SACE Tmax XT
XT1-XT2-XT3-XT4
FC CuAl e t. - Terminali esterni per cavi x XT1-XT2-XT3-XT4.FC CuAl ext. - External terminals for cables XT1-XT2-XT3-XT4.FC CuAl ext. - Externe Anschlusse fur Kabel XT1-XT2-XT3-XT4.FC CuAl ext. - Prises extèrieures pour càbles XT1-XT2-XT3-XT4.FC CuAl ext. - Terminales exteriores para cables XT1-XT2-XT3-XT4.
Doc. N.° 1SDH000719R0816 - B1247
1XT1 XT3 XT2 XT4
1
F-P
-W
2 2XT2 - 70 mm ...185 mm
III IV
1(2)
3(6)
3(6)
1(2)
4(8)
4(8)
2 2XT2 - 2x35 mm ...70mm
III IV
1(2)
3(6)
3(6)
3(6)
1(2)
4(8)
4(8)
4(8)
2 2XT1 - 35 mm ...95 mm
III IV
3(6) 4(8)
1(2) 1(2)
XT3 - 2 22x35 mm ...120 mm
III IV
1(2)
3(6)
1(2)
3(6)
1(2)
4(8)
1(2)
4(8)
XT4 - 2 22x35 mm ...120 mm
III IV
1(2)
3(6)
3(6)
3(6)
1(2)
4(8)
4(8)
4(8)
1(2) 1(2) 1(2) 1(2)1(2) 1(2) 1(2) 1(2) 1(2) 1(2)
XT2 - 2x2 AWG...2/0 AWG XT3 - 2x2 AWG...250 KcmilXT2 - 2/0 AWG...350 Kcmil XT4 - 2x2 AWG...250 KcmilXT1 - 2 AWG...4/0 AWG
SACE Tmax XT | ABB
3
5
1 2
XT1 - XT2 - XT3 - XT4 2 2XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)4
6 2 2XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
ONLY FOR XT1F - XT3F ONLY FOR XT2 F- XT4 F
2 2XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
2
1
FOR XT1F UL ONLY
FOR UL ONLY
2
1
FOR UL ONLY
FOR UL ONLY
6 Nm
2
1 3
453 lb in
16 M
IN0.
63"
MIN
13.5 Nm
21
120 lb in
2MAX 95 mm2MIN 35 mm
CuAlStranded
CuAlFlexible
MAX 4/0 AWGMIN 2 AWG
13
4
2
6 Nm53 lb in
5
SACE | ABBTmax XT
9
11
7 8
2 2XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil) 2 2 XT3 - FC-CuAl EXT- 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
10
2 2XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
2 2XT3 - FC-CuAl EXT- 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
100
(3.9
4")
42 M
IN1.
65"
MIN
22 M
IN0.
87"
MIN
16 Nm142 lb in
31 Nm274 lb in
1
32
20 M
IN0.
79"
MIN
2MAX 185 mm2MIN 70 mm
CuAlStranded
CuAlFlexible
MAX 350 KcmilMIN 2/0 AWG
- Attenzione: fissare i cavi al quadro prima di serrare i morsetti; Setti di ancoraggio a cura del cliente.- Important note: fit the cables to the switchboard before tightening the terminals; Anchor plates to be supplied by the customer.- Achtung: vor dem Festziehen der Klemmen die Kabel an der Schaltanlage befestigen; Verankerungswände vom Kunden beizustellen.- Attention: fixer les câbles au tableau avant de serrer les bornes;Secteurs d’ancrage à la charge du client.- Atención: sujetar los cables al cuadro antes de apretar los bornes; Placas de anclaje a cargo del cliente.
2MAX 150 mm2MIN 35 mm
CuAlStranded
CuAlFlexible
MAX 300 KcmilMIN 2 AWG
1
L 18 mmL 0.71"
3
42
L 20 mmL 0.79"
8 Nm71 lb in
5
SACE Tmax XT | ABB
13 14
12
15
2 XT3 - FC-CuAl EXT- 2x120 mm (2x250 Kcmil)
2 2XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG)
2 2XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG) 2. 2XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
3 POLES81,5 (3.21")81,5 (3.21")
AB
4 POLES64 (2.52")99 (3.90") Ø 2,6
Ø 0.10"
AB
17,50.69"
17,50.69"
X
122
(4.8
0")
70 (2.76") (IV POLES ONLY)
X
155
(6.1
0")
Ø 4,5Ø 0.18"
1,1 Nm9.7 lb in
5
1
3
2
3
1
3
3
4
XT218/33 (0.71"/1.30")A
XT422/42 (0.87"/1.65")
XT2 12 Nm/106 lb in
XT4 16 Nm/142 lb in1
A M
IN
2MAX 70 mm2MIN 35 mm
CuAlStranded
CuAlFlexible
MAX 2/0 AWGMIN 2 AWG
MAX 250 KcmilMIN 2 AWG
2MAX 120 mm2MIN 35 mm
XT2
XT4
2. 2XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
53 lb in
3
4
2
1
6 Nm 5
71 lb in
3
4
2
L 18 mmL 0.71"
L 20 mmL 0.79"
1
8 Nm 5
SACE | ABBTmax XT
17
19
16
2 2XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
18
20
XT1 - XT2 - XT3 - XT4
1
32
1
2
2
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
P-W
XT2
III IV
1(2)
XT3
III IV
1(2)
XT1
III IV
1(2)
XT4
III IV
1(2)
2(4) 2(4) 2(4) 2(4)2(4) 2(4) 2(4) 2(4)
1(2) 1(2)1(2) 1(2)
XT1 - XT2 - XT3 - XT4
2 2XT1 - FC-CuAl EXT - 35 mm ...95 mm (2 AWG...4/0 AWG)
2
31
4
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
SACE Tmax XT | ABB
2625
23 24
2 2 XT3 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)2 2 XT3 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)23 24 2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)23 24 2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
21 22 2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil) 2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil) 2 2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)2 2 XT2 - FC-CuAl EXT - 70 mm ...185 mm (2/0 AWG...350 Kcmil)
100
31 Nm274 lb in
1
32
- Attenzione: fissare i cavi al quadro prima di serrare i morsetti;Setti di ancoraggio a cura del cliente.- Important note: fit the cables to the switchboard before tightening the terminals; Anchor plates to be supplied by the customer.- Achtung: vor dem Festziehen der Klemmen die Kabel an der Schaltanlage befestigen; Verankerungswände vom Kunden beizustellen.- Attention: fixer les câbles au tableau avant de serrer les bornes; Secteurs d’ancrage à la charge du client.- Atención: sujetar los cables al cuadro antes de apretar los bornes; Placas de anclaje a cargo del cliente.
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
13
4
2
5
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
1
L 20 mmL 0.79"
3
42
5
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
L 18 mmL 0.71"
27
© Copyright 2011-2017 ABB. All rights reserved. www.abb.com
2 2XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
2 2XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG) 2 2XT4 - FC-CuAl EXT - 2x35 mm ...120 mm (2x2 AWG...250 Kcmil)
28
30
292 2XT2 - FC-CuAl EXT - 2x35 mm ...70 mm (2x2 AWG...2/0 AWG)
2 2 XT3 - FC-CuAl EXT - 2x35 mm ...150 mm (2x2 AWG...250 Kcmil)
For more information please contact:
ABB S.p.A.ABB SACE DivisionVia Pescaria, 524123 Bergamo - ItalyPhone: +39 035 395 111
1
3
2
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
Ø 2,6Ø 0.10"
C B
43,51.71"
X
501.
97"
X
225
8.85
"
Ø 4,5Ø 1.78"
A
Y
Y
3 POLES43,5 (1.71")81,5 (3.21")
AB
4 POLES78,5 (3.09")64 (2.52")
81,5 (3.21")C 99 (3.90")
2,5 Nm22 lb in
51
3
2
1
3
4
1
3
4
2
5
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
3
4
2
5
Per l’installazione fare riferimento a interruttore fissoFor installation refer to fixed circuit-breakerFür die Installation zu festen Leistungsschlater beziehenPour l'installation reporter à le disjoncteur fixePara la instalación consulte el interruptor fijo
L 18 mmL 0.71"
1L 20 mmL 0.79"