    VAV TERMINAL UNITS

  • 8/13/2019 VAV_Box

    2/10

    Room Temperatue Control

    In VAV systems, room temperature is the primary controlled variable. Output signal from the room temperature controller is fed

    to the control circuit which in turn alters the required setpoint flowrate value of the supply air flow rate. Maintaining/changingroom temperature takes the form of controlling the miniumum and maximum flowrate limits of supply air to the occupied zone.

    Upstream Flow Rate Measurement

    The airflow sensor grid comes with 10 individual traverse lines (Front & Back) connecting to a centeral averaging chamber to

    give a more accurate reading. Each traverse line consist of 3 pressure sensing ports (totalling 30 pressure sensing ports for each

    unit) located at strategic locations (in accordance to Log-Tchebycheff rule) to factor in the usual non-uniform airflow profile.

    With these key features, the sensor delivers the accurate pressure differential readings (velocity pressure) for supply airflow

    control purposes.

    Function Description

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    Air Fow Volume Control

    Supply airflow volume varies with the changing system pressure, which pose a problem to pressure dependent VAV terminal

    units. Therefore in order to remove the dependence on system pressure, required control process is needed to maintain the

    much needed supply airflow volume, ie. measure - compare - maintain.Pressure differential measurement taken is converted into an electrical signal, which is interpreted as the actual airflow value

    flowing through the unit. The controller compares the actual value with the setpoint value and alters the positioning of the

    damper blade with reference to the value difference.

    Legend1. Flow sensing grid

    2. Central averaging chamber

    3. Damper blade

    4. Damper actuator

    5. Fowrate controller

    6. Room temperature controller

    *Base Terminal Unit (Cooling)

    Legend1. Flow sensing grid

    2. Central averaging chamber

    3. Damper blade

    4. Damper actuator

    5. Fowrate controller

    6. Room temperature controller

    7. Heating Elements

    System Illustrations

    SUPPLY AIR

    1

    OUTLETS

    2

    4

    5

    6

    3

    SUPPLY AIR

    1

    INDUCED AIR

    OUTLETSFAN

    2

    4

    5

    6

    73

    Control Signal to supply air flow rate controller

    Vmin

    Supply Air

    Vmax

    Flowr

    ate

    Vmin max

    Supply Air

    Induced Air

    Vconst

    Flo

    wR

    ate

    Control Signal to supply air flow rate controller

    *Modifications available:

    1) Induction chamber

    2) Fan (Series/parrallel)

    3) Heating elements

  • 8/13/2019 VAV_Box

    3/10

    Features

    . Capacities ranging from 40 - 13,600 CMH in

    7 standard sizes

    . Customizable sizes available

    . Available with pneumatic or direct digital

    controls

    . Pressure independent operation

    . Can be used for VAV or constant volume

    applications

    . Factory calibrated to job requirements

    . Full range of accessories available (ie. heating coils, attenuators, access doors, etc)

    Base Unit Constructional Materials

    . Damper casing: 0.7 mm thk GI metal

    . Modulating blade: 1.0 mm thk GI metal

    glass with matt black facing protection

    . Shaft: 12.0 mm thk GI round shaft

    . Leakage seals: Anti-leakage rubber seals

    . VAV actuator controller: Belimo (Other brands avaliable)

    Features . Constructional Materials

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    Dimensional Data

    Base VAV Terminal Unit

    Order

    Size(inch)

    A

    (mm)

    B

    (mm)

    C

    (mm)

    6.0 310 210 500

    8.0 310 255 500

    10.0 360 320 50012.0 410 385 500

    D

    (mm)

    152

    203

    254305

    E

    (mm)

    100

    100

    100100

    F

    (mm)

    210

    210

    210210

    G

    (mm)

    310

    310

    310310

    14.0 510 445 1000

    16.0 615 455 1000

    356

    406

    100

    100

    210

    210

    310

    310

    24.0 x 16.0 975 610 1000 609 x 406 100 210 310

    FB

    A

    E

    D

    C

    G

  • 8/13/2019 VAV_Box

    4/10

    Order

    Size(inch)

    A

    (mm)

    B

    (mm)

    C

    (mm)

    6.0 310 210 152

    8.0 310 255 152

    10.0 360 320 152

    12.0 410 385 152

    D

    (mm)

    700

    700

    700

    700

    14.0 510 445 152

    16.0 615 455 152

    700

    700

    24.0 x 16.0 975 610 152 700

    Accessories

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    Electric Duct Heater

    AD C

    B

    Order

    Size(inch)

    A

    (mm)

    B

    (mm)

    6.0 310 210

    8.0 310 255

    10.0 360 320

    12.0 410 385

    C

    (mm)

    914

    914

    914

    91414.0 510 445

    16.0 615 455

    914

    914

    24.0 x 16.0 975 610 914

    Attenuator Section

    AC

    B

    Order

    Size(inch)

    A

    (mm)

    B

    (mm)

    C

    (mm)

    6.0 310 210 152

    8.0 310 255 203

    10.0 360 320 254

    12.0 410 385 305

    14.0 510 445 355

    16.0 615 455 406

    Round Discharge Collar

    A 102 84

    B C

  • 8/13/2019 VAV_Box

    5/10

    Non-Std

    Arrange-

    ments

    A B C D E F G H I

    J K L M N O P Q Z

    Accessories

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    MOA Attenuator Section

    * All outlets c/w manual dampers

    A84C

    B

    Order

    Size(inch)

    A

    (mm)

    B

    (mm)

    6.0 310 2108.0 310 255

    10.0 360 320

    12.0 410 385

    C

    (mm)

    914914

    914

    914

    14.0 510 445

    16.0 615 455

    914

    914

    Outlet

    (mm)

    152203

    254

    305

    406

    406

    1) Select unit inlet size based on control and acoustic parameters

    2) Select control type:

    i) Standalone

    ii) BACNet

    iii) LONWorks

    3) Select accessories (Multi-Outlet Adaptor, Attenauator) as required

    4) Select reheat coil, fan (if required)

    5) Select control sequence based on system design

    Product Selection Checklist

  • 8/13/2019 VAV_Box

    6/10

    Air Volume Ranges

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    Order Size(inch)Air Volume Range (Min-Max)

    6.0 28 - 262

    8.0 47 - 465

    10.0 68 - 680

    12.0 97- 965

    l/s

    14.0 139 - 1386

    16.0 178 - 1755

    59 - 555

    100 - 985

    144- 1441

    205 - 2044

    cfm

    294 - 2935

    376 - 3717

    100 - 945

    170 -1675

    245 - 2450

    cmh

    350 - 3475

    500 - 4990

    640 - 6320

    Selection Guide

    Discharge Sound - Base Terminal Unit

    Radiated Sound - Base Terminal Un

    SUPPLY AIR

    OUTLETS

    SUPPLY AIR

    OUTLETS

  • 8/13/2019 VAV_Box

    7/10

    Performance Data. Discharge. Radiated

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    43 43 42 39 37 32 40

    54 54 53 49 48 43 50

    60 60 59 55 54 49 58

    64 54 53 59 58 53 60

    - - - - - - -

    - - - - - - -

    - - - - - - -

    32 28 27 23 24 25 30

    Volume

    Flowrate

    (CFM)

    Ps (min)

    51 - - - - - - -

    Discharge

    Sound LevelOctave Band Cenre

    FrequencyN

    R

    204

    357

    505

    25 26 26 25 24 20 28

    40 40 40 37 36 31 35

    51 52 51 48 47 43 50

    - - - - - - -

    - - - - - - -

    28 24 24 21 23 21 25

    39 35 36 33 34 29 35

    - - - - - - -

    - - - - - - -

    - - - - - - -

    30 26 24 21 22 24 30

    40 40 40 37 36 31 39

    52 52 52 49 48 43 50

    57 57 57 54 53 48 53

    61 61 61 58 67 52 59

    32 28 29 26 27 22 29

    39 39 39 36 38 32 40

    46 42 43 40 41 36 42

    50 46 47 44 45 40 45

    - - - - - - -

    31 26 25 21 - 21 25

    36 31 30 26 24 25 30

    40 35 34 30 28 30 35

    1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Single Insulation)Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Double Insulation)Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    200 PaDischarge

    Sound LevelOctave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Single Insulation)Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Double Insulation)Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    S

    iz

    e

    6.0

    83

    332

    - - - - - - -

    - - - - - - -

    30 26 26 24 25 - 29

    40 36 36 34 35 30 35

    - - - - - - -

    28 28 27 23 22 20 25

    44 44 43 39 39 33 41

    54 54 53 49 48 43 48

    8.0

    - - - - - - -

    33 29 29 24 - 23 22

    39 35 35 30 27 29 35

    43 39 39 34 31 32 38

    32 27 28 25 26 21 30

    42 38 38 36 37 32 38

    48 43 44 41 42 37 42

    51 47 47 45 46 42 48

    46 45 42 39 36 31 40

    58 57 54 50 47 43 50

    64 53 60 56 54 49 56

    68 67 64 60 58 53 62

    - - - - - - -

    - - - - - - -

    23 20 20 - - - 20

    33 31 31 25 26 28 30

    - - - - - - -

    30 29 27 23 22 20 25

    45 45 43 41 37 32 40

    56 56 54 50 48 44 40

    - - - - - - -

    - - - - - - -

    30 25 25 23 24 - 28

    41 36 36 35 38 31 40

    - - - - - - -

    - - - - - - -

    22 20 20 21 23 - 20

    33 30 30 24 26 27 32

    45 44 43 39 37 32 40

    56 55 53 50 48 43 50

    62 61 59 56 54 49 58

    66 65 53 60 58 53 60

    32 27 27 26 26 22 29

    43 38 38 36 37 32 38

    48 43 43 42 43 38 46

    52 47 47 45 46 41 50

    22 - - - - - -

    33 29 29 24 21 21 22

    39 35 35 30 27 29 30

    43 39 39 34 31 33 33

    10.0

    - - - - - - -

    - - - - - - -

    29 23 23 22 22 20 27

    40 34 35 33 33 29 45

    - - - - - - -

    32 29 26 22 22 20 25

    47 46 43 39 37 32 40

    57 56 53 49 48 42 50

    12.0

    22 - - - - - -

    34 31 31 25 23 24 30

    40 37 37 31 29 30 36

    44 41 41 35 33 34 40

    32 26 26 25 25 21 30

    43 38 38 36 37 32 36

    49 43 43 42 42 38 45

    52 47 47 46 46 42 50

    48 47 45 39 36 31 42

    60 59 55 51 48 43 52

    56 65 61 57 54 49 57

    69 58 64 61 57 52 61

    - - - - - - -

    - - - - - - -

    -21 - - - - -

    32 29 29 23 24 25 30

    - - - - - - -

    28 26 21 20 21 - 22

    47 45 42 38 36 31 38

    56 54 51 47 45 40 50

    - - - - - - -

    - - - - - - -

    22 22 21 21 - - 25

    38 32 32 31 31 27 32

    - - - - - - -

    - - - - - - -

    -22 - - - - -

    31 28 28 22 24 25 30

    57 56 53 49 46 41 48

    59 58 55 51 48 43 50

    65 64 61 57 54 49 57

    68 67 64 60 57 52 60

    42 36 36 35 35 31 35

    44 38 38 37 37 33 38

    49 43 43 42 42 38 42

    52 46 46 45 45 41 48

    33 30 30 24 21 20 28

    35 32 32 26 23 22 30

    41 38 38 32 29 30 35

    44 41 41 35 32 33 38

    14.0

    - - - - - - -

    - - - - - - -

    27 21 21 21 - - 20

    38 32 32 31 31 27 33

    - - - - - - -

    31 29 23 - - - 20

    47 45 41 37 34 29 40

    57 55 51 47 44 40 50

    16.0

    22 21 21 - - - 19

    35 33 33 27 24 25 30

    41 39 39 33 30 31 38

    44 42 42 36 33 24 40

    32 26 26 25 25 21 29

    44 38 38 37 37 33 38

    49 43 43 42 42 38 42

    52 46 46 45 45 41 50

    581

    826

    132

    528

    924

    1320

    206

    826

    826

    314

    1445

    1008

    1764

    2520

    1257

    2200

    3143

    2065

    53 52 51 48 47 42 51

    58 57 56 53 52 47 53

    69 69 68 65 63 59 65

    74 73 72 69 68 63 70

    27 23 22 - - - -

    32 28 27 23 - - 20

    33 30 28 24 - - 22

    37 34 32 28 24 23 30

    Volume

    Flowrate

    CFM

    46 45 46 43 42 37 42

    Discharge

    Sound Level

    Octave Band Cenre

    FrequencyN

    R

    58 58 58 55 54 49 55

    64 64 64 61 60 55 62

    68 68 68 65 64 59 65

    37 33 33 30 32 26 35

    48 44 45 42 43 38 42

    54 50 50 47 49 43 48

    57 54 54 51 53 47 57

    25 20 - - - - -

    37 32 31 27 23 25 27

    43 38 37 33 29 31 38

    47 42 41 37 33 35 40

    50 50 50 47 46 41 58

    61 62 62 58 57 53 60

    67 58 67 64 63 59 65

    71 72 80 68 67 63 68

    40 37 37 34 36 30 36

    48 44 45 42 43 38 40

    57 54 54 51 53 47 55

    61 57 58 55 56 51 57

    28 24 22 - - - -

    40 36 34 31 25 27 22

    46 42 40 37 31 33 40

    50 46 44 41 35 37 42

    1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Single Insulation)

    Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Double Insulation)

    Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    600 Pa400 PaDischarge

    Sound Level

    Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Single Insulation)

    Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    Radiated Sound Level

    (Double Insulation)

    Octave Band Cenre

    FrequencyN

    R1

    2

    5

    2

    5

    0

    5

    0

    0

    1

    0

    0

    0

    2

    0

    0

    0

    4

    0

    0

    0

    S

    i

    z

    e

    6.0

    38 34 34 32 33 28 35

    43 38 39 36 37 32 38

    44 40 39 35 30 32 40

    48 44 43 39 34 36 43

    49 49 48 45 43 38 42

    54 54 53 49 48 43 51

    54 50 50 48 49 44 55

    58 54 54 52 53 48 58

    8.0

    31 27 26 21 - - 21

    36 31 31 26 21 22 28

    47 43 43 38 32 34 38

    51 47 47 42 37 38 42

    42 38 38 36 37 32 38

    47 42 43 40 41 36 43

    58 54 54 52 53 48 54

    62 57 58 56 56 52 56

    55 55 52 48 46 41 50

    68 67 64 60 58 53 60

    74 72 70 66 64 59 70

    78 77 74 70 68 63 73

    27 23 23 - - - -

    40 37 32 31 27 28 31

    46 43 43 37 33 34 39

    50 47 47 41 37 38 42

    51 50 49 45 43 38 48

    62 60 59 56 54 49 53

    68 67 65 62 60 55 60

    72 71 69 66 64 59 67

    39 34 34 32 33 28 33

    49 44 45 43 43 39 42

    55 50 50 48 49 44 50

    59 54 54 52 53 48 56

    28 24 24 - - - 20

    39 35 35 30 25 27 30

    45 41 41 36 31 33 33

    49 45 45 40 35 37 40

    50 54 52 49 47 42 50

    56 65 63 59 58 53 58

    72 71 69 65 64 64 67

    76 75 73 69 68 63 70

    43 38 38 36 37 32 36

    53 48 48 47 47 43 50

    59 54 54 52 53 48 54

    62 57 58 56 56 52 58

    32 28 28 22 - - 25

    43 39 39 33 28 29 30

    49 45 45 39 34 35 40

    53 49 49 43 38 39 48

    10.0

    38 33 33 32 32 28 32

    50 44 44 43 43 39 43

    55 50 50 49 49 45 50

    59 54 54 52 53 48 56

    52 51 48 45 42 37 41

    64 63 60 56 54 49 58

    70 69 66 62 59 55 65

    74 73 70 66 64 59 68

    12.0

    32 29 29 23 - - 24

    44 41 41 35 29 30 36

    50 46 46 41 35 36 41

    54 51 51 45 39 40 48

    42 37 37 35 36 31 39

    54 48 48 47 47 43 50

    59 54 54 52 53 48 56

    63 57 58 56 56 52 59

    58 56 53 49 46 41 58

    70 68 64 60 58 53 60

    76 74 70 67 64 59 68

    79 77 73 69 67 62 70

    29 27 27 21 - - 22

    41 39 39 33 28 29 31

    47 45 45 39 34 35 44

    50 48 48 42 37 38 46

    63 62 59 55 52 47 56

    65 64 51 57 54 49 58

    71 70 69 63 59 55 66

    74 73 70 68 63 58 70

    48 42 42 41 41 37 42

    50 44 44 43 43 39 46

    56 50 50 49 49 45 52

    58 53 53 52 52 48 55

    39 36 36 30 25 26 30

    41 38 38 32 27 28 32

    47 44 44 38 33 34 40

    50 47 47 41 36 37 43

    67 65 62 58 58 51 60

    69 67 54 60 58 53 65

    75 73 60 66 64 59 67

    78 76 73 69 67 62 70

    52 46 46 46 45 41 46

    54 48 48 47 47 43 49

    58 54 54 53 53 49 54

    62 56 56 56 55 52 56

    42 39 39 33 28 29 32

    44 41 41 35 30 31 39

    50 47 47 41 35 37 44

    53 50 50 44 39 40 48

    14.0

    39 33 33 32 32 28 34

    50 44 44 44 43 40 43

    56 50 50 49 49 45 53

    59 53 52 52 52 48 54

    54 53 49 45 42 37 43

    66 65 61 57 54 49 58

    72 71 67 63 60 55 66

    75 74 70 66 64 59 69

    16.0

    33 30 30 24 - - 22

    45 42 42 36 30 31 34

    51 48 48 44 36 37 44

    54 51 51 45 39 40 48

    43 37 36 36 36 32 36

    54 48 48 47 47 43 47

    60 54 54 53 53 49 55

    63 56 56 56 55 52 57

    51

    204

    357

    505

    83

    332

    581

    826

    132

    528

    924

    1320

    206

    826

    826

    314

    1445

    1008

    1764

    2520

    1257

    2200

    3143

    2065

  • 8/13/2019 VAV_Box

    8/10

    Standard Electric Reheat Coil Selection

    Recommended Installation Method

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    Order Size(inch)Airflow Range

    6.0

    8.0

    10.0

    12.0

    Stages

    14.0

    16.0

    100 - 945

    170 -1675

    245 - 2450

    cmh

    350 - 3475

    500 - 4990

    640 - 6320

    1 , 2

    1 , 2 , 3

    1 , 2 , 3

    1 , 2 , 3

    1 , 2 , 3

    1 , 2 , 3

    120V

    1 Phase

    Allowable Maximum kW

    5.0

    5.5

    5.5

    5.5

    5.5

    5.5

    240V6.0

    9.5

    11.5

    11.5

    11.5

    11.5

    277V6.0

    11.0

    13.0

    13.0

    13.0

    13.0

    208V

    3 Phase

    6.0

    11.0

    17.0

    17.0

    17.0

    17.0

    415V6.0

    11.0

    17.0

    30.0

    34.5

    34.5

    600V6.0

    11.0

    17.0

    30.0

    49.5

    49.5

    Installation Instructions:

    1. The VAV terminals shall be installed at least two support brackets (One for the base unit , the other for accessories if any).

    Each of these brackets shall be fixed with two threaded rods to the ceiling slabs above.

    2. Recommended entry flow conditions as followed:

    i) min 5D from main duct

    ii) min 1D radius from secondary duct

    3. Additional volume control dampers before the inlet are required/recommended.

    4. All connections shall be thermally isolated.

    5. Pressure sensing tubes of the flow sensor shall not be kinkedor otherwise obstructed by the external duct insulation.

    min. 5D

    Main Duct

    Secondary Duct

    min. 1D

  • 8/13/2019 VAV_Box

    9/10

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    General

    a. Variable Air Volume (VAV) terminals units shall be factory assembled, consisting of a sound reducing air chamber, round

    inlet spigot, tight seal damper blade, and rectangular outlet for duct connection. VAV boxes shall be provided for areas as

    indicated on the drawings and equipment schedule.

    b. VAV boxes shall be rectangular or circular type, DDC (Direct Digitial Conrol) controlled pressure inependent designed for

    c. VAV boxes shall be supplied complete with controllers, actuators and sensors by the VAV manufacturer to ensure single

    source responsibility for the unit performance. VAV terminal units shall be LON, BACnet or standalone compatible.

    controller and actuator, if not originally maufacturer by the VAV manufacturer shall be product of a single manufacturer

    e. VAV units and wind tunnel performance data submitted shall be tested in accordance to ISO130-2008, ISO120-1999 or

    equivalent. The manufacturers wind tunnel laboratory shall be available for viewing by relevant bodies upon request.

    f. Factory calibration of VAV units to be done by manufacturer before delivering. The warranty of the complete unit including

    the controls shall be the sole responsibility of the supplier.

    Construction

    a. VAV terminal units shall be supploed in 7 nominal sizes (6.0 , 8.0, 10.0 , 12.0 , 14.0 , 16.0 , 24.0 x 16.0). VAV manufacturer

    b. Multi-outlet arrangements of A-Z shall be available upon customer request. The unit shall have proper opening with collar

    upon customer request. Stainless steel construction shal be available upon customer request.

    c. VAV casing shall be air-tight construction made of galvanized steel not less than 22 gauge (0.7 mm) with interal insulation of at least 25 mm thickness.

    d. Damper balde shall be of no less than 1.6 mm thickness (double skin), with periperal tear resistant Neoprence lip seal to

    ensure minimum leakageat a closed position. Damper shaft shall have damper position indicator to indicate the blades

    current position. All control components shall be mounted inside a protective metal shroud attached to the VAV unit.

    f. Access door shall be provided upon customer request. Access door shall be insulation to ensure minimum air leakage during

    operation.

    be arranged to ensure a true average measurement signal. Factory performance test shall be submitted to verify the

    DDC Controller

    a. The DDC controller shall be fully functional and shall be of the type that operates on open system concept (such as Lonworks

    for ready interfacing and freely intergrating with the buildings Lon based Building Automation Syste BAS), without any. The

    controller shall be capable of stand-alone and networking operation.

    b. The integral damper actuator shall be minimm 5Nm torque, over the shaft mounting type. Stroke shall be fully adjustable from

    0-94 Deg rotation with visible position indicator.

    c. Integral transformer shall be provided for each VAV units to provide power supply for the controller.

  • 8/13/2019 VAV_Box

    10/10

    Technical Specifications

    VAV Terminal UnitsVAV 20 Series - Pressure Independent VAV

    Performance

    a. The static pressure drop across the VAV terminal units at maximum catalogue airflow shall not exceed 70 Pa. The

    throttling range shall be from 100-10%.

    b. Airflow sensors shall be capable of amplifying the velocity signal by at least 2.2 times to improve reading accuracy at low

    air velocity.

    c. Air leakage through the damper shal be within 2% tolerance at an inlet static pressure of 750 Pa of nomial air flow.

    d. Independent of inlet pressure variations, VAV units shall modulate the delivered air volume between the specified

    maximum and minimum air volume with accuracy of the flow performance within +/- 5% tolernace even with irregular

    duct approach.

    e. The noise level in the air-conditioned areas shall not exceed that as specified.