48
Dok Nr. 1.032.027.0 Universal Measuring Device UMG507 Installation and Initial Startup See back page for brief instructions Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel. (0 64 41) 9642-22 Fax (0 64 41) 9642-30 e-mail: [email protected] Internet: http://www.janitza.de 3 2 1

UMG507

  • Upload
    mamfm5

  • View
    13

  • Download
    0

Embed Size (px)

DESCRIPTION

Universal Measuring DeviceUMG507Installation and Initial Startup

Citation preview

Page 1: UMG507

Dok

Nr.

1.03

2.02

7.0

Universal Measuring Device

UMG507Installation and Initial Startup

See back page for brief instructions

Janitza electronics GmbHVor dem Polstück 1D-35633 LahnauSupport Tel. (0 64 41) 9642-22Fax (0 64 41) 9642-30e-mail: [email protected]: http://www.janitza.de

321

Page 2: UMG507

2

Incoming Inspection 4Meaning of the symbols used 4Incoming inspection 4Scope of delivery 5Accessories available 5Model options available 5

Product Description 6Practical guidance on use 6Intended use 6

6

Installation 8Installation location 8Protective conductor 8Supply voltage 8Connection options 9Voltage measurement 10Current measurement 11Interfaces 12RS485 12RS485 Profibus 13Digital inputs and outputs 14Analog inputs and outputs 16

Initial Startup 18Install device 18Connect device 18Apply supply voltage 18Apply measurement voltage 18Apply measurement current 18

Operation 19Operation and display 19Measured value displays 20SELECT mode 20PRG menu 21CONF menu 22Overview 22

Configuration 23LCD contrast 23Connection options 24Current transformer 25Voltage transformer 26Network setting 27RS485 27Ethernet (TCP/IP) 28

Password 30Password mode 30

Checking the Measured Values32Voltage 32Phase sequence 32Current 33Power 33

System Informationen 34Serial number 34Date and time 34Software release 34

Service and Maintenance 35Service 35Maintenance 35What to do in case of faults 36

Technical Specifications 38Overview of measured values 38Measurement uncertainty 39Ambient conditions 40Measurement 40Inputs and outputs 41Dimensioned drawings 42Measured value displays 43

Appendix 46Declaration of conformity 46Connection example 47

Brief Instructions 48

Contents

Page 3: UMG507

3

All rights reserved. No part of the manual maybe reproduced or duplicated without the writ-ten consent of the author. Violations are pun-ishable by law and will be pursued with all le-gal means.

We are unable to accept any liability whatso-ever for any errors in the manual or for lossesresulting from use of the manual. As errorscan never be completely avoided, despite allefforts made, we are grateful for any informa-tion regarding errors. We will make every ef-fort to correct any errors we become aware ofas soon as possible. In most cases, the soft-ware and hardware names mentioned in thismanual are registered trade marks and assuch are subject to the legal provisions. Allregistered trade marks are the property of therespective firms and are acknowledged by us.

Issue notice11.01.2005 First issue.

Page 4: UMG507

4

Incoming inspectionError-free and safe operation of this devicerequires proper transport and storage, setupand assembly and careful operation andmaitennance. If it can be assumed that safeoperation is no longer possible, the devicemust be immediately taken out of service andsecured against accidental startup.The device must be packed and unpackedwith the usual care without force and only us-ing suitable tools. The devices are to be visu-ally inspected for faultless mechanical condi-tion. Please note the installation instructionsenclosed with the device.It is to be assumed that safe operation is nolonger possible if the device e.g.• has visible damage,• no longer works despite an intact power sup-ply,• has been exposed to unfavourable condi-tions for a lengthy time (e.g. storage outsidethe permissible climate limits without adjust-ment to the room climate, condensation, etc.)or transport loads (e.g. fall from a large heighteven without visible external damage, etc.).

Please check for complete scope of deliverybefore starting to install the device.

Warning, dangerous electrical voltage.

This symbol is intended to warn youabout possible dangers, which canoccur during the assembly, initialstartup and during use.

Protective conductor terminal

Meaning of the symbols usedThe following pictograms are used in thismanual:

Incoming Inspection

Page 5: UMG507

5

The installation and startup instruc-tions also describe options which arenot part of the scope of delivery.

Number Product No. Name

1 52 15 xxx1) UMG507 XX2)

1 33 03 xxx1) Installation and startup instructions,1 29 01 926 2 clips1 51 00 104 CD with the following contents:

- „PSWbasic“ programming software.- Supplementary device descriptions.

Product No. Name

0801504 Patch cable 3m, blue. (PC - switch/hub connection)0801505 Patch cable 2m, twisted, grey, (PC - PC connection)5210207 Connection cable, RS232, 2m, DSUB2901903 Seal, 144x1442101102 Battery, lithium CR2450N, 3V/540mAh

1) Refer to delivery note for product number.2) Design options.

Incoming Inspection

UMG507 model optionsOption L AD P E EP

1 RS232, Modbus RTU x x x x x1 RS485, Modbus RTU x x x x x1 RS485, Modbus RTU/Profibus DP V0 - - x - x1 Ethernet, 10baseT - - - x x1 Temperature input (e.g. PT100) - x x x x1 Analog input, 0 - 20mA - x x x x2 Analog outputs, 0/4 - 20mA - x x x x6 Digital inputs x x x x x6 Digital outputs x x x x x1 additional memory, 16MB (flash) - - - x x

Model options available

Scope of delivery

Accessories available

All the delivered options and modeloptions are described on the deliverynote.

x = option available in this model

Page 6: UMG507

6

Practical guidance on useThis device is only to be deployed and usedby qualified personnel in accordance with thesafety provisions and regulations.When using the device, the necessary legaland safety regulations for the respective useare also to be observed.Qualified personnel are persons who are fa-miliar with the setup, installation, putting intoservice and operation of the product and havethe necessary qualifications for their work,e.g.- Training or instruction and/or authorisation toswitch electric circuits and devices on and off,to isolate them, earth and label them in ac-cordance with the safety standards.- Training or instruction in accordance with thesafety standards for the maintenance and useof appropriate safety equipment.

Attention!If the device is not operated in accord-ance with the operating instructions,protection is no longer ensured andthe device can cause hazards.

Intended useInstallationThe UMG507 is suitable for installation infixed and weatherproof control panels. Con-ductive control panels must be earthed. Dueto its high immunity the UMG507 is suitablefor continuous, unmonitored operation.

MeasurementThe UMG507 is inetnded for the measure-ment of electrical variables such as voltage,current, power, etc. in low-voltage switchgear.Measured values are saved adn can be readout through serial interfaces. The voltage andcurrent measurement inputs are continuouslyscanned. Brief interruptions up to a half-waveare reliably detected.The applied voltages must lie within the meas-uring and supply voltage range given on therating plate.The measuring and supply voltages must beconnected to the UMG507 via a disconnect-ing device (switch or circuit-breaker) and anovercurrent protection device (2-10A) in thebuilding installation. The disconnecting devicemust be near the UMG507 and be easilyreached by the user. The disconnecting de-vice must be labelled for the device.Either ../5A or ../1A current transformers canbe optionally connected to the current meas-urement inputs.

Medium and high-voltage systemsMeasurement in medium and high-voltagesystems is generally carried out using currentand voltage transformers. Special safety pro-visions are applied to these, which are not dis-cussed in any greater detail here.

Product Description

Page 7: UMG507

7

TN and TT systemsMeasurement is designed for 3-phase sys-tems with neutral conductors (TN and TT sys-tems).

Fig. Block diagram, UMG507 in the TN sys-tem.

Fig. Block diagram, UMG507 in the IT systemwith N.

Fig. Block diagram, UMG507 in the IT systemwithout N.

IT systemsThe UMG507 is only conditionally suitable foruse in IT systems, as the measurement volt-age is measured at the housing potential andthe input impedence of the device causes aleakage current to the earthing. The leakagecurrent can cause the insulation monitoring inIT systems to respond. It must also be en-sured that the maximum permissible voltageat the inputs of the UMG507 are not ex-ceeded to earth (e.g. in case of a phase-to-earth fault).The connection options shown in Fig. 4.1b(with PEN conductor) or Fig. 4.6a (without aPEN conductor) are suitable for IT systemswithout restriction. Here the IT system is insu-lated through the use of voltage transformers.

It is absolutely necessary to connectthe PEN conductor N.

Product Description

UMG507Systemearthing

DC

AC/DC

230/400V 50/60HzL2

L3

L1

auxiliary power

voltage measurement

4M 4M 4M 4M

PE

Impedance

L1 L3L2 N

UMG507Systemearthing

DC

AC/DC

500V 50/60HzL2

L3

L1

auxiliary power

voltage measurement

4M 4M 4M 4M

PE

Impedance

PE

- L

m

ax. 5

00V

L1 L3L2 N

UMG507Systemearthing

DC

AC/DC

PE

230/400V 50/60HzL2

L3

N

L1

auxiliary power

voltage measurement

4M 4M 4M 4M

PE

PE

- L

m

ax. 5

00V

L1 L3L2 N

Page 8: UMG507

8

Installation locationThe UMG507 is intended for permanent in-stallation in low and medium-voltageswitchgear. It can be installed in any position.

Protective conductorA protective conductor according to the validsafety regulations must be connected at thescrew provided on the rear of the device be-fore the remaining connections with the de-vice can be made.

Supply voltageAn operating voltage is required to run theUMG507. The type and strength of the oper-ating voltage required for the UMG507 isnoted on the rating plate.

230V Standard version120V Special version 63V Special version

Higher voltages between the terminals 31/32and earth (PE) can severely damage theUMG507. In order to prevent an overvoltagethe operating voltage should be earthed.The operating voltage is connected at termi-nals 31 and 32. A maximum voltage of300VAC may occur between the terminals 31and 32 (operating voltage) and earth (PE).

Attention!- The wiring cables for the operating voltagemust be suitable for nominal voltages up to300VAC to earth.

- The operating voltage must be fused. Thefuse must lie within the range from 2A to 10A.

- The building installation must include aswitch or circuit-breaker for the operatingvoltage.

- The switch must be installed close to thedevice and be easy for the user to reach.

- The switch must be labelled as a discon-necting device for this device.

- Before applying the operating voltage en-sure that the voltage and frequency comply tothe values given on the rating plate!

- The device may only be run with an earthedhousing!

- Conductors with soldered individual wiresare not suitable for connections at screw-type terminals!

-The pluggable screw terminals may only beplugged in when no voltage is applied.

- Only pluggable screw terminals with thesame number of poles and the same type(with/without threaded connection) may beconnected with each other.

Voltages which lie above the permis-sible voltage range can severely dam-age the device.

Installation

Page 9: UMG507

9

Installation

Fig.1 Three-phase measurement with PENconductor. (four-wire measurement)

Fig.4 Measurement with two current trans-formers. (four-wire measurement)

Fig.3 Measurement with three current trans-formers and three voltage transformers. (four-wire measurement)

Fig.2 Three-phase measurement without PENconductor. (four-wire measurement)

Fig.5 Medium-voltage measurement with twocurrent and three voltage transformers. (four-wire measurement)

Connection optionsThe UMG507 can measure in systems with Nand even in systems without N through twovoltage transformers. Measurement in sys-tems with L1/L2/L3 and N (PEN) is calledfour-wire measurement here. Measurementin systems with L1/L2/L3 but without N iscalled three-wire measurement.The UMG507 is preset in the factory formeasurement in systems with N (four-wiremeasurement).

Page 10: UMG507

10

Voltage measurementThe UMG507 is suitable for measuring alter-nating voltages of up to 500VAC to earth and870VAC phase-to-phase. The wiring cablesfor the measured voltages must be suitabelfor voltages up to 500VAC to earth and870VAC phase-to-phase.

Attention!The UMG507 is not suitable for meas-urement of direct voltages.

Voltages over 500VAC to earth mustbe connected through a voltage trans-former .

The supply conductors for voltagemeasurement in UMG507 must beprotected by an overcurrent protectivedevice.

Installation

Fig.6 Three-phase measurement without PENconductor with three current transformers.(three-wire measurement)

Fig.7 Three-phase measurement without PENconductor with two voltage transformers andthree current transformers. (three-wire meas-urement)

Fig.8 Three-phase measurement without PENconductor with two voltage transformers andtwo current transformers. (three-wire meas-urement)

Page 11: UMG507

11

Total current measurementIf the current measurement takes placethrough two current transformers, the totalconversion ratio of the current transformersmust be programmed in the UMG507.

Example: summation current transformerCurrent measurement takes place using onecurrent transformer with a conversion ratio of1000/5A and one current transformer with aconversion ratio of 200/5A. The total measure-ment is carried out using a summation trans-former 5+5/5A.The UMG507 must then be set as follows:

Primary current: 1000A + 200A = 1200ASecondary current: 5A

Fig.: Example, current measurement usingsummation transformer.

The secondary connections of the cur-rent transformer must be short-circuited at it before the current supplyconductors to the device are discon-nected!If a test switch is available, which au-tomatically short-circuits the currenttransformer supply conductors, it issufficient to place in in the „Test“ posi-tion, provided that the short-circuitershave been previously tested.

Fig.: Example, current measurement usingadditional ammeter.

Current measurementThe UMG507 is designed for the connectionof current transformers with secondary cur-rents of ../1A and ../5A. Only alternating cur-rents can be measured, not direct currents.Each current measurement input can be per-manently loaded with 6A or loaded for 1 sec-ond with 60A. In systems with voltages up to150VAC (CATIII) or 300VAC (CATII) to earthcurrents of up to 5A can also be directly con-nected to the UMG507 and measured.

If the current has to be measured with anammeter in addition to the UMG507, this mustbe connected in series with the UMG507.

Installation

Page 12: UMG507

12

RS485Terminal resistorsAll devices are connected in a bus structure(line). Up to 32 stations can be connected to-gether in one segment. The cable is termi-nated with resistors at the start and end of asegment.If there are more than 32 stations, repeatersmust be used in order to connect the indi-vidual segments.

ShieldingA twisted-conductor and shielded cable mustbe provided for connections through theRS485 interface. In order to achieve sufficientscreening effectiveness, the screening mustbe connected to large areas of the housing orcabinet parts at both ends of the cable.

Cable typeRecommended cable types:Unitronic Li2YCY(TP) 2x2x0.22 (Lapp cable)Unitronic BUS L2/FIP 1x2x0.64 (Lapp cable)

Cable length1200m for a baud rate of 38.4k.

Installation

Correct

Wrong

Terminal strip in the control cabinet.

Device with RS485 interface.(Without terminating resistor)

Device with RS485 interface.(With terminating resistor at the device)

RS232The achievable distance between two RS232devices depends on the cable used and thebaud rate. As a rule of thumb, for a transferrate of 9600 baud the distance should not ex-ceed 15m to 30m.The permissible ohmic load must be greaterthan 3kOhm and the capacitive load causedby the transmission cable must be smallerthan 2500pF.The 2m connection cable included in theRS232 interface scope of supply can be usedto transfer data with the maximum settablebaud rate of 38.4kBit/s.

Interfaces

Page 13: UMG507

13

RS485 ProfibusThe profibus connection of the UMG507 isdesigned as a 9 pin DSUB socket. We recom-mend a 9 pin profibus connector e.g. from thefirm Phoenix, type „SUBCON-Plus-ProfiB/AX/SC“ with the product number 2744380 for theconnection.

Installation

Connection of the bus cablesThe incoming bus cable is connected at theterminals 1A and 1B. The bus cable for thenext device in the line is connected at the ter-minals 2A and 2B. If there are no more de-vices in the line, the bus cable must be termi-nated with resistors (switch to ON).In the switch setting ON the terminals 2A and2B are switched off for the continued bus ca-ble.

Otherprofibus sta-

tions

Page 14: UMG507

14

Fig. Connection of two relays at the digitaloutputs.

Digital inputs and outputsDigital outputsThe UMG507 has 6 transistor switch outputs.These outputs are separated from theevakluation electronics by optocouplers. Thetransistor collectors are connected togetherwith plus potential (terminal 23). Each transis-tor can switch a maximum of 28V and 30mA.The transistor outputs are not short-circuitproof.

+24V=23

22

DigitalOutput 6

UMG507Digital outputs 1-6

K1

K2

+ -

230V AC

24V DC

Externalauxiliary supply

18

DigitalOutput 2

17

DigitalOutput 1

21

DigitalOutput 5

20

DigitalOutput 4

19

DigitalOutput 3

Installation

Page 15: UMG507

15

S0 Pulse inputEach input can also be used as an S0 pulseinput to DIN EN62053-31. An external auxil-iary voltage of 20..28V DC and an external1.5kOhm resistor each is required for this.

Fig.: Example for connection of an S0 pulsegenerator at the digital input 6.

3,9V

4k4

DigitalInput 1

UMG507Digital inputs 1-6

3,9V

3,9V

4k5

DigitalInput 2

3,9V

4k6

DigitalInput 3

4k7

DigitalInput 4

4k8

DigitalInput 5

3,9V

3,9V

4k9

10

DigitalInput 6

S0 Pulsegenerator

1,5k+

-

24VDC

Installation

Digital inputsThe UMG507 has a total of 6 digital inputswhich can be connected to transducers. Aninput signal is detected at a digital input if avoltage of at least 10V and maximum 28V isapplied. A current of at least 1mA and maxi-mum 6mA then flows.

Fig.: Example for connection of the externalmain switching contacts S1 and S2 to the dig-ital inputs 5 and 6.

3,9V

4k4

DigitalInput 1

UMG507Digital inputs 1-6

3,9V

24VDC

+

-

S2

3,9V

4k5

DigitalInput 2

3,9V

4k6

DigitalInput 3

4k7

DigitalInput 4

4k8

DigitalInput 5

3,9V

3,9V

4k9

10

DigitalInput 6

S1

Page 16: UMG507

16

Installation

Analog inputs and outputsTemperature measurement input „PT100“Temperature sensors with a resistance range of 400 Ohm to 4kOhm can be connected to the„analog input PT100“.The total burden (sensor + cable) of 4kOhm must not be exceeded.

Analog input

Fig. Example, temperature measurement us-ing a KTY83.

Fig. Example, connection of a 0..20mA powersource.

Sensor type Temperature range Resistance range

KTY83 -55 ° .. +175 °C 500 Ohm .. 2.6 kOhmKTY84 -40 ° .. +300 °C 350 Ohm .. 2.6 kOhmPT100 -99 ° .. +500 °C 60 Ohm .. 180 OhmPT1000 -99 ° .. +500 °C 600 Ohm .. 1.8 kOhm

Page 17: UMG507

17

Installation

Fig. Connection of an analog output to ananalog recorder.

Analog outputs

Fig. Connection of the analog outputs at anSPS Programmable controller).

Page 18: UMG507

18

Apply measurement currentThe UMG507 is designed for the connectionof ../1A and ../5A current transformers.Only alternating currents can be measuredthrough the current measurement inputs, notalternating currents. Current transformer ter-minals must be earthed on the secondaryside.Current transformers which are not loaded onthe secondary side can result in dangerouscontact voltages and must therefore be short-circuited.Connect the individual current transformers tothe UMG50 and compare the current dis-played with the applied current. The currentdisplayed by the UMG507 must correspond tothe input current, taking into account the cur-rent transformer transformation ratio.The current transformer rator is set in the fac-tory to 5/5A and may have to be adapted tothe current transformers used.If the current transformer is short-circuited onthe secondary side, the UMG507 must dis-play approx. zero amperes in the correspond-ing external conductor.

Install deviceThe UMG507 is intended for installation inlow-voltage distribution boards, in which maxi-mum overvoltages in the overvoltage categoryIII occur.It can be installed in any position. The en-closed fixing branckets are to be used in thefront panels or switchgear cabinet doors.

Connect deviceApply supply voltageThe size of the measuring and operating volt-age for the UMG507 is given on the ratingplate.Measurement and operating voltages, whichdo not correspond to the values given on therating plate, malfunctions and severe damageto the device can result.The wiring cables for the measuring voltagesto the UMG507 must be suitable for voltagesup to 300V to earth and 520V phase-to-phase.After switching on the measuring and operat-ing voltage specified on the rating plate of theUMG507, all the segments appear in the dis-play. About two seconds later the UMG507switches to the first measured value display.If no display appears, check whether the op-erating voltage lies within the nominal voltagerange.

Initial Startup

Apply measurement voltageThe UMG507 is suitable for the measurementof voltages of up to 500VAC to earth and870VAC phase-to-phase.The UMG507 is not suitable for the measure-ment of direct voltages. Voltages over 500VACto earth must be connected through voltagetransformers.After connecting the measurement voltage,the measured values for the voltages L-N andL-L displayed by the UMG507 must be com-pared with those at the voltage measurementinput. If a voltage transformer factor is pro-grammed, this must be taken into account inthe comparison.

Page 19: UMG507

19

Operation and displayAfter the power supply has been restored theUMG507 is always in the first programedmeasured value dis-play. The UMG507 iscontrolled using thethree keys in thefront.

The keys have different meetings in the vari-ous displays. If you are in a measured valuedisplay, you can use the Key 1 to switch be-tween

the measured value display,the SELECT mode,the configuration menu CONF andthe programming menu PROG

as shown in the figure below.

Fig. Menu overview

Operation

Keep Key 1 depressed forapprox. 2 seconds.

PRG

SELECT

Voltage transformer,RS485,

ethernet,date,

Free parameter entry(address, value).

CONF

CONF

A

A

SELECT CT

CONF

A

A

CT

SELECT

Measured values

SELECT

Display additional infor-mation

SELECT

Measured valuesSelect phase

Measured values

Measured values

Measured values

PRG

PRG

Wh

VArh

Key press briefly press continuously

2

1

3

Select menu Return to the firstmeasured value-display (panel)

Panel right Panel left

Panel up Panel down

EDIT symbol activeKey press briefly press continuously

2

1

3

Next digit previous digit

Number * 10 Number / 10

Digit + 1 Digit - 1

SELECT

PRG CONF

Measured val-ues

1 2 3

Page 20: UMG507

20

SELECT modeAdditional information such as the Date andTime can be called up directly in the meas-ured value displays for various values and themin and max values can be individually de-leted.

Measured value displaysAfter the power supply has been restored theUMG507 always displays the first pro-grammed measured value display. Up to threemeasured values can be shown simultane-ously in the UMG507‘s display.The Keys 2 and 3 can be used to page be-tween the measured value displays. In orderto keep the display of the selection of meas-ured values to be displayed clear, only part ofthe avaialable measured values are prepro-grammed for call up in the measured valuedisplay in the factory.If other measured values are required in theUMG507‘s display, these can be selected ona PC using the programming and readoutsoftware PSWbasic included in the scope ofsupply and can then be transferred to theUNG507 through the serial interface.

Display example:Voltages L1-N, L2-N, L3-N.

Operation

V

V

V

L3

L1

L2

2

3

Meanvalue

Min value

Max value

Power de-mand

Display averaging time.

Delete mean value.

Display Date and Time.Delete min value.

Display Date and Time.Delete max value.

Display running time.

2

3

2

3

2

2

3

Example: Delete max current value in L3.

1

Use keys 2 and3 to page up tothe max currentvalue.

Press 2 times.Select phase.

2 Press once.Select display.

3 Press once.Delete maxvalue.

L1

SELECT

L2

L3

A

A

A

SELECT

L3

A

SELECT

L3

A

Page 21: UMG507

21

PRG menuThe active power demand, min values andmax values can be deleted in groups usingthe PRG progamming menu.

Min valuesPRG

PRG

Wh

VArh

Active power de-mand

Operation

Max values

Reactive power de-mand

Press once.

Delete the ac-tive and reac-tive power de-mands hasbeen selected.

3

1 Press 3 times.

The SELECTsymbol flashes.

2 Press once.

SELECT

PRG

The SELECTsymbol disap-pears.

Example: Delete reactive power demandcounter.

Press once.

The reactivepower demandhas been de-leted.

2

PRG

PRG

VArh

Wh

Press 2 times.

Delete reactivepower demandflashes.

PRG

VArh

Wh

1

PRG

VArh

Wh

A

Page 22: UMG507

22

2

Operation

A

CT

A

CONF

VT

V

V

CONF

ADDR

CONF

k

CONF CONF

CONF

CONF

CONF

Y.M

D.H

M.S

CONF

CONF

CONF menuThe settings required for operation of theUMG507 are stored in the configuration menuCONF. Among others, these are the settingsfor the current transformer, the device addressand the programming of the interfaces.When delivered, these settings are not pro-tected and can be changed. Accidentalchanging of the settings can be prevented byusing the "Password" setting.

3

1Press 2 times.

Press once.

Current trans-former

Voltage trans-former

3

3 RS485,Device ad-dress

RS485, baudrate

Password

Ethernet,type of addressdetermination

Ethernet, ad-dress

Ethernet, gate-way

Date

Free parameterinput (address,value)

3

3

3

3

3

3

Overview

Page 23: UMG507

23

Configuration

LCD contrastThe preferred viewing direction for the LCDdisplay is from "below". The user can adjustthe LCD contrast for the LCD display. Thecontrast settimg can be changed within therange of 10 to 50 in steps of 1.

10 = Characters very light50 = Characters very dark

Factory setting: 20

CONFEDIT

1Press 2 times.The Select textflashes.The currenttransformer set-ting is dis-played.

1Press once.

The first digitflashes.

Program LCD contrastThe value for the LCD contrast is entered di-rectly in the address 3561.

SELECT CT

CONF

A

A

2 Press once.

The Select text disappears.The device is in Programming mode.

3 Press 9 times.

Switch to the „Free parameter input“ menuitem.

Enter the address 3561 first and then the re-quired value.

Change digit.3

Select digit.1

Address

Value

CONF

Page 24: UMG507

24

Connection optionsIn the factory the UMG507 is preset for meas-urement in systems with N (four-wire meas-urement).

0 = Four-wire measurement1 = Measurement without N

Factory setting: 0

Configuration

1Press 2 times.The Select textflashes.The currenttransformer set-ting is dis-played.

1Press once.

The first digitflashes.

Programm connection optionsThe value for the connection options is di-rectly transferred to the address 6289.

SELECT CT

CONF

A

A

2 Press once.

The Select text disappears.The device is in Programming mode.

3 Press 9 times.

Switch to the „Free parameter input“ menuitem.

Enter the address 6289 first and then the re-quired value.

Change digit.3

Select digit.1

Address

Value

CONF

CONFEDIT

Fig.1 Three-phase measurement with PENconductor. (four-wire measurement)

Page 25: UMG507

25

Current transformerCurrent transformers with either a secondarycurrent of 1A or 5A can be connected to theUMG507.

Example: summation current transformerCurrent measurement takes place throughone current transformer with a conversion ra-tio of 1000/5A and a current transformer witha conversion ratio of 200/5A. The total meas-urement is carried out by a summation trans-former 5+5/5A.The UMG507 must then be programmed withthe following values:

Primary current: 1000A + 200A = 1200ASecondary current: 5A

Program current transformer

Currenttransformer Adjustment range Preset

Primary 1A .. 999.9MA 5ASecondary 1A .. 5A 5A

2

1Press 2 times.

Confirm selection.

Press once.

SELECT CT

CONF

A

A

The Select textflashes.

CT

CONF

A

A

The Select textdisappears.

2

1

3

Press once.

The first digit ofthe primary cur-rent flashes.

Change digit.

Change current transformer setting.

1

Select next digit.Press once.

The seconddigit of the pri-mary currentflashes.

2

Change digit.EDIT

CT

CONF

A

A

EDIT

CT

CONF

A

A

3

Move decimalpoint.

Move decimalpoint.

If none of the digits are flashing any more,you can use Key 3 to switch to the volt-age transformer displays.

3

Configuration

Page 26: UMG507

26

Voltage transformerThe pre-programmed voltage transformer ra-tio only has to be changed if voltage trans-formers are connected. The outer conductorto outer conductor (L-L) voltage is given asthe secondary and primary voltage in the dis-play of the UMG507.

Program voltage transformer

2

1Press 2 times.

Auswahl bestätigen.

Press once.

The Select textflashes.

The Select textdisappears.

2

1

3

Press once.

The first digit ofthe primary cur-rent flashes.

Change digit.

Change voltage transformer setting.

1

Select the next digit.Press once.

The seconddigit of the pri-mary currentflashes.

2

Change digit.

3

Move decimalpoint.

Move decimalpoint.

If none of the digits are flashing any more,you can use Key 3 to switch to the volt-age transformer display.

3

SELECT VT

CONF

V

V

VT

EDIT CONF

V

V

VT

CONF

V

V

VT

EDIT CONF

V

V

Voltagetransformer Set range Preset (L-L)

Primary 100V .. 999.9MV 400VSecondary 100V .. 500V 400V

Configuration

Page 27: UMG507

27

Configuration

Network settingEach device in a system must have its ownaddress. The ethernet and RS485 are inde-pendent systems and have their own ad-dresses.

ADDR

CONF

RS485Modbus protocolAddress setting range for use of the Modbusprotocol:

001 ... 247

The factory setting for the address is 001.

Profibus protocolAddress setting range for use of the Profibusprotocol:

000 ... 126

The factory setting for the address is 001.

RS485 Network ad-dress = 1

Program network address

1Press 2 times.The Select textflashes.The currenttransformer set-ting is dis-played.

The current net-work address isdisplayed

2 Press once.

The Select text disappears.The device is in Programming mode.

3 Press 2 times.

Switch to the „Network address“ menu item.

Change network address.

Change digit.3

Press once.

The first digitflashes.

1

ADDR

CONF

1Select digit.

ADDR

EDIT CONF

CT

CONF

A

A

Page 28: UMG507

28

Ethernet (TCP/IP)The network settings for the ethernet arespecified by the network administrator and setat the UMG507 accordingly.If the setting is unknown, do not plug thepatch cable into the UMG507.

Boot DHCP

Boot bP

PRG

PRG

PRG

PRG

Configuration

boot Meaning

oFF The IP address must be entered atthe UMG507.

bP The UMG507 obtains the IP addressand network configuration (sub-network/gateway) from the bootserver.

dHCP The UMG507 obtains the IP addressand network configuration (sub-network/ gateway) from the DHCPserver.

Factory setting: dHCP

The UMG507 obtainsthe IP address and net-work configuration(sub-network/gateway)from the DHCP server.

The UMG507 obtainsthe IP address andnetwork configuration(sub-network/gate-way) from the bootserver.

The UMG507 has beenautomatically assigneda network address.

The UMG507 has beenassigned a network ad-dress.

Search

Ready

Search

Ready

Page 29: UMG507

29

Address and netmask

Configuration

PRG

Boot oFF

The IP address andnetwork configuration(sub-network/gateway)must be entered di-rectly at the UMG507.

2 2

PRGPRG PRG PRG

2

AddressNetmask

Gateway

PRG PRGPRG PRG

Gateway-address

Page 30: UMG507

30

PasswordIn order to make it difficult to accidentallychange the programmed data using the key-board or the WEB interface, a password anda password mode can be programmed. It isonly possible to switch to the prammingmenus and to change the programmed dataafter the password has been correctly en-tered.

In the factory, no password (0000) and nopassword mode (0000) are preset. In thiscase the password query is skipped.

If a password has been changed andis no longer known, the device mustbe sent to the manufacturer.

Setting range:Password = 0 .. 9999Password mode = 0, 1, 2, 128, 129, 130

Factory setting:Password = 0Password mode = 0

Password = 0000 => no password= 1-9999 => with password

Configuration

Password modeThe password mode controls access to theUMG507 over the ethernet. The UMG507 hassix password modes:

0 - Anybody can access the UMG507 overthe ethernet.

1 - Only the host names stored in theUMG507 can access the UMG507 over theethernet.

2 - The UMG507 can only be accessedover the ethernet with a password.

0/1/2 + 128 => 128, 129, 130If 128 is added to the password mode 0, 1 or2 the password is queried for each change toa configuation side.

Password mode

CONF

1Press 2 times.The Select textflashes.The currenttransfomer set-ting is dis-played.

1 Press once.

The first digitflashes.

Program password

SELECT CT

CONF

A

A

2 Press once.

The Select text disappears.The device is in programming mode.

3 Press 5 times.

Switch to the password menu PASS.

Change password and password mode.

Change digit.3

Select digit.1

CONF

Password

Page 31: UMG507

31

Page 32: UMG507

32

VoltageIn the voltage display you should check the L-N and/or L-L voltages. If one or severalvoltages are missing here, there is possibly awiring error.If the displayed values do not correspond tothe actual voltages, check the voltage trans-former setting.

Phase sequenceIf all the voltage circuits have been connected,the UMG507 displays the phase sequence.If all the segments in the display run in aclockwise direction, a right-hand rotating fieldexists. If the segments in the display run in ananti-clockwise direction, a left-hand rotatingfield exists.

Checking the Measured Values

L1

Hz

L1

Hz

L1

L3

L2

V

V

V

If the segments in the display are at a stand-still there is not rotating field. In this case thevoltage circuits have probably not all beenproperly connected.

Page 33: UMG507

33

PowerSelect the display of the active power of thethree phases. Assuming that there is no gen-erator operation, positive active powers of asimilar size should be displayed for eachphase. If not, the current transformers areprobably reversed or assigned to the wrongphase.

Check the total power outputsIf all voltages, currents and outputs for the re-spective outer conductors are correctly dis-played, the total power outputs measured bythe UMG507 must also be correct. To confirmthis, the total outputs measured by theUMG507 should be compared with the workof the active and reactive power meters lo-cated in the incoming supply.

Check the individual powersIf a current transformer has been assigned tothe wrong outer conductor, the correspondingpower will be incorrectly measured and dis-played.The assignment of the outer conductor to thecurrent transformer at the UMG507 is correctif there is no voltage between the outer con-ductor and the corresponding current trans-former (primary).In order to ensure that an outer conductor atthe voltage measurement input is assigned tothe correct current transformer, the respectivecurrent transformer can be short-circuited onthe secondary side. The apparent power dis-played by the UMG507 must then be approx.zero in this phase.If the apparent power is correctly displayedbut the active power is displayed with a „-“sign then the current transformer terminalsare reversed or power is supplied to the powersupply company.

Checking the Measured Values

L1

L2

L3

kW

kW

kW

CurrentSwitch to the currents display. The read offbalues should agree with the currents actuallyflowing. If not, check the wiring and the cur-rency transformer setting.

Check the current directionShort-circuit two current transformers on thesecondary side. The active power displayed inthe remaining phase of the UMG507 mustnow be positive (+) for drawing of active powerand negative (-) for supply (generator opera-tion) of active power.If no active power is displayed the assignmentof the voltages to the currents may be wrong.

Page 34: UMG507

34

Software releaseThe software for the UMG507 is continuouslyimproved and extended. The software statusin the device is identified with a 4 digitnumber, the software release. The softwarerelease cannot be changed by the user.

Serial numberEach device has its own, unchangeable 8digit serial number. The serial number is onthe rating plate and can also be called up viathe display.

System Informationen

Date and timeThe UMG507 displays the local time. TheUTC time is used for data storage. The dateand time in the UMG507 can be set using htePSWbasic software (scope of supply) or us-ing an NTP time server in the net work.

Y.M

D.H

M.S

Date = 10. Nov. 2004Time = 12h 18m 30s

In the example shown the series number5900 0003 is displayed. In the example shown the software release

1.001 is displayed.

UTCUTC (Universal Time Coordinated) is the in-ternational time standard.

NTP server (time server)The time between various computers can beprecisely synchronised to approx. +/- 10msusing an NTP server (Network Time Protocol)which support broadcasts.

Page 35: UMG507

35

ServiceIf questions arise, which are not described inthis manual, please contact us directly.In order to deal with questions, we will needthe following information:

- Device designation (see rating plate),- Serial number (see rating plate),- Auxiliary voltage (see rating plate),- Software release (display) and- Precise description of the error.

You can contact us:Mo to Th 07:00h to 15:00hFr 07:00h to 12:00h

Janitza electronics GmbHVor dem Polstück 1D-35633 LahnauSupport: Tel. (0 64 41) 9642-22

Fax (0 64 41) 9642-30e-mail: [email protected]

MaintenanceThe device is subjected to various safety testsbefore being delivered and is marked with aseal. If a device is opened the safety testsmust be repeated.We only provide a warranty for unopened de-vices.

Repair and calibrationRepair and calibration work can only be car-ried out in the manufacturing factory.

Front foilThe front foil can be cleaned with a soft clothand the usual domestic cleaning agents.Never use acids or cleaning agents contain-ing acids to clean the device.

BatteryThe life expectancy of the battery at a storagetemperature of +45°C is at least 5 years. Thetypical life expectancy of the battery is 8 to 10years.The battery (type CR2450N 3V/540mAh) canbe replaced by the user.

Service and Maintenance

DisposalThe device can be disposed of as electronicscrap in accordance with the legal provisionsfor recycling. The lithium battery installed mustbe disposed of separately.

Page 36: UMG507

36

Possible fault

No display.

Poorly legible display.

No current display.

Current too small.

Current too large.

Voltage L-N too small.

Cause

External fuse has tripped.Internal fuse has tripped.

Device defective.

Contrast setting too darkor too light.

Measuring voltage notconnected.Current transformer notconnected.

Current measurement inthe wrong phase.Current transformer factorincorrectly programmed.

Measuring range ex-ceeded.The peak current value atthe measurement inputhas been exceeded byharmonic components.

Measurement in the wrongphase.Voltage transformer factorincorrectly programmed.

Remedy

Replace fuse.Fuse cannot be replaced by the user.Send the device to the manufacturerfor repair.Send the device to the manufacturerfor repair.

Adjust contrast.

Connect measurement voltage.

Connect current transformer.

Check connection and correct if nec-essary.Read off and program the currenttransformer conversion ratio at thecurrent transformer.

Install larger current transformer.

Attention! It must be ensured that themeasurement inputs are not over-loaded.

Check connection and correct if nec-essary.Read off and program the voltagetransformer conversion ratio at thevoltage transformer. If the voltage isnot measured through a voltage trans-former, program the voltage trans-former conversion ratio as 400/400.Install smaller voltage transformer.

What to do in case of faults

Service and Maintenance

Page 37: UMG507

37

Possible fault

Date skips to1.1.1970

Programming dataor saved data islost.

Active power toosmall / too large.

Active power draw-ing / supply re-versed.

"EEEE A“ in thedisplay.

"EEEE V“ in thedisplay.

Digital output orpulse output do notreact.

Despite the abovemeasures the de-vice still doesn‘twork.

Cause

The battery is dead.

The device has been ex-posed to electromagneticinterferences, which aregreater than those given inthe technical specifications.

The current transformerconversion ratio is incor-rectly programmed. Cur-rent circuit assigned to thewrong voltage circuit.Current at the measure-ment input lies outsite themeasuring range.Voltage transformer conver-sion ratio is incorrectly pro-grammed.

Voltage at the measure-ment input lies outside themeasuring range.

At least one current trans-former connection is re-versed. Current circuit isassigned to the wrong volt-age circuit.

The current measuringrange has been exceeded.

The voltage measuringrange has been exceeded.

No source has been as-signed to the output.

device defekt.

Remedy

Send the device to the manufacturer for abattery replacement.

Take external protective measures, e.g.screening, filtering, earthing or spatialseparation.

Read off and program the current trans-former conversion ratio at the currenttransformer. Check the connection andcorrect if necessary.Install larger or smaller current trans-former.

Read off and program the voltage trans-former conversion ratio at the voltagetransformer. If the voltage is not meas-ured using a voltage transformer, pro-gram voltage transformer 400/400.Install larger or smaller voltage trans-former.

Check the connection and correct if nec-essary.

Check the connection and correct if nec-essary.

Check the measured current and if nec-essary install a suitable current trans-former.

Check the measured voltage and if nec-essary install a suitable voltage trans-former.Program the output.

Send the device to the manufacturer forchecking, with a precise description ofthe fault.

Service and Maintenance

Page 38: UMG507

38

Technical Specifications

Overview of measured values

Designation Measured Mean- Max- Min- values values values values

VoltageUL1-N, UL2-N, UL3-N x x x xUL1-L2, UL2-L3, UL3-L1 x x x x

CurrentIL1, IL2, IL3, IN x x xMean current values IL1, IL2, IL3, IN x

Phase positionCosPhiL1, CosPhiL2, CosPhiL3, CosPhiSum, x x x x

Power outputPL1, PL2, PL3, Psum, x x xQL1, QL2, QL3, Qsum, x x xSL1, SL2, SL3, Ssum, x x xMean output values PL1, PL2, PL1, Psum x

Frequency in L1 x x x xNegative, positive, zero phase sequence system x x x xVoltage symmetry x x x xPhase sequence x x x xK-factor L1, L2, L3, x x x xFourier analysis DFT(1, 3, 5, 7, 9, .. 15)

Voltage UL1-N, UL2-N, UL3-N x x x xCurrent IL1, IL2, IL3, x x x x

THDUL1-N, UL2-N, UL3-N x x xIL1, IL2, IL3 x x x

WorkActive energy (without backstop) xActive energy (drawn) xActive energy (supply) xTarrifs 1 .. 4

Active energy(without backstop) xActive energy (drawn) xActive energy (supply) x

EMAX active power x xEMAX trend value xInputs and outputs

Temperature measurement input x x x xTemperature measurement, internal x x x xAnalog input (0/4 .. 20mA) x x x xAnalog outputs (0, 1) xDigital outputs (1 .. 6) xDigital inputs (1 .. 6) x

Active power, S0-inputs (1 .. 6) xMeters (1 .. 6) x

Page 39: UMG507

39

Measurement uncertaintyThe measurement uncertainty of the UMG507 applies to the use of the following measuringranges. The measured value must lie within the given limits. Outside of these limits the meas-urement uncertainty is not specified. The ambient temperature must lie within the range 18 ...28°C. Outside of this temperature range an additional measuring error must be taken into ac-count.

The specification applies under the following conditions:Annual recalibration.A preheating time of 10 minutes.An ambient temperature of 18 .. 28°C.

If the device is operated outside the range from 18 .. 28°C , an additional measurement errorof ±0.01% of the measured value per °C deviation must be taken into account.

Accuracy class to EN61036:1996, VDE0418 Part 7: May 1997, IEC1036:1996 with current transformer ../5A : Class 1 with current transformer ../1A : Class 2

Measured value Frequency Measurement uncertainties

Voltage 45 .. 65Hz ±(0.2% rdg + 0.02% rng)Current L 45 .. 65Hz ±(0.2% rdg + 0.05% rng)Current N 45 .. 65Hz ±(0.6% rdg + 0.05% rng)Phase 45 .. 65Hz ±0.5°Power 45 .. 65Hz ±(0.4% rdg + 0.1% rngFrequency 45 .. 65Hz ±(0.2% rdg + 0.75% rng

The power measuring range is calculated from the current and voltage measuring ranges cho-sen. (rng P = rng U * rng I).

Measured value Measuring range Crest factor for max. RMS-Measured value

Voltage 50 ... 500Vrms 1.1Current 0.005 ... 6Arms 1.4

Measured value Measurement uncertainties

Accuracy of the internal clock ±2 minutes/month (18°C ... 28 °C)

Abbreviations used:rng = of the measured rangerdg = of the measured value

Technical Specifications

Page 40: UMG507

40

Weight : 850gCalorific value : 2.2MJ (610Wh)Installed location : anyConnectable conductorsSolid , stranded, flexible : 0.08 - 2.5mm2Plug connector, wire end ferrule : 1.5mm2 only one conductor may be

connected for each terminal connection!

Ambient conditionsOperating temperature range : -10°C .. +55°CStorage temperature range : -20°C .. +70°CRelative air humidity : 15% .. 95% without condensationOperating altitude : 0 .. 2000m above sea level

Degree of protectionFront : IP50 to IEC529Front with seal (option) : IP65 to IEC529Rear : IP20 to IEC529Pluggable screw terminal : IP20 to IEC529

Auxiliary power (see rating plate) : 300V CATIIITest voltage : 3150V DCRange 1 (standard) : 85 .. 265V AC, 80 .. 370V DCRange 2 (option) : 40 .. 115V AC, 55 .. 165V DCRange 3 (option) : 15 .. 50V AC, 20 .. 70V DCBack-up fuse : 4A .. 10A (medium time lag)Power consumption : max. 5W, max. 9VA

Measurement

Current measurementOvervoltage category : 300V CATII, 150V CATIIITest voltage : 2000V DCPower consumption : approx. 0.2 VANominal current for ../5A (../1A) : 5A (1A)Limit current : 9.5A (sinusoidal)Overload, continuous : 6A (sinusoidal)Overload : 60A for 1 sec.

Voltage measurementOvervoltage category : 500V CATIIITest voltage : 4200V DCImpedance : 4MOhm/PhasePower consumption : approx. 0.1 VAMeasuring range L-N : 50 .. 500V ACMeasuring range L-L : 90 .. 870V ACFrequency of the fundamental component : 45Hz.. 65Hz

Technical Specifications

Page 41: UMG507

41

Inputs and outputs

Digital inputs and outputsOvervoltage category : 32V CATIRefreshment rate

inputs, outputs, flags : 50Hz 200ms; 60Hz 167ms6 Digital inputs

Maximum counting frequency (S0) : 20HzCurrent input : approx 1mA .. 6mA

6 Digital outputs, positive switching (not short-circuit proof)As switching output

Switching voltage : max. 28VDCSwitching current : max. 30mASwitching frequency (50Hz system) : max. 2.5HzSwitching frequency (60Hz system) : max. 3HzAuxiliary voltage, external : 20V .. 28VDC

As pulse output (S0)Switching frequency : max. 20HzSwitching current : max. 30mAMax. cable length : 100mAuxiliary voltage, external : 20V .. 28VDC

Analog inputs and outputs (options)Overvoltage category : 32V CATIAccuracy : +-1.5% vMb.2 analog outputs : 0/4 .. 20mA

Burden : max. 300 OhmExternal auxiliary power : 20V .. 28V DC

Residual ripple : max. 2V, 50Hz1 analog input „0 .. 20mA“ : 0 .. 20mA1 analog input „PT100“ : PT100, PT1000, KTY83, KTY84

Interfaces (options)Overvoltage category : 32V CATI

RS232 : 3-pin screw-plug in terminals.Protocol : Modbus RTU

Transfer rate : 38.4kbpsRS485 (option) : Connector, SUB D 9-pin

Protocol, profibus (option) : Profibus DP/V0 to EN 50170Transfer rate : 9.6kBaud up to 1.5MBaud

Protocoll, Modbus RTU : Modbus RTU/Slave, RTU/MasterTransfer rate : 9600bps, 19.2kbps, 38.4kbps, 115.2kbps

Ethernet 10/100Base-TX (option)Connection : RJ-45Functions : Modbus gateway, embedded webserverProtocols : TCP/IP, EMAIL(SMTP), DHCP(BootP),

Modbus-TCP, Modbus over Ethernet, Ping, NTP.

Technical Specifications

Page 42: UMG507

42

Fig. View of the rear of the device. Shows alloptions.

Technical Specifications

Dimensioned drawingsBurst size: 138+0.8 x 138+0.8 mm

Side viewRear

All dimensions in mm

144

136

156

fixing

4.3

75 (max 79)62.557

Control panelmax. 10

Page 43: UMG507

43

3

3

3

3

3

3

3

3

3

Max valueVoltage L1-L2Voltage L2-L3Voltage L3-L1

Mean valueVoltage L1-L2Voltage L2-L3Voltage L3-L1

Measured valueVoltage L1-L2Voltage L2-L3Voltage L3-L1

Measured valueMax val current L1Max val current L2Max val current L3

Mean valueCurrent L1Current L2Current L3

Measured valueCurrent L1Current L2Current L3

Max valueActive power L1Active power L2Active power L3

Mean valueActive power L1Active power L2Active power L3

Measured valueActive power L1Active power L2Active power L3

Mean valueApparent power L1Apparent power L2Apparent power L3

Measured valueApparent power L1Apparent power L2Apparent power L3

Max valueApparent power L1Apparent power L2Apparent power L3

Mean valueReactive power L1Reactive power L2Reactive power L3

Measured valueReactive power L1Reactive power L2Reactive power L3

Max valueReactive power L1Reactive power L2Reactive power L3

Max valueVoltage L1-NVoltage L2-NVoltage L3-N

Mean valueVoltage L1-NVoltage L2-NVoltage L3-N

Measured valueVoltage L1-NVoltage L2-NVoltage L3-N

Min valueVoltage L1-L2Voltage L2-L3Voltage L3-L1

Slave pointer valueCurrent L1Current L2Current L3

Min valueVoltage L1-NVoltage L2-NVoltage L3-N

Active energy sup-plied, T30

Active energydrawn, T02

Active energydrawn, T01

Active energydrawn, T00

Mean frequency valMax frequency valMin frequency val

Measured valueFrequency L1

Phase-sequencedisplay

Mean valuecos(phi) L1cos(phi) L2cos(phi) L3

Measured valuecos(phi) L1cos(phi) L2cos(phi) L3

Max valuecos(phi) L1cos(phi) L2cos(phi) L3

Min valuecos(phi) L1cos(phi) L2cos(phi) L3

3 2 22

3

Appendix

Measured value displays (factory default settings)

Page 44: UMG507

44

3

3

Cap. reactive en-ergy, T20

Cap. reactive en-ergy, T22

Cap. reactive en-ergy, T21

Inductive reactiveenergy, T10

Inductive reactiveenergy, T11

Inductive reactiveenergy, T12

Mean valueHarmonic. I L1Harmonic. I L2Harmonic. I L3

Max valueHarmonic. I L1Harmonic. I L2Harmonic. I L3

3

3

3

Measured valueSum. active power

Sum. reactive powerSum. cos(phi)

Mean valueSum. active power

Sum. reactive powerSumme cos(phi)

Measval curr. in NMeanval curr. in NMax val curr. in N

Mean valueHarmonic. U L1Harmonic. U L2Harmonic. U L3

Max valueHarmonic. U L1Harmonic. U L2Harmonic. U L3

Active power EMAXresidual time

Messperiodendauer

Setpoint val numberEMAX setpoint val

TrendResidual time

Max value activepower EMAXResidual time

Measuring period

Min value activepower EMAXResidual time

Measuring period

3

3

3

Measured value(T0)

device internal tem-perature

Measured value(T1)

Analog Input„PT100“

Measured valueAnalog Input

0 .. 20mA

Mean valueAnalog Input

0 .. 20mA

Max valueAnalog Input

0 .. 20mA

Min valueAnalog Input

0 .. 20mA

3 2 22

Appendix

Output valueAnalog Output 1

Output valueAnalog Output 2

3

3

These measured value displays are not available in all device options.

Page 45: UMG507

45

3 2 22

Input 1digitalon/off

Input 2digitalon/off

Input 6digitalon/off

3

3

EMAX-Mean valueResidual time

Messperiodendauer

SolwertnummerTrendwertSollwert

Residual time

HöchstwertResidual time

Messperiodendauer

3

3

Appendix

Software ReleaseX.XXX

SeriennummerXXXXXXXX

WochentagJahr / MonatTag / Stunde

Minute / Sekunde

Output 1digitalon/off

Output 2digitalon/off

Output 6digitalon/off

Diese Messwertanzeigen stehen nicht in allen Gerätevarianten zur Verfügung.

Page 46: UMG507

46

The UMG507 fullfils the safety requirements of the:Directive 89/336/EEC in conjunction with DIN EN61326 (2002-03) and theDirectives 73/23/EEC and 93/68/EEC in conjunction with EN 61010-1 (2002-08)

Safety regulationsSafety regulations for electrical measurement, control and laboratory equipment

: EN61010-1 08:2002, IEC 61010-1:2001Class of protection : I (device with protective conductor)

EMC requirementsEmitted interference,residential area : DIN EN61326:2002-03, Table 4 Class BNoise immunity, industrial area : DIN EN61326:2002-03, Table A.1

Housing : Electrostat. discharge, IEC61000-4-2(4kV/8kV): Electromagn. fields, IEC61000-4-3:2002 (10V/m): Electromagn. fields, IEC61000-4-8:2000 (100A/m)

Operating voltage : Voltage dip, IEC61000-4-11 (0.5 period.): Bursts, IEC61000-4-4 (2kV): Impulse voltages, IEC61000-4-5 (1kV L to N): Conducted HF signals, IEC61000-4-6 (3V)

Measured inputs : Impulse voltages, IEC61000-4-5 (2kV): Conducted HF signals, IEC61000-4-6 (3V): Bursts, IEC61000-4-4 (2kV)

RS485, dig. inputs and outputs : Conducted HF signals, IEC61000-4-6 (3V): Bursts, IEC61000-4-4 (1kV)

Appendix

Declaration of conformity

Page 47: UMG507

47

Fig

. UM

G50

7 C

onne

ctio

ns o

verv

biew

with

all

optio

ns.

Appendix

Connection example

Page 48: UMG507

48

Secondary current

Secondary voltage

Set current transformer

Brief Instructions

CT

CONF

A

A

VT

CONF

V

V

Set voltage transformer

Primary current

Primary voltage

2

1

3

1

1

2

2 x

1 x

2 sec.

Select programming menu.

Select current transformer.

Select digit.

Change digit.

Shift decimal point.

Save and display measured value.

2 x

1 x

2 sec.

Select programming menu.

Select voltage transformer.

Select digit.

Change digit.

Shift decimal point.

Save and display measured value.

1

2

1

3

2

1

3 1 x

Confirm selection.