XPS
Surge Arrester - System Voltage 2 kV to 245 kV
XPS Station Class Silicone-Housed Arresters
Metal Oxide Surge Arrester XPS
2
Performance data
Maximum system voltages (Vm) 2.52 - 245 kVrms
Duty cycle rated voltages (Vr) 3 - 240 kVrms
Classifying current (ANSI/IEEE) 10 kA peak
Discharge current withstand strength: High current 4/10 µs 100 kA peak Low current 2000 µs 900 A peak
Energy capability: 2 impulses, (IEC CI. 7.5.5) 9.8 kJ / kV of MCOV Fullfi lls requirements of ANSI transmission-line discharge test for 245 kV systems Short-circuit / Pressure relief capability 65 kA rms sym Cantilever strength 20000 in - lbs / 2260 Nm Service conditions: Ambient temperature -50°C to + 45 °C Design altitude 6000 ft / 1830 m Frequency 15 - 62 Hz
Application
The XPS polymer arrester has been verifi ed to meet sta-tion class requirements of ANSI C62.11 (IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits). The XPS arrester is designed to meet the following performance data:
Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. For use when requirements of lightning in-tensity, energy capability and pollution are moderate.
Superior design where low weight, reduced clearances, fl exible mounting, and shatter-proof housing is required.
1) Higher strength designs available on request
2) Higher altitude designs available on request
Station Class Silicone-Housed Arresters XPS
3
Nameplate
Direct-Molded Construction
ABB’s type XPS surge arrester consists of high performance metal oxide disks molded in a shat-ter-proof polymer housing. The XPS now has a new construction to enhance overall lifetime performance.
The metal oxide disks are enclosed in a support as-sembly consisting of reinforced epoxy/fi berglass loops connecting the upper and lower aluminum end pieces. The silicone polymer material is then molded directly to the metal oxide loop assembly eliminating any air pockets which could cause moisture ingress over time.
Each arrester is furnished with a mounting base for an 8.75 in / 222 mm to 10.0 in / 254 mm diameter bolt circle along with 4-hole NEMA pad, line and ground terminals for electrical connections.
100% Silicone Based Housing
The silicone rubber housing features high tracking and arc resistance, excellent hydrophobic properties, and resistance to weathering, UV radiation and pollution.
Benefi ts
The incorporation of polymer material in a station class surge arrester has resulted in many additional advantages. Among these are:
Reduced Electrical ClearancePolymer construction has resulted in much smaller housing dimensions in comparison with porcelain units of the same voltage rating. This size reduction enables effi cient use of space for switchgear enclosures, mobile substations and other applications where space restrictions are present.
LightweightThe type XPS arrester is less than 50 percent the weight of its porcelain counterpart, which results in easier handling and installation.
Damage ResistantPolymer construction reduces possible shipping and handling damage, as well as, damage due to vandalism.
Safety
Shatter-resistant construction provides greater protection for personnel, as well as, nearby equipment.
STYLE No.
kV rms kV rmsRATING
PRESSURE RELIEF
GRADING RING
BEFORE INSTALLING READ INSTRUCTIONS
MADE IN USA
MCOV
kA rms
TYPE XPS STATION CLASS SURGE ARRESTER
WT.
CLASS
IL 38-337-1
SERIAL No.
ABB Inc.
9.27
12.3
18.6
12.3
20.4
18.5
24.6
18.5
24.6
36.920.424.6
36.9
36.9
47.1
36.9
47.1
59.1
41.4
53.2
70.9
59.1
76.8
70.9
88.6
24.6
30.7
47.4
20.4
12.3
with current wave, kV peak
9.27
Guaranteed Performance Data
Power frequency voltage, kV rms
4
TOV (5)FOW (8)LPL (7)
12.3
18.5
20.4
30.7
20.4
30.7
30.7
41.4
53.2
41.4
59.1
53.2
36.9
70.9
53.2
SPL (6)30/60 µs
XPS Station Class Silicone-Housed Arresters
8/20 µsNom.Vn (1)2.404.164.164.806.906.906.908.328.328.328.3212.012.012.012.012.4712.4712.4712.4712.4713.213.813.813.820.7820.7820.7820.7820.7822.8623.0023.0023.0023.0024.9424.9424.9424.9424.9424.9434.534.534.534.534.546.0
Max.Vm (2)2.524.374.375.047.247.247.24 8.738.738.738.7312.612.612.612.613.1013.1013.1013.1013.1013.914.514.514.521.821.821.821.821.8
24.00 24.1524.1524.1524.15 26.1926.1926.1926.1926.1926.19
36.2 36.236.236.236.248.3
RatingVr (3)
3366691069101291012159101215181012151815182124271821242730182124273036273036394536
MCOV(4)
2.552.555.105.105.107.658.405.107.658.4010.27.658.4010.212.77.658.4010.212.715.38.4010.212.715.312.715.317.019.522.015.317.019.522.024.415.317.019.522.024.429.022.024.429.031.536.529.0
1 s5.265.267.177.177.1710.511.77.1710.711.914.010.711.914.317.510.711.914.317.921.511.914.317.921.517.921.524.527.631.521.525.027.631.535.121.525.027.631.535.841.431.535.841.444.852.641.4
10 s5.045.046.846.846.8410.011.26.8410.211.413.410.211.413.616.810.211.413.617.120.511.413.617.120.517.120.523.526.430.220.523.926.430.233.620.523.926.430.234.239.630.234.239.642.950.439.6
3 kA 10.410.413.813.813.820.824.413.820.823.027.620.823.027.634.520.823.027.634.541.423.027.634.541.434.541.446.452.959.741.446.452.959.766.341.446.452.959.766.379.559.766.379.586.299.479.5
5 kA10.810.814.314.314.321.525.214.321.523.828.521.523.828.535.921.523.828.535.642.823.828.535.642.835.642.848.254.761.942.848.254.761.968.442.848.254.761.968.882.161.968.882.689.010382.6
10 kA11.311.315.015.015.022.625.015.022.625.030.022.625.030.037.522.625.030.037.545.025.030.037.545.037.545.050.457.664.845.050.457.664.872.045.050.457.664.872.086.464.872.086.493.610886.4
20 kA12.512.516.516.516.524.929.216.524.927.532.924.927.532.941.324.927.532.941.349.327.532.941.349.341.349.355.563.471.349.355.563.471.379.249.355.563.471.379.295.171.379.295.110311995.1
40 kA13.913.918.518.518.527.832.618.527.830.836.927.830.836.946.227.830.836.946.155.430.836.946.155.446.155.462.070.879.855.462.070.879.888.655.462.070.879.888.610779.888.6107116133107
0.5 µs10 kA12.312.317.117.117.124.528.717.124.427.034.224.427.034.240.524.427.034.240.551.327.034.240.551.340.551.354.762.270.451.354.762.270.477.851.354.762.270.478.293.470.478.293.410211793.4
76.846.0 48.3 39 31.5 44.8 42.9 86.2 89.4 93.6 103 116 102
5
Station Class Silicone-Housed Arresters XPS
with current wave, kV peakPower frequency voltage, kV rms
SPL (6)TOV (5)FOW (8)LPL (7)
30/60 µs8/20 µs
(1) Vn = Nominal System Voltage per ANSI C84.1
(2) Vm = Maximum System Voltage per ANSI C84.1
(3) Vr = Duty Cycle Rated Voltage per ANSI C62.11
(4) MCOV = Maximum Continuous Operating Voltage per ANSI C62.11
(5) TOV = Temporary Overvoltage with No Prior Energy
(6) SPL = Switching Protective Level
500 A 3 - 132 kV 1,000 A 144 - 240 kV (7) LPL = Lightning Protective Level
(8) FOW = Front of Wave
Nom.Vn (1)46.046.046.046.046.06969696969115115115115115115115138138138138138138161161161161161161230230230
230
Max.Vm (2)48.348.348.348.348.372.572.572.572.572.5123123123123123123123145145145145145145170170170170170170245245245
245
RatingVr (3)
454854607254607290969096108110120132144108110120132144168132144168172180192180192216
240
MCOV(4)
36.53942485742485770767076848898106115848898106115131106115131140144152144152173
190
1 s53.756.163.170.284.264.571.786.0105112107114124126138154165124126138157165200157165196203210221215221248
280
10 s51.353.760.467.280.661.568.482.0100107102109118121132147161118121132150164191150164188194201211205211237
268
88.694.5107119142107119139178189173189220225244261293220225244261293332251293332351363388363388437
484
3 kA 99.4106120133161120133161199212199213239252265292318239252265292319364292319371385398424398424477
530
5 kA104110124137167124138167206219207221247262274301329247262276303331376303331384397411438411438495
548
10 kA108116130144174130144174216231216231260274288317346260274288317346404317346404418432461432461518
576
20 kA119127143159191143159191238254238255286302317349381286302317349381435349381444460476507476507570
634
40 kA133142160178215160178215266284266285319336355390426319336355390426486390426496514532567532567637
709
0.5 µs10 kA118126140156189140157189234249235251281296311343374281296311344374427344374436452467498467498560
623230 245 228 180 266 255 460 504 520 548 602 674 591
6
XPS Station Class Silicone-Housed Arresters
Technical data for housings
1) Increase clearances ”S” and ”T”, 3% per each 1000 ft over 6000 ft / 305 m over 1830 m
2) Arrester assembly consists of arrester unit, line, ground terminals and grading rings for ratings 108 kV and above
3) Minimum dimensions for arresters, other apparatus standards and other specifi cations or local codes may require greater spacing
4) Mounting slots for 0.50 in / 12.7 mm diameter hardware, three equally spaced on 8.75 in / 222.25 mm to 10.0 in / 254 mm bolt circle, thickness of lug 0.25 in / 6 mm
H TSHeight
Vr
369101215182124273036
45
54
72
96108110
132
168
180
216
240
Style No.
Q003SA002AQ006SA005AQ009SA008AQ010SA008AQ012SA010AQ015SA012AQ018SA015AQ021SA017AQ024SA019AQ027SA022AQ030SA024AQ036SA029A
Q045SA037A
Q054SA042A
Q072SA057A
Q096SA076BQ108SA084BQ110SA088B
Q132SA106B
Q168SA131B
Q180SA144B
Q216SA173B
Q240SA190B
in13.513.517.417.417.417.417.423.323.323.323.323.3
31.2
31.2
41.7
49.658.558.5
68.7
84.5
84.5
103
110
mm351351450450450450450592592592592592
793
793
1059
126014861486
1745
2146
2146
2606
2807
in11.211.223.623.623.623.623.642.042.042.042.042.0
66.7
66.7
84.0
108133133
150
200
200
242
266
mm284284599599599599599
10671067106710671067
1694
1694
2133
276033883388
3832
5082
5082
6151
6776
lb181822222222223333333333
47
47
60
749393
110
137
139
169
183
kg8.28.210101010101515151515
21
21
27
334242
50
62
63
77
83
in77777789
10111213
15
17
20
253940
46
62
65
76
84
mm178178178178178178203228254279305330
381
432
508
6359901016
1168
1575
1651
1930
2133
in111111111111121314151617
19
20
23
275152
58
78
81
92
100
111111111111
1
1
2
2
3
4
5
5
6
6
mm279279279279279279305330355381406432
483
508
584
58612951321
1473
1981
2057
2336
2540
48 Q048SA039A 31.2 793 66.7 1694 47 21 16 406 19 1483
39 Q039SA031A 31.2 793 66.7 1694 47 21 14 355 18 1457
60 Q060SA048A 31.2 793 66.7 1694 47 21 18 457 21 1533
90 Q090SA070A 49.6 1260 108 2760 74 33 23 584 26 2560
108 Q108SA084B 58.5 1486 133 3388 93 42 39 990 51 31295
144 Q144SA115B 76.6 1946 175 4457 123 56 50 1270 62 41575
120 Q120SA098B 58.5 1486 133 3388 93 42 43 1092 55 31397
172 Q172SA140B 84.5 2146 200 5082 139 63 63 1600 79 52006
192 Q192SA152B 94.7 2405 217 5527 154 70 69 1753 85 62159
228 Q228SA180B 110 2807 266 6776 183 83 80 2032 96 62438
Station Class Silicone-Housed Arresters XPS
7
Standard Hardware
Line terminal Ground terminal Drilling plan
1) Line and ground terminals can accomodate copper or aluminum cable size Number 2 to 1000 MCM / 0.25 to 1.19 in / 6 to 30 mm diameter. Ground terminal can be located on any lug.
Outlines
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6
10.9
277
1.5
38
0.25
60.25
6
0.25
6
3.00
76
3.12
79
1.75
44
1.75
44
3.00
76
3.93 Dia.
100
3.50
89
1.97
50
0.19
5
0.19
5
1.97
50
0.19
5
3.68
93
Mtg. Slots for 0.50 Dia.Hardware(3) Equally Spaced on8.75" to 10.0" B.C.Thickness of Lug = 0.25"
Ground Terminal
H6.6
168
H
12
300
24
600
H
12
300
24
600
16
400
H
32
800
H
16
400
32
800
H
0.56 Dia.
3 0 Installation Layout
S
T
120˚
120˚
T
ABB Inc.100 Distribution CircleMount Pleasant, PA 15666
Tel. 724-696-1568Fax 724-696-1502
www.abb.com
Des
crip
tive
Bul
letin
2G
NM
1100
07/J
une
2005
A
BB
Mt.
Ple
asan
t
Note: ABB Power Technologies is working continuously to improve our products.We therefore reserve the right to change designs, dimensions and data without prior notice.