ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – LOAD BREAK SWITCH Q1 Q2
Sheet N° :1 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 1
Order N° : Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01
N° CHECKS CARRIED OUT ACCEPTED REFUSED
01 - Impulse withstand voltage 125 kV peak X
02 - Power frequency withstand voltage 50 kV rms/1 min X
03 - Internal arc withstand (kA 1s) 12.5kA rms/1 sec
X
04 - rated current 400 A X
05 - busbar rated current 400 A X
06 - index of protection IP 215 X
07 State of cleanliness X
08 3 Voltage indicator presence X
09 Switch test : open / close X
10
11 Open and Closed position contacts remote control of the switch X
12 Homopolar fault remote control X
13
14 Tor captor homopolar presence X
15 Homopolar fault X
16 Mechanical interlock (safety) devices presence and test X
17 Wiring control. X
18 Peephole of thermographie X
19 On voltage X
20
21
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01- PROTECTION TRANSFORMER – Q3;Q4;Q5;Q6.
Sheet N° : 2 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 2
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01
N° CHECKS CARRIED OUT ACCEPTED REFUSED
01 Verification of characteristics : operating voltage 20kV rated voltage 24kV X
02 - Impulse withstand voltage 125 kV peak X
03 - Power frequency withstand voltage 50 kV rms/1 min
X
04 - Internal arc withstand (kA 1s) 12.5 kA rms/1 sec X
05 - rated current 400 A X
06 - busbar rated current 400 A X
07 - index of protection IP 215 X
08 State of cleanliness X
09 3 Voltage indicator presence X
10 Switch test : open / close X
11 Manual tripp push button X
12 Presence of coil to triping X
13 Temperature alarm first stage (140°) separate box X
14 Temperature triping second stage (150°) separate box X
15 Triping on H.V. mealting fuse X
16 Wiring control. – LV monitoring cables - X
17 Open and Closed position contacts remote control of the switch X
18 Temperature alarm remote control + local X
19 Temperature triping remote control + local. X
20 Triping remote control. X
21 Presence of fuse with hammer X
22 Presence of 3 spare fuse X
23 Mechanical interlock (safety) devices presence and test X
24 H.V. & L.V. wiring X
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01- PROTECTION TRANSFORMER – Q3;Q4;Q5;Q6.
Sheet N° : 3 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 3
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01
N° CHECKS CARRIED OUT ACCEPTED REFUSED
25 On voltage X
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – DRY TRANSFORMER – T1;T2;T3;T4.
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Sheet N° : 4 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 4
Item and location : UNIT SUBSTATION RCD01
N° CHECKS CARRIED OUT ACCEPTED REFUSED
01 Verification of the characteristics on the identification plate X
02 Conformity with the data sheet TRIHAL type from Scneider X
03 Transformer power 1600 kVA X
04 Primary voltage 20 kV X
05 No load secondary voltage 410/230 V X
06 Frequency 50 Hz X
07 Insulation level 125/50 kV X
08 Coupling Dyn 11 X
09 Setting taps 0 /+ 2.5 / + 5 % X
10 Manufacturer Schneider X
11 Year of manufacture 2004 X
12 Serial Number
13 Verification of the equipment and accessories
14 Stage of cleanliness X
15 Presence of temperature indicator + contact temperature°C X
16 temperature adjustment : alarm 140°C X
17 tripping 150°C X
18 faults simulation Temperature alarm X
19 faults simulation Temperature tripping of the protection transformer cell X
20 Voltage adjustment position ............. value .......... % 20KV X
21 Presence of lifting rings X
22 Presence of rollers X
23 Test reports available X
24 Presence of fault transformer signalisation in the separate box X
25 Presence of grill protection to avoid direct contact with the other X
26 Presence of the key on the door X
27 On voltage X
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – DRY TRANSFORMER – T1;T2;T3;T4.
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Sheet N° : 5 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 5
Item and location : UNIT SUBSTATION RCD01
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB01
Sheet N° : 6 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 6
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09520 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
General characteristics
01 Okken type from Schneider X
02 Earthing : Earthing connection (door, envelop..) X
03 Marking X
04 Tightening X
05 General appearance (cleanliness, paint, finish) X
General circuit breaker CB01
06 2500 A – ICC 50 kA - 3 poles – adjustment setting X
07 adjustment setting IR 2500 A Im 7000 A 0.2s X
08 Current transformers : Number 4 class 1 X
09 Mesure device : PM 500 (A – V – P …) + remote control X
10 Measurement socket X
11 Open and Closed position contacts remote control of the main circuit breaker X
12 Operating handle X
13 Draw out on carriage type circuit breaker X
14 Mechanical interlock HT BT (safety) devices presence and test X
15 On voltage X
16
17
18
19
20
21
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB01
Sheet N° : 7 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 7
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09520 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
Secondary feeder circuit breakers
20 Padlock interlocking X
21 Outgoing feeder No 330 BD 01 CB02 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 Ka Dec STR23 X
22 Outgoing feeder No 330 BD 03 CB03 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
23 Outgoing feeder No 330 BD 07 CB04 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
24 Outgoing feeder No 330 BD 10 CB05 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 Ka Dec STR23 X
25 Outgoing feeder No 330 BD 13 CB06 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 Ka Dec STR23 X
26 Outgoing feeder No RCD1 DPB 02 CB07 X
Mark :Schneider Type :NS100 H N Poles : 3 X
Setting Ir : 63 A setting Im 630A ICC 70 Ka Dec STR22 X
27 Outgoing feeder No 125 DPB 02 CB08 X
Mark :Schneider Type :NS800 N N Poles : 3 X
Setting Ir : 800 A setting Im 5600A ICC 50 Ka Dec microl X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB01
Sheet N° : 8 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 8
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09520 B
28 Outgoing feeder No Capacitor bank CB09 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
29 Outgoing feeder No SPARE CB10 X
Mark :Schneider Type :NS160 N N Poles : 3 X
Setting Ir : A setting Im A ICC 36 kA Dec STR22 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB02
Sheet N° : 9 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 9
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09521 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
General characteristics
01 Okken type from Schneider X
02 Earthing : Earthing connection (door, envelop..) X
03 Marking X
04 Tightening X
05 General appearance (cleanliness, paint, finish) X
General circuit breaker CB01
06 2500 A – ICC 50 kA - 3 poles – adjustment setting X
07 adjustment setting IR 2500 A Im 7000 A 0.2s X
08 Current transformers : Number 4 class 1 X
09 Mesure device : PM 500 (A – V – P …) + remote control X
10 Measurement socket X
11 Open and Closed position contacts remote control of the main circuit breaker X
12 Operating handle X
13 Draw out on carriage type circuit breaker X
14 Mechanical interlock HT BT (safety) devices presence and test X
15 On voltage X
16
Coupling circuit breaker
17 Fixe part supplied only to avoid to put 2 transformers in parralelle X
18
19 Power connection with MDB 01 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB02
Sheet N° : 10 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 10
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09521 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
Secondary feeder circuit breakers
20 Padlock interlocking X
21 Outgoing feeder No 330 BD 02 CB02 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
22 Outgoing feeder No 330 BD 04 CB03 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
23 Outgoing feeder No 330 BD 08 CB04 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
24 Outgoing feeder No 330 BD 11 CB05 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
25 Outgoing feeder No 330 DPB01 CB06 X
Mark :Schneider Type :NS160 N N Poles : 3 X
Setting Ir 160 A setting Im 1600A ICC 36 kA Dec STR22 X
26 Outgoing feeder No 330 DPB02 CB07 X
Mark :Schneider Type :NS160 N N Poles : 3 X
Setting Ir 160 A setting Im 1600A ICC 36 kA Dec STR22 X
27 Outgoing feeder No 125A GF 01 CB08 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB02
Sheet N° : 11 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 11
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09521 B
28 Outgoing feeder No Capacitor bank CB09 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
29 Outgoing feeder No 125 DPB 01 CB10 X
Mark :Schneider Type :NS800 N N Poles : 3 X
Setting Ir : 800 A setting Im 5600A ICC 50 kA Dec microl X
30 Outgoing feeder No SPARE CB11 X
Mark :Schneider Type :NS160 N N Poles : 3 X
Setting Ir : A setting Im A ICC 36 kA Dec STR22 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB03
Sheet N° : 12 By : TERRISSE/HAUTA Date : 14.12.O4 Folio12
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09522 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
General characteristics
01 Okken type from Schneider X
02 Earthing : Earthing connection (door, envelop..) X
03 Marking X
04 Tightening X
05 General appearance (cleanliness, paint, finish) X
General circuit breaker CB01
06 2500 A – ICC 50 kA - 3 poles – adjustment setting X
07 adjustment setting IR 2500 A Im 7000 A 0.2s X
08 Current transformers : Number 4 class 1 X
09 Mesure device : PM 500 (A – V – P …) + remote control X
10 Measurement socket X
11 Open and Closed position contacts remote control of the main circuit breaker X
12 Operating handle X
13 Draw out on carriage type circuit breaker X
14 Mechanical interlock HT BT (safety) devices presence and test X
15 On voltage X
16
Coupling circuit breaker
17 Fixe part supplied only to avoid to put 2 transformers in parralelle X
18
19 Power connection with MDB 04 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB03
Sheet N° : 13 By : TERRISSE/HAUTA Date : 14.12.O4 Folio13
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09522 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
Secondary feeder circuit breakers
20 Padlock interlocking X
21 Outgoing feeder No 330 BD 05 CB02 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
22 Outgoing feeder No 330 BD 06 CB03 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
23 Outgoing feeder No 330 BD 09 CB04 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
24 Outgoing feeder No 330 BD 12 CB05 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
25 Outgoing feeder No RCD1 DPB01 CB06 X
Mark :Schneider Type :NS100 H N Poles : 3 X
Setting Ir 100 A setting Im 1000A ICC 70 kA Dec STR22 X
26 Outgoing feeder No 330 DPB03 CB07 X
Mark :Schneider Type :NS250 N N Poles : 3 X
Setting Ir 250 A setting Im 1750A ICC 36 kA Dec STR22 X
27 Outgoing feeder No 330DPB 04 CB08 X
Mark :Schneider Type :NS100 H N Poles : 3 X
Setting Ir 100 A setting Im 1000A ICC 70 kA Dec STR22 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board MDB03
Sheet N° : 14 By : TERRISSE/HAUTA Date : 14.12.O4 Folio14
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09522 B
28 Outgoing feeder No 125 GF 02 CB09 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 Ka Dec STR23 X
29 Outgoing feeder No 330 LP 01 CB10 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
30 Outgoing feeder No Capacitor bank CB11 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
31 Outgoing feeder No SPARE CB12 X
Mark :Schneider Type :NS250 N N Poles : 3 X
Setting Ir A setting Im A ICC 36 kA Dec STR22 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board – MDB04
Sheet N° : 15 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 15
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09523 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
General characteristics
01 Okken type from Schneider X
02 Earthing : Earthing connection (door, envelop..) X
03 Marking X
04 Tightening X
05 General appearance (cleanliness, paint, finish) X
General circuit breaker CB01
06 2500 A – ICC 50 kA - 3 poles – adjustment setting X
07 adjustment setting IR 2500 A Im 22800 A X
08 Current transformers : Number 4 class 1 X
09 Mesure device : DIRIS PM 500 (A – V – P …) + remote control X
10 Measurement socket X
11 Open and Closed position contacts remote control of the switch X
12 Auxiliary cabling contacts X
13 Operating handle X
14 Draw out on carriage type circuit breaker X
15 Mechanical interlock HT BT (safety) devices presence and test X
16 On voltage X
17
Coupling circuit breaker
18 Fixe part supplied only to avoid to put 2 transformers in parralelle X
19 Auxiliary contacts cabling X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board – MDB04
Sheet N° : 16 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 16
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09523 B
N° CHECKS CARRIED OUT ACCEPTED REFUSED
Secondary feeder circuit breakers
20 Padlock interlocking X
21 Outgoing feeder No 330 BD 50 CB02 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
22 Outgoing feeder No 330 BD 51 CB03 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
23 Outgoing feeder No 330 BD 52 CB04 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4410A ICC 45 kA Dec STR23 X
24 Outgoing feeder No 330 BD 53 CB05 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4410A ICC 45 kA Dec STR23 X
25 Outgoing feeder No 330 BD 54 CB06 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4410A ICC 45 kA Dec STR23 X
26 Outgoing feeder No 330 BD 55 CB07 X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
27Outgoing feeder No 330 BD 56 CB08
X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4410A ICC 45 kA Dec STR23 X
ZAR ZALAU SYSTEM 02 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – Main distribution board – MDB04
Sheet N° : 17 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 17
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 drawing ZR330 09523 B
28Outgoing feeder No 330 BD 57 CB09
X
Mark :Schneider Type :NS400 N N Poles : 3 X
Setting Ir : 400 A setting Im 2800A ICC 45 kA Dec STR23 X
29Outgoing feeder No 330 BD 58 CB10
X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4410A ICC 45 kA Dec STR23 X
30 Outgoing feeder No Capacitor bank CB11 X
Mark :Schneider Type :NS630 N N Poles : 3 X
Setting Ir : 630 A setting Im 4400A ICC 45 kA Dec STR23 X
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – CAPACITOR BANK 01 02 03 04
Sheet N° : 18 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 18
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 CAPACITOR BANK 01 – 02 – 03 - 04
N° CHECKS CARRIED OUT ACCEPTED REFUSED
1 Presence of capacitor bank 01 X
2 Presence of capacitor bank 02 X
3 Presence of capacitor bank 03 X
4 Presence of capacitor bank 04 X
5 State of cleanliness of equipment X
6 Cabinet with front doors X
7 Ventilation grills or other X
8 Circuit protection devices X
9 Presence and rating of three pole contactor ( 5 pieces ) X
10 Connection space X
11 Presence of slow discharge devices X
12 Presence of fast discharge devices X
13 Position varimetric adjuster accessible on the front face with doors closed X
14 Wiring connections X
15 Fixation of device inside the panel X
16 Presence of earth terminal X
17 Cabling and equipment marking X
18 Presence of Danger - Electric Shock placard on front face X
19 Presence of lifting rings X
20 Presence of drawing inside the panel X
21 Check correct operation of varimetric adjuster in manual and automatic X
22 Setting power factor 0,95 X
23 Connection and setting of Capacitor bank N°04 X
24 On voltage batteries 1 – 2 – 3 X
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 – CAPACITOR BANK 01 02 03 04
Sheet N° : 19 By : TERRISSE/HAUTA Date : 14.12.O4 Folio 19
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01 CAPACITOR BANK 01 – 02 – 03 - 04
N° CHECKS CARRIED OUT ACCEPTED REFUSED
25 On voltage Battery 4 X
ZAR ZALAU SYSTEM 01 -CONFORMITY SHEET S T Gs1
TechnicalSpecification RCD01 - SUBSTATION BUILDING
Sheet N° : 20 By : TERRISSE/HAUTA Date : 25 01O5 Folio 20
Order N° : 6168 on 13/02/2004 Project N° A130050 R
Item and location : UNIT SUBSTATION RCD01
N° CHECKS CARRIED OUT ACCEPTED REFUSED
01 State of cleanliness inside aspect : X
02 Exterior wall aspect X
03 Roof waterproof X
04 Insolation of building (water in the gutter) X
05 Painting walls and ceiling X
06 Soil paint with anti dust paint X
07 Presence of Anti panic barre on the door
08 Safty equipment following data scheet X
09 Presence of Danger - Electric Shock placard on the doors X
10 Presence and good location of normal Inside lighting (lighting panel + installation) X
11 Presence and good location of Emergency lighting X
12 Presence , good location and characteristic of UPS for workshop Emergency lighting X
13 Presence and good location of outlet X
14 Presence and good location of ventilation transformers room X
15 Presence and good location of ventilation in the substation X
16 Presence of extingwisher X
17 Presence of fire detection installation X
18 Presence of outside lighting panel X
19 Earthing installation and connection around the substation X
20 Gutter cover ( to be installed ) X
21 State of cleaness of the floor X
22
23
24
ZAR PROJECT SYSTEM 01 -CONFORMITY SHEET S T P G
TechnicalSpecification 20 KV SPECIAL LINKS RCD01
Sheet N° : 21 By : TERRISSE/HAUTA Date : 14.12.O4 Folio : 21
Order N° : 6168 on 13/02/2004
Item and location : High voltage installation
N° CHECKS CARRIED OUT ACCEPTED REFUSED
1 HV cable tray and HV conducts : X
- laying X
2
3 HV cable 20 kV 3 x 1 x 185² copper 24 kV + ground (no insulated copper) : X
4 - laying in distribution manhool X
5 - marking in distribution manhool To be done
6 - laying on cable trays X
7 - marking on cable trays X
8 - connection to substation X
9 - On voltage X
ZAR ZALAU SYSTEM 04 - CONFORMITY SHEET S T GS1
TechnicalSpecification LIGHTING EXTERIOR CABINET – RCD 01 LP 01
Sheet N° : 22 By : TERRISSE/HAUTA Date : 14.12.O4 Folio : 22
Order N° : 6168 on 13/02/2004 Project N° A130050 R:
Item and location :Outside lighting panel
N° CHECKS CARRIED OUT ACCEPTED REFUSED
1 General appearance X
2 Cabinet dimensions, extension possibility 30% X
3 Cladding protection index IP 55 X
4 Presence of padlockable door or fascias X
5 Presence of document pocket X
6 Attachment of cladding X
7 Rating of general switch 63A X
8 Presence of padlockable interlock system on general load break switch (possibility of 3 padlocks)
X
9 Presence of protection of general load break switch against direct contacts X
10 Busbar rating X
11 Presence of protection of busbar against direct contacts X
12 Verification of number of circuit breaker outgoing feeders X
13 Verification of ratings in relation to the diagram X
14 Circuit breaker breaking capacity ( 10 – 20 KA ) X
15 Type of circuit breaker X
16 Verification of wire colours X
17 Verification of wire tightening X
18 Verification of wire marking X
19 Incoming feeder cables connection space X
20 Outgoing feeder cable connection space X
21 Verification of protection conductors connections to earth bar X
22 Verification of correct earthing continuity X
23 Attachment and marking of switchgear X
24 Marking and colour of cabinet X
ZAR ZALAU SYSTEM 04 - CONFORMITY SHEET S T GS1
TechnicalSpecification LIGHTING EXTERIOR CABINET – RCD 01 LP 01
Sheet N° : 23 By : TERRISSE/HAUTA Date : 14.12.O4 Folio : 23
Order N° : 6168 on 13/02/2004 Project N° A130050 R:
Item and location :Outside lighting panel
N° CHECKS CARRIED OUT ACCEPTED REFUSED
25 On voltage X
ZAR PROJECT SYSTEM 03 - CONFORMITY SHEET S T P G
TechnicalSpecification UPS SUBSTATIONS UNIT FOR EMERGENCY LIGHTING
Sheet N° : 24 By : TERRISSE/HAUTA Date : 14.12.O4 Folio : 24
Order N° : 6168 on 13/02/2004 Project N° :
Item and location : RCD O1.
N° CHECKS CARRIED OUT ACCEPTED REFUSED
1
2 Verification of earthing to terminals X
3 Verification of battery type X
4 Verification of number of items X
5 Verification of correct battery connection X
6 Verification of dry battery X
7 General fault inverter reported to terminals X
8 Verification of conformity of cabling and connections X
9 Test report available X
10 Verification of correct operation of assembly X
11 On voltage X
ZAR ZALAU SYSTEM 02 - CONFORMITY SHEET S T GS1
TechnicalSpecification LOW VOLTAGE DISTRIBUTION PANEL BOARDDPB 01
Sheet N° : 25 By : TERRISSE/HAUTA Date : 14.12.O4 Fol 25
Order N° : 6168 on 13/02/2004 Project N° :
Item and location : RCD01 substation
N° CHECKS CARRIED OUT ACCEPTED REFUSED
1 General appearance, paint, marking X
2 Dimensions, extension possibilities 30 % X
3 Incoming / outgoing feeder cables connection space X
4 Cladding protection index IP55 X
5 Door closing, padlock system X
6 Cable glands X
7 Cabinet attachment device X
8 Attachment and marking of switchgear X
9 Load break switch : X
- breaking capacity , rating, direct contacts protection, padlocking possibility X
10 Outgoing feeder circuit breakers : X
- quantity X
- breaking capacity X
- rating X
- type X
12 Cabling : X
- colour X
- cross-section X
- tightening X
- marking X
13 Earthing bar, protection conductors connections X
14 Earthing X
15 Busbar X
16 On voltage X
ZAR ZALAU SYSTEM 02 - CONFORMITY SHEET S T GS1
TechnicalSpecification LOW VOLTAGE DISTRIBUTION PANEL BOARDDPB 02
Sheet N° : 26 By : TERRISSE/HAUTA Date : 14.12.O4 Fol 26
Order N° : 6168 on 13/02/2004 Project N° :
Item and location : RCD01 substation
N° CHECKS CARRIED OUT ACCEPTED REFUSED
1 General appearance, paint, marking X
2 Dimensions, extension possibilities 30 % X
3 Incoming / outgoing feeder cables connection space X
4 Cladding protection index IP55 X
5 Door closing, padlock system X
6 Cable glands X
7 Cabinet attachment device X
8 Attachment and marking of switchgear X
9 Load break switch : X
- breaking capacity , rating, direct contacts protection, padlocking possibility X
10 Outgoing feeder circuit breakers : X
- quantity X
- breaking capacity X
- rating X
- type X
12 Cabling : X
- colour X
- cross-section X
- tightening X
- marking X
13 Earthing bar, protection conductors connections X
14 Earthing X
15 Busbar X
16 On voltage X