Taco Presentation
LoadMatch
B-1
180°F315000 BTU/H
64.6 GPM
170°F
IHL-1
165.5°F
170.5°F
5000 BTU/H2.1 GPM
IHL-2
166.4°F
171.4°F
10000 BTU/H4.1 GPM
IHL-3
167.9°F
172.9°F
15000 BTU/H6.2 GPM
IHL-4
169.8°F
174.8°F
20000 BTU/H8.2 GPM
IHL-5
172.1°F
177.1°F
25000 BTU/H10.3 GPM
IHL-6
175°F
180°F
30000 BTU/H12.3 GPM
P-1
64.6 GPM31.1 FT
2.1 GPM10.5 FTHP-IHL-1
4.1 GPM10.5 FTHP-IHL-2
6.2 GPM11.1 FTHP-IHL-3
8.2 GPM10.5 FTHP-IHL-4
10.3 GPM10.7 FTHP-IHL-5
12.3 GPM11 FTHP-IHL-6
IHL-7
165.5°F
170.5°F
5000 BTU/H2.1 GPM
IHL-8
166.4°F
171.4°F
10000 BTU/H4.1 GPM
IHL-9
167.9°F
172.9°F
15000 BTU/H6.2 GPM
IHL-10
169.8°F
174.8°F
20000 BTU/H8.2 GPM
IHL-11
172.1°F
177.1°F
25000 BTU/H10.3 GPM
IHL-12
175°F
180°F
30000 BTU/H12.3 GPM
2.1 GPM10.5 FTHP-IHL-7
4.1 GPM10.5 FTHP-IHL-8
6.2 GPM11.1 FTHP-IHL-9
8.2 GPM10.5 FTHP-IHL-10
10.3 GPM10.7 FTHP-IHL-11
12.3 GPM11 FTHP-IHL-12
IHL-13
165.5°F
170.5°F
5000 BTU/H2.1 GPM
IHL-14
166.4°F
171.4°F
10000 BTU/H4.1 GPM
IHL-15
167.9°F
172.9°F
15000 BTU/H6.2 GPM
IHL-16
169.8°F
174.8°F
20000 BTU/H8.2 GPM
IHL-17
172.1°F
177.1°F
25000 BTU/H10.3 GPM
IHL-18
175°F
180°F
30000 BTU/H12.3 GPM
2.1 GPM10.5 FTHP-IHL-13
4.1 GPM10.5 FTHP-IHL-14
6.2 GPM11.1 FTHP-IHL-15
8.2 GPM10.5 FTHP-IHL-16
10.3 GPM10.7 FTHP-IHL-17
12.3 GPM11 FTHP-IHL-18
NAME: LOCATION:
Wet Rotor Circulating Pump
IHL-18
175°F
180°F
30000 BTU/H12.3 GPM 12.3 GPM
11 FTHP-IHL-18
Wet Rotor Circulating Pump
IHL-18
175°F
180°F
30000 BTU/H12.3 GPM 12.3 GPM
11 FTHP-IHL-18
Twin Tee
Wet Rotor Circulating Pump
IHL-18
175°F
180°F
30000 BTU/H12.3 GPM 12.3 GPM
11 FTHP-IHL-18
Twin Tee
Eliminate: Control valve Balance valve
Adjustments:Will have to either increase flow or coil area as you along the system.
Benefits: Saves on piping. Less pressure drop for circulator pump. Eliminates control valve leaks.
LoadMatch System
Pumps
Wet Rotor:
20 year life. Replacement cartridges cost around $150. No need to remove pump to replace cartridge. Can be variable speed. (300:1)
Self Sensing:
Drive comes with pre-programmed curves. Program can be edited in the field. Provide shut-off head for maximum efficiency. Standard dry run protection. Can only be lead/lag. Standard vibration isolation on drive.
Chilled Beams
Passive Beams
Active Beams
Design Considerations:
Chilled water should be between 55 and 60 deg. F. Handles sensible load only. Need DOAS system to handle latent load, ventilation requirements, and pressurization. Avoid openings to outdoors where using chilled beams. Provide dewpoint sensor in room and at ceiling for each space. Verify pressure in building stays positive.
Radiant cooling panels: 20-40 BTU/SF Passive chilled beams: 120-150 BTU/SF Active chilled beams: 400-750 BTU/SF
LoFlo with Chilled Beams
iWorx
Features:
Pre-programmed controllers for standard equipment.Graphic control interface controller brings in other controllers and automatically creates graphics.Web-based.Uses NiagraAX framework.Can communicate with LonWorks, BACnet IP, BACnet MSTP, and Modbus.Only need to provide home screen graphics.Truly open protocol.Best used with light commercial and buildings with standard equipment.