Upload
michaeljmack
View
104
Download
2
Embed Size (px)
Citation preview
CUPERTINO ELECTRIC
INTERNATIONAL ASSOCIATIONINTERNATIONAL ASSOCIATIONOFOF
ELECTRICAL INSPECTORSELECTRICAL INSPECTORS
2002 SOUTHWESTERN SECTION2002 SOUTHWESTERN SECTIONANNUAL MEETINGANNUAL MEETING
EMERGENCY, LEGALLY REQUIREDEMERGENCY, LEGALLY REQUIRED
ANDAND
OPTIONAL STANDBY SYSTEMSOPTIONAL STANDBY SYSTEMS
Rudy Bergthold, P.E.
CUPERTINO ELECTRIC, INC.
San Jose, California
CUPERTINO ELECTRIC
• Designers and Installers have become relaxed in using the terms emergency and standby.
• Any generator is an emergency generator.
• Any load connected to an alternative source of supply is an emergency load.
• Relaxed standards for the use of the terms emergency and standby can lead to confusion, added cost and failing to pass inspection.
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBY
CATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED STANDBY 701
OPTIONAL STANDBY ARTICLE 702
SCOPE Legally required and classified as emergency by codes or AHJ. • Egress lighting • Life safety systems • Fire alarm & communication • Fire pumps• Elevators• Essential VentilationPrimarily for artificial illumination in places of assembly - • Safe exiting• Panic control• Essential for safety of human life• Reference NFPA 101-1997 and NFPA 110-1996
Legally required and classified as legally required standby by codes or AHJ.• Permanently installed equipment • Smoke removal• Sewage Disposal• Industrial Processes• HVAC/Ventilation• Communication equipmentWhen stopped, could create hazards or hamper rescue or fire fighter.• Reference NFPA 110-1996 & IEEE 446-1995
• Intended to protect public and private facilities where life safety does not depend on the performance of the system. Only those systems that are permanently installed• Data processing• HVAC• Industrial Process
APPROVAL Approved for use on emergency systems.
Equipment approved for intended use.
Equipment approved for intended use.
TESTS Witness test of complete system and periodically afterward. • Tested on a schedule acceptable to AHJ.• Battery Maintenance Program required. • Written Record of tests and maintenance.• Means to test under load required.
Witness test of complete system.• Tested on a schedule acceptable to AHJ.• Battery Maintenance Program required.• Written Record of tests and maintenance.• Means to test under load required.
None
Based on 1999 NEC
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYCATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED
STANDBY 701OPTIONAL STANDBY
ARTICLE 702
CAPACITY/ RATING
• Capacity to operate all emergency loads simultaneously.• May be used for peak load shed.• Portable/temporary required when generator is out of service for major maintenance or repair.• Highest priority if combined.• Selective load pickup/load shedding of legally required and optional standby.
• Allowed to supply legally required and optional standby loads.• Second priority if combined.• Capacity to operate all legally required standby loads simultaneously.• Selective load pickup/load shedding of optional standby.
• Lowest priority if combined • No mandatory loads
TRANSFER EQUIPMENT
• Automatic transfer identified for emergency use and approved by AHJ.• No inadvertent connection of sources.• Bypass/Isolation allowed. • Electrically operated, mechanically held.• Supply only emergency loads.
• Automatic transfer identified for standby use and approved by AHJ.• No inadvertent connection of sources.• Bypass/Isolation allowed.• Electrically operated, mechanically held.
• Suitable for intended use.• No inadvertent connection of sources.• Manual or automatic.
Based on 1999 NEC
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYCATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED
STANDBY 701OPTIONAL STANDBY
ARTICLE 702
SIGNALS • Audible and Visual where practicable• Derangement (BKR open, low fuel)• Carrying load• Not functioning (battery charger fail)• Ground fault (Alarm not trip) posted instructions
• Audible and Visual where practicable • Derangement• Carrying load• Not functioning (battery charger)
• Audible and Visual where practicable.• Derangement• Carrying load
SIGNS • At service entrance indicate type and location of onsite emergency power sources.• At grounding location if remote from emergency source.
• At service entrance indicate type and location of legally required standby power sources.• At grounding location if remote from standby source.
• At service entrance indicating type and location of standby sources.• At grounding location if remote from source.
WIRING • Boxes, enclosures, transfer switches, generators, panels, etc. permanently marked as emergency.• Wiring kept independent except in transfer equipment, at exit/emer- gency fixtures, at unit equipment.• Locate circuits to minimize hazards; flood, fire, ice, vandalism.• In high rise/life safety or assembly occupancies over 1000 people:
a. Circuits in fully sprinklered spaces or 1 hours resistive circuit construction.
Permitted to occupy the same raceway, cable, box or cabinet as general wiring.
No special restrictions.
Based on 1999 NEC
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYCATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED
STANDBY 701OPTIONAL STANDBY
ARTICLE 702
WIRING b. Listed thermal barrier for electrical components.
c. Minimum 2” of concreted. Listed cable assemblye. Equipment in sprinklered space or 1
hour rating.
SOURCES OF POWER
Transfer within 10 seconds Transfer within 60 seconds No transfer time specified.
STORAGE BATTERY
• 1.5 hours to 87.5 percent of normal voltage• Sealed battery OK need not be transparent.• Wet cell needs to be transparent • No automotive batteries• Automatic charging.
• 1.5 hours to 87.5 percent of normal voltage• Sealed battery OK need not be transparent• Wet cell needs to be transparent• No automotive batteries.• Automatic charging.
Not applicable.
GENERATOR SET
• Automatic start.• Time delay retransfer 15 minutes provided• Two hour fuel supply (8 hours UBC) on premise• Two sources of fuel and cooling if served from public utility system. • Automatic fuel source transfer.• Start battery needs independent charger.
• Automatic start.• Time delay retransfer 15 minutes provided• Two hour fuel supply on premise.• Two sources of fuel and cooling if served from public utility system.• Automatic fuel source transfer.• Start battery needs independent charger.
Not applicable.
Based on 1999 NEC
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYCATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED
STANDBY 701OPTIONAL STANDBY
ARTICLE 702
GENERATOR SET • Battery charger and dampers connected to generator.• Fuel transfer pumps powered from generator.
UNINTERRUPTIBLE POWER SUPPLIES(Lighting Inverter)
• May be used but refer to batteries and generator above.
• May be used but refer to batteries and generator above.
Not applicable.
SEPARATE SERVICE
• If acceptable to AHJ• Per Article 230• Widely separate electrically and physically from normal.
• If acceptable to AHJ• Per Article 230• Widely separate electrically and physically from normal.
Not Applicable.
UNIT EQUIPMENT • Rechargeable battery and battery charger.• Local and/or remote lamps.• Relay to energize lamps.• 1.5 hours to 87½ percent battery output.• 60% light output for 1.5 hours• Permanently fixed in place.• Flexible cord and plug connection permitted if not over 3’ long.
• Rechargeable battery and battery charger.• Local and/or remote lamps.• Relay to energize lamps. • 1.5 hours to 87½ percent battery output.• 60% light output for 1.5 hours.• Permanently fixed in place.• Flexible cord and plug connection permitted if not over 3’ long.
Not applicable.
Based on 1999 NEC
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYBased on 1999 NEC
CATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED STANDBY 701
OPTIONAL STANDBY ARTICLE 702
UNIT EQUIPMENT
•Circuit also feeds normal lighting in space or, if 3 circuits used in space may be on separate circuit from same panel and locked on.• Clearly mark circuit at panel.
•Circuit also feeds normal lighting in space or, if 3 circuits used in space may be on separate circuit from same panel and locked on.• Clearly mark circuit at panel.
BRANCH CIRCUIT LOADS
• No appliances and no other lamps on emergency lighting circuits.• Automatic transfer required for power branch circuits that supply emergency equipment.
Not applicable. Not applicable.
EMERGENCY ILLUMINATION
• Emergency illumination includes required means of egress.• Single lamp out cannot cause total darkness.• HID sources need emergency lamp on until normal illumination restored.• Include all required means of egress lighting, exit signs, and other lights necessary.• No single lamp failure leaves space requiring illumination in darkness.• Operate HID fixtures until normal restored. (Quartz restrike)
If acceptable to AHJ• Not tapped within service disconnecting means.• Separate physically.
Not applicable.
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYBased on 1999 NECCATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED
STANDBY 701OPTIONAL STANDBY
ARTICLE 702
LIGHTING CIRCUITS
Supplied from alternate source when normal power interrupted.• Independent supply with means to automatically transfer.• Two or more systems with independent power supply where only one is required.• Automatic switching unless both systems normally in service.• May be part of general lighting system.
Permitted to occupy the same raceway, cable, box or cabinet as general wiring.
Permitted to occupy the same raceway, cable, box or cabinet as general wiring.
SWITCHING Authorized persons have control.• When two single throw switches in parallel, one accessible only to authorized personnel.• Additional switches to turn lights on but not off.• No 3 way or 4 way.• No switches in series.
No special restriction. Not applicable.
SWITCH LOCATIONS
• Convenient to authorized persons only• In places of assembly (i.e. theater) – switch convenient in lobby. • No switch in projection booth unless to only turn lights on.• Exterior lights may by turned off by photo cell.
No special restriction. Not applicable.
CUPERTINO ELECTRIC
EMERGENCY VS. STANDBYEMERGENCY VS. STANDBYBased on 1999 NECCATEGORY EMERGENCY ARTICLE 700 LEGALLY REQUIRED
STANDBY 701OPTIONAL STANDBY
ARTICLE 702
OVERCURRENT PROTECTION
• Accessible to authorized persons only.• Coordinated system (fully rated vs. integrated).
• Accessible to authorized persons only.
Same as general building supply system.
GROUND FAULT PROTECTION
Tripping not required, indication only. Tripping not required, indication only. Tripping required if more than 150 volts to ground and 1000 AMPS.
CUPERTINO ELECTRIC
TYPICAL TRANSFER SYSTEMS
CUPERTINO ELECTRIC
TYPICAL EQUIPMENT CONFIGURATIONS
CUPERTINO ELECTRIC
TYPICAL SYSTEM WITH A SINGLE GENERATOR SERVICE ALL LOADS. MAY EMPLOY LOAD SHED.
CUPERTINO ELECTRIC
TYPICAL SYSTEM WITH OPTIONAL LOADS USING UNIT EQUIPMENT FOR EGRESS LIGHTING.
CUPERTINO ELECTRIC
TYPICAL SYSTEM WITH BOTH EMERGENCY AND OPTIONAL STANDBY ALTERNATE SOURCES.
CUPERTINO ELECTRIC
TWO TYPES OF ALTERNATE SOURCES, FOUR TYPES OF TRANSFER.
CUPERTINO ELECTRIC
MEDIUM VOLTAGE SYSTEM WITH LOW VOLTAGE EMERGENCY LOADS.
CUPERTINO ELECTRIC
TYPICAL THREE POLE TRANSFER SWITCH CONNECTIONS.
CUPERTINO ELECTRIC
TYPICAL FOUR POLE TRANSFER SWITCH CONNECTION.
CUPERTINO ELECTRIC
TYPICAL UNIT EQUIPMENT CONNECTION. BATTERY SERVES LOAD FOR 90 MINUTES WHEN NORMAL SUPPLY TO GENERAL ILLUMINATION FAILS.
CUPERTINO ELECTRIC
SWITCHABLE UNIT EQUIPMENT. BATTERY SERVES LOAD FOR 90 MINUTES WHEN NORMAL SUPPLY TO GENERAL ILLUMINATION FAILS.
CUPERTINO ELECTRIC
SEPARATE CIRCUIT FOR EGRESS LIGHTING WHEN ROOM/AREA SERVED WITH 3 OR MORE CIRCUITS.
CUPERTINO ELECTRIC
GENERATOR SIZING EXAMPLEGENERATOR SIZING EXAMPLE
Notes: (1) Running Load = 150KVA (180A @ 480V 3Phase). See Sheet B for calculation.
(2) Refer to Sheet C for Generator Sizing for Combination Loads.
(3) Refer to Sheet D for Total Load Generator Sizing.
DESCRIPTION LOAD(KW)
CLASSIFICATION OF LOAD GENERATOR LOAD DURING:
EMERGENCYLEGALLY
REQUIRED STANDBY
OPTIONAL STANDBY
ROUTINE OUTAGE
OUTAGE WITH
FA/LSS
OUTAGE WITH FA &
PUMP
OUTAGE WITH
EQUIPMENT IN
OPERATION
Egress Lighting 100 100 100 100 100 100
Fire Alarm/LSS 50 50 50 50 50 50
Smoke Control 200 200 200 200 200
Fire Pump 125 125 855 (1) 855 (1)
Computer Room 400 400 400 400
Elevator 100 100 100 100 100 100
Garage Exhaust 100 100 100 100 100 100
Walk-in Refrigerator 25 25 25 25
TOTALS 1100 475 300 425 775 550 971 (2) 1100 (3)
CUPERTINO ELECTRIC
GENERATOR SIZING EXAMPLEGENERATOR SIZING EXAMPLE
FIRE PUMP STARTINGFIRE PUMP STARTINGSHEET B
Fire Pump = 150 Hp, 480V 3Ph, Code G Squirrel Cage Motor Started Across the Line.
TABLE 430 – 150: 150Hp = 180 Amps @ 480V.
TABLE 430 – 7(b): Code G = 5.6 – 6.29 KVA/Hp.
Starting KVA = 6.29 x 150Hp = 943.5 KVA = 1135 Amps.
NFPA 20 limits Starting Voltage Drop to 15%.
Approximation of Voltage Drop equals Ratio of Starting Current to Maximum Available Fault Current.
AmpsCircuit Short Required AmpsStarting
0.1515%
7567Amps0.151135
0.15 AmpsStarting
AmpsCKT Short Required
The Normal Source Impedance for 480V Diesel Generators is between 10% and 17% or 0.1pu and 0.17pu
Normal Source FLA = Short CKT Amps x Source Impedance pu
= 7567 x 0.17
= 1286 Amps
480V 3Phase Generator KW = 0.8pf x Normal FLA x 0.48 x 1.732
= 0.18 x 1286 x 0.48 x 1.732
= 855KW
Normal Starting Requirement (Generator KW) is 4 to 6 times Fire Pump Horsepower.
pu Impedance SourceFLA Source Normal
AmpsCircuit Short
CUPERTINO ELECTRIC
SHEET C
From Sheet B
Fire Pump starting required Short Circuit Amps = 7576
Total of Connected Loads = 675KW.
New Combination Required Short Circuit Amps = 7576 + 1014
= 8590 Amps
Normal Source FLA = Short CKT Amps x Source Impedance pu
= 8590 x 0.17
= 1460 Amps
480V 3Phase Generator KW = 0.8pf x Normal FLA x 0.48 x 1.732
= 0.18 x 1460 x 0.48 x 1.732
= 971 KW
GENERATOR SIZING FORGENERATOR SIZING FOR
COMBINATION OF LOADS WITH FIRE PUMPCOMBINATION OF LOADS WITH FIRE PUMP
1014Amps1.732 x 0.48 x 0.8
675 Loads Other of AmpsLoad Running
CUPERTINO ELECTRIC
SHEET D
From Sheet B
Fire Pump starting required Short Circuit Amps = 7576
Total of Running Loads = 1100 KW.
New Combination Required Short Circuit Amps = 7576 + 1654
= 9230 Amps
Normal Source FLA = Short CKT Amps x Source Impedance pu
= 9230 x 0.17
= 1569 Amps
480V 3Phase Generator KW = 0.8pf x Normal FLA x 0.48 x 1.732
= 0.18 x 1569 x 0.48 x 1.732
= 1043 KW
Minimum Size = Connected Load when Minimum Starting Calculation is less than Connected Load.
= 1100 KW
GENERATOR SIZING FORGENERATOR SIZING FOR
TOTAL OF ALL LOADSTOTAL OF ALL LOADS
Amps16541.732 x 0.48 x 0.8
1100 Loads Other of AmpsLoad Running