high accuracy from 1% In to 600% In Three phase power source supply, but even there is only one phase work, the meter

    will keep running.

    Read the meter at power failure, can still read the meter by the button or with infrared function

    310(40)A, 320(80)A, 330(100)A

    3220/380V

    Class 2

    Direct connect

    CT connect

    Direct connect

    PT connect:

    Reactive energy

    Active energy

    -40C to +70CStorage

    -20C to +60COperating temperature

  • Dimension & Installation

    5104 h MTBF15 YearsService life

    IEC62052-11/21IEC62053-21/22/23IEC62056-21/ 42/ 53/ 61/ 62

    Standard

    Approx. 1.8 kgNet weight

    290mm x 170mm x85mmDimension

    0.5s /d (23C)Clock error

    0.001 InStart current

    50Hz 5%Reference frequency

    0.7Un ~1.3UnVoltage range

    85%Relative humidity

    Unit: mm

    PMAC915 Three Phase Multi-tariff kWh Meter

    28

  • PMAC921 Single Phase Multi-tariff kWh Meter

    Feature

    LCD display Measure active energy, no need to calibrate for a long working time LSI design, less spare part, low power consumption, simple structure. Keep a good linear error within the range 1%Ib~Imax. Use quality component with long service life, reliable accuracy, cannot be affected by

    the frequency, temperature, voltage, harmonic.

    Function

    Measure reverse and forward energy, and reverse energy is measured as forward energy Timely single phase power consumption measurement with 3 tariffs and 12 time periods Automatically read and store the energy, it can store 12 months data Real time Clock RS485 communication port realize remote meter concentrative reading. Infrared communication port to realize point to point communication. Waking up the meter by pressing the key and meter reading function during power off.

    -40C to +70CStorage

    -25C to +55COperating temperature

  • PILOT reserves the right to modify features without prior notice in view of continued improvement

    Zhuhai Pilot Technology Co., Ltd.Add: No. 15, Keji 6 Road, Chuangxin Haian, Tangjia Hi-tech Zone, Zhuhai, Guangdong, China Post Code: 519085Tel: +86 756 3629687/ 3629673 Fax: +86 756 3629600/ 3629700 Email: [email protected] http://www.pmac.com.cn

    Your representative