Quasar Manual

Embed Size (px)

Citation preview

  • 7/30/2019 Quasar Manual

    1/48

    1

    INSTRUCTION MANUALFOR

    QUASARDIGITAL PANEL METER

    Class 1.0

  • 7/30/2019 Quasar Manual

    2/48

    2

    Table of contents

    Page No.

    Section 1. General Details 3

    Section 2. Front Panel Details 3

    Section 3. Installation 11

    Section 4. Mechanical Dimensions 12

    Section 5. Specific Points 12Section 6. Programming the meter 13

    Section 7. Warranty & Disclaimer 14

    Appendix 1. Technical Specifications 15

    Appendix 2. Modbus Details 17

    Appendix 3. Memory Map 26Appendix 4. Meter Programming Procedure 32

    Appendix 5. Display Screens - 3phase, 3wire. 37

    Appendix 6. Display Screens - 3phase, 4wire. 40

    Appendix 7. Wiring Diagram 43

    Appendix 8. Dimensional Details 47

  • 7/30/2019 Quasar Manual

    3/48

    3

    1.0 General Details: QUASAR is a 96 x 96 mm, flush mounted,

    single screen multiple parameter display digital panel meter for

    measuring electrical parameters. The meter is designed with

    DSP technology to combine measurements of bothinstantaneous and cumulative values in an electrical feeder.

    The device is built with a custom made, backlit, LCD display

    to provide high-resolution view of various parameters to the

    viewer. The parameters are displayed over all screens which

    can be scrolled up & down by front panel push buttons. The

    feeder parameters like CT / PT ratings, baud rates, port

    address, demand parameters etc. are set by additional pushbuttons (PBs) on the front panel.

    2.0 Front Panel Details: Please see fig. 1. The front panel has one

    LCD display, 4 PBs and a LED. The functions of the PBs are

    explained in the sections 2.3, 2.7 and Appendix 4. The LED

    flashes at a rate proportional to the kWh in the feeder.

    2.1 Display Features: QUASAR comes with a custom made LCD

    display. The power parameters are displayed through all

    screens. Please refer Appendix 5& 6 for details of parameters

    displayed in each screen. Please also refer to Table-1&2 for a

    ready reckoner of screen references.

    The following displays appear immediately after power on-

    1. all segments check

    2. serial no.

    3. Version no.Finally it continuously displays the selected power on screen

    until keys are pressed.

  • 7/30/2019 Quasar Manual

    4/48

    4

    2.2 Front panel push buttons: There are four Push buttons (PBs)

    on the front panel to do following functions:

    a) scrolling thro display

    b) min/max/present values selectionc) reset of min/max values

    d) front panel programming.

    Fig.- 1

  • 7/30/2019 Quasar Manual

    5/48

    5

    Table-1: 3phase, 3wire

    P a r a m e t e rUnit

    L1(r-y)

    L2(b-y)

    Tot/

    Avg

    Max/m

    in

    optionVoltage(Line

    Voltage)

    V 2, 16 2, 17 1

    Current A 3, 18 3, 19 1

    Active power kW 4 4 10, 1 (onlyfor total)

    Reactive power L kVAr L 5 5 10(Lor C) (onlyfor total)

    Reactive power C kVArC 5 5 10(Lor C) (onlyfor total)

    Apparent power kVA 6 6 10 (onlyfor total)

    Power factor PF 7 7 11

    Phase angle

    (w.r.t. Voltages)

    - V 8 8

    Phase angle (B/w

    Voltages & currents)

    - A 9 9

    Frequency Hz 11 *

    Power demand (max.) Pd 11

    Active energy kWh 12

    Reactive energy L kVArLh 13

    Reactive energy C kVArCh 14

    Apparent energy kVAh 15

    Voltage Fundamental ~1 16 17

    Voltage Distortion ~D 16 17

    Current Fundamental ~1 18 19

    Current Distortion ~D 18 19

  • 7/30/2019 Quasar Manual

    6/48

    6

    Table-2: 3phase, 4 wire

    Parameter

    Unit

    P1 P2 P3 Tot/

    Avg

    Max/m

    in

    optionVoltage (P-N) V 2, 17 2, 18 2, 19 1

    Voltage (P-P) V 3 3 3

    Current A 4, 20 4, 21 4, 22 1

    Active power kW 5 5 5 11, 1 (onlyfor total)

    Reactive power L kVAr

    L

    6 6 6 11(L orC) (onlyfor total)

    Reactive power C kVAr

    C

    6 6 6 11(L orC) (onlyfor total)

    Apparent power kVA 7 7 7 11 (only

    for total)Power factor PF 8 8 8 12

    Phase angle

    (w.r.t. Voltages)

    - V 9 9 9

    Phase angle

    (between voltages

    & currents)

    - A 10 10 10

    Frequency Hz 12 * *

    Power demand

    (max.)

    Pd 12

    Active energy kWh 13

    Reactive energy L kVArLh 14

    Reactive energy C kVArCh 15

    Apparent energy kVAh 16

    Voltage

    Fundamental

    ~1 17 18 19

    Voltage Distortion ~D 17 18 19

    Current

    Fundamental

    ~1 20 21 22

    Current Distortion ~D 20 21 22

  • 7/30/2019 Quasar Manual

    7/48

    7

    Notes:

    All display screens of 3 parameters each are available. (nos. in

    the above Tables indicate the order of the default display

    screens).Note: * in above Tables indicates that Freq. of phase 1 is

    displayed if phase1 is available, freq. of phase 2 is displayed if

    phase1 is not available and phase 2 is available, freq. of phase

    3 is displayed if phase1&2 are not available and phase 3 is

    available.

    The power up screen will be by default- total power (of all

    phases), average voltages (of all phases) & average currents (of

    all phases). The default power ON screen is programmable. It

    will remain in this display until keys are pressed as explained

    below.

    2.3 Functions of front panel push buttons :

    Display scroll PBs5555 & 6666 .

    The display scroll PBs are indicated as 5555 & 6666.

    All screens of display can be viewed one after the other by

    pressing 5 or 6 PBs of front panel. Pressing 5&

    6keys simultaneously will take display to auto scroll mode.

    The display will scroll through all screens at a fixed rate of 3

    secs. In auto scroll mode, pressing 5 or 6key will take

    display to manual mode. (No time out for any mode ofdisplay).

  • 7/30/2019 Quasar Manual

    8/48

    8

    Max / min values selector PB MODE

    QUASAR stores max/min values of the feeder (only for

    parameters ticked in Table-1&2). The PB designated as

    MODE is meant to read these max/min values. Normally

    latest updated values will be displayed.By pressing the push button MODE, the display can be

    switched to Min., Max. or present values one after the other.

    The display will remain in Min & Max modes until the PB is

    pressed again. In case there is a maximum timeout of 2 mins,

    the display will go back to Present values. Min/Max modes are

    not supported in auto scroll mode.

    Reset Push button

    Resets the max/min values, except power demand & energies.

    2.4 Energy & Pulse outputs:

    Units and precision of energy will vary with the CT*PT ratios

    selected as shown in table below.

    CT*PT Display format Unit

    < 10 xxxxxx.xx k

    < 100 xxxxxxx.x k

  • 7/30/2019 Quasar Manual

    9/48

    9

    PULSE OUTPUT: kWh pulse output LED is available.

    2.5 Resetting (clearing) the stored parameters:Pressing reset key on front panel clears off all the max./min.

    values except the following parameters.

    a) Power demand max. value can be cleared only in the

    programming mode.

    b) Energy counters can be cleared only in programming

    mode.

    2.6 Harmonics for Voltage & Current:

    Phase wise voltages/currents are separately available as -

    Total

    Fundamental (~)

    Distortion (D)2.7 Set up & Configuration:

    Set up configuration is possible through front panel keys or

    RS485 port (optional). Viewing and modifying of setup

    through front panel is possible all the time and is password

    protected.

    Programming mode can be entered from front panel by

    pressing simultaneously 5

    and Mode keys. Meter restartsafter coming out of programming mode.

    Pulses/kWh Voltage/current

    2,500 / (external CT*PT) 3ph 4W 415 V (L-L) / 5A

    12,500 / (external CT*PT) 3ph 4W 415 V (L-L) / 1A10,000 / (external CT*PT) 3ph 4W/3W 110 V (L-L) / 5A

    50,000 / (external CT*PT) 3ph 4W/3W 110 V (L-L) / 1A

  • 7/30/2019 Quasar Manual

    10/48

    10

    Refer appendix 4 for details of programming through front

    panel.

    Refer appendix 2&3 for details of programming through

    RS485.

    Following are the setup (programming) options -

    a) CT primary/secondaryChange in CT ratio will automatically change the

    resolution of the parameters displayed. Primary and

    secondary values can be selected between 1 to 9999.

    Default factory settings: 1

    b) PT primary/secondary

    Change in PT ratio will automatically change the

    resolution of the parameters displayed. Primary andsecondary values can be selected between 1 to 9999.

    Default factory settings: 1

    c) Clear - Clear energy counters

    - Clear max. /min. demand

    d) Power demand

    Mean value of power in specified integration period

    - Parameter kW or kVA

    Integration period 1,2,3,4,5,6,10,12,15,30,60mins. (not

    w.r.t RTC)

    Default factory settings: kW & 30mins. Any change in

    power demand settings, clears max./min. demand values.

    e) Default Power ON screen

    The default power ON screen can be selected as one of the

    all displays.Default factory settings: Total power, average voltage of

    all 3 phases & average current of all 3 phases.

  • 7/30/2019 Quasar Manual

    11/48

    11

    f) Slave ID setting(Available only for meter with RS485

    option)

    Unique slave IDs can be set for each meter for monitoring

    from a PC. Default factory settings: 1

    g) Port properties settings (Available only for meter withRS485 option)Baud rate- 4800 bps or 9600 bps

    Parity- Even, odd, none

    Default factory settings: 4800 bps, even.h) Password setting (only for front panel programming)

    Default password is 0000.

    2.8 RS485 COMMUNICATION (optional):

    With this option, the meters can be networked and various

    parameters can be monitored on a central PC.

    All parameters will be available via the RS 485 port.

    Set up configuration is also possible through this port.

    Protocol: MODBUS in RTU mode.

    Refer appendix 3 and appendix 2 for RS485 & MODBUSdetails.

    3.0 Installation:

    3.1 Incoming Inspection: Before the meter is installed, visual

    inspection for any damage due to transport, has to be done. If

    there are any damages, please refer the warranty sheet and take

    appropriate action.

    3.2 Re-Packing: If the meter has to be returned to the supplier, themeter has to be repacked in its original packing.

  • 7/30/2019 Quasar Manual

    12/48

    12

    3.3 Optimum Field conditions: For the reliability and better life

    of product, the unit has to be operated at moderate

    temperatures and humidity. The meter is designed to work

    from 5 to 60 degrees C and humidity of 95%RH non

    condensing.

    3.4 Storage: In case of meter not installed after receipt, it has to bestored in a dry place in its original packing material.

    3.5 Extra Precautions: Make sure that voltage, current ratings and

    the configuration of meter is as per the requirements. Wrong

    connection can severely damage the meter, which is not

    covered under warranty.

    3.6 Wiring connections: Wiring of the meter has to be done as per

    wiring diagrams in appendix-7.

    4 Mechanical dimensions; As per appendix-8.

    4.1 Mounting on the panel: The meter is supplied with clip on

    type mounting accessories. After inserting the meter into the

    designated cut out on the panel, the clip on clamps have to be

    fixed on the back side to hold the meter against the panel

    firmly.

    5.0 Specific Points: QUASAR uses CT/PT inputs for measuring

    and display of electrical parameters. Following points should

    be noted :

    5.1Power demand calculation:Integration period starts and continues from power on, i.e. if

    integration period selected is 30mins. and if 20mins of

    integration period is completed and power fails, then in the

    next power ON, the power is accumulated for the next 10 minsand then demand is computed.

  • 7/30/2019 Quasar Manual

    13/48

    13

    5.2 Current reversal conditions:

    a) kWh energy is updated as it is with the sign i.e. negative

    energies are subtracted & positive energies are added and

    stored in a single register (no forward & reverse). The

    negative reading is made positive by adding 10^8.

    b) For kWh energy, demand is calculated by algebraicallyadding the powers, but if final demand is negative then

    display shows 0.0.0.0 just to indicate that something is

    wrong.

    c) When the meter connections are wrong, it will not show

    display parameters properly.

    5.3 Unit of Voltage and current when kilo:Unit of voltage: for PT ratio 30 unit is k steady and V

    will be blinking, indicating unit is in kilo Volt.

    Unit of current: for CT ratio 75 unit is k steady and A

    will be blinking, indicating unit is in kilo Amps.

    Note: i) For Voltage and current k will not be there in Total

    Power, Avg Voltage & current display (Default display no is 1)

    ii) Meter is not designed for export mode.

    6.0 Programming the meter: Parameters like CT/PT ratios etc

    have to be programmed into the meter so that it can read the

    feeder data correctly. Please refer Appendix 4 for details of

    how to programme the meter.

  • 7/30/2019 Quasar Manual

    14/48

    14

    7.0 Warranty:

    Larsen & Toubro Limited warrants that all the L&T products will

    meet L&T's published product specifications, and will be free of

    defects in workmanship and materials for a period of 12 months

    from the date of invoice from L&T.

    L&T's obligation under this warranty shall be limited to servicing orreplacing defective parts subject to the following terms and

    conditions provided the notice of defects and satisfactory proof

    thereof is given to L&T by its distributor or its customer within the

    Warranty period.

    1.L&T shall provide repairs and maintenance service for all

    equipment sold/or distributed by L&T, and products which cannot

    be repaired by L&T will be returned, subject to L&T's prior consentfor free repairs.

    2.Defective parts shall be serviced or replaced by L&T on one way

    freight paid basis.

    This warranty does not cover any defect in the product caused by

    accident, misuse, neglect, alteration modification or substitution of

    any of the components or parts, or any attempt at internal

    adjustment by unauthorized service personnel.

    Under no circumstance shall L&T be liable for any consequential or

    resulting injury or for loss, damage of expense directly or

    indirectly from the use of this product.

    The foregoing warranty is in lieu of all other warranties, expressed

    or implied, and is the sole and exclusive remedy for any claim

    arising from any defect in L&T products.

    Disclaimer: Sufficient care is taken to provide all information

    regarding the product but L & T does not claim any responsibilityfor the damages caused by using the product directly or indirectly.

  • 7/30/2019 Quasar Manual

    15/48

    15

    Appendix 1: TECHNICAL SPECIFICATIONS

    Accuracy For power Class 1.0

    IEC 62052-11,62053-21/ IS 13779

    For Voltage 10%

    For Current 0.5% of readout 2 digits

    Voltage (Vn) 3Ph 4W- 415V AC (-40% to +20%)

    3Ph 4W- 110V AC (-40% to +20%)

    3Ph 3W- 110V AC (-40% to +20%)

    Current (In) 5A or 1A (Imax=2In)

    Starting current 0.2%In (Class 1.0)

    Frequency 50 Hz +5%

    Load characteristics < 8 VA in potential circuit

    < 0.5 VA in current circuit

    Electromagnetic compatibility:Electrical Fast transient As Per IEC 62052-11,62053-21,

    Test Level: 4kV, 5kHz(Refer to

    IEC61000-4-4)

    Surge immunity As Per IEC 62052-11,62053-21,Test

    Level: 4kV(Refer to IEC61000-4-5)

    Influence of short time over currents:

    20 times Imax for 0.5 sec at rated

    frequency. As Per IEC62053-21

  • 7/30/2019 Quasar Manual

    16/48

    16

    Case material Plastic moulded Protected to

    IP51- IEC 62052-11,62053-

    21/IS 13779 (Class 1.0)(with

    panel)

    Insulation properties:

    Insulation resistance As per IEC62052-11,62053-21/IS13779 (Class 1.0)

    AC Voltage Test 2kV AC RMS, 50Hz for

    1 minute as per IEC62052-11

    Impulse voltage 6kV, 1.2/50sec, as per

    IEC62052-11

    Voltage Dips and Interrupts As per IEC61000-4-11

    Display Backlit LCD, 10mm height

    digits

    Pulse output

    Pulses/kWh Voltage/current

    2,500 / (external CT*PT) 3ph 4W 415 V (L-L) / 5A

    12,500 / (external CT*PT) 3ph 4W 415 V (L-L) / 1A10,000 / (external CT*PT) 3ph 4W/3W 110 V (L-L) / 5A

    50,000 / (external CT*PT) 3ph 4W/3W 110 V (L-L) / 1A

    Temperature -100c to 600c for operation

    -200c to 700c for storageHumidity 95% RH non condensing

    Dimension 96 x 96 mm - depth 105 mmWeight < 600gms

  • 7/30/2019 Quasar Manual

    17/48

    17

    Appendix 2: MODBUS DETAILS

    1. Details of communication interface:

    RS485 interface is available to communicate with the meter.

    The interface is available at the terminals. For connection

    details refer Appendix 7.

    1.1 Interface Standard:

    The configuration details to communicate with the meter are

    given below-

    Standard RS485 (half duplex)

    Baud rate Selectable- 9600, 4800 bpsParity Selectable- None, odd or even

    Start bit 1 Stop bit 1

    1.2 Protocol:

    The RS485 interface uses MODBUS Protocol inRTU mode.

    Communicating with the meter involves sending commands to

    the meter for reading and writing the particular register. Themeter can be addressed with specific user defined meter

    address (slave ID) from 1-255.

    2 Details of MODBUS protocol:

    In the explanation of protocol the examples used are specific to

    L&T meters. The details of the protocol are also limited to

    L&T meters.

    2.1 Remote Terminal unit Framing:

    In RTU mode data is sent as 8-bit binary characters. In RTU

    mode, message characters must be transmitted in a continuous

    mode.

  • 7/30/2019 Quasar Manual

    18/48

    18

    The receiving device monitors the elapsed time between

    receipt of characters i.e. inter byte delay. Ifinter byte delay is

    three and one half the character time (for e.g. at 9600bps,

    the max. inter byte delay expected will be 1ms*3.5), the

    receiving device can timeout.

    The max. response time of the meter to a command, i.e. thetime taken to send the first byte out in response to the

    command is max. 60ms.

    ADDRESS FUNCTION DATA CHECK

    8 BITS 8 BITS N * 8 BITS 16 BITS

    2.2 Address field:

    The meter can be addressed with specific user defined address

    from 1-255. Each slave must be assigned a unique address and

    only the addressed slave responds to query that contains its

    address. When the slave sends a response the slave address

    informs the master which slave is communicating.

    In broadcast message, an address of 0(zero) is used. All slavesinterpret this as an instruction to read and take action on the

    message, but do not issue a response message.

    2.3 Function field:

    The function code field tells the addressed slave what function

    is to be performed. The higher order bit in this field is set by

    the slave device to indicate that other than a normal response is

    being transmitted to the master device (See Section 3 forexception response). The following functions have been

    implemented in the meter.

  • 7/30/2019 Quasar Manual

    19/48

    19

    2.4 Data Field:

    The data field contains the information needed by the slave to

    perform the specific function or it contains data collected by

    the slave in response to a query.

    2.5 Error Check Field: This allows the master and slave device to

    check a message for error transmission.The error check field uses a CRC-16 check in the RTU mode.

    3. Exception responses:

    Exception response is a notification of an error. The exception

    response codes are listed in the table 3-1.When a slave detects

    one of these errors, it sends a response to the master consisting

    of slave address, function code, error code and error check

    field. To indicate that the response is a notification of an error,

    the high order bit of the function code is set to 1.

    CODE MEANING ACTION

    03 Read holding

    registers

    Obtains current binary value in one

    or more holding registers.

    04 Reading Input

    registers

    Obtains current binary value in one

    or more Input registers.06 Preset single

    register

    Place a specific binary value

    into a holding register.

    16 Preset multiple

    registers

    Places specific binary values into a

    series of consecutive holding registers.

  • 7/30/2019 Quasar Manual

    20/48

    20

    Table 3-1

    CODE NAME MEANING

    01 ILLEGAL

    FUNCTION

    The message function received is

    not an allowable action for slave.

    02 ILLEGAL

    DATA

    ADDRESS

    The address referenced in the data

    field is not an allowable address

    for the addressed slave location.

    03 ILLEGAL

    DATA VALUE

    The value referenced in the data

    field is not allowable in the

    addressed slave location.

    Example: Query Message

    The query requests the status of input 0036 in slave no.10.

    Since the function is an invalid function for the L&T meters so

    the following error response will be generated.Response Message

    The function code field is the original function code with thehigh order bit set and exception code 01 indicates an illegal

    function field.

    SLAV

    E

    ADDR

    FNC H.O

    START

    ADDR

    L.O.

    START

    ADDR

    H.O

    NO.

    OF REG

    L.O NO.

    OF

    REG

    ERROR

    CHECK

    FIELD

    ERROR

    CHEC

    FIELD

    0A 01 00 24 00 02 FC BB

    SLAVE

    ADDR

    FUN

    C

    EXCEPTIO

    N CODE

    ERROR

    CHECK

    ERROR

    CHECK

    0A 81 01 F0 52

  • 7/30/2019 Quasar Manual

    21/48

    21

    4. Explanation of various function:

    The purpose of this section is to define the general format for

    the specific command available to programmers. The form of

    each query message (in RTU transmission mode) and an

    explanation of the function the query message performs areprovided.

    All numbers in Modbus format are entered in hexadecimal.

    4.1 Read Output Register (Function Code 03) Query:

    Read output Register (03) allows the user to obtain the binary

    contents of holding register in the addressed slave. The

    addressing allows up to Max.90 registers to be obtained at eachrequest.

    Broadcast mode is not allowed. The below example reads

    registers of 1st phase voltage from slave number 17(decimal).

    Since 1st phase voltage is stored in the address 0000 and 0001

    so to read phase voltage both addresses should be read

    simultaneously.

    Example:

    Query MessageSLAV

    E

    ADDR

    FNC H.O

    START

    ADDR

    L.O.

    START

    ADDR

    H.O

    NO

    OF

    REG

    L.O

    NO.

    OF

    REG

    ERROR

    CHECK

    FIELD

    ERROR

    CHECK

    FIELD

    11 03 00 00 00 02 C6 9B

    NOTE: If a particular parameter is stored in more than one

    address location. Then for reading that particular parameter allthe address locations should be read simultaneously. Otherwise

  • 7/30/2019 Quasar Manual

    22/48

    22

    meter will not respond or the response will not be the correct

    value.

    For further details see memory map of parameters.

    Response:

    The addressed slave will respond with its address and the

    function code, followed by the information field. Theinformation field contains 1 byte describing the quantity of

    data bytes to be returned. The contents of register requested

    (DATA) are two bytes each. The first byte includes the higher

    order bits and the second byte includes lower order bits.

    Response MessageSLA

    VE

    ADD

    R

    FNC BTE

    COU

    NT

    DATA

    O/P

    REG

    H.O.

    0000

    DATA

    O/P

    REG

    L.O.

    0000

    DATA

    O/P

    REG

    H.O.

    0001

    DAT

    A

    O/P

    REG

    L.O.

    0001

    ERR.

    CHE.

    FLD

    ERR.

    CHK

    FLD

    11 03 04 00 00 5D E6 52 E8

    In this particular example the data obtained for 1st phase

    voltage is0x00005DE6 which if converted into integer will be 24038.So

    to get the voltage of the phase this particular value should be

    multiplied with the specified multiplication factor (MF) which

    is 0.01 in this case. (For further details see the memory map of

    the parameters). So 24038 x 0.01=240.38 which is the phase

    voltage.

    4.2 Preset Single Register (Function Code 06):

    CAUTION:

    Function (06) will overwrite controller memory.

  • 7/30/2019 Quasar Manual

    23/48

    23

    Function (06) allows the user to modify the contents of a

    holding register. The contents of only those holding registers

    can be modified which are write only. The values are provided

    in binary, up to the maximum capacity of the controller (16-

    Bits in L&T meters) and unused higher bits must be set to zero.When used with slave address zero (Broadcast mode), all slave

    controllers will load the specified registers with the content

    specified.

    Example:

    This example will set the CT primary value in slave number

    17.The address of CT primary is 2048 and value to be

    programmed is 1000.Query MessageSLAV

    E

    ADDR

    FNC H.O

    START

    ADDR

    L.O.

    START

    ADDR

    DATA

    VAL.

    H.O

    DAT

    A

    VAL.

    L.O

    ERR.

    CHK

    FLD

    ERR.

    CHK

    FLD

    11 06 08 00 03 E8 89 84

    The normal response to a preset single register request is to

    transmit the query message after the register has been altered.Response Message

    SLAV

    E

    ADDR

    FNC H.O

    START

    ADDR

    L.O.

    START

    ADDR

    DATA

    VALUE

    H.O

    DATA

    VALUE

    L.O

    ERR.

    CHK

    FLD

    ERROR

    CHECK

    FIELD

    11 06 08 00 03 E8 89 84

    If the value is an illegal value then the response message will

    be an exception response (Error message).

  • 7/30/2019 Quasar Manual

    24/48

    24

    For the details of max and min. values of any parameter, please

    refer to manual.NOTE: For programming RTC the values the data for setting

    the RTC should be BCD (Binary Coded Decimal).Example:

    For setting date 29 and day 5 at location 257 the query message

    will be as follows

    Query Message

    4.3 Preset Multiple Registers(Function Code 16):

    CAUTION:

    Function (16) will overwrite controller memory.

    Function (16) allows the user to modify the contents of holdingregisters.

    The contents of only those holding registers can be modified

    which are writeable only. The values are provided in binary up

    to the maximum capacity of the controller (16-Bits in L&T

    meters), unused higher bits must be set to zero.

    Maximum of 10 registers can be programmed by this function.

    When used with slave address zero (Broadcast mode) all slave

    controllers will load the specified registers with the contents

    specified.

    SLAVE

    ADDR

    FNC H.O

    START

    ADDR

    L.O.

    START

    ADDR

    DATA

    VALUE

    H.O

    DATA

    VALUE

    L.O

    ERR.

    CHK

    FLD

    ERR.

    CHK

    FLD

    11 06 01 01 29 05 04 F5

  • 7/30/2019 Quasar Manual

    25/48

    25

    Example:

    This example will set the CT primary and CT secondary value

    in slave number 17.The address of CT primary is 2048,CTsecondary is 2049 and value to be programmed for CT primary

    and secondary are 1000 and 100 respectively.

    Query MessageA

    D

    D

    R

    F

    U

    N

    C

    H.

    O.

    A

    DD

    L.

    O.

    A

    DD

    Q

    T

    Y.

    H.O

    Q

    T

    Y.

    L.O

    B

    Y

    T

    SN

    T

    H.

    O

    D

    AT

    L.

    O

    D

    AT

    H.

    O

    D

    AT

    L.

    O

    D

    AT

    E

    R

    R

    FL

    D

    E

    R

    R

    FL

    D

    1

    1

    1

    0

    0

    8

    0

    0

    0

    0

    0

    2

    0

    4

    0

    3

    E

    8

    0

    0

    6

    4

    4

    1

    3

    4

    The normal response to a preset multiple register request is to

    echo the address function code, starting address and number of

    registers to be loaded.

    Response message

    SLA

    VE

    ADD

    R

    FNC H.O

    START

    ADDR

    L.O.

    START

    ADDR

    QTY

    H.O

    QTY

    L.O

    ERR.

    CHK

    FLD

    ERR.

    CHK

    FIEL

    D

    11 10 08 00 00 02 41 38

  • 7/30/2019 Quasar Manual

    26/48

    26

    Appendix 3: MEMORY MAPRead only Parameters (Function Code 4):

    Memory map (Address list)

    Address Parameters Words MF

    (If no specific format is

    mentioned, format is HEX)

    READ ONLY PARAMETERS

    Instantaneous Parameters

    30,001 Phase 1 Voltage 2 0.01

    30,003 Phase 2 Voltage 2 0.01

    30,005 Phase 3 Voltage * 2 0.01

    30,007 Phase 1 Current 2 0.001

    30,009 Phase 2 Current 2 0.001

    30,011 Phase 3 Current * 2 0.001

    30,013 Phase 1 Active Power 2 0.0001

    30,015 Phase 2 Active Power 2 0.000130,017 Phase 3 Active Power * 2 0.0001

    30,019 Phase 1 Reactive Power 2 0.0001

    30,021 Phase 2 Reactive Power 2 0.0001

    30,023 Phase 3 Reactive Power * 2 0.0001

    30,025 Phase 1 Apparent Power 2 0.0001

    30,027 Phase 2 Apparent Power 2 0.000130,029 Phase 3 Apparent Power * 2 0.0001

  • 7/30/2019 Quasar Manual

    27/48

    27

    30,031 Phase 1 Power Factor 2 0.001

    30,033 Phase 2 Power Factor 2 0.001

    30,035 Phase 3 Power Factor * 2 0.001

    30,037 Total Active Power 2 0.0001

    30,039 Total Reactive Power 2 0.0001

    30,041 Total Apparent Power 2 0.0001

    30,043 Total Power Factor 2 0.001

    Format: for above addresses 30,013 to 30,043

    1st word (MSW) 0x0000 if value positive

    0xFFFF if value negative

    2nd

    word value itself, if positive as indicated by 1st

    word2s complement of value, if negative as indicated by 1st

    word

    30,045 Line Frequency 2 0.01

    30,047 Reserved 2

    30,049 Phase 1 Voltage Angle 2 0.1

    30,051 Phase 2 Voltage Angle 2 0.1

    30,053 Phase 3 Voltage Angle * 2 0.1

    30,055 Phase 1 Phase Angle 2 0.1

    30,057 Phase 2 Phase Angle 2 0.1

    30,059 Phase 3 Phase Angle * 2 0.1

    30,061 Phase 1 Voltage Fundamental 2 0.01

    30,063 Phase 2 Voltage Fundamental 2 0.0130,065 Phase 3 Voltage Fundamental * 2 0.01

  • 7/30/2019 Quasar Manual

    28/48

    28

    30,067 Phase 1 Voltage Distortion 2 0.01

    30,069 Phase 2 Voltage Distortion 2 0.01

    30,071 Phase 3 Voltage Distortion * 2 0.01

    30,073 Phase 1 Current Fundamental 2 0.0001

    30,075 Phase 2 Current Fundamental 2 0.0001

    30,077 Phase 3 Current Fundamental * 2 0.0001

    30,079 Phase 1 Current Distortion. 2 0.0001

    30,081 Phase 2 Current Distortion 2 0.0001

    30,083 Phase 3 Current Distortion * 2 0.0001

    30,085 Average Voltage 2 0.01

    30,087 Average Current 2 0.001

    30091 Vry* 2 0.01

    30093 Vyb* 2 0.01

    30095 Vbr* 2 0.01

    Minimum / Maximum of Instantaneous Parameters

    30,129 Minimum Phase 1 Voltage 2 0.0130,131 Minimum Phase 2 Voltage 2 0.01

    30,133 Minimum Phase 3 Voltage * 2 0.01

    30,135 Maximum Phase 1 Voltage 2 0.01

    30,137 Maximum Phase 2 Voltage 2 0.01

    30,139 Maximum Phase 3 Voltage * 2 0.01

    30,141 Minimum Phase 1 Current 2 0.00130,143 Minimum Phase 2 Current 2 0.001

  • 7/30/2019 Quasar Manual

    29/48

    29

    30,145 Minimum Phase 3 Current * 2 0.001

    30,147 Maximum Phase 1 Current 2 0.001

    30,149 Maximum Phase 2 Current 2 0.001

    30,151 Maximum Phase 3 Current * 2 0.001

    30,153 Minimum Phase 1 Power Factor 2 0.001

    30,155 Minimum Phase 2 Power Factor 2 0.001

    30,157 Minimum Phase 3 power Factor * 2 0.001

    30,159 Maximum Phase 1 Power Factor 2 0.001

    30,161 Maximum Phase 2 power Factor 2 0.001

    30,163 Maximum Phase 3 Power Factor * 2 0.001

    30,165 Minimum Average Voltage 2 0.01

    30,167 Maximum Average Voltage 2 0.01

    30,169 Minimum Average Current 2 0.001

    30,171 Maximum Average Current 2 0.001

    30,173 Minimum Average Power Factor 2 0.001

    30,175 Maximum Average Power Factor 2 0.00130,177 Minimum Frequency 2 0.001

    30,179 Maximum Frequency 2 0.001

    30,181 Minimum Total Active power 2 0.0001

    30,183 Maximum Total Active power 2 0.0001

    30,185 Minimum Total Reactive power 2 0.0001

    30,187 Maximum Total Reactive power 2 0.000130,189 Minimum Total Apparent Power 2 0.0001

  • 7/30/2019 Quasar Manual

    30/48

    30

    30,191 Maximum Total Apparent Power 2 0.0001

    30,193 Minimum Power Demand 2 0.0001

    30,195 Maximum Power Demand 2 0.0001

    Read Only Parameters (Function Code 4):

    Cumulative energies since installation

    independent of Tariffs.

    30,513 Cumulative energy - forward kVAh 2 0.01

    30,515 Cumulative energy - forward kWh 2 0.01

    30,517 Cumulative energy - forward kVArh lag 2 0.01

    30,519 Cumulative energy - forward kVArh lead 2 0.01

    Read Only Parameters (Function Code 4):

    31,281 Power Demand 2 0.01

    Read Write Parameters(Supported by function code 6 and 16 for Writing and by function code

    3 for Reading.)Communication Parameters

    42,385 Meter Address 1 1

    42,386 Baud Rate 1 1Format: For read 1 -> 4800 2 -> 9600

    For write 5 -> 4800 6 -> 9600

    42,387 Parity 1 1

    Format: 0 -> None Parity 1 -> Odd Parity 2 -> Even Parity

    CT PT ratio settings (1 to 9999 max)

    42,049 CT Primary 1 1

  • 7/30/2019 Quasar Manual

    31/48

    31

    42,050 CT Secondary 1 1

    42,051 PT Primary 1 1

    42,052 PT Secondary 1 1

    (max. CTpri/Ctsec)*(PTpri/Ptsec)

  • 7/30/2019 Quasar Manual

    32/48

    32

    Appendix 4: METER PROGRAMMING PROCEDUREProgramming of various parameters in Quasar is done by

    selecting the appropriate screen and changing the parameters.

    Following sections explain the setting procedure.

    1.0 Entering into programming mode:Press both Mode & up buttons together.

    Screen will appear as shown. First digit will

    flash. You have to set password.

    1.1 Entering the pass word:

    Let us say password is 1234. Press up button to change the

    value of the flashing digit. Press Rst button to shift to nextdigit. Press up button to change its value. Set 1234 in all

    digits. Press mode. Meter will display PASS ACCEPtEd

    momentarily and go to a new screen CtPt rAt.

    2.0 Selecting the parameters to be set:

    Once the meter is at above screen, the user can select a screen

    to set any of the following parametersCtPt rAt

    Change ratios of CTs and PTsCLr dAtA Reset the MD value and cumulative energy

    values.

    SEt nd You can set the integration time and choose either

    KW or

    KVA for integration.

    SEt Id set the node address of meter

    SEt Port set the baud rate for communication

    SEt dISP set the default display screenSEt PASS set the password

    Press Up button to choose any of the above screens.

    ProgPASS 0000

  • 7/30/2019 Quasar Manual

    33/48

    33

    3.0 Setting CT/PT Ratio:

    Reach the screen CtPt rAt as explained

    above. Press Mode, display shows existing

    CT primary rating. Press mode key First

    digit will flash. Change the value by usingup and Rst buttons. Say you have set CT

    primary as 0200.After setting the required

    value press mode. Meter will display L uP

    dAtE. Press mode again meter will display

    ACCEPtEd briefly and return to display as

    shown. Press up button to go to Ct SECy.

    Press Mode, display shows existing CT

    secondary rating. First digit will flash,

    change the value by up and Rst buttons.

    Say you have set CT secondary as 0001.

    After setting the required value press mode

    meter will display L uP dAtE. Press mode

    again meter will display ACCEPtEd briefly

    and return to display as shown. Press up

    button to go to Pt Prny.

    Set the ratings of PT primary and secondary in the same

    manner as explained above. After finishing with PT

    Secondary, press down button. Meter will display ESCAPE

    and return to CtPt rAt. Press up button to go to next screen

    CLr dAtA.

    0100Ct Prny

    0200Ct Prny

    0001Ct SECy

  • 7/30/2019 Quasar Manual

    34/48

    34

    4.0 Clearing the existing data:

    After reaching the screen CLr dAtA, press mode, display

    will change to CLr dnd. Press mode, display will be L uP

    dAtE. Press mode again display will be ACCEPtEd

    followed by CLr dnd.Press up button. Display will change to CLr Egy. Press

    mode, display will be L uP dAtE. Press mode again display

    will be ACCEPtEd followed by CLr Egy. Press Down

    button, display will show ESCAPE followed by CLr dAtA.

    Press up button, display will enter next screen SEt nd.

    5.0 Setting the Demand parameters:After reaching the screen SEt nd, press

    mode, display will show existing value for

    md integration time. The value will be

    flashing. By pressing up button change the

    value to required setting. Press Mode,

    display will show L uP dAtE. Press mode

    again display will show ACCEPtEd

    followed by the up dated screen.

    Press up button, display will show nd kW. Press mode. kW

    will flash. By using up button choose kW or kVA. Press

    mode, display will show L uP dAtE. Press mode again

    display will show ACCEPtEd followed by nd kW. Press

    down button to ESCAPE followed by SEt nd. Press up

    button to go to next screen SEt Id.

    Note: Configuration of kVA demand is LEAD treated asUPF.

    30nd Intg

  • 7/30/2019 Quasar Manual

    35/48

    35

    6.0 Setting the node address for meter:

    After reaching the screen SEt Id, press

    mode, display will show existing value for

    Meter Id. The value will be flashing. By

    pressing up button change the value torequired setting and use Rst button to go

    next digit.

    Press Mode, display will show L uP dAtE.

    Press mode again display will show ACCEPtEd followed by

    SEt Id screen. Press up button to go to the next screen SEt

    Port.

    7.0 Setting the port characteristics:After reaching the screen SEt Port, press

    mode, display will show existing value for

    baud rate. Press mode again value will be

    flashing. By pressing up button change the

    value to required setting. Press Mode

    display will show L uP dAtE. Press mode

    again display will show ACCEPtEd

    followed by up dated screen.

    Press up button, display will change to parity

    setting screen as shown. Press mode,

    parameter EuEn will flash. Using up button

    choose EuEn or odd or nonE parity.

    Press mode, display will change to L uP date. Press mode

    again display will show ACCEPtEd followed by updatedscreen. Press down button display will show ESCAPE

    001nEtEr Id

    9600bAud rAtE

    EuEnPArIty

  • 7/30/2019 Quasar Manual

    36/48

    36

    followed by SEt Port. Press up button to go to next screenSEt dISP.

    8.0 Setting the default display:

    After reaching the screen SEt dISP, pressmode, display will show existing default

    screen number. Press mode, number will be

    flashing. By using up button change screen

    number, which will become default screen.

    Press mode, display will show L uP dAtE.

    Press mode again display will show

    ACCEPtEd followed by up dated screen.Press up button to go to the next screen SEt PASS.

    Note: Position 00 means screen NO 1,01 means screen NO 2

    and so on.

    9.0 Setting the pass word:

    After reaching the screen SEt PASS, press

    mode, display will show default password

    screen as shown. The zero will be flashing. By

    using up button, change the number into

    required new password.

    Press mode, display will show L uP dAtE. Press mode

    again display will show ACCEPtEd followed by SEt PASS

    screen. Press up button to go to the next screen CtPt rAt.

    Press down button to ESCAPE. Meter will show rEStArt

    and then return to normal display mode.

    00Position

    0000PASS ord

  • 7/30/2019 Quasar Manual

    37/48

    37

    Appendix 5: DISPLAY SCREENS -3PH, 3WIREScreen 1

    Total Power, Ave. Volts & Amps

    Screen 2

    Line Voltages

    Screen 3

    Currents

    Screen 4

    Inst. Active Power

    Screen 5

    Inst. Reactive Power

    Screen 6

    Inst. Apparent Power

    Screen 7

    Inst. Power Factor Power

  • 7/30/2019 Quasar Manual

    38/48

    38

    Screen 8

    Voltage angles

    Screen 9

    Phase angles

    Screen 10

    Total Active, Reactive &

    Apparent Power

    Screen 11

    Power demand, Total PF &

    Frequency

    Screen 12Cum. Active Energy

    Screen 13Cum. Inductive Energy

  • 7/30/2019 Quasar Manual

    39/48

    39

    Screen 14Cum. Capacitive Energy Screen 15Cum. Apparent Energy

    Screen 16

    Ph 1 - Total, Fundamental &

    Distortion Voltages

    Screen 17

    Ph 2 - Total, Fundamental &

    Distortion Voltages

    Screen 18

    Ph1 - Total, Fundamental &

    Distortion Currents

    Screen 19

    Ph2 - Total, Fundamental &

    Distortion Currents

  • 7/30/2019 Quasar Manual

    40/48

    40

    Appendix 6: DISPLAY SCREENS-3PHASE, 4WIRE

    Screen 1

    Total Power Ave. Volts & Am

    Screen 2

    3Ph. Voltages

    Screen 4

    3Ph. Currents

    Screen 5

    Inst. 3Ph. Active Power

    Screen 6

    Inst. 3Ph. Reactive Power

    Screen 7

    Inst. 3Ph. Apparent Power

    Screen 3

    Phase to phase voltages

  • 7/30/2019 Quasar Manual

    41/48

    41

    Screen 8

    Inst. 3Ph. Power Factor

    Screen 9

    Voltage angles

    Screen 10

    Phase angles

    Screen 11

    Total Active, Reactive &

    Apparent Power

    Screen 12

    Power demand, Total PF &

    Frequency

    Screen 13

    Cum. Active Energy

    Screen 14

    Cum. Inductive Energy

    Screen 15

    Cum. Capacitive Energy

  • 7/30/2019 Quasar Manual

    42/48

    42

    Screen 16

    Cum. Apparent Energy

    Screen 17

    Ph 1 - Total, Fundamental &

    Distortion Voltages

    Screen 18

    Ph 2 - Total, Fundamental &

    Distortion Voltages

    Screen 19

    Ph 3 - Total, Fundamental &

    Distortion Voltages

    Screen 20

    Ph1 - Total, Fundamental &

    Distortion Currents

    Screen 21

    Ph2 - Total, Fundamental &

    Distortion Currents

    Screen 22

    Ph3 - Total, Fundamental &

    Distortion Currents

  • 7/30/2019 Quasar Manual

    43/48

    43

    Appendix 7

    Wiring Diagram - 3 Ph. 4 Wire with CT & PT

  • 7/30/2019 Quasar Manual

    44/48

    44

    Wiring Diagram - 3 Ph. 4 Wire with CT & without PT

  • 7/30/2019 Quasar Manual

    45/48

    45

    Wiring Diagram - 3 Ph. 3 Wire with CT & PT

  • 7/30/2019 Quasar Manual

    46/48

    46

    Wiring Diagram - 3 Ph.3 Wire with CT & without PT

  • 7/30/2019 Quasar Manual

    47/48

    47

    Appendix 8: DIMENSIONAL DETAILS

  • 7/30/2019 Quasar Manual

    48/48

    Manufactured byLARSEN & TOUBRO LIMITED,KIADB INDUSTRIAL AREA,HEBBAL, HOOTAGALLI,MYSORE 570 018.Visit us www.lntebg.com

    www.larsentoubro.com

    Part No. 4D060100 Rev. 8