PUBLIC INFORMATION CENTRE NO. 2

Wednesday December 8, 20106:00 p.m. to 8:00 p.m.

North Bolton Elevated Tank/Reservoir and FeedermainMunicipal Class Environmental Assessment

Page 2: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Welcome to Public Information Centre No. 2

You can participate in the Study by:

Signing the attendance registerReviewing the display panelsAsking questions and discussingyour ideas with usSubmitting your comment sheetby January 12, 2011Indicating on your comment sheetwhether you would like to beadded to the Study Mailing List

Display boards will be available on the Region’s website,www.peelregion.ca/pw/water/ and click on Environmental Assessments – Caledon

Display PanelsDisplay Panels1. Welcome to Public Information

Centre No. 22. Introduction/Purpose of Public

Information Centre No. 23. Municipal Class EA Process4. Water Supply, Demand and Storage5. Graphical System Schematic of

Zone 6 Water Supply6. Servicing Needs7. Project Timeline8. Overall Evaluation Approach for

Water Storage Site9. Alternative Elevated Tank Sites10. Preferred Elevated Tank Site11. Typical Elevated Water Tank

Construction Process12. Alternative Feedermain Routes13. Preliminary Preferred Feedermain

Alternative14. Overview of Construction Impacts15. Actions to Limit Construction impacts16. Traffic Management17. Traffic Management (Cont’d)18. Impacts and Mitigation19. Next Steps20. Project Contacts

Panel 1

Page 3: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

The purpose of the Public Information Centre (PIC) is to provide interested and/or potentially affected stakeholders with anopportunity to participate in the planning and decision-making process.

IntroductionPeel Region is planning to construct a 9.0 ML (2.38 MG) Elevated Water Storage Tank to provide therequired storage and service to the Community of Bolton.The purpose of the study is to identify the preferred location of the new elevated tank.The elevated tank will augment the distribution system, provide pressure equalization, fire and emergencystorage to meet the demands of the existing developments, as well as the approved and futuredevelopment, as outlined by the 2007 Peel Region Water and Wastewater Servicing Master Plan Update.A 600mm/400mm (24”/16”) diameter feedermain, approx. 5.0 Km in length, is also proposed to beconstructed from the proposed elevated tank at South Hill to North Hill; to strengthen the Bolton-Zone 6distribution system redundancy.Currently there is a single feed to the North Hill from the South Hill. This new feedermain will stabilizecurrent flows and pressures and provide added security of supply to the North Hill.This Study has been undertaken as a Schedule ‘C’ under the requirements of the Municipal Class EA.

Purpose of Public Information Centre No. 2

Confirm the preferred alignment of the feedermain route

Confirm the preferred location of the elevated tank site

STUDY AREA

Panel 2

Page 4: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Municipal Class Environmental Assessment Process

Identify problem andopportunities

Identify Reasonable AlternativeSolutions to the problem

Evaluate Alternative Solutionsconsidering environmental and

traffic conditionsIdentify Alternative Solutions to

the problem

Complete ESRIdentify Alternative Designs forPreferred Solution

Inventory of natural, socio-economic and cultural

environmentIdentify impacts of Alternative

Designs after mitigation

Evaluate Alternative Designs

Place ESR on public record for30 days

Notify public and governmentagencies of completion of ESRand provision for Part II Order

Select Preferred Design

Design and

Construction

An Environmental Assessment (EA) is a clear and transparent planning process that includes theassessment of project impacts. The term ‘environment’ includes natural, socio-economic, cultural,transportation and cost.

Consult review agencies andpreviously interested and directly

affected publicWE ARE HERE

Phase 1

PROBLEM OROPPORTUNITY

Phase 2

ALTERNATIVESOLUTIONS

Phase 3

ALTERNATIVEDESIGN

CONCEPTS FORPREFERREDSOLUTION

Phase 4

ENVIRONMENTALSTUDY REPORT

Phase 5

IMPLEMENTATION

Panel 3

Page 5: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

TYPICAL PATTERN OF WATER DEMANDTYPICAL PATTERN OF WATER DEMAND

SIZING WATER SUPPLY FACILITIESTypical water consumption rates for residential and commercialproperties are multiplied by projected population and land useswithin the Pressure District to provide the necessary Averageand Peak demand figures used to design the variouscomponents of the system.Water Treatment Plants and Pumping Stations are typicallydesigned to meet the Maximum Day demand. Storage isrequired to meet the Peak Hour demands during the day andFire Flow requirements.

Water Supply, Demand and Storage

CURRENT & PROJECTED WATER DEMANDSThe figure below outlines the projected water demands andstaging of storage, based on the planned population andwater consumption rates. The current storage consist of a3.7 ML (1 MG) elevated tank. An additional 9.0 ML (2.38MG) storage is required to accommodate the approvedCommunity Plan growth.

PROJECTED STORAGE REQUIREMENT FORPROJECTED STORAGE REQUIREMENT FORBOLTONBOLTON –– PRESSURE ZONE 6PRESSURE ZONE 6

0

10

20

30

40

50

60

0 12 24 36 48 60 72 84 96 108 120 132 144 156 168

Pres

sure

(psi)

Time (hr)

2014 Max Day Demand Conditions

Existing Condition With Future Feedermain to North Hill

0

2

4

6

8

10

12

14

2000 2005 2010 2015 2020 2025 2030 2035

Requ

ired

Stor

age

Volu

me

(ML)

Year

WATER STORAGE STAGINGBOLTON - Pressure Zone 6

STORAGE VOLUMEREQUIRED BASED ONWATER DEMAND

CONSTRUCTION OF 9.0 ML (2.38 MG)ELEVATED TANK

CURRENTSTORAGE

Panel 4

Page 6: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Graphical System Schematic of Zone 6 Water Supply

Mayfield West Elevated TankZone 7

Zone 6Proposed Reservoir

297.2 m TWL

Panel 5

Page 7: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Currently, there is single feed to the NorthHill from the South HillThe new feedermain will stabilize currentflows and pressures and provide addedsecurity of supply to the North Hill

The new elevated 9.0 ML (2.38 MG) tank on theSouth Hill will provide additional storage toaccommodate the approved Community Plan growth

NorthBoosterStation

Servicing Needs

SouthBoosterStation

PRESSUREZONE 6

PRESSUREZONE 6

PRESSUREZONE 5

Panel 6

Page 8: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Early 2011

File EA Reportand 30-day

Public ReviewPeriod

Project Timeline

Two Primary StorageOptions (Inground vs.

Elevated Tank) and MultipleFeedermain Options

presented atPIC No. 1

November 2008

Additional HydraulicStudy Undertaken to

Confirm StorageSize and Confirm

Benefit ofFeedermain

Early 2010

April 2008

Commence EAStudy

Summer 2008

PreliminaryEvaluation and

Studies for ElevatedTank/Reservoir

Sites andFeedermain Routes

December 2009

Alternative Sites forElevated TankRe-evaluated

December 2010

PIC No. 2Selection of

Preferred ElevatedTank Site andFeedermainAlignment

January 12, 2011

Deadline for Publicand Review AgencyComment to Region

Summer 2010

Additional Studiesfor Elevated Tankand Feedermain

Routes

Two PrimaryFeedermain Options

Identified

Summer 2009

Tender andConstruction

2011

Additional StudiesUndertaken for Elevated

Tank Site Options onSouth Hill and

Feedermain Routes

Fall 2010

2012

Commissioningof Elevated

Tank

Panel 7

Page 9: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Overall Evaluation Approach for Water Storage SiteFour (4) concept areas were evaluated within the study area for the water storagesiting:

Conceptual Area 1 – Inground Reservoir– Requires highest elevation– Generally located at Old Church Road– Significantly north of Bolton

Conceptual Area 2 – North Hill - Elevated Tank– Nearest area of low pressures– At northern limit of Bolton, but near residential– Good elevations for elevated tank

Conceptual Area 3 – Northwest Bolton - Elevated Tank– At northern limit of Bolton– Within agricultural lands– Good elevations for elevated tank

Conceptual Area 4 – Coleraine Drive - Elevated Tank– Aesthetically acceptable – near existing tank and within employment

area– Lower elevations for elevated tank– Constructing the tank in this area would allow the Region to comply

with the permitted uses and would shorten the distance of thefeedermain to the new elevated tank

To satisfy the North Hill demands and provide security of supply to the residents ofBolton, a proposed feedermain route would connect the South Hill and North Hill.An elevated tank at Coleraine Drive would allow for a smaller diameter feedermain.

Panel 8

Page 10: PUBLIC INFORMATION CENTRE NO. 2 · Early 2010 April 2008 Commence EA Study Summer 2008 Preliminary Evaluation and Studies for Elevated Tank/Reservoir Sites and Feedermain Routes December

North Bolton Elevated Tank/Reservoir andFeedermain Class EA

Alternative Elevated Tank Sites

Three (3) Alternative site locations were identified forthe proposed 9.0 ML (2.38 MG) Elevated Tank.

The original elevated tank site identified in the 2007Peel Region Water and Wastewater Servicing MasterPlan Update was situated north of the study area; ithas been eliminated from consideration due toenvironmental constraints and higher costs.

Alternative Site No. 3 is the Preliminary Preferred Site,which is the northwest corner of the Hopewellproperty, as shown in the figure on right. This site wasselected based on the following:

– Approximately 3 acres flat area for tank site plus~2 acres for a permanent access road

– Close to existing infrastructure– Set back from Coleraine Drive to reduce visual

impact on existing residences– Minimum Environmental Impacts; 30 metre

setback from water feature.Property acquisition will be required for an accessroad and feedermains to the elevated tank site.

Orientation and the tank layout is conceptual only andis subject to change.

Alternative Site No. 1

Alternative Site No. 3Preferred

Alternative Site No. 2

Panel 9