Safe Operation of Heater-Column-He

Embed Size (px)

Citation preview

  • 8/2/2019 Safe Operation of Heater-Column-He

    1/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 1

    Safe operation of

    equipment Process Heaters

    Heat exchangersColumns

  • 8/2/2019 Safe Operation of Heater-Column-He

    2/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 2

    Equipment safety

    Design safetySafety in operation

    Safety during maintenance

  • 8/2/2019 Safe Operation of Heater-Column-He

    3/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 3

    Safe operation ProcessHeaters

    Knowledge of equipmentPurposeType

    Tube/refractory materialBurner/Soot blowerDraught

    NaturalForcedInduced

    Balanced

  • 8/2/2019 Safe Operation of Heater-Column-He

    4/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 4

    Safe operation ProcessHeaters

    Knowledge of proceduresNormal operationStart up

    Shut downEmergencyDecoking

    Refractory dry outSoot blowingHanding

    overSpecial procedures

  • 8/2/2019 Safe Operation of Heater-Column-He

    5/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 5

    Safe operation ProcessHeaters

    Field monitoringBox conditionTube appearance,

    skin temperatureHot spotsFlame pattern

    Stack damper/ flue gasBack fireOil dripping

    Gas monitor sensors

  • 8/2/2019 Safe Operation of Heater-Column-He

    6/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 6

    Safe operation ProcessHeaters

    Process control - DCSFlow,Temperaturedraught, Excess air etc..

    Safety interlocks - PLCShutdown interlocksStart up bypass

    Emergency shutdownInterlock bypass recordsGas monitors

  • 8/2/2019 Safe Operation of Heater-Column-He

    7/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 7

    Safe operation ProcessHeaters

    Start upFlow through coilBox purgingLining up of fuelLining up of atomising steamPilot flameMain flameSlow heating

  • 8/2/2019 Safe Operation of Heater-Column-He

    8/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 8

    Safe operation ProcessHeaters

    Shut downSlow cooling

    Fuel isolationBurner purging

    Box purging

  • 8/2/2019 Safe Operation of Heater-Column-He

    9/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 9

    Interlocks in FurnaceLow Pass Flow

    Low Fuel oil pressureLow Fuel gas pressureLow Comb. Air PressureLow Comb. Air flowHigh Arch Pressure

    High Arch TemperatureAtom. Steam pre ssure lowFD Fan LEL Alarm / ID fan Failure

  • 8/2/2019 Safe Operation of Heater-Column-He

    10/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 10

    Furnace lighting up

    Clean the inside areaBox up the furnaceEnsure all FO/FG valves are closed

    Wide open the stack dampersOpen secondary air louversPurge the furnace for 20 mins with box

    purging steamEstablish FO CirculationEstablish the flow through the coil

  • 8/2/2019 Safe Operation of Heater-Column-He

    11/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 11

    Furnace lighting up

    Ensure primary and secondary air louversare half openEnergize furnace trip system

    Light pilot burnerNow open main gas audco valve one byone and light up FG burner( if burner donot light up in 10 secs,close audco valve

    and purge the heater once again)Slowly increase the outlet temperatureand increasing firing

  • 8/2/2019 Safe Operation of Heater-Column-He

    12/13

    3/24/2012 R.Sivakumar CDU-2 (MFG) 12

    Furnace lighting up

    Then light up oil fire after purgingthe oil gun ,adjust the P of theatomizing steamEnsure uniform firing in all burner to

    keep the heat distribution uniformBring the heater to normal operating

    conditionAPH to be taken in line.

  • 8/2/2019 Safe Operation of Heater-Column-He

    13/13

    3/24/2012R.Sivakumar CDU-2 (MFG)

    13

    COLUMN

    Safety / Relief valvesBottom Level Controller

    Low & High Level switchesTwo temperature point at topLow / High Level Switches for

    R.DrumPressure ControllerDiff. Pressure indicators.