3/24/2012 R.Sivakumar CDU-2 (MFG) 1
Safe operation of
equipment Process Heaters
Heat exchangersColumns
8/2/2019 Safe Operation of Heater-Column-He
2/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 2
Equipment safety
Design safetySafety in operation
Safety during maintenance
8/2/2019 Safe Operation of Heater-Column-He
3/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 3
Safe operation ProcessHeaters
Knowledge of equipmentPurposeType
Tube/refractory materialBurner/Soot blowerDraught
NaturalForcedInduced
Balanced
8/2/2019 Safe Operation of Heater-Column-He
4/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 4
Safe operation ProcessHeaters
Knowledge of proceduresNormal operationStart up
Shut downEmergencyDecoking
Refractory dry outSoot blowingHanding
overSpecial procedures
8/2/2019 Safe Operation of Heater-Column-He
5/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 5
Safe operation ProcessHeaters
Field monitoringBox conditionTube appearance,
skin temperatureHot spotsFlame pattern
Stack damper/ flue gasBack fireOil dripping
Gas monitor sensors
8/2/2019 Safe Operation of Heater-Column-He
6/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 6
Safe operation ProcessHeaters
Process control - DCSFlow,Temperaturedraught, Excess air etc..
Safety interlocks - PLCShutdown interlocksStart up bypass
Emergency shutdownInterlock bypass recordsGas monitors
8/2/2019 Safe Operation of Heater-Column-He
7/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 7
Safe operation ProcessHeaters
Start upFlow through coilBox purgingLining up of fuelLining up of atomising steamPilot flameMain flameSlow heating
8/2/2019 Safe Operation of Heater-Column-He
8/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 8
Safe operation ProcessHeaters
Shut downSlow cooling
Fuel isolationBurner purging
Box purging
8/2/2019 Safe Operation of Heater-Column-He
9/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 9
Interlocks in FurnaceLow Pass Flow
Low Fuel oil pressureLow Fuel gas pressureLow Comb. Air PressureLow Comb. Air flowHigh Arch Pressure
High Arch TemperatureAtom. Steam pre ssure lowFD Fan LEL Alarm / ID fan Failure
8/2/2019 Safe Operation of Heater-Column-He
10/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 10
Furnace lighting up
Clean the inside areaBox up the furnaceEnsure all FO/FG valves are closed
Wide open the stack dampersOpen secondary air louversPurge the furnace for 20 mins with box
purging steamEstablish FO CirculationEstablish the flow through the coil
8/2/2019 Safe Operation of Heater-Column-He
11/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 11
Furnace lighting up
Ensure primary and secondary air louversare half openEnergize furnace trip system
Light pilot burnerNow open main gas audco valve one byone and light up FG burner( if burner donot light up in 10 secs,close audco valve
and purge the heater once again)Slowly increase the outlet temperatureand increasing firing
8/2/2019 Safe Operation of Heater-Column-He
12/13
3/24/2012 R.Sivakumar CDU-2 (MFG) 12
Furnace lighting up
Then light up oil fire after purgingthe oil gun ,adjust the P of theatomizing steamEnsure uniform firing in all burner to
keep the heat distribution uniformBring the heater to normal operating
conditionAPH to be taken in line.
8/2/2019 Safe Operation of Heater-Column-He
13/13
3/24/2012R.Sivakumar CDU-2 (MFG)
13
COLUMN
Safety / Relief valvesBottom Level Controller
Low & High Level switchesTwo temperature point at topLow / High Level Switches for
R.DrumPressure ControllerDiff. Pressure indicators.