44
Page 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy ® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT CONTROLLER USED WITH ENERGENCE ® AND STRATEGOS ® ROOFTOP UNITS (Supports DB1 v1.14; M2 v7.13) Description The Prodigy ® M2 unit controller: ʼn provides control functions for Energence ® rooftop unit, ʼn includes a user interface consisting of a dot matrix display, navigation arrow buttons, a select button, and a USB port, ʼn provides status and diagnostic information for troubleshooting, ʼn allows adjustment of time delays and setpoints that enable advanced features, ʼn is controlled by a standard room thermostat, direct digital controller (DDC), or a zone sensor, ʼn can be configured as a device on the network when daisy-chained to the L Connection ® Network, ʼn may be connected to a PC which has been loaded with Unit Controller software, ʼn accepts add-on boards to build variations according to application or equipment type. ʼn USB verification and profile sharing. Website For all available Prodigy ® documentation, see the Lennox Commercial website (www.lennoxcommercial.com). Table Of Contents USB Firmware Update 2 .............................. M2 unit controller, expansion board locations, SmartWireœ connections 3 ........................ M2 unit controller LED operation indications 4 ............ Startup 4 ............................................ Menu interface 6 ..................................... Operation: DISPLAY 7 ...................................... GUIDED SETUP 9 ............................... SERVICE 11 ...................................... TEST 12 ......................................... DATA 13 ......................................... SETTINGS 15 .................................... INSTALL NEW M2 22 .............................. Blower Operation with Occupancy and CEC Title 24 23 ..... Economizer (Damper) 24 ............................... APPENDIX: Abbreviations 27 .................................. Parts List 27 ...................................... USB Service Report Example 28 .................... Alarm Codes 31 ................................... Wiring Diagrams 35 ................................ M2 unit controller signal reference diagram 41 ......... M2 unit controller board connections diagram 42 ....... QUICK START GUIDE (BACK COVER) 43 ............

Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 1

506215-01 3/2014Supersedes2/2013 Litho U.S.A.

Prodigy®

M2 Unit Controller

INSTALLATION & SETUP GUIDE FOR THE M2 UNIT CONTROLLERUSED WITH ENERGENCE® AND STRATEGOS® ROOFTOP UNITS

(Supports DB1 v1.14; M2 v7.13)

Description

The Prodigy® M2 unit controller:

� provides control functions for Energence® rooftop unit,� includes a user interface consisting of a dot matrix

display, navigation arrow buttons, a select button, and aUSB port,

� provides status and diagnostic information fortroubleshooting,

� allows adjustment of time delays and setpoints thatenable advanced features,

� is controlled by a standard room thermostat, direct digitalcontroller (DDC), or a zone sensor,

� can be configured as a device on the network whendaisy-chained to the L Connection® Network,

� may be connected to a PC which has been loaded withUnit Controller software,

� accepts add-on boards to build variations according toapplication or equipment type.

� USB verification and profile sharing.

Website

For all available Prodigy® documentation, see the LennoxCommercial website (www.lennoxcommercial.com).

Table Of Contents

USB Firmware Update 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .M2 unit controller, expansion board locations,

SmartWire� connections 3. . . . . . . . . . . . . . . . . . . . . . . .M2 unit controller LED operation indications 4. . . . . . . . . . . .Startup 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Menu interface 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Operation:

DISPLAY 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GUIDED SETUP 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SERVICE 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TEST 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DATA 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .SETTINGS 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .INSTALL NEW M2 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Blower Operation with Occupancy and CEC Title 24 23. . . . .Economizer (Damper) 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .APPENDIX:

Abbreviations 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Parts List 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .USB Service Report Example 28. . . . . . . . . . . . . . . . . . . .Alarm Codes 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Wiring Diagrams 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .M2 unit controller signal reference diagram 41. . . . . . . . .M2 unit controller board connections diagram 42. . . . . . .QUICK START GUIDE (BACK COVER) 43. . . . . . . . . . . .

Page 2: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 2

M2 (A55) unit controller - location, controls, inputs/outputs

USB Firmware update

Prodigy USB Flash Drive Update Capability

USB firmware updating is only available on Prodigy Display,(DB), firmware versions v1.09.xx and later. To read thedisplay firmware version, navigate to menu DATA >FACTORY > READ DB SOFTWARE VERSION. Check thefollowing table to determine if your display board firmwareversion supports USB Flash Drive updating:

Display (DB)version

Flash Drive Updating Supported?

Display board M2 Main Board

1.08.xx and earlier NO NO

1.09.xx D and later NO YES

1.09.xx H and later YES YES

To determine if the M2 Main Board supports firmwareupdates through the Prodigy Display's USB port, navigate tomenu DATA > FACTORY > READ M2 SOFTWAREVERSION. Check the following table to determine if your M2board firmware version supports USB Flash Drive updating:

M2 versionFlash Drive UpdatingSupported M2 Board?

7.0x.xx (no suffix) NO

7.0x.xx S NO

7.0x.xx U and later YES

Auto-update

The firmware on the Prodigy (M2) controller or on the displayboard (DB1) can be auto-updated by inserting a USB stickwith new firmware version in the USB slot while the M2 boardis operating.

DB1 FIRMWARE NOTE: The menus described in thefollowing will only be available for v1.09.xx H and laterversions of the DB1 firmware.

Upon USB insertion, the display will change to “USB”. Pressselect button and then scroll down to FIRMWARE UPDATEand press the select button. “CHECKING FILE” will displayfirst; then “UPDATING”, followed by “NN%”.

Page 3: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 3

Page 3

It will take a few minutes to update the M2 board with the newfirmware. After reaching 100%, M2 UPDATE COMPLETEwill display first; then it will check and update DB1 board.Upon completion, the boards will reset and restart.

Manual update

The firmware on the Prodigy (M2) controller or on the displayboard (DB1) can be manually updated by inserting a USBstick which may contain more than one firmware version inthe USB slot.

Files needed for update

Files needed to upgrade Prodigy controller from USB stick:

1) For DB1: DBxxxxxx.BIN2) For M2: M2xxxx.SL1

The “xxx” here are place holders for version numberinformation in the actual file names, and varies from oneversion to the next.

The DB1 upgrade file has a BIN file extension, and must belocated in the root folder of the thumb drive. No more than 10

files should be in the root folder of the thumb drive. If locatedanywhere else the Prodigy will not find the DB1 file.

The M2 upgrade file has an SL1 file extension, and must belocated in the \firmware\m2 folder of the thumb drive. Iflocated anywhere else the Prodigy will not find the M2 file.

DB1 FIRMWARE NOTE: The menus described in thefollowing will only be available for v1.09.xx H and laterversions of the DB1 firmware.

After inserting the USB stick, navigate to SERVICE >SOFTWARE RECOVERY > UPDATE M2 SOFTWARE (orUPDATE DB1 SOFTWARE). Press the select button, thenuse the up/down arrows to select a firmware version. Pressselect; “CHECKING FILE” will display first; then“UPDATING”, followed by “NN%”.

It will take a few minutes to update the board with the newfirmware. After reaching 100%, M2 (or DB1) UPDATECOMPLETE will display first; then it will reset and restart theboard.

Repeat this procedure, if desired, for the other board. Youmay remove the USB anytime after the RESTART begins.

M2 unit controller board, expansion board locations, SmartWire� connections

Figure 1 shows the controller components and the locations for expansion boards.

EXPANSIONPORT

EXPANSIONPORT

CONTROLBOARD

CONTROLBOARD

L CONNECTION(optional connec­

tion method for UnitController software)

USB CONNECTION(for Unit Controller

software)

OR

BACnet orLonTalk

SmartWireconnections

To disconnectTSTAT.COM fromCOM cut jumper.

To disconnectHMD.COM fromCOM cut jumper.

AENTH

B

Figure 1. M2 unit controller board and expansion boards

Page 4: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 4

M2 unit controller LED indicators

Some indicators on the circuit board are visible with the cover in place; others are not. The indicators and their meanings aredescribed in table 1.

Table 1. LED operation indicationsLED Status Indication Meaning

Heartbeat GREEN SLOW FLASH NORMAL OPERATION

GREEN FAST FLASH CHECK 24V, UPDATE FIRM­WARE, OR REPLACE BOARD

UNLIT STEADY OFF NO VOLTAGE TO M2 BOARDOR DEFECTIVE BOARD

GREEN STEADY ON DEFECTIVE BOARD (REPLACE)

OAS(Note: LED is

not present in

the newer M2

hardware.

GREEN STEADY ON OUTSIDE AIR IS SUITABLE

GREEN FLASHINGIAQ MODE OR MECHANICALCOOLING DURING FREE COOL­ING

PCConnection

LOCAL(YELLOW)

FLICKERING ONCOMMUNICATION TO PC USBCONNECTOR

NETWORK(GREEN)

FLICKERING ON NETWORK COMMUNICATION

S-BUS BUS (GREEN) FLICKERING ON NETWORK TRAFFIC PRESENT

TX (YELLOW) FLICKERING ON M2 IS TRANSMITTING

BACnet(option)

RX (GREEN) FLICKERING ON M2 IS RECEIVING

TX (YELLOW) FLICKERING ON M2 IS TRANSMITTING

LED Status Indication Meaning

LonTalk(option)

RX (GREEN) FLICKERING ON M2 IS RECEIVING

TX (YELLOW) FLICKERING ON M2 IS TRANSMITTING

SERVICE(RED)

FLASHING 1 SEC.ON; 1 SEC. OFF

NODE IS NOT CONFIGURED;APPLICATION LOADED

SERVICE(UNLIT)

STEADY OFFNODE IS COMPLETELY CON­FIGURED

SERVICE(RED)

CONSTANT ONNODE IS CONFIGURED; NO AP­PLICATION LOADED

SERVICE(RED)

QUICK FLASHESDURINGINITIALIZATION

MESSAGES BEING PASSED TOM2; NORMAL OPERATION

ThermostatInput

YELLOW INDICATES ATHERMOSTATDEMAND

G- BLOWER ONW1- 1ST STAGE HEATW2- 2ND STAGE HEATY1- 1ST STAGE COOLY2- 2ND STAGE COOLOCP- OCCUPIED

Thermostat LEDs indicate only with incoming thermostat connection visSmartWire� connector.

Slow Flash = 1 sec on; 1 sec off.

Fast Flash = 1 msec on; 1 msec off.

A “flickering” LED flashes significantly faster than a “fast flash“.

NOTE - LEDs are energized by 24 vac thermostat inputs.

Startup

Connections between RTU & M2 unit controller

The M2 unit controller connects to the rooftop unit usingSmartWire� connectors. Each connector is “keyed” so thatno connector can be installed in the wrong location. Be sureall connectors are in place and completely inserted (seefigure 1).

Sensor Common Isolation

Thermostat (TSTAT) and humidity (HUM) sensor commonsmay be isolated if they are powered remotely. Slide switch toOPEN to isolate (see figure 1).

USB interface usage

The USB port is used for verifying service, downloadingreports, transferring unit profiles and performing firmwareupdates. Onsite data collection requires use of a USB flashdrive. Data written to the drive includes date, time, serialnumber, catalog number, basic data, error code buffer, andunit configuration.

PC interface

The PC interface is used with unit controller software tochange programming. The M2 interface uses a USB A to Bmale cable. You may also use a 9 pin/RS485 connection tothe phone jack or S-BUS connector. A list of serviceconnection kits is on Page 27.

SmartWire� Field Wiring Connections

The SmartWire� connectors, P297, P298 and P299, allow

for easy field wiring connection points.

2-amp fuse or wire jumper

The 24VAC supply outputs, (R), on these connectors arerouted through the 2-amp fuse, F1, on earlier boards or awire jumper on later boards.

TSTAT COM switch (earlier boards) OR TSTAT COM wire jumpers (later boards)

TSTAT COM is located to the left of P297. This switch wouldbe set to the LEFT or the wire jumpers would be cut only inunique situations where the device supplying the thermostatsignals to the Prodigy® controller has its own power sourceand does not share a common reference voltage with theProdigy controller. Otherwise the switch needs to be set tothe default, closed position, to the RIGHT and the wirejumper would remain intact, as shipped from the factory.

HMD COM switch (earlier boards) OR HMD COM wire jumpers (later boards)

HMD COM is located to the left of P299. This switch wouldbe set to the RIGHT or the wire jumpers would be cut only inunique situations where the device supplying the thermostatsignals to the Prodigy controller has its own power sourceand does not share a common reference voltage with theProdigy controller. Otherwise the switch needs to be set tothe default, closed position, to the LEFT and the wire jumperwould remain intact, as shipped from the factory.

Page 5: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 5

Page 5

Startup (continued)

User interface menu

The user interface is accessed through the menu navigationarrows and the select button . The diagram infigure 2 shows a high level overview of the main menuoptions along with the next level list of selections. The lowerlevel options are described later in this manual.

“Home” location, DISPLAY—When the unit is powered on,one of the features in the DISPLAY column will be shown (theword 'DISPLAY' is never shown). What is displayed in this“home” screen, is dependant on the priority message present

at the time, in priority order of top-to-bottom of the left columnin figure 2. For example, if an alarm is present, that will bedisplayed until it has been silenced or cleared.

To access the other three columns, first press and thenuse to scroll between SERVICE, DATA, ANDSETTINGS. Next, press to open the SERVICE (or DATAor SETTINGS) menu. Use until desired item isdisplayed.

To return to DISPLAY, use (if deep in the menu structure,hold it down; it will step back to display).

ALARM(S)

STATUS

MODE

CALLS

USB

TEST

OFFLINE

IN / OUTPUTS

REPLACE

SOFTWARE

RECOVERY

RUNTIMES

HISTORY

SENSORS

NETWORK

FACTORY

STATUS

UNIT

SETPOINTS

CONTROL

OPTIONS

INSTALL

Dashed line forautomatic displayedmessages

Usearrows

tomove

NOTE - Use the left button during normaloperation to clear delays (hold 2 seconds)or reset the controller (5 seconds).

Usearrows

tomove

Usearrows

tomove

SETTINGS

DATA

SERVICE

Figure 2. M2 unit controller main interface menu

Page 6: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 6

Menu Interface

Table 2 shows the major levels of the menu interface. Manyof these options have more levels and are described in thefollowing sections that detail DISPLAY, SERVICE, DATA,and SETTINGS.Use rectangular button (ENTER) or  to progress tonext menu level (i.e. Level 1 to Level 2).Use to “back up” to the next higher menu level (i.e. Level2 to Level 1).Use to move (scroll) within a menu level; also use tochange values of selected item.

Table 2. Menu Interface

Level 1 Level 2 Level 3

NOTE - Features and options not currently available are greyed out inthe manual and will show a message of “N/A” on the display

(dis­playarea)

ALARM SILENCE (push ENTER button to silence)

ALARMS(multiple)

SILENCE ALL (push ENTER button to silence allalarms; or push ► to view alarms and ▲▼ toscroll thru description list.)

MODE

COMP LOADSHEDDING

COOLING

COOLING W/FREECOOLING

DAMPER MODU­LATING WHILECOMPRESSORON

FREE COOLING

DEHUMIDIFICA­TION

FAN ONLY

FAN ONLY - OAS

FRESH AIR COOL

FRESH AIR HEAT

HEATING

HVAC OFF

IDLE

IDLE - OAS

LOW AMBIENTLOCKOUT

MORNINGWARMUP

M2 FAILED TORESPOND

M2 RESET

OFF ON ALARM

PRE-COOL

PRE INSTALL

RESTARTING..

SMOKE

TEST

PROCESSING

(one blinking LED)

LonTalkNEURON IDXX:XX:XX:XX:XX:XX

USB

WRITING USB

WRITING ALARM/STATUS LOG

USB COMPLETE

UPDATE FIRMWARE (For versions 1.09 xx H and later)

SER­VICE

US

E A

RR

OW

S T

O M

OV

E

TEST

GUIDED (N/A)

BLOWER

FANS

COOL

HEAT

DAMPER

HUMIDITROL

MGV

VAV

SENSORS

OUTPUTS

CONTROLLER

OFFLINE

LOCKOUT

BLOWER ONLY (N/A)

COOLING ONLY (N/A)

HEATING ONLY (N/A)

RESET

IN / OUT­PUTS

THERMOSTAT

ZONING (N/A)

SENSORS

RELAYS

NETWORK

REPLACE

FILTER

BELT

UV LAMP

FANS

BLOWER

COMPRESSOR

SOFT­WARE RE­COVERY

UPDATE M2 SOFTWAREUPDATE DB1 SOFTWARE(FOR DB VERSIONS 1.09H ANDLATER ONLY)

Table 2. Menu Interface (cont'd)

Level 1 Level 2 Level 3

DATA

US

E A

RR

OW

S T

O M

OV

E

RUNTIMES

POWER ON

FILTER: XX HRS

BELT: XX HRS

UV LAMP: XX HRS

BLOWER: XX HRS - XX CYC

COOLING

HEATING

FREE COOLING: XX HRS - XX CYC

FANS

EXHAUST

HUMIDITROL: XX HRS - XX CYC

HISTORY

ALARMS

STATUS

LAST USB REPORT

READ INSTALL RPT

CLEAR HISTORY

SENSORS(also ac­cessiblethru In /Outputs)

TSTAT

BRPM:XX

OAT:XXºF

RAT:XXºF

DAT:XXºF

ZAT:XXºF

IAQ:XX PPM

SMK:OFF/ON

RH:XX%

IE:XX MA

OE:XX MA

GLO:OFF/ON

DI2:OFF/ON

DI3:OFF/ON

DI4:OFF/ON

NETWORKLCONN ADDRESS

BACNET

LonTalk

FACTORY

READ M2 SOFTWARE VERSION

READ DB SOFTWARE VERSION

READ FACTORY RPT

CATALOG NO.

MODEL NO.

SERIAL NO.

STATUS

OCCUPIED/UNOCCUPIED

SETPOINTS HH CC F

APP MODE 255 255

COMM TYPE

COMM TIMER

#CURR ALRMS N: A1, A2, … AN

BLOWER

DAMPER STATUS

DAMPER POS

SET­TINGS

US

E A

RR

OW

S T

O M

OV

E

UNITUNIT NO.

DATE/TIME

UNITS F/C

SET­POINTS

COOLING

HEATING

DAMPER

REHEAT

EXHAUST

IAQ

ALARMS

CONTROL

LOCAL

THERMOSTAT

LCONN

BACnet

LonTalk

MSAV

REHEAT

SMOKE MODE

GUIDED SETUP

ECTO

OPTIONS N/A

INSTALL

NEW M2

DAMPER

LANGUAGE (ENGL/SPAN/FREN)

FLOAT SW

BLOWER PROVING SW

DIRTY FILTER SW

BLOWER OVERLOAD SW

PHASE MONITOR

UV LAMP

ELECTRIC HEAT STAGES

UPDATE DISPLAY SOFTWARE

Page 7: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 7

Page 7

DISPLAY Interface DISPLAY

The display shows operating mode if in normal operation.Alarm, status, calls and plugging in the USB will interrupt thedisplay. Alarm messages will stay displayed until corrected orsilenced using the local menu.

ALARM Example – MODE message “COOLING” isdisplaying when a smoke alarm occurs; then “ALARM (XX)SMOKE A173” displays until cleared. You must clear allalarms and status to see normal MODE message. Strike 3alarms will say “ALARM(XX) STRIKE 3 COMP1 HIGHPRESS S4” after the alarm message.

USB – normal MODE message is displayed when USB isplugged in.

Normal Mode Messages

The format of the message is mode and setpoint (see table3).

Table 3. Possible MODE messagesCOMP LOADSHEDDING

Unit is running at lower power capacity

COOLING Cool demand present; unit is cooling

COOLING W/FREECOOLING

Compressor cooling and outdoor damper isopen to maximum.

DAMPERMODULATING WHILECOMPRESSOR ON

Compressor is on during free-cooling, anddamper is modulating.

FREE COOLING No compressor cooling

DEHUMIDIFICATION Unit is dehumidifying

FAN ONLY Fan only

FAN ONLY - OASFan only, outdoor air is suitable for freecooling

FRESH AIR COOL Cool ventilation air to neutral value

FRESH AIR HEAT Heat ventilation air to neutral value

HEATING Heat demand present; unit is heating

HVAC OFF No heat, cool, ventilation allowed

IDLE Demand satisfied; blower off

IDLE - OASSame as IDLE, plus outdoor air is suitablefor free-cooling

LOW AMBIENTLOCKOUT

Outdoor air is too cold to allow fans to run

MORNING WARMUP Outdoor air damper closed

M2 FAILED TORESPOND

Display is missing messages from M2

M2 RESET M2 controller is resetting

OFF ON ALARM Unit is off due to presence of alarm

PRE-COOL

Compressor not allowed—free cooling.(During the first 30 minutes of the first cool­ing demand following a change from unoc­cupied to occupied, calls for mechanical[compressor] cooling are ignored if aneconomizer is installed and if outdoor air issuitable for free cooling.)

PREINSTALL Must follow installation menus

RESTARTING.. Only displayed at power-up

SMOKE Smoke input detected

TEST Network has unit in test mode

PROCESSINGDisplay is busy processing data from M2controller

(one blinking LED) This indicates bootloader mode

Unit Operation

This section describes the display and control buttons, howto configure the unit, and how to read stored configurationdata, status, and alarms.

The M2 unit controller is an input and output junction point.If in the thermostat mode, thermostat inputs at P297 resultin an output to unit components (see table 9 on Page 41). Ifthe heartbeat LED is not flashing, see table 1 (Page 4) forheartbeat operation. If the display shows an alarm, refer totable 8 (Page 31) for more information. If the thermostatinput indicating lights are not responding appropriately,check the thermostat or a DDC control acting asthermostat inputs into P297.

Basic cooling and heating functions may be energized to testmajor unit components by using the M2 unit controller testingfunction or by using jumper wires on the Field WiringTermination plug P297.

To access the other three columns, first press and thenuse to scroll between SERVICE, DATA, ANDSETTINGS. Next, press to open the SERVICE (or DATAor SETTINGS) menu. Use until desired item isdisplayed.

Alarms

Figure 3 shows how alarms may be viewed and silenced.

ALARM(xx) SMOKE DETECTED.

DISPLAYWINDOW

LEFT SCROLLINGMESSAGE

(To SILENCE an alarm,press ENTER)

ALARMSxx,xx,...

(To SILENCE ALL alarms,press ENTER)

(To view descriptions of in­dividual alarms, press � )

(scroll through descriptionsof individual alarms)

Figure 3. Alarm Code Readout Examples

The most recent 84 alarms will be stored with date/timestamp. When more than 84 alarms are encountered theoldest are over-written.

Selected alarms (marked with * in table 8) result in theclosure of the service relay contacts (DO1). The contactsremain closed until the Prodigy resets, or the alarm history iscleared by the user.

This is the default operation of the service relay. Other modesof operation may be selected and are described in theProdigy Application Guide (Advanced Features).

Page 8: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 8

DISPLAY Interface DISPLAY (Continued)

USB Menu

When the Lennox USB drive is plugged in during normalMODE, a menu will be displayed providing options to saveand load unit profiles as well as capturing unit data for serviceverification.

Multiple units may use the same USB drive. The filename ofthe service reports will be based on the unit's serial number;for example 5608J5875.txt. The filename of the unit profileswill be based on the unit's catalog number; for exampleAA1AA.dat.

REPORT

USB

WRITING USB REPORT...

PROFILES

USB COMPLETE

ISDAT FILE

PRESENT ONDRIVE?

YES

NO

UPLOAD PROFILE c:\<cat#>.dat?

SAVE PROFILE c:\<cat#>.dat?

YES

NO

YES

NO

UPLOADING PROFILE... UPLOAD COMPLETE M2 RESET

SAVING PROFILE... DOWNLOAD COMPLETE

FIRMWAREUPDATE CHECKING FILE... UPDATING M2...

NEWERM2 SOFTWARE

ON FLASHDRIVE?

YES

NO

CHECKING FILEINTEGRITY...

ISFILEOK?

M2 UPDATEDYES

NO

BAD CRCM2 UPDATE NOT FOUND

NEWERDB1 SOFTWARE

ON FLASHDRIVE?

UPDATING DB1...CHECKING FILEINTEGRITY...

ISFILEOK?

DB1UPDATED

YES

NO

BAD CRC

YES

NO

DB1 UPDATENOT FOUND

DB1RESETS

WHILE M2 OR DB1 AREUPDATING, DISPLAYINDICATES PERCENTCOMPLETE (NN%)

SERVICE REPORT...

SMARTAIRFLOWREPORT

STARTING BLOWER

% XX

WRITING REPORT

USB COMPLETE

PROGRESS IN %THE SUB-NODES WILLBE VISIBLE ONLY

WHENSMARTAIRFLOW™ IS

INSTALLED.

NOTE: THIS MENU BECOMESVISIBLE WHEN A USB FLASH

DRIVE IS INSERTED INTO THEDB1.

Page 9: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 9

Page 9

GUIDED SETUP Menu Interface GUIDED SETUP

Upon initial unit start-up, the M2 Unit Controller's menuinterface defaults to a GUIDED SETUP. This setup isdescribed on this and the following page.

This guided setup is available at any time should you wish togo back through and re-configure the system's setupparameters.

M2 WILL NOW RESET

USED W/ITHLCONN,LonTalk (N/AW/BACNET)

SAVE PROFILE TOUSB STICK

CONTROL

SETTINGS

GUIDED SETUP

SET DATE/TIME

Usearrows

tomove

THERMO­STAT

SETCON­TROLMODE LOCAL

BACNETMACAD­DRESS

AD:XXX BAUDRATE

XX.XK

RETURN AIR BACKUP?

OCPHEAT BUSTPT

XX.XºF UNOCPHEAT BU STPT

XX.XºF OCPCOOL BU STPT

XX.XºF UNOCPCOOL BU STPT

XX.XºF

START UPDELAY XX

OVERRIDETIMER X

BLOWERONOCP

ALWAYS ON

CYCLES

NETWORKSENSOR

XXX ! SET !

MTH:XX ! SET !DAY:XX YR:20XX HR:XX MIN:XX 09:45:01

SETUP EQUIPMENT DESCRIBED ON NEXT PAGE

OCPHEAT BU STPT

XX.XºF UNOCPHEAT BU STPT

XX.XºF OCPCOOL BU STPT

XX.XºF UNOCPCOOL BU STPT

XX.XºF

TSTAT

RAT

NONE

LONTALK

LCONNADDR:XX ! SET !

CO2NO

YESRH TEMP

NO

YES

NO

YES

NO

YES

ENTERADVANCEDGUIDED SETUP

MONITOR ONLY

REMOTE

ZONE

M2 WILL NOW RESET

NO ZONE W/LonTalk

ZONE

NO

YES ! SETUP IS COMPLETE! PRESS ■ TO EXITINSERT USB STICK AND PRESS ■

(Control Mode is set; continue with SETUP EQUIPMENT)

SET UNIT NO.

EXIT SETUP

SETUP EQUIPMENT

EXIT ADVANCEDSETUP

CONTROL MODE SET

BACKUPMODE

CONTROLMODE

Usearrows

tomove

Usearrows

tomove

Page 10: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 10

GUIDED SETUP Menu Interface GUIDED SETUP (Continued)

DAMPERFULLOPEN STPT

DAMPERSTARTOPEN STPT

SETUPEQUIP­MENT

CHANGEHUMIDITROLSETTINGS?

MSAV HIGH SPEED XXX%

SELECT SENSOR TYPE NO SENSOR USE DI4

NETWORK SENSOR

HUMIDITYSETPOINT

LOCAL SENSOR

SETDAMPERTYPE

MANUAL

ECON

GLOBAL

ENTH

TEMP

SETINPUTCON­TROL

MOAD

SW1 MUST BESET TO TEMP

SW1 MUST BESET TO ODE

SW1 MUST BESET TO GLO

XX%MIN DMPBLWRLOW

XX%MIN DMPBLWRHIGH

MIN DMP POSITION

XX%

SET EXHAUSTFAN SETPT

XX%

SELECTTEMPSTPT

OFFSET

OAT STPT

XXºF

XXºF

SUPPLYAIRSTPT

XX.XºF

YES

XXX PPMCHECK CO2SENSORTHEN PRESS

XXX PPM

SET HUMIDITROLCONTROLCONDITION

MSAV LOW SPEED XXX%

OCC/BLOWERNO CONDITIONS

CHANGEMSAV SETTINGS?

NO

YES

XX%RH DEADBAND XX%

NO

YES

CHANGE OADAMPERSETTINGS?

NO

YES

! SET !

3,4, or 5

ton unit detected?

NO

YES

Power ExhaustDetected

?NO

! SET !

CHANGEDEMAND VENTCONTROLSETTINGS?

NO

YES

! SET !

! SET !

YMSAV

N

! SET !

YHUM

N

YDAMP

N

YDVC

N

(SYSTEM CHECKS UNIT CONFIGURATIONAND PROMPTS THE USER FOR ONLY THEINSTALLED OPTION[S].)

sw1=glo

?

sw1=ode

?

sw1=temp

?

N

Y

N

Y

N

Y

THIS COMPLETES SYSTEM SETUP --see previous page for save options

EQUIPMENT SETUP COMPLETE

“HUM” ONLYAPPEARS IF UNITIS CONFIGUREDFROM FACTORYWITHHUMIDITROL, ORIF A NEW M2BOARD HAS BEENCONFIGURED TOSUPPORTHUMIDITROL.

See Page 19 for complete MSAV details

Page 11: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 11

Page 11

SERVICE Menu Interface SERVICE

From the DISPLAY mode, press and then use toscroll to SERVICE. Next, press to enter the SERVICEmenu. Use until desired item is displayed.

TEST

OFFLINE

IN/OUTPUTS

REPLACE

SOFTWARE RECOVERY

SERVICE

Usearrows

tomove

Using SERVICE, you may run tests that check a functionaloperation (e.g. HEATING) or you may run tests that singleout a system component for checking. The diagram thatfollow in this section show how to navigate through thesystem to access service and test functions.

When the list of tests appears, use the up/down arrows untilthe test you want to run appears. Then press the SELECTBUTTON to begin running the test.

SERVICE > TEST

In the SERVICE menu, use until TEST is displayed.Press to enter the TEST menu.

GUIDED

BLOWER

FANS

COOL

HEAT

DAMPER

REHEAT

SENSORS

OUTPUTS

CONTROLLER

See table 4(Page 12]) for detailsof TEST menu.

TEST

Usearrows

tomove

Using the TEST menu, the service technician may run asequence of tests to gather information available while thatcomponent is turned on. The unit will return to normal modewhen leaving the TEST menu. See table 4 for details.

Any Status/Alarm codes found during testing will be logged tothe event history.

Upon exit from TEST mode, the unit will return to normaloperation if no key is pushed for 1 hour.

SERVICE > OFFLINE

In the SERVICE menu, use until OFFLINE is displayed.Press to enter the OFFLINE menu.

LOCKOUT UNIT LOCKED OUT

BLOWER ONLY

COOLING ONLY

HEATING ONLY

RESET M2 RESET

OFFLINE

Usearrows

tomove

SERVICE > IN / OUTPUTS

In the SERVICE menu, use until IN / OUTPUTS isdisplayed. Press to enter the IN / OUTPUTS menu.

THERMOSTAT

ZONING

ON/OFF INPUT SENSORS TSTAT FROM G, W1, W2,

Y1, Y2, OCP

BL SPEED RPM

(OPEN/CLOSED)

OAT:XXFRAT:XXF (SENSEDDAT”XXF TEMPERATURES)ZAT:XXF

IAQ (PPM) XXX

SMK:XXX ON/OFFRH:XX% REL. HUM.OE:XXMA (OUTDR. ENTH)IE:XMA (INDR ENTH)GLO:XXX ON OR OFFDI2:XXX ON/OFFDI3:XXX ON/OFFDI4:XXX ON/OFF

RELAYS COMP C1-C4 ON/OFF

SVC RL RLY ON/OFF

HUMIDITROL RV1-RV2 ON/OFF

EXHAUST EX1-EX2 ON/OFF

BLOWER BL ON/OFF

FAN F1 - F6 ON/OFF

NETWORK

IN/OUT­

PUTS

BLOWERSPEED

DAMPERPOS

Usearrows

tomove

Usearrows

tomove

Usearrows

tomove

SERVICE > REPLACE

In the SERVICE menu, use REPLACE to reset the runtimecounters for the listed device when a new hardwarecomponent has been installed in the system.

Use until REPLACE is displayed. Press to enter theREPLACE menu. Select one of the listed options and press

;this will reset the runtime for the new part to zero.

FILTER

BE;T

UV LAMP

FANS

BLOWER

COMPRESSOR

REPLACETO RESETXXXXXRUNTIMECOUNTERPRESS

WHEREXXXXX ISTHESELECTEDITEM

RESETUse

arrowsto

move

SERVICE > SOFTWARE RECOVERY

In the SERVICE menu, use SOFTWARE RECOVERY toupdate firmware (see USB Firmware update Page 2).

Page 12: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 12

SERVICE Menu Interface SERVICE (Continued)

SERVICE > TEST (Continued) Table 4. TEST

TEST

TSTAT

BLOWER SPEED

DAMPER POS

OAT:XX ºF

RAT:XX ºF

DAT:XX ºF

ZAT:XX ºF

IAQ (PPM)

SMK:OFF/ON

RH:XX%

IE:XX MA

OE:XX MA

GLO:OFF/ON

D12:OFF/ON

DI3:OFF/ON

DI4:OFF/ON

Use sensor tests to choose each sensor and read the current sensed value.

NOTE 1. The number of fans, 1 min, 6 max, and their respective controloutput depends on the unit configuration. Only the fans present in unit aredisplayed. Refer to unit schematics for additional information.

NOTE 2. The number of stages, 1 min, 4 max, depends on unit con­figuration. Only stages present in unit are displayed.

NOTE: Unit configuration determineswhich menu items are displayed

HUMIDI­TROL

CONTROL­LER

Turns on/off stage 1fan individually.

Turns on/off stage 2fan individually.

Monitors return air temp. of all stages.Dampers close for compressor tests.

Monitors discharge air temp. Blower, dampers,fans actuate automatically during tests.

Monitors return air temp. Stage 1 thru 4 compr low-speed test. Dampers are closed for compressor tests.

Monitors discharge air temperature. Blower, damp­ers, fans are actuated automatically during tests.

Monitors return air temperature of all stages. Dampersautomatically close and blower comes on for heat test.

Monitors discharge air temperature of all stages. Dampersautomatically close and blower comes on for heat test.

Monitors discharge air temperature. Stage 1 thru 4 heat test;dampers automatically close and blower comes on for heat test.

Monitors discharge air temperature. Stage 1 thru 4 heat test;dampers automatically close and blower comes on for heat test.

Damper allows testing economizer, motorized damper, and powered exhaust.Position allows monitoring damper position and control using arrow keys.

(If installed) Measures andreports voltage (0-10V)

(If installed) Measures andreports voltage (0-10V)

Allow turning on FANn individually

Allow turning on FAN1 individually

Shows RPM for blowerand allows adjustment

Display status of the switchwith blower low speed

Display status of the switchwith blower low speed.

Run blower onminimum speed

Run blower onmaximum speed

Monitors indoor enthalpy sensor.

Monitors outdoor enthalpy sensor.

Turns on stage 1 re­heat; displays report.

Turns on stage 2 re­heat; displays report.

Output test of service relay.

Output test of DO2.

M2 OK” if no errors. Checks memoryand installation of controller options.

Output test of DO3.

“TEST OK” if no errors. Checks switchesand screen.

“SETUP OK” if no errors. Checks proper installa­tion of controller boards, switches, and settings

GUIDED

BLOWER

FANS

COOL

HEAT

DAMPER

MGV

VAV

SENSORS

OUTPUTS

BLOWER HI

BLOWER LOW

PROVING SWITCH

FILTER SWITCH

RPM

FAN1

FANn (see note 1)

COOL-FULL

COOLn (see note 2)

HEAT-FULL

HEATn (see note 2)

POSITION

IEN:XX MA

OEN:XX MA

EXHAUST

HUM Y1

HUM Y2

XXX

A01 / A02

SERVICE RELAY

DO2

DO3

M2 TEST

DISPLAY TEST

SETUP

BL OFF/ON

BL OFF/ON

PSW CLO

FSW OPE

XX RPM

FN1 OFF/ON

FNn OFF/ON

RAT XXF

XXX% OPEN

EXHAUST1

HUM Y1 OK

HUM Y2 OK

RLY OFF/ON

DO2 OFF/OON

DO3 OFF/ON

DAT XXF

RAT XXF

DAT XXF

RAT XXF

DAT XXF

RAT XXF

DAT XXF

EXHAUST2

DP XXX%

SET OFF/ON

SET OFF/ON

EX1OFF/ON

EX2 OFF/ON

Usearrows

tomove

Usearrows

tomove

Usearrows

tomove

Usearrows

tomove

Usearrows

tomove

Will allow adjustment ofblower torque in %.

Will be displayed only ifSmartAirflow™ option is in­stalled.

ACTUAL SUPPLYCFM

SPEED

XXXX CFM

XX %

Page 13: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 13

Page 13

DATA Menu Interface DATA

From the DISPLAY mode, press and then use toscroll to DATA. Next, press to enter the DATA menu. Use

until desired item is displayed.

Use DATA to view information stored in the M2 UnitController.

RUNTIMES

HISTORY

SENSORS

NETWORK

FACTORY

STATUS

DATA

Usearrows

tomove

DATA > RUNTIMES

In the DATA menu, use until RUNTIMES is displayed.Press to enter the RUNTIMES menu.

View accumulated runtime hours logged against variouscomponents and systems by the M2 unit controller.

POWER ON

FILTER: XX HRS

BELT: XX HRS

UV LAMP: XX HRS

BLOWER: XX HRS

COOLING COOL#: X HRS

HEATING HEAT#: X HRS

FREE COOLING: XX HRS - XX CYC

FANS FAN#: X HRS

EXHAUST STAGE#: X HRS X CYC

REHEAT: XX HRS - XX CYC

RUNTIMES

Press select but­ton where shown;otherwise, accu­mulated runtimeswill display (if con­figured with listedoption) whilescrolling down.

INST: X HRS

Usearrows

tomove

DATA > HISTORY

In the DATA menu, use until HISTORY is displayed.Press to enter the HISTORY menu.

Read the accumulated historical data of alarms, status, andUSB reports logged by the M2 unit controller.

ALARMS (###) ALARM

STATUS

LAST USB REPORT

READ INSTALL

!CLEAR!

Use the up/down arrows to scrollthrough a list of ALARM events.

!CLEAR” flashes 3times; then alarmsare cleared.

CLEARHISTORY

HISTORY

Usearrows

tomove

DATA > SENSORS

In the DATA menu, use until SENSORS is displayed.Press to enter the SENSORS menu.

View the current sensed value for various systems being sentto the M2 unit controller.

TSTAT

BLOWER SPEED

OAT:XXºF

RAT:XXºF

DAT:XXºF

ZAT:XXºF

IAQ (PPM)

SMK: OFF/ON

RH: XX%

IE: XX MA

OE: XX MA

GLO: OFF/ON

DI2: OFF/ON

DI3 OFF/ON

DI4: OFF/ON

SENSORS

As each sensor is listed, itsreading is automatically dis­played.

G:ON/OFF

W1:ON/OFF

W2:ON/OFF

Y1:ON/OFF

Y2:ON/OFF

OCP:ON/OFF

Use a

rrow

s

XXXX

XXX

Usearrows

tomove

Page 14: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 14

DATA Menu Interface DATA (Continued)

DATA > NETWORK

In the DATA menu, use until NETWORK is displayed.Press to enter the NETWORK menu. Read theNETWORK addresses stored in the M2 unit controller.

NETWORK LCONN ADDRESS XX

BACNET MAC ADDR XX

BAUD RATE XX.XK

DEVICE INSTANCE XX

LONTALK PROGRAM ID XX

NEURON ID XX

Usearrows

tomove

DATA > FACTORY

In the DATA menu, use until FACTORY is displayed.Press to enter the NETWORK menu. Read theFACTORY information stored in the M2 unit controller.

FACTORY

Use the up/down arrowsto scroll through the read­able entries. Use the se­lect button to view soft­ware versions.

READ M2 SOFTWARE VERSION M2 VX.XX.XX

READ DB SOFTWARE VERSION DB1 VX.XX.XX

READ FACTORY REPORT

CATALOG NO. (catalog number)

MODEL NO. (model number)

SERIAL NO. (serial number)

Usearrows

tomove

DATA > STATUS

In the DATA menu, use until STATUS is displayed.Press to enter the STATUS menu.

Read the STATUS information stored in the M2 unitcontroller.

STATUS

Use the up/down arrowsto scroll through the read­able entries. Use the se­lect button to view data.

OCC/UNOCC [OCC/UNOCC]

STPTS HH CC F HH:XX CC:XX

APP MODE 255 255

COMM TYPE LCONN, BACNET, LonTalk LEGACY,LonTalk, NONE

COMM TIMER NO TRAFFIC,<1. <2, <3,<4, <5,5+ MIN

#CURRENT ALRMS: # CURR ALRMS: N:A1, A2, ...AN A1, A2, .. A7

WHERE N = 0 - 7, 7+

Usearrows

tomove

SMOKE: XX %

XX%

ACTUAL SUPPLY CFM

TARGET SUPPLY CFM

BLOWER

Usearrows

tomove

YES

NO

DAMPER TARGET

DAMPER

XX%

DAMPER ACTUAL NOT INSTALLED,CLOSEDCLOSED OASDVC XXFEEE COOL XXMIN POS OAS XXMINPOS XX

SmartAirflow™INSTALLED?

YES

NO

ACTUAL OA CFM XXX cfm

TARGET OA CFM

ECON DIFFPRESSURE

IN. H20 (0-2)

XXX cfm

XXX cfm

XXX cfm

SEENOTEBELOW

NOTE: Display will indicate OAS when outdoor air could be used

for free cooling. For older hardware OAS LED will be an additional

indication. No OAS indication (display or LED) is available during

demand control ventilation (DVC) operation, although free cool­

ing can still occur. xx is the damper position percent open feed­

back signal.

SmartAirflow™INSTALLED?

Page 15: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 15

Page 15

SETTINGS Menu Interface SETTINGS-

From the DISPLAY mode, press and then use toscroll to SETTINGS. Next, press to enter the SETTINGSmenu. Use until desired item is displayed.Use SETTINGS to make changes to the Unit Controller afterinitial installation.Many of the setting changes are the same as install.Changes are limited by the unit's build information. If youinstall new options, you can make changes to equipmentsettings beyond the factory values.Load shed to include power percentage and hard wire.

UNIT

SETPOINTS

CONTROL

OPTIONS

INSTALL

SETTINGS

Usearrows

tomove

SETTINGS > UNIT

In the SETTINGS menu, use until UNIT is displayed.Press to enter the UNIT menu. View and change thecurrent settings.

UNIT

USE ARROWSTO ADJUST

DATE AND TIME

UNIT NO. XXX !SET !

DATE/TIME

TIME 15:45:00 DISPLAY TIME

DATE 01.01.00 DISPLAY DATE

SET CLK MTH: 03 DAY:18 YR: 2011

HR: 13 MIN: 33 ! SET !

13:33:07

Usearrows

tomove

CURRENT TEMPERATUREFORMAT

UNITS F/C

DEGREES FAHRENHEIT

DEGREES CELSIUS

SET TEMPERATUREDISPLAY FORMAT

DEGREES FAHRENHEIT

DEGREES CELSIUS

! SET !

! SET !

SETTINGS > SETPOINTS > COOLING HEATING

REHEATEXHAUSTIAQ

(Also see SETTINGS > SETPOINTS > DAMPER)

In the SETTINGS menu, use until SETPOINTS isdisplayed. Press to enter the SETPOINTS menu.

View and change the current system setpoints setup in theM2 unit controller as shown in the following diagrams forCOOLING, HEATING, REHEAT, EXHAUST and IAQ.

REHEATWILL NOTBE VISIBLEUNLESS ITWASINSTALLEDAT THEFACTORY.

XX%RH [0-99%] OR DEHUMIDI-STAT CONTROL

SETPOINTS

(SEPARATE DIA­GRAM FOLLOWS)

Usearrows

tomove

COOLING OCP COOL BU STPT XX.XºF

UNOCP COOL BU STPT XX.XºF

FREE COOLING STPT XX.XºF

COMP TIME OFF DELAY

COOLING OPTION

HEATING OCP HEAT BU STPT XX.XºF

UNOCP HEAT BU STPT XX.XºF

DAMPER ! SET !

REHEAT REHEAT STPT

REHEAT DEADBAND 3%

EXHAUST SMOKE POS 50%

EXHAUST FAN STPT 50%

DAMPER START OPEN STPT 700PPM

DAMPER FULL OPEN STPT 1200PPM

IAQ/DCV

MAX OA CFM XXX CFM

MAX DAMPERPOS XX% OPEN

YES

NO

SmartAirflow™INSTALLED?

Page 16: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 16

SETTINGS > SETPOINTS > DAMPER

Use SETTINGS > SETPOINTS > DAMPER as shown in the following diagrams; default settings will be used. You mayadjust those settings to suit the building's requirements.

NOTE - Early hardware used pots and DIP switches; newer hardware does not.

OFF-SET

DAMPER

SEEFIGURE 4(PAGE 26)

NOTE: FORDETAILS, SEEECONOMIZERSECTION Page 24

SETPOINTS

ECONOMIZERMODE

TEMP SET DIP SW1 TO TMP,

PRESS � WHENREADY TO CONTINUE

SET DIP SW1 TO ODE,

PRESS � WHENREADY TO CONTINUE

SET DIP SW1 TO GLO,

PRESS � WHENREADY TO CONTINUE

XXºF ! SET !

CONTROL XXºF ! SET !

SEEFIGURE 4(PAGE 26)

SUPPLY AIR STPT XX.XºF [44.9 TO 65.3ºF] ! SET !

MIN OCP BLOWER LOW XXX% [0 TO 100%} ! SET !

MIN OCP BLOWER HIGH XXX% [0 TO 100%] OR ! SET !POTENTIOMETER CONTROL

FAH XX.X% [40.2 TO 70ºF] OR ! SET !DISABLED

FAC XX.X% [59.9 TO 90.4ºF] OR ! SET !DISABLED

ENTH

GLOBAL

Usearrows

tomove

Usearrows

tomove

OATSTPT

Early hardware

XX% [10TO 100CFM]

XX.X% [10TO 100CFM]

XX.X%[10 TO100 CFM]

XX MIN[20 TO60 MIN]

! SET !

! SET !

! SET !

! SET !

OFF­SET

DAMPER

NOTE: FORDETAILS, SEEECONOMIZERSECTION Page 24

SETPOINTS

ECONOMIZERMODE

TEMP CON­TROL

XXºF ! SET !

GLOBAL

Usearrows

tomove

Usearrows

tomove

XX.XMA

! SET !

OATSTPT

XXºF ! SET !

ENTH CON­TROL

! SET !DIFF OFFSET

XX.XMA

! SET !ODESTPT

Newer hardware

SUPPLY AIR STPT XX.XºF [44.9 TO 65.3ºF] ! SET !

MIN OCP BLOWER LOW XXX% [0 TO 100%} ! SET !

MIN OCP BLOWER HIGH XXX% [0 TO 100%] ! SET !

FAH XX.X% [40.2 TO 70ºF] OR ! SET !DISABLED

FAC XX.X% [59.9 TO 90.4ºF] OR ! SET !DISABLED

ALARMS

ENABLEALARM

LOW SUPPLYAIRFLOWALARM

LOW OUTDOORAIRFLOWALARM

NO

YES

ALARMTRIGGERPERIOD

HIGH OUTDOORAIRFLOWALARM

NOTE: ALARMS NODE WILL NOT BE VISIBLEUNTIL SMARTAIRFLOW™ OPTION IS IN­STALLED.

Page 17: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 17

Page 17

SETTINGS Menu Interface SETTINGS (Continued)

SETTINGS > CONTROL

In the SETTINGS menu, use until CONTROL isdisplayed. Press to enter the CONTROL menuaccess/change system setpoints.

LOCAL

THERMOSTAT

L CONN

BACNET

LONTALK

MSAV

REHEAT

SMOKE MODE

GUIDED SETUP

ECTO

CONTROL

Usearrows

tomove

SETTINGS > CONTROL > LOCAL

(Used in absence of thermostat or network control)

Select SETTINGS > CONTROL > LOCAL as shown in thefollowing diagram; default settings will be used. You mayadjust those settings to suit the building's requirements.

LOCAL RETURN AIR BACKUP YES/NO

OCP HEAT BU STPT XX.XºF

UNOCP HEAT BU STPT XX.XºF

OCP COOL BU STPT XX.XºF

UNOCP COOL BU STPT XX.XºF

CONTROL

Usearrows

tomove

SETTINGS > CONTROL > THERMOSTAT SETUP

Hook up to SmartWire� thermostat connections. SelectSETTINGS > CONTROL > THERMOSTAT and select YESas shown in the following diagram.

THERMOSTATCONTROLTHERMOSTATCONTROL?

YESNO

SETTINGS > CONTROL (DDC Integration or L CONN [L Connection])

Select SETTINGS > CONTROL > L CONN as shown in the following diagram; default settings will be used. You may adjustthose settings to suit the building's requirements.

LCONN ADDR:XX CONTROL MODE MONITOR ONLY

REMOTE

ZONE

BACKUPMODE

OCPHEAT BUSTPT

UNOCPHEAT BU STPT

OCPCOOL BU STPT

UNOCPCOOL BU STPT

START UPDELAY

OVERRIDETIMER

BLOWERONOCP

ALWAYS ON

CYCLES

NET­WORKSENSOR

TSTAT

RAT

NONE

CO2NO

YESRH TEMP

NO

YES

NO

YES

ZONE

CONTROL

XX.XºF

XX X

XX.XºF XX.XºF XX.XºF

Usearrows

tomove

Usearrows to

move

Page 18: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 18

SETTINGS Menu Interface SETTINGS (Continued)

SETTINGS > CONTROL > BACnet

Select SETTINGS > CONTROL > BACnet as shown in the following diagram; default settings will be used. You may adjustthose settings to suit the building's requirements. The following diagram shows the BACnet menu's structure and how tomake changes.

BACNETMACAD­DRESS

AD:XXX BAUDRATE

XX.XK CONTROLMODE

BACKUPMODE

OCPHEAT BUSTPT

UNOCPHEAT BU STPT

OCPCOOL BU STPT

UNOCPCOOL BU STPT

START UPDELAY

OVERRIDETIMER

BLOWERONOCP

ALWAYS ON

CYCLES

NET­WORKSENSOR

TSTAT

RAT

NONE TEMP

MONITOR ONLY

REMOTE

ZONE

ZONEXX.XºF XX.XºF XX.XºF

XX X

CONTROL

XX.XºF

Usearrows

tomove

NO

YES

SETTINGS > CONTROL > LonTalk

Select SETTINGS > CONTROL > LonTalk as shown in the following diagram; default settings will be used. You may adjustthose settings to suit the building's requirements. The following diagram shows the LonTalk menu's structure and how tomake changes.

CONTROLMODE

BACKUPMODE

OCPHEAT BUSTPT

UNOCPHEAT BU STPT

OCPCOOL BU STPT

UNOCPCOOL BU STPT

START UPDELAY

OVERRIDETIMER

BLOWERONOCP

ALWAYS ON

CYCLES

NET­WORKSENSOR

TSTAT

RAT

NONE

LONTALK

CO2NO

YESRH TEMP

NO

YES

NO

YES

ZONE

CONTROLMONITORONLY

XX.XºF XX.XºF XX.XºF XX.XºF

XX X

SETTINGS > CONTROL > REHEAT

When you select REHEAT, default settings will be in place.You may adjust those settings to suit the building'srequirements. The following diagram shows the REHEATmenu's structure and illustrates how to use the controls tomake changes.

CONTROL

REHEATDEADBAND

NETWORKSENSOR

XX% [0 - 99%ORDEHUMIDISTAT]

! SET !

Use a

rrow

sto

move

REHEAT SENSOR TYPE NONE

DEHUMIDISTAT

LOCAL SENSOR

REHEAT STPT ! SET !

XX% [1 - 10%] ! SET !

Page 19: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 19

Page 19

SETTINGS Menu Interface SETTINGS (Continued)

SETTINGS > CONTROL > MSAV

(Multi‐stage air volume)

Select SETTINGS > CONTROL > MSAV as shown in thefollowing diagram; default settings will be in place. You mayadjust those settings to suit the building's requirements. Thefollowing diagram shows the MSAV menu's structure andillustrates how to use the controls to make changes.

CONTROL

MSAV

YES

SmartAir­Flow™ or

non-A Box­installed?

NOBLOWER

XX%[20 to 100%] ! SET !

YES

N=2?NO

YES

N=3?NO

SETTINGS

(N=4)

NOTE - “N” IS THENUMBER OFCOMPRESSORS INTHE UNIT

COOLINGHIGH CFM

HEAT CFM

COOLINGLOW CFM

VENT CFM

COOLMED CFM

COOL MEDHIGH CFM

COOL MEDLOW CFM

MSAV HIGH SPEED

MSAV LOW SPEED

XX%[20 to 100%] ! SET !

SmartAirFlow™Installed

START BLOWERTO CALIBRATE?

YES

NO

SAVE SETTINGS YES /NO

YES /NO

1.. STARTING BLOWER

2.. BLOWER ON

3.. CLOSING DAMPER

4.. CALIBRARING SETTINGS

5.. Display CALIBRATING SETTINGS for 5 seconds

6.. CALIBRATION PROGRESS IN xx %

7.. CALIBRATION COMPLETE

NOTE: M2 WILL RESET AFTER THE CLIBRATION

PROCESS.

CALIBRATION / VALIDATING

NO

YES

YES

NO

! SET !

NOTE - SAVE SETTING WITHOUTRECALIBRATING

Page 20: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 20

SETTINGS > CONTROL > MSAV > DAMPER

(Multi‐stage air volume)

Select SETTINGS > CONTROL > MSAV > DAMPER asshown in the following diagram; default settings will be inplace. You may adjust those settings to suit the building'srequirements. The following diagram shows the MSAVmenu's structure and illustrates how to use the controls tomake changes.

CONTROL

MSAV

YES

SmartAirFlow™Installed?

NO

DAMPER XXX CFM

SETTINGS

OUTDOORAIRFLOW

SAVE SETTINGS YES /NO

YES

NO

SETOUTDOORAIRLFOW CFM

LOW SPEED -0 - 100%

HIGH SPEED -0 - 100%

YESMSAVUNIT

?

NO

YES

LOW SPEED

HIGH SPEED

XX%[0 to 100%] ! SET !

XX%[0 to 100%] ! SET !

WRITE_MSAV_SETTINGS

SAVESETTINGS?

BLOWER

NO

VFD BYPASSENGAGE

DISENGAGE

YES

VFDbypass

configured?

! SET !

NO

SETTINGS > CONTROL > SMOKE MODE

When you select SMOKE MODE, default settings will be inplace. You may adjust those settings to suit the building'srequirements. The following diagram shows the SMOKEMODE menu's structure and illustrates how to use thecontrols to make changes.

SMOKE MODE

Usearrows

tomove

UNIT OFF

BLWR OFF, EXH ON,DAMPER SHUT

PURGE-BLWR ON, EXHON, DAMPER OPEN

NEGATIVE-BLWR ON, EXHON, DAMPER SHUT

POSITIVE-BLWR ON, EXHOFF, DAMPER OPEN

CONTROL

! SET !

Page 21: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 21

Page 21

SETTINGS Menu Interface SETTINGS (Continued)

SETTINGS > CONTROL > ECTO

When you select ECTO, default settings will be in place. Youmay adjust those settings to suit the building's requirements.The following diagram shows the ECTO menu's structureand illustrates how to use the controls to make changes.

BLOCK/PARAM/COUNT

RESET TOFACTORYECTO

ECTO B#: X[0, 2 TO10]

ARE YOUSURE?

YES

NO

M2 RESET

P#:XX[1 TO 27]

CNT:XXX[0 TO 255]

! SET !CONTROL

THE BLOCK, PARAMETER, AND COUNT RANGES SHOWN HEREARE LIMITS AND WILL BE RESTRICTED IN SOME CASES.

EXAMPLE: When told to set ECTO 6.27=1 navigate toSETTINGS > CONTROL > ECTO >BLOCK/PARAM/COUNT>B# and enter 6. At P# enter 27. AtCNT: enter 1. Display shows flashing "!SET!", and returns toBLOCK/PARAM/COUNT for another change. When changesare done, use the left arrow to back out of the CONTROLmenu, and UPDATING SETTINGS is shown while changes aremade, and then M2 resets to use the new values.

SETTINGS > INSTALL > (all except NEW M2)

Use SETTINGS > INSTALL as shown in the followingdiagram; default settings will be used. Use menu to changelanguage used, and ancillary components installed. Anexpert manual and service software are available for morecomplex installations (see Table 7, Page 27). If any alarmsare present, take corrective action prior to installation.

UPDATE DISPLAY SOFTWARE menu only appears in DB1

versions that do not end in "H". If the display does not have aHOST boot-loader (indicated by the H), then a Windows PCand USB cable (A­to­A, or with B­to­A adapter) are needed toperform firmware upgrade on DB1.

NOTE - The M2 should be reset in order for changes to be

updated within the controller.

Use INSTALL > FLOAT SWITCH to set up a condensate panoverflow switch. Use INSTALL > UPDATE DISPLAYSOFTWARE to install new display software.

EXITBOOTLOADERBY HOLDINGBACK ARROW �FOR ~ 3SECONDS

INSTALL NEW M2 (SEE PREVIOUS DIAGRAM)

NOT INSTALLEDDAMPER ECON

MOAD ! SET !

ENGLISHLANGUAGE FRENCH

SPANISH ! SET !

FLOAT NOT INSTALLEDSWITCH INSTALLED ! SET !

BLOWER NOT INSTALLEDPROVING SW INSTALLED ! SET !

DIRTY NOT INSTALLEDFILTER SW INSTALLED ! SET !

BLOWER NOT INSTALLEDOVERLOAD S135 INSTALLED ! SET !

PHASE NOT INSTALLEDMONITOR INSTALLED ! SET !

UV LAMP NOT INSTALLEDINSTALLED ! SET !

ELECTRIC NOT INSTALLEDHEAT 1 STAGESTAGES 2 STAGES

3 STAGES4 STAGES ! SET !

UPDATE DISPLAYDISPLAY WILL RESET ! RESET !SOFTWARE

Usearrows

tomove

Page 22: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 22

SETTINGS > INSTALL > NEW M2

Use SETTINGS > INSTALL > NEW M2 to go through the setup and change settings as needed when installing areplacement M2 (new M2 units have no factory pre-sets).

! SET !

Y/N

! SET !

! SET !

! SET !

NEW M2

M2 RESET

INSTALL

AFTER RESET, RETURN TO SETTINGS > INSTALL > NEW M2 AND SCROLL TOCATALOG NO. AND CONTINUE CONFIGURING THE BOARD TO MATCH THE UNIT.

CLEAR ARE YOUALL SURE?CONFIGURATIONS

UNIT SERIAL NO. XXXXXXXXX UNIT NO. XXX MODEL NO. XXXXXXXXXXXX

CATALOG NO. XXXXX

NOT INSTALLEDDAMPER MOAD

ECON

WHEN INSTALLING A NEW M2, ENTER THE SERIAL, UNIT NO.AND MODEL NO. THE M2 WILL AUTOMATICALLY RESET.

! SET !

Usearrows

tomove

THIS MENU ITEM IS ONLY VISIBLE AS A SELECTION WHENTHE BLOWER CONTROL MODE IS SET FOR MSAV(ECTO0.01 = 3) OR "M" IN BLOWER­TYPE OF MODEL NUMBER.

EXHAUST NOT INSTALLEDSTAGES 1 EXHAUST STAGE

2 EXHAUST STAGES

HUMIDITROL NOYES

PHASE/VOLTAGE NOT INSTALLEDDETECTION INSTALLED

MSAV/VFD AUTOMATICBYPASS MANUAL

NONE

! SET !SMARTAIRFLOW INSTALLED NOT INSTALLED

Page 23: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 23

Page 23

Blower Operation with Occupancy and CEC Title 24

The blower runs to service heat and cool demands,regardless of the space occupancy. But when there is noheating or cooling demand there are options for how theblower should operate in conjunction with occupancy signalsto keep the space ventilated, or the air stirred.

In SETTINGS>CONTROL menus the option for BLOWERON OCP is selected as CYCLES or ALWAYS ON. Thesecorrespond to ECTO 6.17 settings of 0 or 1, respectively.These settings govern whether the blower runs continuouslywhen the space is considered occupied (=1), or cycles on/offwith the heating and cooling demand (=0). ECTO 6.17 onlyapplies to the room sensor control modes, and not to the localor network thermostat modes. In those modes the blower iscontrolled by the G thermostat or DDC signal.

To comply with the California Energy Commission Title 24standard there are two additional blower/occupancy settingsthat are set directly by changing ECTO 6.17 from theSETTINGS>CONTROL>ECTO menu. These two additional

options are available when using LonTalk or BACnetnetworks that supply a room occupancy signal (in addition tothe scheduled occupancy). The same two options are alsoavailable when using the Lennox L Connection network withcomfort sensors that have added an optional roomoccupancy sensor. If a room occupancy sensor is notinstalled and configured on the network, then options 0 and 1for ECTO 6.17 as previously described should continue to beused.

The two new ECTO 6.17 options for CEC Title 24 are:

� ECTO 6.17 = 2: Blower runs when both the occupancyscheduler and the room occupancy sensor indicate thatthe space is occupied.

� ECTO 6.17 = 3: Same as option 2, but the blower alsoruns for 30 minutes and is OFF for 90 minutes when theoccupancy scheduler indicates occupied but the roomoccupancy sensor indicates that the space is notoccupied.

Page 24: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 24

Economizer (Damper)

General

The economizer, when configured, controls

� damper position, which determines how much outdoorair is used to meet free cooling or indoor air quality (IAQ)requirements, and

� the optional power exhaust fans.

On a cooling demand, outdoor air is used for free coolinginstead of first-stage compressor(s) when outdoor air issuitable (OAS).

Outdoor Air Suitable (OAS) LED (Early M2 hardware)

A yellow LED which is labeled OAS provides economizerstatus. A steady yellow LED indicates that outdoor air issuitable for free cooling. A flashing yellow OAS light indicatesthe IAQ sensor requires outdoor air. (A flashing yellow LEDcan also mean that the economizer dampers are open tobring in fresh air while a compressor is on.) If the economizeris already operating, a flashing yellow OAS light indicates theIAQ sensor requires more outdoor air than is suitable for freecooling.

DIP Switch Settings (Early M2 hardware)

The DIP switch setting determines the mode used to enablefree cooling. The DIP switch also has a mode to set thedamper minimum position and test damper operation. DIPswitch is factory-set when the economizer isfactory-configured.

Free Cooling Discharge Air Setpoint

When outdoor air conditions are suitable and economizer isset to provide free cooling, dampers will modulate to achievea discharge air temperature of 55°F (13°C) default. Thissetpoint is adjustable between 45° and 65°F.

The setpoint can also be automatically increased whenoutdoor or return air temperatures drop. See Outdoor AirReset and Return Air Reset in the Discharge Air Controlsection in the Prodigy Application Guide (AdvancedFeatures) manual. These settings must be enabled andadjusted using the Prodigy CONTROL/ECTO menu to makechanges to ECTO values. Refer to the Prodigy ApplicationGuide. The unit does not have to be operating in discharge aircooling mode to adjust the free cooling discharge air setpoint,or to use setpoint reset.

During free cooling operation, the damper modulates tomaintain a discharge air temperature equal to the freecooling discharge air setpoint. If the damper has beencontinuously at its maximum open position for at least threeminutes, then a second stage cooling demand will be allowedto turn on the first stage of mechanical cooling. While themechanical cooling is on, the damper is held to its maximumposition, and does not modulate until the second stagedemand is satisfied. On a third stage cooling demand, thesecond stage of mechanical cooling will be turned on.

Outdoor Air Suitability

There are five modes which can be used to determine if theoutdoor conditions will enable free cooling.

� Old hardware: DIP switch is set toODE (Outdoor Enthalpy), and theEnthalpy Setpoint potentiometeris set A-through-D.

� New hardware: Configuration isset to Single EnthalpyEconomizer Control and ECTO 6.26 setpoint value isset to between 12 and 19mA, 150 to 240 counts.

Enthalpy Setpoint

This setting pertains to the ODE free cooling mode only. TheM2 will enable free cooling when outdoor air enthalpy (A7) isless than the enthalpy setpoint. Table 5 shows theapproximate enthalpy setpoints for each potentiometersetting at 50% relative humidity. The ECTO 6.26 column isthe correlating values used in the new hardware.

Example:—At setting “A”, the enthalpy control will modulatedampers open when outdoor air is at 73°F and 50% relativehumidity. If space temperatures are too warm, rotate thepotentiometer to “B” (old hardware) or enter a count of 173(ECTO 6.26 if new hardware). The enthalpy control will nowmodulate dampers open when outdoor air is 70°F and 50%relative humidity.

NOTE - When in outdoor enthalpy mode, a value between

130-240 counts is entered. When in differential enthalpy

mode a 2mA (or 26 count) difference between outdoor and

indoor enthalpy corresponds to about a 3.5°F difference in

temperature at constant relative humidity (or about a 12%RH

difference at constant temperature). When in differential

enthalpy mode, a value between 0-75 counts is entered.

Table 5. Enthalpy Control Setpoints

The recommended enthalpysetpoint is “A”. If the econom­izer is allowing air which is toowarm or too humid to enter thesystem, the enthalpy controlmay be changed to a lower set­ting (B, C, or D).

ControlSetting

Enthalpy Control Setpoint At 50% Relative Humidity Ap­proximate Degrees F (C)

ECTO 6.26cnt (mA)

A 73 (23) 150 (11.8)

B 70 (21) 173 (13.6)

C 67 (19) 199 (15.5)

D 63 (17) 224 (17.6)

Page 25: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 25

Page 25

Economizer (Damper) (Continued)

There are six options available to determine outdoor airsuitability (OAS) for free cooling. See table 6. Economizersettings are shown for each mode in figure 4.The appropriate sensors are provided when the economizer

is factory-configured. When the economizer isfield-configured, the ODE mode requires additionalfield-provided sensor(s). See table 6. The TEMP mode usessensors provided with all units.

Table 6. Free Cooling Options

Free cooling mode

DIP SWpositions

MODESelection

CONTROLSelection

OAS Setpoint CalculationOlder M2Hardware

Newer M2 Hardware

Temperature offset 1,2 to TMP TEMP OFFSET OAT<RAT-OFFSET (0 to 40 F)

Temperature setpoint 1,2 to TMP TEMP OAT STPT OAT<OAT STPT (41 to 75 F)

Remote 1,2 to TMP TEMP ANY OAS sent by network.

Enthalpy differential (Potentiometer set to DIFF) for old

hardware, or ECTO 6.26 = 0 to 75 counts for OFFSET

in new hardware. Old hardware does not use an OFF­

SET.

1,2 to ODE ENTH N/AODE<IDE (old hardware) or ODE

< IDE ­ OFFSET (new hardware)

Enthalpy setpoint (Potentiometer set to A-D) for old

hardware, or ECTO 6.26 = 130 to 240 counts for new

hardware.

1,2 to ODE ENTH N/AODE<POT (old hardware) orODE < ECTO 6.26 (new hard­ware)

Global input 1,2 to GLO GLOBAL N/A GLO input

Mode Outdoor air is suitable for free cooling when:

TEMP OFFSET Outdoor air temperature (RT17) is less than return air temperature (RT16) by at least the OFFSET value.

TEMP OAT STPT Outdoor air temperature (RT17) is less than the OAT STPT value.

RemoteEither of the TEMP modes can be used when a network OAS signal is provided by an energy management or buildingcontrol system, via BACnet, LonTalk, or L Connection. The network can command OAS, NOT OAS, or AUTO. AUTOreturns to local control of OAS, which is the selected TEMP mode..

ENTH (differential)Outdoor air enthalpy* (A7) is less than return air enthalpy (A62) by at least the OFFSET value. (There is no OFFSETvalue in old hardware.)

ENTH (setpoint)Outdoor air enthalpy (A7) is less than enthalpy setpoint potentiometer position A, B, C, or D (for old hardware), or lessthan ECTO 6.26 STPT value (new hardware).

GLOBALGlobal input is energized by (P297-9). This setting is also used for outdoor air damper applications. Global input alsobrings on the blower. (This mode is NOT used when OAS signal is provided via network connection. GLO is only usedwhen a 24VAC signal is used to energize the P297-9 GLO input.)

Enthalpy includes effects of both temperature and humidity.

Page 26: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 26

STEADY YELLOW“OUTDOOR AIRSUITABLE” LEDINDICATESOUTDOOR AIRCAN BE USEDFOR COOLING

ECONDIPSWITCH

M2 UNIT CONTROLLER

0-100% MINIMUM POSI­TION POTENTIOMETER

TEMP OFFSET, TEMP OATSTPT, and Remote MODE.

ODE DIFFERENTIAL (Outdoor Enthalpy)

Set to DIF

A

BC

D

DIFENTH SET PNT

ODE (Outdoor Enthalpy)

A

BC

D

DIF

Set to A

ENTH SET PNT

GLO (Global Enthalpy)

Note-All economizer modes of operation, except DSET, will modulatedampers to 55°F (13°C) discharge air.

Free Cooling Settings Economizer Controls and Location

Figure 4. Economizer controls and free cooling settings (Early M2 Hardware)

Page 27: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 27

Page 27

APPENDIX

AbbreviationsA55 M2 board. Main controller board for RTUA59 C2 board. Second compressor add-on boardA133 GP1 Board. General purpose add-on board DIP selects 3 functionsAI Analog inputAO Analog outputBL BlowerBRPM Blower RPMC2 2nd compressor add-on board (A59)C1 1st stage coolingC2 2nd stage coolingC3 3rd stage coolingC4 4th stage coolingCAI Combustion air inducerCAVB Constant air volume with bypass damperCOM Electrical commonCLK ClockCP1 Compressor 1CP2 Compressor 2CP3 Compressor 3CP4 Compressor 4CSP Cooling setpointDAC Discharge (supply) air controlDACC Discharge (supply) air control coolingDACH Discharge (supply) air control heatingDAP Discharge (supply) air pressureDAT Discharge (supply) air temperatureDB DeadbandDCV Demand controlled ventilationDDC Direct Digital ControllerDI Digital inputDiff DifferentialDIP DIP switchDPOS Damper positionDO Digital outputECON EconomizerECTO Electronic configure to order (control parameters)FAC Fresh air cooling controlFAH Fresh air heating controlFAT Fresh air tempering control. See FAC & FAHFC Free coolingG Thermostat demand, blowerGLO Global mode or input (economizer)GP1 General purpose board GP1-1 (A133)H1 1st stage heatingH2 2nd stage heatingH3 3rd stage heatingH4 4th stage heatingHP1 Heat pump add-on board (A61)HP High pressureHSP Heating setpointHT HeatingIAQ Indoor air quality. Often synonymous with CO2 level in ppm

IDE Indoor enthalpy. Depends on temperature and humidityIE Indoor enthalpy.“w.c. Inches of water columnLCONN L ConnectionLED Light emitting diode. An indicator light, found either as individual

elements or grouped together as segments to form charactersLP Low pressureLT LimitM2 Main M2 unit controller board (A55).MCB1 Motor control boardMGV Modulating gas valveMOAD Motorized outdoor air damperMSAV Multi Stage Air VolumeOAC Outdoor air controlOAS Outdoor air suitable for free coolingOAT Outdoor air temperatureOCP Thermostat demand, occupied modeODE Outdoor enthalpy. Depends on temperature and humidityOE Outdoor enthalpy.PID Proportional, integral and derivative based control loopPPM Parts per million (mostly used for CO2 measurements)RAP Return air pressureRAT Return air temperatureRH Relative humidityRS ResetRTU Roof top unitRT6 Discharge air temperature sensorRT16 Return air temperature sensorRT17 Outdoor air temperature sensorSMK Smoke detection mode (alarm)SP SetpointStg StageSTPT SetpointTB Terminal blockTSTAT ThermostatUNOCP UnoccupiedUSB Universal Serial Bus, connect to PC or flash driveW1 Thermostat demand, heat stage 1W2 Thermostat demand, heat stage 2W3 Thermostat demand, heat stage 3W4 Thermostat demand, heat stage 4VAC Alternating current voltageVAV Variable air volume. Accomplished with a variable frequency drive

(VFD)VDC Direct current voltageVFD Var. frequency drive. An AC inverter used to vary motor speedVT VentilationY1 Thermostat demand, cooling stage oneY2 Thermostat demand, cooling stage twoY3 Thermostat demand, cooling stage threeY4 Thermostat demand, cooling stage fourZAT Zone air temperature

Table 7. Service parts available for Prodigy® Controller

Description

Catalognumber Description

Catalognumber Description

Catalognumber

M2 Unit Controller Replacement kit 59W47 M2 USB service kit tube 59W52 M2 Training board (no suitcase,USB, or M2)

59W56

DB1-1 M2 Display Replacement kit 59W49 M2-1 Display battery (10-pack) 59W53 SmartWire� Field Termination kit 59W57

MCB1 M2 Motor Control Replace­ment kit

59W50 M2-1 Fuse (2-Amp ATC, 5-pack) 59W54 Lennox Prodigy USB Memory Stick(5-pack)

59W59

M2 BACnet� Replacement kit 59W51 M2 Deluxe Training kit (suitcase,UC, USB kit, expert manual, M2,trainer)

59W55 Service Software & Expert Manualon USB

59W60

Page 28: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 28

USB Service Report Example

==========================================================================USB SERVICE REPORT==========================================================================Service Date 1/1/2010Service Time 12:00:00Serial No. 5609K00002M2 Version 7.02.00 DB1Version 1.05.00Unit No. 2Sbus Address 2BACnet Address. 2CAT No. NO CNMODEL NO. LGH036H4ES1YStatus HEATING==========================================================================Runtime Data Total Power On 1832 HRS 79 CYCLES Before Install 286 HRS −−−−−−− Filter 2040 HRS −−−−−−− Belt 1063 HRS −−−−−−− Blower 1162 HRS 131 CYCLES Compressor 1 46 HRS 66 CYCLES Compressor 2 14 HRS 17 CYCLES Compressor 3 0 HRS 0 CYCLES Compressor 4 0 HRS 0 CYCLES Outdoor Fan 1 14 HRS 32 CYCLES Outdoor Fan 2 0 HRS 2 CYCLES Outdoor Fan 3 0 HRS 0 CYCLES Outdoor Fan 4 0 HRS 0 CYCLES Outdoor Fan 5 0 HRS 0 CYCLES Outdoor Fan 6 0 HRS 0 CYCLES Heat Stage 1 96 HRS 17 CYCLES Heat Stage 2 96 HRS 16 CYCLES Reheat 0 HRS 13 CYCLES Free Cooling 42 HRS 1608 CYCLES UV Lamp 2368 HRS −−−−−−−==========================================================================

Sensor Data OAT : 80 degF RAT : 76 degF DAT : 69 degF ZAT : 59 degF RH : 34 % CO2 : 415 ppm==========================================================================

Alarm/Status Log ( 58) 12.14.2009 12:07:15 HEAT 1 NO PROOF GAS VALVE GV1 ( 85) 12.14.2009 12:03:24 INCORRECT HUMIDITROL SETTINGS ( 82) 12.14.2009 12:03:24 CONTROLLER RESET ( 95) 12.09.2009 19:54:37 SETTINGS HAVE CHANGED (120) 12.09.2009 18:52:54 ADD−ON BOARD MCB PROBLEM========================================================================== END OF REPORT

Page 29: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 29

Page 29

USB Service Report Example (If SmartAirflow™ is Installed)

========================================================================

==

USB SERVICE REPORT

========================================================================

==

Service Date 10/26/2009

Service Time 16:28:05

Serial No. 5609K00002

M2 Version 7.00.00

DB1Version 1.03

Unit No. 2

Sbus Address 1

BACnet Address. 1

CAT No. NO CN

MODEL NO. LGH036H4ES1P

Status IDLE

========================================================================

==

Runtime Data

Total Power On 666 HRS 46 CYCLES

Before Install 286 HRS ­­­­­­­

Filter 661 HRS ­­­­­­­

Belt 373 HRS ­­­­­­­

Blower 473 HRS 100 CYCLES

Compressor 1 46 HRS 58 CYCLES

Compressor 2 14 HRS 17 CYCLES

Compressor 3 0 HRS 0 CYCLES

Compressor 4 0 HRS 0 CYCLES

Outdoor Fan 1 14 HRS 24 CYCLES

Outdoor Fan 2 0 HRS 2 CYCLES

Outdoor Fan 3 0 HRS 0 CYCLES

Outdoor Fan 4 0 HRS 0 CYCLES

Outdoor Fan 5 0 HRS 0 CYCLES

Outdoor Fan 6 0 HRS 0 CYCLES

Heat Stage 1 4 HRS 11 CYCLES

Heat Stage 2 4 HRS 12 CYCLES

Humiditrol 0 HRS 5 CYCLES

Free Cooling 42 HRS 1608 CYCLES

UV Lamp 751 HRS ­­­­­­­

========================================================================

==

Sensor Data

OAT : 80 degF

RAT : 76 degF

DAT : 69 degF

ZAT : 59 degF

RH : 34 %

CO2 : 415 ppm

========================================================================

SmartAirflow

 

Calibrated on 9/27/2012 13:10:49

 

Supply Airflow Calibration Table

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

PWM(%) Speed(rpm) Airflow(cfm)

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

20 350 715

30 470 810

40 590 907

50 670 1079

60 780 1265

70 860 1423

80 950 1680

90 1160 1839

96 1250 2198

 

Supply Airflow Targets

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

Mode Desired Airflow(cfm)PWM(%)

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

Cool High 1950 94

Cool Low 1200 56

Cool Med High 1800 91

Cool Med Low 1500 75

Heat 1900 93

Ventilation 1300 64

Smoke 2000 95

 

Economizer Differential Pressure at maximum Supply Airflow

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

Damper Position (%) Diff.Pressure(in.H2O)

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

0 0.25

50 0.1

100 0.05

 

Outside Airflow Targets

­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­

Minimum Outdoor Air/Minimum DCV: 400 cfm

Maximum DCV: 650 cfm

Minimum CO2: 500 ppm

Maximum CO2: 1200 ppm

 

========================================================================

==

Alarm/Status Log

( 82) 10.26.2009 16:27:04 CONTROLLER

RESET

( 5) 10.26.2009 16:25:13 BLOWER S52

========================================================================

==

END OF REPORT

Page 30: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 30

USB Service Report Example (If SmartAirflow™ is Calibrated)

SmartAirFlow

Page 31: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 31

Page 3

1

EventCode

Table 8. Alarm Codes

Display Message Action

0

1 ALARM(1) ERRATIC POWER CHECK POWER CONNECTIONS

2 ALARM(2) CHECK SETTINGS RESET CONTROLLER. CHECK UNIT SETTINGS. CONTACT LENNOX IF PROBLEM PERSISTS.

3 Reserved

4* ALARM(4) SMOKE A173 SMOKE MODE. CHECK FOR SOURCE OF SMOKE.

5 ALARM(5) BLOWER S52 UNIT OFF. AIR FLOW SWITCH OPEN 16 SEC AFTER DEMAND. CHECK BLOWER PARTS

6* ALARM(6) FILTER S27 REPLACE FILTER OR CHECK FILTER SWITCH S27

7 ALARM(7) CONTROLLER PROBLEM RESET CONTROLLER. CHECK UNIT SETTINGS. CONTACT LENNOX IF PROBLEM PERSISTS.

8* ALARM(8) STRIKE 3 ON BLOWER S52 LOCKOUT. MULTIPLE CODE 5. CHECK BLOWER PARTS

9 - 11 Reserved

12 ALARM(12) COMP 1 HIGH PRESS S4 COMP OFF. CHECK CHARGE, FANS, COIL.

13* ALARM(13) STRIKE 3 ON COMP 1 HIGH PRESS S4 COMP LOCKOUT. CHECK CHECK CHARGE, FANS, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

14 ALARM(14) COMP 2 HIGH PRESS S7 COMP OFF. CHECK CHARGE, FANS, COIL.

15* ALARM(15) STRIKE 3 ON COMP 2 HIGH PRESS S7 COMP LOCKOUT. CHECK CHECK CHARGE, FANS, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

16 ALARM(16) COMP 3 HIGH PRESS S28 COMP OFF. CHECK CHARGE, FANS, COIL.

17* ALARM(17) STRIKE 3 ON COMP 3 HIGH PRESS S28 COMP LOCKOUT. CHECK CHARGE, FANS, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

18 ALARM(18) COMP 4 HIGH PRESS S96 COMP OFF. CHECK CHARGE, FANS, COIL.

19* ALARM(19) STRIKE 3 ON COMP 4 HIGH PRESS S96 COMP LOCKOUT. CHECK CHECK CHARGE, FANS, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

20 ALARM(20) UNIT SHUTDOWN A42 CHECK PHASE MONITOR

21* ALARM(21) STRIKE 3 UNIT SHUTDOWN A42 CHECK PHASE MONITOR

22 ALARM(22) COMP 1 LOW PRESS S87 COMP OFF. CHECK CHARGE, FILTERS, AIR FLOW. COIL

23* ALARM(23) STRIKE 3 ON COMP 1 S87 COMP LOCKOUT. CHECK CHECK CHARGE, FILTER, AIR FLOW, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

24 ALARM(24) COMP 2 LOW PRESS S88 COMP OFF. CHECK CHARGE, FILTERS, AIR FLOW. COIL

25* ALARM(25) STRIKE 3 ON COMP 2 S88 COMP LOCKOUT. CHECK CHECK CHARGE, FILTER, AIR FLOW, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

26 ALARM(26) COMP 3 LOW PRESS S98 COMP OFF. CHECK CHARGE, FILTERS, AIR FLOW. COIL

27* ALARM(27) STRIKE 3 ON COMP 3 S98 COMP LOCKOUT. CHECK CHECK CHARGE, FILTER, AIR FLOW, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

28 ALARM(28) COMP 4 LOW PRESS S97 COMP OFF. CHECK CHARGE, FILTERS, AIR FLOW. COIL

29* ALARM(29) STRIKE 3 ON COMP 4 S97 COMP LOCKOUT. CHECK CHECK CHARGE, FILTER, AIR FLOW, COIL. USE SERVICE MENU TO CLEAR LOCKOUTS.

30 ALARM(30) CHECK 2 AMP FUSE UNIT SHUTDOWN S149 CHECK OVERFLOW SW

31* ALARM(31) STRIKE 3 UNIT SHUTDOWN S149 CHECK OVERFLOW SW

32 ALARM(32) COMP 1 FRZSTAT OPEN S49 COMP OFF. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

33* ALARM(33) STRIKE 3 COMP 1 FRZSTAT OPEN S49 COMP LOCKOUT. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

34 ALARM(34) COMP 2 FRZSTAT OPEN S50 COMP OFF. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

35* ALARM(35) STRIKE 3 COMP 2 FRZSTAT OPEN S50 COMP LOCKOUT. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

36 ALARM(36) COMP 3 FRZSTAT OPEN S53 COMP OFF. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

37* ALARM(37) STRIKE 3 COMP 3 FRZSTAT OPEN S53 COMP LOCKOUT. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

38 ALARM(38) COMP 4 FRZSTAT OPEN S95 COMP OFF. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

39* ALARM(39) STRIKE 3 COMP 4 FRZSTAT OPEN S95 COMP LOCKOUT. CHECK FRZSTAT, AIR FLOW, CHARGE, COIL, FILTER, OUTSIDE TEMP

40 ALARM(40) RETURN AIR OVER HEAT LIMIT RT16 HEAT ABOVE SETPOINT. CHECK SPACE CONDITIONS OR SENSOR

41 ALARM(41) RETURN AIR UNDER COOL LIMIT RT16 COOL BELOW SETPOINT. CHECK SPACE CONDITIONS OR SENSOR

42ALARM(42) CHECK 2 AMP FUSE UNIT SHUTDOWN S42 ORS135

CHECK EXT MTR OVERLOADS

43* ALARM(43) STRIKE 3 UNIT SHUTDOWN S42 OR S135 CHECK EXT MTR OVERLOADS

Page 32: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 3

2

Table 8. Alarm CodesEventCode

ActionDisplay Message

EventCode

44* ALARM(44) GAS VALVE ON NO DEMAND GV1 UNIT OFF. GV1 POWER BUT NO DEMAND. CHECK GAS PRESS, GAS VALVE

45* ALARM(45) GAS VALVE ON NO DEMAND GV3 UNIT OFF. GV3 POWER BUT NO DEMAND. CHECK GAS PRESS, GAS VALVE

46 - 48 Reserved

49* ALARM(49) NO 24VAC ON A59 (C2) BOARD THIRD AND FOURTH COMPRESSORS ARE OFF.

50 ALARM(50) PRIMARY HEAT 1 LIMIT OPEN S10 HEAT SECT 1 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

51* ALARM(51) STRIKE 3 PRIMARY HEAT 1 LIMIT OPEN S10 HEAT SECT 1 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

52 ALARM(52) SECONDARY HEAT 1 LIMIT OPEN S21 HEAT SECT 1 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

53* ALARM(53) STRIKE 3 SECONDARY HEAT 1 LIMIT OPEN S21 HEAT SECT 1 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, FILTER, LIMIT, AND WIRING.

54

ALARM(54) HEAT 1 ROLL OUT OPEN HEAT SECT 1 CHECK GAS ROLL OUT S47

ALARM(54) HEAT 1 S15 LIMIT OPEN HEAT SECT 1 LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

55*

ALARM(55) STRIKE 3 HEAT 1 ROLL OUT OPEN HEAT SECT 1 CHECK GAS ROLL OUT S47

ALARM(55) STRIKE 3 HEAT 1 S15 LIMIT OPEN HEAT SECT 1 LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

56 ALARM(56) HEAT 1 CAI SWITCH S18 HEAT SECT 1 CHECK COMBUSTION AIR MOTOR & PROOF SWITCH

57* ALARM(57) STRIKE 3 HEAT 1 CAI SWITCH S18 HEAT SECT 1 OFF CHECK COMBUSTION AIR MOTOR & PROOF SWITCH

58 ALARM(58) HEAT 1 NO PROOF GAS VALVE GV1 HEAT SECT 1 CHECK IGNITION CONTROL, FLAME PROOF, GV1, GAS SUPPLY

59* ALARM(59) STRIKE 3 NO PROOF GAS VALVE GV1 HEAT SECT 1 CHECK IGNITION CONTROL, FLAME PROOF, GV1, GAS SUPPLY

60 ALARM(60) PRIMARY HEAT 2 LIMIT OPEN S99 HEAT SECT 2 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

61* ALARM(61) STRIKE 3 PRIMARY HEAT 2 LIMIT OPEN S99 HEAT SECT 2 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

62 ALARM(62) HEAT 2 LIMIT OPEN S100 HEAT SECT 2 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.

63* ALARM(63) STRIKE 3 HEAT 2 LIMIT OPEN S100 HEAT SECT 2 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, FILTER, LIMIT, AND WIRING.

64 ALARM(64) HEAT 2 ROLLOUT OPEN S69 CHECK ROLLOUT SENSOR AND GAS

65* ALARM(65) STRIKE 3 ROLLOUT OPEN S69 CHECK ROLLOUT SENSOR AND GAS

66 ALARM(66) HEAT 2 CAI SWITCH S45 HEAT SECT 2 CHECK COMBUSTION AIR MOTOR & PROOF SWITCH

67* ALARM(67) STRIKE 3 HEAT 2 CAI SWITCH S45 HEAT SECT 2 OFF CHECK COMBUSTION AIR MOTOR & PROOF SWITCH

68 ALARM(68) HEAT 2 NO PROOF GAS VALVE GV3 HEAT SECT 2 CHECK IGNITION CONTROL, FLAME PROOF, GV3, GAS SUPPLY

69* ALARM(69) STRIKE 3 NO PROOF GAS VALVE GV3 HEAT SECT 2 CHECK IGNITION CONTROL, FLAME PROOF, GV3, GAS SUPPLY

70 - 72 Reserved

73 ALARM(73) NETWORK SENSOR ERROR CHECK WITH INTEGRATOR FOR REFRESH RATE, NETWORK STATUS LIGHTS AND WIRING

74* ALARM(74) ZONE SENSOR A2 CHECK ZONE SENSOR AND WIRING

75* ALARM(75) OUTDOOR TEMP SENSOR RT17 CHECK SENSOR AND WIRING

76* ALARM(76) CHECK 2 AMP FUSE HUMIDITY SENSOR A91 CHECK SENSOR AND WIRING

77* ALARM(77) DISCHARGE AIR TEMP SENSOR RT6 CHECK SENSOR AND WIRING

78* ALARM(78) RETURN AIR TEMP SENSOR RT16 CHECK SENSOR AND WIRING

79* ALARM(79) ADD-ON BOARD PROBLEM ADD-ON BRD PROBLEM, RESET TO CLEAR

80 ALARM(80) ADD-ON BOARD PROBLEM ADD-ON BRD PROBLEM

81 ALARM(81) REHEAT SETUP ERROR CHECK REHEAT SETTINGS

82 ALARM(82) CONTROLLER RESET NO ACTION NEEDED

83* ALARM(83) INCORRECT SETTINGS CHECK CONFIGURATION

84 Reserved

85 ALARM(85) INCORRECT HUMIDITROL SETTINGS CHECK HUMIDITROL SETTINGS

86* ALARM(86) CONFLICTING TSTAT INPUT CHECK TSTAT INPUTS FOR SIMULTANEOUS HEAT AND COOL AND WIRING

87 Reserved

88 ALARM(88) CONTROLLER PROBLEM INTERNAL CONTROLLER PROBLEM. RESET TO CLEAR.

Page 33: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 33

Page 3

3

Table 8. Alarm CodesEventCode

ActionDisplay Message

EventCode

89 Reserved

90 ALARM(90) CONTROLLER PROBLEM INTERNAL CONTROLLER PROBLEM. RESET TO CLEAR.

91* ALARM(91) OUTDOOR ENTH SENSOR A7 CHECK ECON DIP SWITCH AND ENTH DIAL SETTINGS, SENSOR AND WIRING

92* ALARM(92) INDOOR ENTH SENSOR A62 CHECK ECON DIP SWITCH AND ENTH DIAL SETTINGS, SENSOR AND WIRING

93* ALARM(93) BACKUP MODE CHECK COMM LOSS WITH NETWORK SENSOR

94 ALARM(94) BAD ZONE SENSOR SETPOINT CHECK SETPOINT AND EMS PROGRAMMING

95 ALARM(95) SETTINGS HAVE CHANGES SETTINGS HAVE CHANGED AT THE UNIT

96, 97 Reserved

98 ALARM(98) CONTROLLER PROBLEM INTERNAL CONTROLLER PROBLEM. RESET TO CLEAR.

99 ALARM(99) OUTDOOR ECON SENSOR A24 CHECK SENSOR AND WIRING

100* ALARM(100) AIR VOL CONTROL SETUP ERROR CHECK FOR PROPER INSTALLATION OF GP BOARD AND SETTINGS

101 ALARM(101) MGV CONTROL SETUP ERROR CHECK FOR PROPER INSTALLATION OF GP BOARD AND SETTINGS

102* ALARM(102) GP CONTROL SETUP ERROR CHECK FOR PROPER INSTALLATION OF GP BOARD AND SETTINGS

103* ALARM(103) ADVANCED CONTROL SETUP ERROR CHECK PRODIGY SETTINGS

104 Reserved

105 ALARM(105) ADVANCED ECON CONTROL SETUP ERROR CHECK ECON SWITCHES, DIALS, AND PRODIGY SETTINGS

106* ALARM(106) BUILDING PRESS SENSOR A34 CHECK SENSOR AND WIRING

107* ALARM(107) DUCT SUPPLY PRESS SENSOR A30 CHECK SENSOR AND WIRING

108 ALARM(108) DUCT SUPPLY HIGH PRESS SENSOR A30 CHECK SENSOR AND WIRING

109* ALARM(109) STRIKE 3 DUCT SUPPLY PRESS SENSOR A30 CHECK SENSOR AND WIRING

110 ALARM(110) WAITING ON NETWORK DATA CHECK NETWORK OR COMFORT SENSOR AND WIRING

111 ALARM(111) CONTROLLER PROBLEM INTERNAL CONTROLLER PROBLEM. RESET TO CLEAR.

112 ALARM(112) CONTROLLER PROBLEM INTERNAL CONTROLLER PROBLEM. RESET TO CLEAR.

113 Reserved

114* ALARM(114) CONTROLLER PROBLEM POWER NOISE PROBLEM. RESET TO CLEAR.

115 ALARM(115) UNIT OFFLINE FOR TEST CHECK PRODIGY SERVICE TEST MODE

116&117 Reserved

118 ALARM(118) NO DISPLAY DISPLAY NOT DETECTED

119 STATUS(119) RESET CAUSED BY WATCHDOG TIMEOUT CONTACT LENNOX

120* ALARM(120) ADD-ON BOARD MCB PROBLEM MCB CONFIGURATION SETUP PROBLEM. RESET TO CLEAR OR ADVANCED SETUP.

121* ALARM(121) LINE FREQ DOES NOT MATCH UNIT CONFIG

122* ALARM(122) 24VAC PRIMARY VOLTAGE LOW

123* ALARM(123) 24VAC PRIMARY VOLTAGE HIGH

124* ALARM(124) 24VAC SECONDARY VOLTAGE LOW

125* ALARM(125) 24VAC SECONDARY VOLTAGE HIGH

126* ALARM(126) LINE PHASING DOES NOT MATCH UNIT CONFIG

127 Reserved

128* ALARM(128) 24VAC POWER LOSS

129* ALARM(129) VFD SHUTDOWN VFD FAULT DETECTED. CHECK BELT AND FOR BLOWER OVERLOAD. FIX SOURCE OF FAULT AND RESET M2.

130 ALARM(130) VFD BYPASS ENGAGED VFD BYPASS MODE IS ENGAGED. BLOWER MAY OR MAY NOT BE ON. DISENGAGE AT MSAV MENU.

131 Reserved

132 ALARM(132) VFD BYPASS NOT CONFIGURED VFD BYPASS MODE HAS NOT BEEN SELECTED. UNIT OPERATES AS IF BYPASS IS NOT INSTALLED.

133 ALARM(133) CHECKING POWER M2 UNABLE TO DETERMINE CORRECT PHASE/VOLTAGE.

134 ALARM(134) LOW SUPPLY CFMSMARTAIRFLOW™ ENABLED RTU ­ INDICATES AIRFLOW TARGET CANNOT BE ACHIEVED. CHECK CAUSE OFAIRFLOW REDUCTION SUCH AS DIRTY FILTER, CHANGES IN DUCT WORK, ETC

Page 34: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 3

4

Table 8. Alarm CodesEventCode

ActionDisplay Message

EventCode

135* ALARM(135) NO AIRFLOW BLOWER RPM IS TOO LOW AS INDICATES BY BLOWER STATUS. THIS MEANS THAT THE BLOWER IS NOT WORKING."

136*ALARM(136) OUTSIDE AIR DAMPER/ECON MECHANICALFAULT

OUTDOOR AIR DAMPER MAY BE IN A STUCK CONDITION.

137 ALARM(137) LOW OUTDOOR AIRFLOW OUTDOOR AIR DAMPER MAY BE IN A STUCK CONDITION.

138 Reserved

139 ALARM(139) OUTDOOR AIRFLOW TOO HIGH VENTILATION CFM IS TOO HIGH SO THE RTU IS WASTING ENERGY.

140ALARM(140) CFM TARGET TOO LOW ­ THIS SETUP MIN XXXXCFM

VERIFY THE MSAV.BLOWER SETTINGS AND SET THE CM TARGETS ABOVE XXXX CFM

141ALARM(141) CFM TARGET TOO HIGH ­ THIS SETUP MAXXXXX CFM

VERIFY THE MSAV.BLOWER SETTINGS AND SET THE CM TARGETS BELOW XXXX CFM

142 Reserved

143* ALARM(143) DAMPER PRESSUREDAMPER DIFFERENTIAL PRESSURE SENSOR VALUE IS NOT WITHIN THE VALID RANGE. MAY BE PROBLEM WITHTHE SENOR TUBING, HIGH RETURN DUCT RESISTANCE ETC.

144 ALARM(144) FIRMWARE UPDATE M2 CONTROL BOARD FIRMWARE UPDATE RECORDED

145* ALARM(145) VCB NOT PRESENT SMARTAIRFLOW™ IS INSTALLED BUT VCB BOARD IS NOT PRESENT/NOT RECOGNIZED BY M2.

146 Reserved

147* ALARM(147) OA DAMPER ERRORWHEN THE DIFFERENCE BETWEEN THE TARGET POSITION AND THE ACTUAL POSITION OF DAMPER IS GREAT­ER THAN 30%, OR THE DAMPER MOTOR FEEDBACK < 0.5V, OR TEMPERATURE MEASUREMENTS INDICATE POS­SIBLE STUCK DAMPER BLADES.

148* ALARM(148) SMARTAIRFLOW CONFIG ERRORSMARTAIRFLOW™ OPTION IS INSTALLED BUT BLOWER TYPE IS NOT EP CAPABLE OR DAMPER IS NOT INSTALLED.ONLY BLOWER TYPES M (VGD) AND E (ECM) ARE EP CAPABLE.

149* ALARM(149) VCB PRESSURE SENSOR ERROR HIGH OR LOW OUT OF RANGE READING FOR THE VCB1 PRESSURE SENSOR.

150* ALARM(150) NOT ECONOMIZING WHEN IT SHOULD DAMPER IS NOT OPEN ADEQUATELY AND RTU IS WASTING ENERGY.

151* ALARM(151) ECONOMIZING WHEN IT SHOULD NOT DAMPER IS OPEN EXCESSIVELY AND RTU IS WASTING ENERGY.

Page 35: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 35

Wiring Diagrams (036, 048, 060 Units)

Page 36: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 36

Wiring Diagrams (ACCESSORIES)

Page 37: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 37

Wiring Diagrams (ACCESSORIES)

P299J299A

1

2

3

B

4

5C

6

7

10

D

8

9

DI-1

R

C

DI-2

R

DI-3

R

DI-4

C

P304

USE DI3 TO CONNECT:

1. OVERFLOW SWITCH

2. PHASE MONITOR MODULE

USE DI2 TO CONNECT:1. OVERLOAD CONTACTS

J298

8

9

10

P153

J153

1

3

2

4

5

6

P1

93

J1

04

2

1 1

J1

93

2

TB37

1

3

2

4

K1

K2

K4

5

6

A130

5

6

Page 38: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 38

Wiring Diagrams (240, 300 Units) N

OT

E −

IF

AN

Y W

IRE

IN

TH

IS A

PPL

IAN

AC

E I

S R

EPL

AC

ED

IT M

UST

BE

RE

PLA

CE

D W

ITH

WIR

E O

F L

IKE

SIZ

E,

RA

TIN

G, T

ER

MIN

AT

ION

AN

D I

NSU

LA

TIO

N T

HIC

KN

ESS

.

WA

RN

ING

− E

LE

CT

RIC

SH

OC

K H

AZ

AR

D, C

AN

CA

USE

INJU

RY

OR

DE

AT

H .

UN

IT M

UST

BE

GR

OU

ND

ED

IN

AC

CO

RD

AN

CE

WIT

H N

AT

ION

AL

AN

D L

OC

AL

CO

DE

S.D

ISC

ON

NE

CT

AL

L P

OW

ER

BE

FOR

E S

ER

VIC

ING

.

S42

USE

D O

N ”

M”

VO

LTA

GE

UN

ITS

AN

DU

NIT

S W

ITH

HIG

H E

FFIC

IEN

CY

MO

TO

RS

ON

LY O

N U

NIT

S W

ITH

HU

MID

ITR

OL

OPT

ION

T43

T43

L14

L30

DI

1

DI

2

A55

EX

TE

RN

AL

HU

MID

ITR

OL

CO

NTA

CT

S

F6 A

ND

F10

FU

SES

AR

E U

SED

ON

”Y

”V

OLT

AG

E U

NIT

S O

NLY

S49

AN

D S

50 A

RE

PA

RT

OF

5VD

C C

IRC

UIT

Page 39: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 39

KEY COMPONENT

A55 PANEL, MAIN

A59 PANEL, COMPRESSORS 3 AND 4

A169 PANEL, MOTOR CONTROL

A184 CONTROL, VCB BOARD

B1 COMPRESSOR 1

B2 COMPRESSOR 2

B3 MOTOR, BLOWER

B4 MOTOR, OUTDOOR FAN 1

B5 MOTOR, OUTDOOR FAN 2

B10 MOTOR, EXHAUST FAN 1

B11 MOTOR, EXHAUST FAN 2

B13 COMPRESSOR 3

B20 COMPRESSOR 4

B21 MOTOR, OUTDOOR FAN 3

B22 MOTOR, OUTDOOR FAN 4

B23 MOTOR, OUTDOOR FAN 5

B24 MOTOR, OUTDOOR FAN 6

C1 CAPACITOR, OUTDOOR FAN 1

C2 CAPACITOR, OUTDOOR FAN 2

C6 CAPACITOR, EXHAUST FAN 1

C8 CAPACITOR, EXHAUST FAN 2

C18 CAPACITOR, OUTDOOR FAN 3

C19 CAPACITOR, OUTDOOR FAN 4

C20 CAPACITOR, OUTDOOR FAN 5

C21 CAPACITOR, OUTDOOR FAN 6

CB8 CIRCUIT, BREAKER T1

CB10 CIRCUIT BREAKER, MAIN DISCONNECT UNIT

CB18 CIRCUIT, BREAKER T18

F6 FUSE, EXHAUST FAN

F10 FUSE, OUTDOOR FAN MOTOR

F30 FUSE, TRANSFORMER T29 PRIMARY

F31 FUSE, TRANSFORMER T29 SECONDARY

HR1 HEATER COMPRESSOR 1

HR2 HEATER COMPRESSOR 2

HR5 HEATER COMPRESSOR 3

HR11 HEATER COMPRESSOR 4

J11 JACK, GFI, RECEPTACLE

J18 JACK, EXHAUST FAN COMP

J24 JACK, EXHAUST FAN

J47 JACK, OUTDOOR FAN 1

J52 JACK, OUTDOOR FAN 2

J86 JACK, OUTDOOR FAN INTERFACE

J87 JACK, OUTDOOR FAN INTERFACE 2

J106 JACK, OUTDOOR FAN 3

J107 JACK, OUTDOOR FAN 4

J108 JACK, OUTDOOR FAN 5

J109 JACK, OUTDOOR FAN 6

J118 JACK, COMPRESSOR 3 AND 4, CONTROL

J119 JACK, COMPRESSOR 3 AND 4, INPUT

J132 JACK, BLOWER , EXHAUST FAN MOTOR 1

J133 JACK, BLOWER , EXHAUST FAN MOTOR 2

J138 JACK, EXHAUST FAN 2

J139 JACK, EXHAUST FAN 3

J263 JACK, HIGH AND LOW PRESSURE SWITCHES

J264 JACK, BLOWER DECK

J265 JACK, CONTACTORS AND RELAYS

K2,-1 CONTACTOR, COMPRESSOR 2

K3, -1 CONTACTOR, BLOWER

K10,-1,2 RELAY, OUTDOOR FAN 1

K14,-1 CONTACTOR, COMPRESSOR 3

K65-1,2 RELAY, EXHAUST FAN

K68,-1 RELAY, OUTDOOR FAN 2

K146,1 CONTACTOR, COMPRESSOR 4

K149,-1 RELAY, OUTDOOR FAN 3

K150,-1 RELAY, OUTDOOR FAN 4

Page 40: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 40

K152,-1 RELAY, OUTDOOR FAN 5

K153,-1,2 RELAY, OUTDOOR FAN 6

L14 VALVE, SOLENOID REHEAT COIL 1

L30 VALVE, SOLENOID REHEAT COIL 2

P18 PLUG, EXHAUST FAN COMP

P24 PLUG, EXHAUST FAN

P47 PLUG, OUTDOOR FAN 1

P52 PLUG, OUTDOOR FAN 2

P86 PLUG, OUTDOOR FAN INTERFACE

P87 PLUG, OUTDOOR FAN INTERFACE 2

P106 PLUG, OUTDOOR FAN 3

P107 PLUG, OUTDOOR FAN 4

P108 PLUG, OUTDOOR FAN 5

P109 PLUG, OUTDOOR FAN 6

P118 PLUG, COMPRESSOR 3 AND 4, CONTROL

P119 PLUG, COMPRESSOR 3 AND 4, INPUT

P132 PLUG, EXHAUST FAN MOTOR 1

P133 PLUG, EXHAUST FAN MOTOR 2

P138 PLUG, EXHAUST FAN 2

P263 PLUG, HIGH AND LOW PRESSURE SWITCHES

P264 PLUG, BLOWER DECK

P265 PLUG, CONTACTORS AND RELAYS

P267 PLUG,OUTDOOR FAN AREA

P268 PLUG, TRANSFORMERS

P269 PLUG, HUMIDITROL

P299 PLUG, SAFETY

PT5 PRESSURE TRANSDUCER, ECONOMIZER

RT17 SENSOR, OUTDOOR AIR

S4 SWITCH, LIMIT HI PRESS COMPRESS 1

S7 SWITCH, LIMIT HI PRESS COMPRESS 2

S11 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 1

S28 SWITCH, LIMIT HI PRESS COMPRESS 3

S42 SWITCH, OVERLOAD RELAY BLOWER MOTOR

S48 SWITCH, DISCONNECT

S49 SWITCH, FREEZE STAT COMPRESS 1

S50 SWITCH, FREEZE STAT COMPRESS 2

S53 SWITCH, FREEZE STAT COMPRESS 3

S84 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 2

S85 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 3

S87 SWITCH, LOW PRESS, COMP 1

S88 SWITCH, LOW PRESS, COMP 2

S94 SWITCH, LOW PRESS, LOW AMBIENT KIT COMP 4

S95 SWITCH, FREEZE STAT COMPRESS 4

S96 SWITCH, LIMIT HI PRESS COMPRESS 4

S97 SWITCH, LOW PRESS, COMP 4

S98 SWITCH, LOW PRESS, COMP 3

Page 41: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 41

Page 4

1

Table 9. M2 unit controller signal reference diagram

63

24 VAC COM24VAC

-

S - BUS

2 2 32 3 23 323

S +S2

P298 P299P297

2

MS 9413-10-407MS 9413-03-401 MS 9413-10-408 MS 9413-10-409

3

Pin # Label Description Type Description Part Number

P297 Thermostat Assembly MS 9413-10-407

1 R TRANSFORMER 1 24VAC POWER 24VAC Header & Label MS 9413-10-011

2 C TRANSFORMER 1 24V COMMON 24V COMM - Header MSLO 9408-010-576-960-000-00

3 G BLOWER SIGNAL 24VAC DI - Label MZ 9400-10-007

4 W1 1ST STAGE HEATING 24VAC DI Screw terminal MF 9306-002-0A-002-G

5 W2 2ND STAGE HEATING 24VAC DI Screw terminal MF 9306-006-43-000-G

6 Y1 1ST STAGE COOLING 24VAC DI Screw terminal MF 9306-002-49-000-G

7 Y2 2ND STAGE COOLING 24VAC DI

8 OCP OCCUPIED SIGNAL 24VAC DI

9 GLO GLOBAL CONTROL INPUT 24VAC DI

10 RSV RESERVED NA

P298 IAQ Interface Assembly MS 9413-10-408

1 R TRANSFORMER 1 24VAC POWER 24VAC Header & Label MS 9413-10-012

2 C TRANSFORMER 1 24V COMMON 24V COMM - Header MSLO 9408-S10-000

3 IAQ+ INDOOR AIR QUALITY 0-10VDC AI - Label MZ 9400-10-008

4 GND INDOOR AIR QUALITY 0-10VDC AI Screw terminal MF 9306-002-60-000-G

5 HUM RH SENSOR 0-10VDC AI Screw terminal MF 9306-002-64-000-G

6 GND DIGITAL GROUND GND Screw terminal MF 9306-003-4D-000-G

7 TMP ZONE SENSOR 0-10VDC AI Screw terminal MF 9306-003-4L-000-G

8 DO1 SERVICE RELAY OUTPUT 24VAC DO

9 GND 24 VAC COMMON 24V COMM

10 DO2 EXHAUST FAN 24VAC DO

P299 Safety Assembly MS 9413-10-409

1 DI1 SMOKE DETECTOR (NO) 24VAC DI Header & Label MS 9413-10-013

2 R TRANSFORMER 1 24VAC POWER 24VAC - Header MSLO 9408-010-075-960-000-00

3 C TRANSFORMER 1 24V COMMON 24V COMM - Label MZ 9400-10-009

4 DI2 DIGITAL INPUT 2 FORMER (S42 & S135) 24VAC DI Screw terminal MF 9306-003-0H-000-G

5 R TRANSFORMER 1 24VAC POWER 24VAC Screw terminal MF 9306-002-0P-002-G

6 DI3 DIGITAL INPUT 3 FORMER (S149 & A42 FOR A BOX) 24VAC DI Screw terminal MF 9306-002-37-001-G

7 R TRANSFORMER 1 24VAC POWER 24VAC Screw terminal MF 9306-003-01-000-G

8 DI4 DIGITAL INPUT 4 FORMER (HUMIDITROL INPUT) 24VAC DI

9 C TRANSFORMER 1 24V COMMON 24V COMM

10 RSV RESERVED NA

Page 42: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 4

2

Table 10. M2 board connections diagram

Pin# Label Description Type

10P262 Economozer control

1 R 24VAC Power 24 VAC

2 GND Digital Ground 24 VAC COM

3 VOT Damper Control 2-10 VDC AO

4 DPOS Damper Position Feedback 2-10 VDC AI

5 GND Digital GroundRES 0-5 VDC

6 RT16+ Return Air Temp 7 K68 Relay Outdoor Fan 2 24 VAC DO 5 RSV Reserved 24 VAC DI

P270 D

ISP

LA

Y P

CB

7 A7 S Outdoor Enthalpy Sensor 4-20 mA AI 8 COM 24 VAC Common COM P270 Sensor Board

8 20 VDC 10 Volts DC Power 20 VDC 9 K13 Relay Combustion Air Blower 1 24 VAC DO 1 + RS-485 Communication BUS

9 A62 S Indoor Enthalpy Sensor 4-20 mA AI 10 K19 Relay Combustion Air Blower 2 24 VAC DO 2 - RS-485 Communication BUS

10 A173 Smoke Detector 24 V DI 11 COM 24 VAC Common COM 3 COM 24 VAC Common Transformer 1 24 VAC COM

11 T1 Smoke Detector 24V 24 VAC Power

12 K65 Relay Exhaust Fan 24 VAC DO 5 T1 24 VAC Transformer 1 24 VAC

12 COM Smoke Detector 24 Common P266 Heating Control P271 Heating 1 Safety

P263 High $ Low Pressure 1 COM 24 VAC Common 24 VAC COM 1 S10-C Primary Limit Burner 1 C

SW 24 VAC1 L1 Reversing Valve 24 VAC DO 2 A3, K15 Heat 1, Electric Heat 1 24 VAC DO 2 S10-NC Primary Limit Burner 1 NC

2 COM 24 VAC Common 24 VAC COM 3 W2, K16 Heat 2, Electric Heat 2 24 VAC DO 3 S10-NC Primary Limit Burner 1 NO

3 S4 High Pressure Compressor 1 SW 24 VAC 4 COM 24 VAC Common 24 VAC COM 4 S21-C Secondary Limit Burner 1 CSW 24 VAC

4 T1 24VAC Power 24 VAC 5 A12, K17 Heat 3, Electric Heat 3 24 VAC DO 5 S21-NC Secondary Limit Burner 1 NC

5 S87 Low Pressure Compressor 1 NC SW 24 VAC 6 W2, K15 Heat 4, Electric Heat 4 24 VAC DO 6 S47 Rollout Switch Burner 1 CSW 24 VAC

6 S7 High Pressure Compressor 2 SW 24 VAC P267 Outdoor Fan Area 7 S47 Rollout Switch Burner 1 NC

7 T1 24VAC Power 24 VAC 1 RT17 Outdoor Air TempRES 0-5 VDC

8 S18 Cab Proof Switch 1SW 24 VAC

8 S88 Low Pressure Compressor 2 SW 24 VAC 2 GND Digital Ground 9 S18 Cab Proof Switch 1

P264 Blower Deck Area 3 S11 Low Pressure Fan 1 SW 24 VAC 10 GV1 Gas Valve Sense 1 24 VAC DI

1 RT6 Discharge Air TempRES 0-5 VDC

4 R 24 VAC 24 VAC DO P272 Heating 2 Safety

2 GND Digital Ground 5 S84 Low Pressure Fan 2 SW 24 VAC 1 S99-C Primary Limit Burner 2 C

SW 24 VAC3 S49 Freezestat 1 (NC) SW 5 VDC 6 S6 Defrost Temp SW 5 VDC 2 S99-NC Primary Limit Burner 2 NC

4 VSS 5VDC 5 VDC 7 VSS 5VDC 5 VDC 3 S99-NO Primary Limit Burner 2 NO

5 S50 Freezestat 2 (NC) SW 5 VDC 8 S46 Defrost Pressure 1 SW 5 VdC 4 S100-C Secondary Limit Burner 2 CSW 24 VAC

6 S52 Air Flow Switch (NO) SW 5 VDC P268 Power 5 S100-NC Secondary Limit Burner 2 NC

7 VSS 5VDC 5 VDC 1 T1-1 24 VAC Power Transformer 1 24 VAC 6 S69 Rollout Switch Burner 2 CSW 24 VAC

8 S27 Dirty Filter Switch (NO) SW 5 VDC 2 T1-COM 24 VAC Common Transformer 1 24 VAC COM 7 S69 Rollout Switch Burner 2 NC

P265 Contactors / Relays 3 T18-1 24 VAC Power Transformer 1 24 VAC 8 S45 Cab Proof Switch 2SW 24 VAC

1 COM 24 VAC Common 24 VAC COM 4 T18-COM 24 VAC Common 24 VAC COM 9 S45 Cab Proof Switch 2

2 K1 Contactor Compressor 1 24 VAC DO P269 Reheat - Humiditrol 10 GV3 Gas Valve Sense 2 24 VAC DI

3 K2 Contactor Compressorr 2 24 VAC DO 1 T43 24 VAC Power 24 VAC

4 K3 Contactor Blower 24 VAC DO 2 T43 24 VAC Common 24 VAC COM

5 COM 24 VAC Commo 24 VAC COM 3 L14 Reheat Solenoid 1 24 VAC DO

6 K10 Relay Outdoor Fan 1 24 VAC DO 4 L30 Reheat Solenoid 2 24 VAC DO

Page 43: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 43

Quick Start Guide

CAUTIONCheck rooftop unit electrical power for proper voltage and phasing. Check gas train components.

1. Turn on unit, correct alarm issues as necessary.2. Follow GUIDED SETUP menu to properly configure unit (see Page 9).3. Be sure unit is in normal operating mode as seen in display (COOLING, HEATING, IDLE, etc).4. Conduct unit startup to verify operation under SERVICE-> TEST menu (see Page 12).5. Insert USB memory stick into display cover to verify service and collect unit information.

Control Mode Menu Setup Needed Tips

THERMOSTAT (Factory set for 2 stage thermostat) � Check 2 AMP fuse if wiring error.

� Check LEDs for signals.

� Check ground switch position.

LOCAL MODE Change default backup setpoints; seeSETTINGS -> CONTROL -> LOCAL(Page 17).

� Give unit time to startup, error codes 74 and 93are expected.

� Humidity control requires sensor or error code 76

MSAV Change motor torque; see SETTINGS -> CONTROL -> MSAV(Page 19).

� Use LENNOX MSAV trained technician.

� Final motor CFM needs to be set by Test andBalance technician

� Blower charts are located in unit EHB.

BACnet Select control mode; see SETTINGS -> CONTROL -> BACNET(Page 18).

� Setup information to be verified with integrator.

� Follow wiring instructions including networktermination

� Remember to set MAC address 0-127

� Expert level BACnet service manual available.

LonTalk Select control mode; see SETTINGS-> CONTROL -> LONTALK(Page 18).

� Setup information to be verified with integrator.

� Follow wiring instructions including networktermination

� XIF file available. Neuron ID on sticker.

� Expert level LonTalk service manual available.

L Connection Select control mode; seeSETTINGS -> CONTROL -> LCONN(Page 17).

� Follow wiring instructions including networktermination

� Comfort Sensors are 24 VAC polarity sensitive.

� All network devices need to be correctlyaddressed

Damper Select control mode; seeSETTINGS -> SETPOINTS -> DAMPER(Page 16).

� Verify damper minimum positions

� Refer to Economizer section of manual for moredetail

Reheat Select sensor type; see SETTINGS -> CONTROL -> REHEAT(Page 18).

� Two possible connections, SENSOR andHUMIDISTAT

� Analog sensor wiring is polarity sensitive

For Lennox Service Support 1-800-4LENNOX. For Lennox Commercial website, go to www.lennoxcommercial.com.

Page 44: Prodigy Supersedes2/2013 Litho U.S.A. M2 Unit ControllerPage 1 506215-01 3/2014 Supersedes2/2013 Litho U.S.A. Prodigy® M2 Unit Controller INSTALLATION & SETUP GUIDE FOR THE M2 UNIT

Page 44

Revision History

12/2009 Initial production release.

6/2011 Revised software support; (3/11); add LONTALK in table on page 4; remove SmartWire Repair Tool Kit

11/2011 New firmware upload procedures; MSAV additions.

3/2013 Change diagram 537108-01 to 537108-02; revise trademarks throughout manual; added error code 147;DB1 menu changes; changes to economizer operation for new hardware.

6/2013 Add information concerning SmartAirflow™.

7/2013 Updated information concerning UNIT F/C options on page 6 and 15.