SCALE: 1" = 50'-0" LOCATION MAP SCOPE OF WORK DESIGN WEST ENGINEERING MECHANICAL ELECTRICAL ENERGY CONSULTANTS San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100 Phone: 909.890.3700 Fax: 909.890.3770 Email: [email protected] Contact: Adrian Jacquez CONTRACTOR SHALL INSTALL EQUIPMENT (CFCI - UNLESS OTHERWISE NOTED ON PLANS) FOR A RIVERSIDE COUNTY EMPLOYEE FUNDRAISER EVENT PROJECT DIRECTORY SCALE: NONE VICINITY MAP Hans Kernkamp General Manager-Chief Engi 31125 IRONWOOD AVENUE MORENO VALLEY, CA 92555 EVENT LOCATION 31125 IRONWOOD AVENUE MORENO VALLEY, CA 92555 SITE 1 2 3 4 5 7 PROJECT FOR: EMPLOYEE CAMPAIGN 31125 IRONWOOD AVENUE MORENO VALLEY, CA 92555 6 San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700 Fax: 909-890-3770 Email: [email protected] DESIGN WEST ENGINEERING MECHANICAL ELECTRICAL ENERGY CONSULTANTS R:\_PROJECT\2020\20-063 UNITED WAY EVENT, COUNTY OF RIVERSIDE\20-063 E TITLESHT - 2020-04-01 - JEFF MULLENAX RIVERSIDE COUNTY FUNDRAISER EVENT 03/16/2020 JWM PRELIMINARY ELECTRICAL 03/19/2020 JWM FINAL ELECTRICAL BADLANDS LANDFILL TITLE SHEET E0.0 Sheet List Table Sheet Number Sheet Title E0.0 TITLE SHEET E0.1 ELECTRICAL LEGEND, NOTES & LUMINAIRE SCHEDULE E0.2 SINGLE LINE DIAGRAM E1.1 ELECTRICAL SITE PLAN E2.1 ENLARGED EVENT AREA E3.1 ELECTRICAL DETAILS E4.1 ELECTRICAL SPECIFICATIONS

design west engineering - Riverside County Purchasing

Embed Size (px)

Citation preview

SCALE: 1" = 50'-0"

LOCATION MAP

SCOPE OF WORK

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700Fax: 909.890.3770Email: [email protected]: Adrian Jacquez

CONTRACTOR SHALL INSTALL EQUIPMENT (CFCI - UNLESS OTHERWISE NOTED ONPLANS) FOR A RIVERSIDE COUNTY EMPLOYEE FUNDRAISER EVENT

PROJECT DIRECTORY

SCALE: NONE

VICINITY MAP

Hans Kernkamp General Manager-Chief Engineer

31125 IRONWOOD AVENUE

MORENO VALLEY, CA 92555

EVENT LOCATION

31125 IRONWOOD AVENUE

MORENO VALLEY, CA 92555

SITE

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

T

IT

LE

SH

T - 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

TITLE SHEET

E0.0

Sheet List TableSheet Number Sheet Title

E0.0 TITLE SHEET

E0.1 ELECTRICAL LEGEND, NOTES & LUMINAIRE SCHEDULE

E0.2 SINGLE LINE DIAGRAM

E1.1 ELECTRICAL SITE PLAN

E2.1 ENLARGED EVENT AREA

E3.1 ELECTRICAL DETAILS

E4.1 ELECTRICAL SPECIFICATIONS

POWER LEGEND AND SYMBOLSSYMBOL DESCRIPTION

NOTE TO CONTRACTOR

CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB SITE AND SHALLIMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BERESPONSIBLE FOR THE SAME.

DO NOT SCALE DRAWINGS

1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CALIFORNIA CODE OF REGULATIONS (CCR),NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES AND REGULATIONS.

2. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE TO UL REQUIREMENTSTO ACCOMMODATE CONDUCTORS SHOWN.

3. WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL APPLY TOTHE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF MECHANICAL, PLUMBING AND OTHER EQUIPMENT REQUIRINGELECTRICAL CONNECTION PRIOR TO ANY WORK.

5. CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE FINAL CONNECTION ASREQUIRED TO ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.

6. LOCATION OF LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR DOORS, INSTALL SWITCHES ONSIDE OPPOSITE TO DOOR HINGE. VERIFY FINAL HINGE LOCATION IN FIELD PRIOR TO ANY WORK.

7. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOWDRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER TRADES RELATING TO WORK TO VERIFY SPACE INWHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALLTIMES.

8. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL WALL OUTLET BOXES FOR SWITCHES, BELL/STROBES, FIREALARM PULL STATIONS. RECEPTACLES ETC. WITH CABINETS, FURNITURE, EQUIPMENT ETC., TO AVOID CONFLICT.

9. FURNISH PULL STRING IN EACH RACEWAY RUN OVER 10' IN LENGTH, IN WHICH PERMANENT WIRING IS NOT INSTALLED.

10. NOT MORE THAN THREE LIGHTING OR CONVENIENCE OUTLET CIRCUITS ARE PERMITTED IN ONE CONDUIT, PROVIDESEPARATE CONDUIT FOR EACH HOMERUN INDICATED ON THE DRAWING, UNLESS INDICATED OTHERWISE.

11. PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS. COORDINATE LOCATIONS OFBOXES WITH OTHER TRADES TO AVOID CONFLICT. PULL BOXES SHALL BE ACCESSIBLE. THE SIZE OF PULL BOX SHALLCOMPLY WITH N.E.C. REQUIREMENTS.

12. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDEENVIRONMENT (UP TO 16') SHALL BE WEATHERPROOF TYPE, NEMA 3R.

13. NO CONDUIT RUNS SHALL BE ALLOWED IN CONCRETE SLABS. ALL CONDUITS WILL BE PLACED ABOVE ACCESSIBLECEILING SPACES UNLESS SPECIFICALLY INDICATED TO BE UNDERGROUND.

14. LIGHTING, POWER, TELEPHONE AND COMMUNICATIONS OUTLETS SHALL NOT BE PLACED BACK-TO-BACK.

15. WHERE MORE THAN ONE LIGHT SWITCH OCCURS AT SAME LOCATION, SWITCHES SHALL BE MOUNTED IN A MULTIPLEGANG BOX UNDER A SINGLE COVER PLATE. PLATES WITH MORE THAN (3) LIGHT SWITCHES SHALL BE LABELED TOINDICATE THE LIGHT FIXTURES CONTROLLED.

16. DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE DIRECTLY ON EQUIPMENT,PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.

17. ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL" LABEL SHALL APPEAR ONALL ELECTRICAL EQUIPMENT.

18. ALL DISTRIBUTION AND CONTROL EQUIPMENT (SUCH AS CB's, SWITCHES, CONTACTORS, ETC.), TERMINATIONS SHALL BEFULLY RATED PER UL AS FOLLOWS:

a. 125A OR LESS : 60°C OR MORE;b. MORE THAN 125A : 75°C OR MORE.

19. ANY ERRORS, OMISSIONS, OR DESIGN DISCREPANCIES ON PLANS OR SPECIFICATIONS SHALL BE BROUGHT TO THEATTENTION OF THE ELECTRICAL ENGINEER FOR CLARIFICATION OR CORRECTION PRIOR TO CONSTRUCTION ANDPREPARATION OF SUBMITTAL PACKAGES.

20. CONDUCTORS SHALL HAVE UNDERWRITER'S LABORATORIES, INC.(UL) LISTED, 600 VOLT INSULATION OF TYPE SPECIFIEDBELOW OR ELSEWHERE IN THE SPECIFICATIONS. CONDUCTORS SHALL BE COPPER.

1. BRANCH CIRCUITS - LIGHTING AND POWER.

a. #10 AWG AND SMALLER, SOLID WIRE TYPE THW OR THHN/THWN, THHW(THHN FOR DRY LOCATION ONLY).b. #8 AWG TO #2 AWG, STRANDED TYPE THW OR THHN/THHW.c. #1 AWG AND LARGER, STRANDED TYPE XHHW.

2. FEEDERS : TYPE THW OR THHN/THWN, OR XHHW.

21. PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN EACH RACEWAY INCLUDING CONDUITS, PLUG STRIPS,WIREMOLD. SIZE OF GROUNDING SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE ARTICLE 250.

22. WIRING METHOD SHALL BE EMT ABOVE GROUND AND MOUNTED IN CONCEALED SPACES AND SCHEDULE-40 PVC FORUNDERGROUND INSTALLATION. USE RIGID WHEN ENCASED IN CONCRETE OR SUSCEPTIBLE TO DAMAGE.

23. USE 10AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 75 FEET.USE 10AWG CONDUCTORS FOR 20 AMPERE, 277V BRANCH CIRCUITS LONGER THAN 200 FEET.

24. ALL SWITCH LOCATIONS ARE REQUIRED TO HAVE A NEUTRAL CONDUCTOR PROVIDED AT THE SWITCH LOCATION PERCEC 404.2(C).

25. UNLESS OTHERWISE INDICATED, SHARING OF NEUTRAL/GROUNDED CONDUCTORS AMONG SINGLE PHASE BRANCHCIRCUITS OF DIFFERENT PHASES INSTALLED IN THE SAME RACEWAY IS NOT PERMITTED. PROVIDE DEDICATEDNEUTRAL/GROUNDED CONDUCTOR FOR EACH INDIVIDUAL BRANCH CIRCUIT.

26. ALL ELECTRICAL CONDUIT, CONDUCTORS, EQUIPMENT, FIXTURES, ECT. SHOWN SHALL BE FURNISHED & INSTALLED BYCONTRACTOR U.O.N..

APPLICABLE CODES

ABBREVIATIONS

GENERAL NOTES

1. 2019 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.

2. 2019 CALIFORNIA BUILDING CODE (CBC),PART 2, TITLE 24 C.C.R. (IBC WITH AMENDMENTS)

3. 2019 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. (NEC WITH AMENDMENTS)

4. 2019 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. (UMC WITH AMENDMENTS)

5. 2019 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. (UPC WITH AMENDMENTS)

6. 2019 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R. (IFC WITH AMENDMENTS)

7. 2019 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.

8. 2019 TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

9. 2019 CALIFORNIA ENERGY CODE (PART 6, TITLE 24 C.C.R.)

10. 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSG), PART 11, TITLE 24 C.C.R.

SWITCH, SINGLE POLE 20A. MOUNTED INSIDE LOCKABLE WEATHERPROOF BOX, 48" ABOVEGRADE TO TOP OF DEVICE. BOX SIZE TO BE DETERMINED BY SWITCH NUMBER IN BOX.

LIGHTING LEGEND AND SYMBOLSSYMBOL DESCRIPTION

+96" OR 7'-6" AFFMOUNTING HEIGHT FROM FINISHED FLOOR TO BOTTOM LINE OF OUTLET OR EQUIPMENT. FORLIGHT FIXTURES, IT IS TO BOTTOM OF FIXTURE.

MAIN SWITCHBOARD, POWER OR LIGHT, FLOOR STANDING ENCLOSURE, (SEE SINGLE LINEDIAGRAM AND LOAD SUMMARY)

BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (RECESSED MOUNTED)

BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (SURFACE MOUNTED)

CONDUIT STUBBED AND CAPPED, 3/4" UON

RACEWAY CONCEALED IN WALLS OR ABOVE CEILING, 3/4" UON

CONDUIT CONCEALED IN OR UNDER FLOOR, 3/4" UON, COORDINATE WITH G.C.: OR, BURIALCONDUIT UNDERGROUND IN SCHEDULE - 40 PVC UNLESS NOTED OTHERWISE. VERIFY DEPTHAND TRENCHING WITH G.C.

SPECIALTY OUTLET. VERIFY NEMA CONFIGURATION AS NOTED ON PLANS.L5-30R

DISCONNECT SWITCH H.P. RATED 600 VOLTS RATED. "F" INDICATES FUSE TYPE. FUSES PERAPPROVED MANUFACTURERS SHOP DRAWINGS.

MAGNETIC MOTOR STARTER H.P. RATED (NUMBER INDICATES NEMA SIZE)#2

OR

200-Y CONDUIT WIRING DESCRIPTION PER FEEDER SCHEDULE ON OTHER PLAN

TEMPORARY OVERHEAD CABLING

CONCRETE ELECTRICAL PULL BOX WITH LID APPROPRIATE FOR INSTALLATION LOCATION. LIDSHALL BE LABELED "ELECTRICAL" OR "COMM" ACCORDING TO USE.

EQUIPMENTID. No.

SHEET No.DETAIL No.

EQUIPMENT REFERENCE

DETAIL REFERENCE

ABOVE CEILING, CONCEALED, JUNCTION BOX, WITH COVER, PER NATIONAL ELECTRICAL CODE(NEC) TABLE 314.16(A)/(B), 4" SQUARE DEEP, WITH PLASTER RING.

RECESSED WALL MOUNTED JUNCTION BOX, WITH COVER, PER NATIONAL ELECTRICAL CODE(NEC) TABLE 314.16(A)/(B), 4" SQUARE DEEP, WITH PLASTER RING.

MOLDED CASE CIRCUIT BREAKER

SWITCH AND FUSE ASSEMBLY

GROUNDING CONNECTION AT SWITCHGEAR/DISTRIBUTION BOARD WITH NEUTRAL BONDING.

UTILITY COMPANY PULL SECTION LUGS

GN

GROUNDING CONNECTION TO MAIN BUILDING GROUND SYSTEM U.O.N.

EXISTING (DASH INDICATES) ELECTRICAL EQUIPMENT

3/4" UON HOMERUN TO CIRCUITS #1 AND #3 IN PANEL "A". (CROSSMARKSINDICATE NUMBER OF PHASES AND NEUTRAL. PROVIDE GROUND WIRE.)

3/4" CONDUIT WITH 2 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 3 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 4 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 5 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 2 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE SIZE)

3/4" CONDUIT WITH 3 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE SIZE)

3/4" CONDUIT WITH 4 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE SIZE)

3/4" CONDUIT WITH 5 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE SIZE)

1" CONDUIT WITH 6 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE SIZE)

#10

#10

#10

#10

#10

A-1,3

IN-LINE UTILITY COMPANY METER

UTILITY METER WITH CIRCUIT TRANSFORMERS (CT'S) METER

SOLID STATE DEVICE CONNECTED TO THE POWER DISTRIBUTION SYSTEM

TRANSFORMER WITH SECONDARY GROUNDOR

GROUND FAULT PROTECTION DEVICE CONNECTED TO THE POWER DISTRIBUTION SYSTEM

GROUND WELL

G ON-SITE GENERATOR SET

200-D CONDUIT WIRING DESCRIPTION PER FEEDER SCHEDULE ON OTHER PLAN

A AMPEREAF AMPERE FRAME RATING (CIRCUIT BREAKER)AFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAFU AMPERE FUSE RATING (FUSE)AIC AMPERE INTERRUPTING CAPACITYAS AMPERE SWITCH RATING (FUSE)AT AMPERE TRIP RATING (CIRCUIT BREAKER)AWG AMERICAN WIRE GAUGEBKBD BACKBOARDBLDG BUILDINGBKR BREAKERC CONDUITCB CIRCUIT BREAKERCKT CIRCUITCFSD COMBINATION FIRE SMOKE DAMPERCO CONDUIT ONLYCONC CONCRETECT CURRENT TRANSFORMERCU COPPERCL CENTERLINEDISC DISCONNECTDSBN DISTRIBUTION SECTIONDN DOWNDWG DRAWINGEA EACHEC ELECTRICAL CONTRACTOREM EMERGENCYEMT ELECTRICAL METALLIC TUBINGEXIST, (E) EXISTINGEXO EXTERNAL OPERABLE DISCONNECTF FUSEFA FIRE ALARMFACP FIRE ALARM CONTROL PANELFF FINISHED FLOORFG FINISHED GRADEFLA FULL LOAD CURRENTFLUOR FLUORESCENTGEN GENERATORGFCI GROUND FAULT CIRCUIT INTERRUPTERGFP GROUND FAULT PROTECTIONGND GROUNDHOA HAND-OFF-AUTOMATICHP HORSE POWERHV HIGH VOLTAGEIDF INTERMEDIATE DISTRIBUTION FRAMEIG ISOLATED/INSULATED GROUNDINCAND INCANDESCENTISC SHORT CIRCUIT CURRENT AVAILABLE IN RMS

SYMMETRICAL AMPERESJ-BOX JUNCTION BOXKCMIL THOUSAND CIRCULAR MILSKW KILOWATTKV KILO VOLTKVA KILO VOLT-AMPERELDC LOCAL DISTRIBUTION CABINETLDF LOCAL DISTRIBUTION FRAMELCL LONG CONTINUOUS LOADLTG LIGHTINGLV LOW VOLTAGEMFR MANUFACTURERMAX MAXIMUMMCC MOTOR CONTROL CENTERMIN MINIMUMMH MANHOLE / METAL HALIDEM/M METER AND MAIN SECTIONMULTI MULTI-METER SECTIONMV MEDIUM VOLTAGENC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'SASSOCIATION

NEW (N) NEW, TO BE FURNISHED AND INSTALLED BYCONTRACTOR

NF NON-FUSEDNIC NOT IN CONTRACTN/L NIGHT LIGHTNO NUMBER, NORMALLY OPENNTS NOT TO SCALEOC ON CENTEROD OUTSIDE DIAMETERP POLEPB PULL BOXPF POWER FACTORPNL PANELPOC POINT OF CONNECTIONPP POWER POLEPWR POWERPVC POLYVINYL CHLORIDEQUAD QUADRUPLEXQTY QUANTITYREQD REQUIREDREQMT REQUIREMENTRGS RIGID GALVANIZED STEELRMC RIGID METALLIC CONDUITRM ROOMRNC RIGID NONMETALLIC CONDUITSHT SHEETSN SOLID NEUTRALSPEC SPECIFICATIONSSPDT SINGLE POLE, DOUBLE THROWSPST SINGLE POLE, SINGLE THROWSW SWITCHSWBD SWITCHBOARDTC TIME CLOCKTEL TELEPHONETERM TERMINALTP TEMPORARY POLETYP TYPICALUGPS UNDERGROUND PULL SECTIONUL UNDERWRITERS LABORATORYUPS UNINTERRUPTIBLE POWER SUPPLYUON UNLESS OTHERWISE NOTEDV VOLT, VOLTAGEVA VOLT-AMPEREVFC VARIABLE FREQUENCY CONTROLLERVFD VARIABLE FREQUENCY DRIVEW WATTWH WATT-HOURWP WEATHERPROOFWT WEATHERTIGHTWW WIREWAYXP EXPLOSION PROOFZ IMPEDANCE

4W FOUR-WIRE3W THREE-WIRE5S JUNCTION BOX

(4 11/16" SQUARED X2 1/8" DEEP)Ø DIAMETER, PHASE# NUMBER°C DEGREE CELSIUS

(E) EXISTING DEVICE TO REMAIN(R) REMOVE EXISTING DEVICE AND ASSOCIATED

CONDUIT AND WIRE(RL) REMOVE EXISTING DEVICE AND RELOCATE AS

SHOWN ON PLAN(NL) NEW LOCATION OF RELOCATED DEVICE

1. EQUALS SHALL BE CONSIDERED UPON SUBMITTAL REVIEW AND APPROVAL. PLEASE NOTE THAT IF AN ALTERNATE IS CONSIDERED:

a. THE CONTRACTOR IS COMPLETELY AND SOLELY RESPONSIBLE FOR ALL ASPECTS OF THE SUBSTITUTION INCLUDING UPDATING CONSTRUCTION DOCUMENTS, OBTAINING APPROVALS AND COORDINATING WITH ALL TRADES TO ENSURECHANGES TO AFFECTED BUILDING SYSTEM ARE ACCOUNTED FOR AND ACCEPTABLE TO THE ENGINEERING TEAM. CONTRACTOR SHALL ENSURE SUBSTITUTED EQUIPMENT MEETS OR EXCEEDS DESIGN INTENT REGARDING RATINGS,PERFORMANCE, DIMENSIONAL CLEARANCES, PHYSICAL DIMENSIONS (MAX/MIN), WEIGHT LIMITATIONS, AND OTHER ASPECTS, PROVING SUBSTITUTION IS SUITABLE TO THE APPLICATION. ENGINEERS WILL REVIEW THE RATING ANDPERFORMANCE OF SUBSTITUTED EQUIPMENT ONLY AND WILL NOT ASSUME RESPONSIBILITY FOR SUBSTITUTION AT ANY LEVEL.

b. IF CONTRACTOR CANNOT MAKE SUBSTITUTED EQUIPMENT WORK IN THIS PROJECT, CONTRACTOR SHALL REVERT TO REQUIREMENTS OF PERMITTED CONSTRUCTION DOCUMENTS AT THEIR EXPENSE.

c. IT IS UNDERSTOOD BY ALL PARTIES THAT ANY SUBSTITUTIONS OF SPECIFIED PRODUCTS ARE DONE FOR THE PURPOSE OF COST SAVINGS TO THE OWNER. THEREFORE, ANY MATERIAL SUBSTITUTION OR DEVIATIONS PROPOSED BY THECONTRACTOR SHALL BE INCLUDED WITH THE INITIAL BID AND SHALL SHOW A LINE ITEMS CREDIT TO THE OWNER FOR EACH SUBSTITUTION IN LIEU OF SPECIFIED PRODUCTS.

2. PROVIDE ALL REQUIRED MOUNTING HARDWARE ANCHORAGE AND SUPPORTS TO INSTALL LIGHTING FIXTURES.

3. THE CONTRACTOR SHALL PROVIDE A COMPLETE AND OPERABLE LIGHTING SYSTEM AS PART OF THIS BUILDING CONTRACT.

4. LED LIGHT FIXTURES SHALL BE IN ACCORDANCE WITH IES, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND AS SPECIFIED.

5. LED LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES (ROHS)-COMPLIANT.

6. LED DRIVERS SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED:· MINIMUM EFFICIENCY: 85% AT FULL LOAD.· MINIMUM OPERATING AMBIENT TEMPERATURE: -20 DEG C. (-4 DEG F.)· INPUT VOLTAGE: 120 - 277V (±10%) AT 60 HZ., UNLESS OTHERWISE INDICATED.· INTEGRAL SHORT CIRCUIT, OPEN CIRCUIT, AND OVERLOAD PROTECTION.· POWER FACTOR: >=0.95.· TOTAL HARMONIC DISTORTION: <=20%.· COMPLY WITH FCC 47 CFR PART 15.

22. LED MODULES SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED:· COMPLY WITH IES LM-79 AND LM-80 REQUIREMENTS.· MINIMUM CRI 80 AND COLOR TEMPERATURE 4000K UNLESS OTHERWISE SPECIFIED IN LUMINAIRE SCHEDULE.· MINIMUM RATED LIFE: 50,000 HOURS PER IES L70.· LIGHT OUTPUT LUMENS AS INDICATED IN THE LUMINAIRE SCHEDULE.

25. ALL FIXTURES MOUNTED OUTDOORS SHALL BE UL LISTED FOR WET LOCATION.

LUMINAIRE SCHEDULE NOTES

LUMINAIRE SCHEDULETYPE VOLTS WATTAGE LAMPS FIXTURE DESCRIPTION MFR. CATALOG #MOUNTING SYMBOLNOTES

120VF1 35EXTERIOR SECURITY LUMINAIRE WITHTWIST-LOCK PHOTOCELL STANDARD AND INA SILVER FINISH

LITHONIAINTEGRATEDLED OLAL2-40K-120-PER4 X 4

POLE

LUMENS

3,165

120VF2 9 EXTERIOR LUMINAIRE WITH PRISMATIC LENSAND IN AN OIL-RUBBED BRONZE FINISH WESTINGHOUSE 62034004 X 4

POLE500 INTEGRATEDLED

AVAILABLE AT HOME DEPOT.

AVAILABLE AT HOME DEPOT.

120VF3 48' SPOOLED STRING LUMINAIRE WITH 24"LAMP INTERVAL. LAMP NOT INCLUDED. TARGETTI USA

STRING LUMINAIRE:DLD-CL-MD-24-BK

LAMP:DLV-G25-MD-04-22-120-D

AIRCRAFTCABLE HUNG

G25 GLOBELED WITH E26

BASE

345 PERLAMP

4.5 PERLAMP

STRING LIGHT AND LAMP AREQUICK SHIP PRODUCTS,CONTACT FACTORY FOR

ORDERING. CONTRACTORSHALL PROVIDE AIRCRAFTCABLE AND IS TO PROVIDEALL NECESSARY MOUNTINGHARDWARE & MOUNT PER

MANUFACTURERSPECIFICATIONS.

SPIDERBOX FOR TEMPORARY POWER. TYPE AND CONFIGURATIONS PER PLAN.

OWNER PROVIDED AND INSTALLED POSTS, SEE PLAN FOR LOCATIONS.

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

F

RN

TS

HT

- 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

ELECTRICAL LEGEND,

NOTES & LUMINAIRE

SCHEDULE

E0.1

2

GENERAL NOTES

PANEL SCHEDULES

CONSTRUCTION NOTES

1. REFER TO 'GENERAL NOTES' ON ELECTRICAL LEGENDS AND NOTESSHEET FOR WIRING METHODS, MATERIALS, AND REQUIREMENTS.

2. ALL CIRCUIT BREAKERS, PANELBOARDS AND TRANSFORMERS SHALLBE OF THE SAME MANUFACTURER.

3. ALL GROUND CONNECTIONS SHALL BE CADWELD.

4. ALL PANELBOARDS SHALL BE FULLY RATED FOR THE AVAILABLE FAULTUNLESS OTHERWISE NOTED.

5. THE FEEDER LENGTHS SHOWN ON THESE DRAWINGS ARE FORCALCULATION PURPOSES ONLY AND ARE NOT VALID FOR BIDDING.

6. CONTRACTOR SHALL UPDATE ALL MODIFIED PANEL DIRECTORIES ORCREATE A NEW TYPED DIRECTORY, IF ONE DOES NOT EXIST,IDENTIFYING EACH CIRCUIT AND INSTALLED CIRCUIT LOADS, MOUNTEDIN GLASS OR PLASTIC INSIDE DOOR. THE CONTRACTOR SHALL BERESPONSIBLE FOR UPDATING DIRECTORIES TO INDICATE ALL NEWCIRCUITS AND ACTUAL AREA SERVED WHICH IS NOT NECESSARILY THEDESCRIPTION INDICATED ON THE BID DOCUMENTS. USE A COMPUTEROR TYPEWRITER TO CREATE DIRECTORY; HANDWRITTEN DIRECTORIESARE NOT ACCEPTABLE.

7. EQUIPMENT DATA AND CONFIGURATIONS SHOWN ON THE SINGLE LINEDIAGRAM PROVIDE GENERAL EQUIPMENT INFORMATION.CONTRACTOR SHALL REVIEW ELECTRICAL PLANS ANDSPECIFICATIONS TO VERIFY ALL EQUIPMENT ASSOCIATED DESIGNINFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDINGALL NECESSARY COMPONENTS REQUIRED FOR A COMPLETE ANDOPERATIONAL INSTALLATION. ANY DISCREPANCIES BETWEENDESCRIPTIONS, SPECIFICATIONS, AND EXISTING CONDITIONS ARE TOBE PRESENTED TO THE ENGINEER OF RECORD PRIOR TO COMPLETIONOF THE BID PROCESS FOR CLARIFICATION. NO EQUIPMENT SHALL BEORDERED UNTIL DISCREPANCIES ARE RESOLVED THROUGH A FORMALRFI PROCESS.

8. CONTRACTOR SHALL CONDUCT, WITH ASSISTANCE OF SWITCHGEARMANUFACTURER OR LICENSED ENGINEER, AN ELECTRICAL HAZARDANALYSIS CONSISTING OF AN ARC FLASH, SHORT CIRCUIT, ANDCOORDINATION STUDY TO DETERMINE APPROPRIATE LEVELS OFPERSONNEL PROTECTIVE EQUIPMENT (PPE) AS REQUIRED BY NFPA70E AND IEEE STD 1584, AND TO ENSURE PROPER COORDINATION(INCLUDING GROUND FAULT COORDINATION) EXISTS BETWEEN ALLOVER-CURRENT PROTECTIVE DEVICES SHOWN ON SINGLE-LINEDIAGRAM ADDITIONALLY:8.1. STUDY SHALL INCLUDE ALL PORTIONS OF ELECTRICAL

SINGLE-LINE DIAGRAM. NORMAL SYSTEM CONNECTIONS ANDTHOSE THAT RESULT IN MAXIMUM FAULT CONDITION SHALL BEADEQUATELY COVERED IN THE STUDY. PERFORM STUDY WITHTHE AID OF A COMPUTER PROGRAM, SKM CAPTOR, OR EQUAL.STUDY SHALL IDENTIFY SELECTIVE COORDINATION SUCH THATDEVICE CLOSEST TO FAULT WILL TRIP FIRST. GROUND FAULTPORTION OF THE STUDY SHALL DEMONSTRATE COORDINATIONOF MAIN BREAKER AND ANY FEEDER GROUND FAULT DEVICESWITH DOWNSTREAM CIRCUIT BREAKERS 30A AND LESS.

8.2. CONTRACTOR SHALL BE RESPONSIBLE TO RECOMMENDSETTINGS OF ALL DEVICES AND TO INCLUDE GROUND FAULTSETTINGS NECESSARY TO ACHIEVE SYSTEM COORDINATION.CONTRACTOR SHALL FIELD ADJUST DEVICES ACCORDINGLYUTILIZING A QUALIFIED MANUFACTURER'S REPRESENTATIVE.

8.3. DURING THE CONSTRUCTION PHASE OF THE PROJECT ALLGROUND FAULT RELAYS SHALL BE SET AT SHORTEST AVAILABLETIME DELAY.

8.4. RESULTS OF COORDINATION STUDY SHALL BE SUBMITTED ASPART OF OVERALL SWITCHGEAR SUBMITTAL AND SHALL INCLUDEPROTECTIVE DEVICE TIME VERSUS CURRENT COORDINATIONCURVES, GROUPING APPROPRIATE DEVICES TOGETHER.TABULATIONS OF RELAY AND CIRCUIT BREAKER TRIP SETTINGS,FUSE SELECTION, AND COMMENTARY REGARDING SAME.

8.5. A GROUND FAULT SYSTEM TEST SHALL BE CONDUCTED BY ANINDEPENDENT TESTING AGENCY PER NEC (CEC-WHEREADOPTED) 230.95(C). GROUND FAULT SYSTEM TEST SHALL BEPERFORMED IN PRESENCE OF LOCAL AHJ. VERIFICATION OFDEVICE SETTINGS PER THE COORDINATION STUDY SHALL BEPERFORMED BY SAME INDEPENDENT TESTING AGENCY. GROUNDFAULT TEST RESULTS SHALL BE DELIVERED TO ENGINEER ORRECORD.

8.6. PERFORM ARC FLASH ANALYSIS TO DETERMINE FLASHBOUNDARY, FLASH HAZARD CATEGORY, PPE REQUIREMENTS,AND MINIMUM ARC RATING(CAL/SQUARE CM). ABOVEINFORMATION SHALL BE INDICATED AT EACH ARC FLASH SOURCEON A NEC (CEC WHERE ADOPTED) COMPLIANT ARC PLASHHAZARD LABEL(S) AS MANUFACTURED BY BRADY.

9. GROUND ALL ELECTRICAL EQUIPMENT, BRANCH CIRCUITS, FEEDERS,PANEL AND DISTRIBUTION BOARDS, ELECTRICAL SERVICES, ETC. PERADOPTED NEC ARTICLES 250.

10. ALL ELECTRICAL EQUIPMENT (I.E. SWITCHGEAR, TRANSFORMERS,DISTRIBUTION BOARDS, PANELBOARDS, DISCONNECT SWITCHES, ETC.)SHALL BE PROVIDED WITH A PHENOLIC NAMEPLATE WITH ENGRAVEDLETTERS PER SPECIFICATIONS. ALL NAMEPLATES SHALL BEFASTENED WITH A MINIMUM OF TWO (2) MACHINE SCREWS. NO SELFADHESIVE NAMEPLATES ARE ALLOWED.

11. ANY FLOOR-STANDING ELECTRICAL EQUIPMENT (I.E. INVERTERS,DISTRIBUTION BOARDS, SWITCHBOARDS, ATS SWITCHES, MOTORCONTROL CENTERS, ETC.) WHICH ARE MOUNTED AT/BELOW GRADEAND/OR SUSCEPTIBLE TO WATER DAMAGE SHALL BE MOUNTED ON AMINIMUM 4" HIGH HOUSEKEEPING PAD WHICH EXTENDS 4" BEYONDEQUIPMENT IN ALL DIRECTIONS.

12. ELECTRICAL CONTRACTOR TO INCLUDE IN BID ALL ASSOCIATED COSTSFOR THIRD PARTY TESTING OF ELECTRICAL EQUIPMENT, GROUNDFAULT, CONDUCTORS, ETC.

4000AUGPS

(E) 2000A 480Y/277V 3Ø 4W ' MSA '

EXISTING SERVICE GROUNDEXISTING FEED FROM SCEUTILITY TRANSFORMER

1 2 3 4

(E)150A3P

G

N

(E)2000A3P

EXISTINGFLARE #1

EXISTINGFIELD OFF.

PANEL

EXISTING

(E)40A3P

(E)30A3P

(E)150A3P

5

(E)100A3P

6

(E)300A3P

7 8 9

FUTUREPUMP EXISTING

EXISTINGS & S OFF.

PANEL

EXISTING

SPARE

EXISTINGFLARE #2

EXISTING

SPARE(N)200A3P

T-LP112.5 KVA

PRI:480V 3PH 3WSEC:208Y/120V 3PH 4W

G200A3P

MTS200A

4PNEMA 3R

IN COMBINATION WITH PANEL BOARD BRANCH CIRCUIT BREAKERS ANDDISTRIBUTION BOARD CIRCUIT BREAKER SHALL BE U.L. LISTED SERIESRATED TO WITHSTAND AVAILABLE FAULT CURRENT FOR PANELBOARDAND CIRCUIT BREAKER NOTED. PROVIDE LABELING AS REQUIRED PERNEC 110-22.

(1) #1/0 CU. BOND TO DRIVEN GROUND ROD IN GROUND WELL.

PROVIDE NEW CIRCUIT BREAKER IN EXISTING DISTRIBUTION PANELBOARD. CIRCUIT BREAKER SHALL BE RATED TO WITHSTAND AVAILABLEFAULT CURRENT.

(1) #4 C.U. BOND TO DRIVEN GROUND ROD FOR SEPARATELY DERIVEDSERVICE PER NEC 250.30(A)(5). GROUND ROD SUPPLIED BY TEMPORARYGENERATOR EQUIPMENT SUPPLIER.

PROVIDE 200A CAM LOCKS AT BOTTOM OF MTS FOR CONNECTION TOTEMPORARY GENERATOR.

CONDUCTORS SIZE INCREASED DUE TO VOLTAGE DROP.

PROVIDE AND INSTALL AN SO CORD AND NEMA 14-50R CAP ON BOTH ENDSFROM THE POWER PEDESTALS TO THE SPIDERBOXES.

1

2

3

4

5

480Y/277V 3Ø 4W NEMA 3R 100KW(125KVA) DIESEL STANDBY GENERATORSET WITH CIRCUIT BREAKER AND 2HRMIN STANDBY TIME TANKBASE. (SHOWNFOR REFERENCE ONLY. PROVIDED BYOTHERS)

SO CORD WITH CAM LOCKCONNECTION (PROVIDEDBY OTHERS)

225-Y

NEWPANEL

'LP'

NEWPANEL

'HP'

6

65kAIC

DIST: 240'VD: 1.06%

FAULT CURRENT:10,928

DIST: 595'VD: 2.09%

FAULT CURRENT:4,201

DIST: 5'VD: 0.02%

FAULT CURRENT:2,170

DIST: 5'VD: 0.01%

FAULT CURRENT:9,923

NEWPOWERPED. 'B'

NEWPOWERPED. 'C'

225-Y6

350-Y

175-D

175-B6175-B 6 200-B 6

DIST: 401'VD: 2.98%

FAULT CURRENT:3,850

DIST: 401'VD: 2.98%

FAULT CURRENT:3,850

DIST: 506'VD: 2.98%

FAULT CURRENT:3,827

5 4

2

1

1

3

20-YSETSTYPELABEL PHASE GROUND CONDUIT

1 3 # 12 3/4"

30-Y 1 3 # 10 3/4"

1 3 # 8 1"

1 3 # 6

1 3 # 6

1 3 # 4

1 3 # 4

1 3 # 2

1 3 # 1

1 3 # 1

1

1

1

1

1

1

3 # 250 KCM

1

1

2

40-Y

50-Y

60-Y

70-Y

80-Y

90-Y

100-Y

125-Y

150-Y

175-Y

200-Y

225-Y

250-Y

300-Y

350-Y

400-Y

450-Y

500-Y

600-Y

700-Y

800-Y

1000-Y

1200-Y

1600-Y

2000-Y

2500-Y

3000-Y

4000-Y

1600A-4W

4000A-4W

1000A-4W

700A-4W

600A-4W

500A-4W

450A-4W

20A-4W

3000A-4W

2000A-4W

2500A-4W

800A-4W

1200A-4W

400A-4W

350A-4W

300A-4W

250A-4W

225A-4W

200A-4W

175A-4W

150A-4W

125A-4W

100A-4W

80A-4W

60A-4W

50A-4W

30A-4W

40A-4W

70A-4W

90A-4W

2

2

2

2

3

3

4

5

6

8

10

3 # 1/0

3 # 2/0

3 # 3/0

3 # 4/0

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 250 KCM

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 500 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 4/0

1"

1"

1"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

1-1/2"

1 # 4/0

1#500KCM

1 # 2/0

1 # 1/0

1 # 1/0

1 # 2

1 # 2

1 # 12

1#500KCM

1#250KCM

1#350KCM

1 # 1/0

1 # 3/0

1 # 2

1 # 2

1 # 4

1 # 4

1 # 4

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

4"

4"

4"

4"

4"

3"

3"

4"

4"

4"

4"

4"

4"

4"

3"

2 1/2"

2 1/2"

2"

2"

NEUTRAL1 # 12

1 # 10

1 # 10

1 # 6

1 # 6

1 # 4

1 # 4

1 # 2

1 # 1

1 # 1

1 # 250 KCM

1 # 1/0

1 # 2/0

1 # 3/0

1 # 4/0

1 # 350 KCM

1 # 500 KCM

1 # 600 KCM

1 # 4/0

1 # 250 KCM

1 # 350 KCM

1 # 500 KCM

1 # 600 KCM

1 # 500 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

600V FEEDER SCHEDULE 3Ø 4W

NOTE:ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THEAMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTORSIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

20-D

600V FEEDER SCHEDULE 3Ø 3WSETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT

1 3 # 12

30-D 1 3 # 10

1 3 # 8

1 3 # 6

1 3 # 6

1 3 # 4

1 3 # 4

1 3 # 2

1 3 # 1

1 3 # 1

1

1

1

1

1

1

3 # 250 KCM

1

1

2

40-D

50-D

60-D

70-D

80-D

90-D

100-D

125-D

150-D

175-D

200-D

225-D

250-D

300-D

350-D

400-D

450-D

500-D

600-D

700-D

800-D

1000-D

1200-D

1600-D

2000-D

2500-D

3000-D

4000-D

1600A-3W

4000A-3W

1000A-3W

700A-3W

600A-3W

500A-3W

450A-3W

20A-3W

3000A-3W

2000A-3W

2500A-3W

800A-3W

1200A-3W

400A-3W

350A-3W

300A-3W

250A-3W

225A-3W

200A-3W

175A-3W

150A-3W

125A-3W

100A-3W

80A-3W

60A-3W

50A-3W

30A-3W

40A-3W

70A-3W

90A-3W

2

2

2

2

3

3

4

5

6

8

10

3 # 1/0

3 # 2/0

3 # 3/0

3 # 4/0

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 250 KCM

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 500 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 4/0

1 # 4/0

1#500KCM

1 # 2/0

1 # 1/0

1 # 1/0

1 # 2

1 # 2

1 # 12

1#500KCM

1#250KCM

1#350KCM

1 # 1/0

1 # 3/0

1 # 2

1 # 2

1 # 4

1 # 4

1 # 4

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

3/4"

3/4"

1"

1"

1"

1"

1-1/4"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

4"

4"

4"

4"

4"

3"

3"

4"

4"

4"

4"

4"

4"

4"

3"

2 1/2"

2 1/2"

2"

2"

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NANOTE:ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THEAMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTORSIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

20-B

600V FEEDER SCHEDULE 1Ø 3WSETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT

1 2 # 12

30-B 1 2 # 10

1 2 # 8

1 2 # 6

1 2 # 6

1 2 # 4

1 2 # 4

1 2 # 2

1 2 # 1

1 2 # 1

1

1

1

40-B

50-B

60-B

70-B

80-B

90-B

100-B

125-B

150-B

175-B

200-B

20A-3W

200A-3W

175A-3W

150A-3W

125A-3W

100A-3W

80A-3W

60A-3W

50A-3W

30A-3W

40A-3W

70A-3W

90A-3W

2 # 1/0

2 # 2/0

2 # 3/0

1 # 12

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

3/4"

3/4"

1"

1"

1"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

2"

2"

1 # 12

1 # 10

1 # 10

1 # 6

1 # 6

1 # 4

1 # 4

1 # 2

1 # 1

1 # 1

1 # 1/0

1 # 2/0

1 # 3/0

1-1/4"

1-1/2"

NOTE:ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THEAMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTORSIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

7

1SINGLE LINE DIAGRAM

750-B 750-B 7 50-B

NEMA 3R NEMA 3R NEMA 3R

NEMA 3R

NEMA 3R

NEMA 3R

NEWPOWERPED. 'A'

6

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

S

LD

- 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

SINGLE LINE DIAGRAM

E0.2

(N) MANUAL TRANSFERSWITCH 'MTS' ON

PREFAB CONCRETEPAD

TEMPORARYGENERATOR AREA

225-Y

3

1. THE CONTRACTOR SHALL INSPECT AND VERIFY ALL FIELD CONDITIONSPRIOR TO INSTALLATION OF EQUIPMENT.

2. COORDINATE TRENCH ROUTING AND EQUIPMENT LOCATIONS WITHEXISTING CONDITIONS AND NEW WORK.

3. SUPPORT CONDUIT(S) EVERY 10'-0" AND WITHIN 3'-0" OF ANY JUNCTIONBOX OR TERMINATION.

4. PROVIDE AND INSTALL ALL GRC RISERS WITH 40 MIL. TAPE.

CONTRACTOR IS TO TRANSITION FROM NONMETALLIC CONDUIT TO RIGIDSTEEL CONDUIT AFTER RISING ABOVE GROUND LEVEL.

PROVIDE AND INSTALL 2' X 3' UNDERGROUND PULLBOX, SEE DETAIL:

PROVIDE AND INSTALL (1) 2 1/2" FOR CONDUCTORS AND (1) 2" CONDUITONLY FOR FUTURE USE, SEE DETAIL:

PROVIDE AND INSTALL PRE-CAST CONCRETE PAD FOR EQUIPMENT. SIZEDPER BELOW:

· MANUAL TRANSFER SWITCH: 6'-0"W X 3'-0"D MINIMUM· TRANSFORMER/PANELS: 9'-0"W X 5' 0"D MINIMUM

SEE DETAIL: FOR TRANSFORMER/PANEL UNISTRUT DETAIL.

PROVIDE AND INSTALL (2) 2" CONDUIT (ONE 2" SPARE CONDUIT) FORPOWER PEDESTAL, SEE DETAIL:

PROVIDE AND INSTALL (3) 2" CONDUIT (ONE 2" SPARE CONDUIT) FORPOWER PEDESTAL, SEE DETAIL:

MOUNT LUMINAIRE ON POST WITH ARM BRACKET. PROVIDEWEATHERPROOF JUNCTION BOX ON BACK OF FIXTURE, ROUTE CONDUITDOWN IN RIGID CONDUIT AND TRANSITION TO SCHEDULE 40 PVCUNDERGROUND BETWEEN FIXTURES UNDER ROADWAY ENTRANCE ANDTHEN TO PANELBOARD 'LP'. PROVIDE ALL NECESSARY COMPONENTS ASTO MAKE A COMPLETE INSTALLATION OF LUMINAIRES ON POST.

1

2

3

4

1E3.1

2E3.1

4E3.1

2E3.1

5

6

7

2E3.1

N

O

P

A

R

K

I

N

G

N

O

P

A

R

K

I

N

G

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2350

2

3

5

0

2

3

5

0

2350

2

3

4

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2320

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2330

2330

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2330

2

3

3

0

2

3

3

0

2330

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

2

2

0

2

2

2

0

2

2

3

0

2

2

3

0

2

2

3

0

2

2

3

0

2

2

4

0

2

2

4

0

2

2

4

0

2

2

4

0

2

2

4

0

2240

2

2

4

0

2

2

4

0

2

2

4

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

5

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

6

0

2

2

7

0

2270

2

2

7

0

2

2

7

0

2270

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

7

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2

2

8

0

2280

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

2

9

0

2

3

0

0

2

3

0

0

2

3

0

0

2300

2300

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2300

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

0

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2310

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2

3

1

0

2310

2

3

1

0

2310

2

3

1

0

2310

2

3

1

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2320

2

3

2

0

2320

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

3

0

2330

2330

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2330

2

3

3

0

2

3

3

0

2330

2

3

3

0

2

3

3

0

2330

2330

2330

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2330

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2

3

3

0

2340

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2340

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2

3

4

0

2340

2

3

4

0

2

3

4

0

2

3

5

0

2350

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2350

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2350

2

3

5

0

2

3

5

0

2

3

5

0

2350

2350

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

5

0

2

3

6

0

2

3

6

0

2

3

6

0

2360

2

3

6

0

2

3

6

0

2

3

6

0

2

3

6

0

2

3

6

0

2

3

7

0

2

3

7

0

2

3

7

0

2

3

7

0

(N) MANUALTRANSFER SWITCHON CONCRETE PAD

PROPOSED LOCATIONFOR STEP-DOWN

TRANSFORMER 'T-LP',PANEL 'HP' & PANEL 'LP'

PROPOSED LOCATION FORELECTRICAL PULLBOX AND

POWER PEDESTAL(PULLBOX NOT TO SCALE)

PROPOSED LOCATION FORELECTRICAL PULLBOX AND(2) POWER PEDESTALS(PULLBOX NOT TO SCALE)

(E) 4000A MAINSWITCHBOARD WITH 2000AMAIN 480Y/277V 3PH 4W

PROPOSED LOCATIONFOR TEMPORARYGENERATOR

4

4

3

3

3

3

3

2

2

1

2

2

5 6

7

2

(E) SCE UTILITYTRANSFOMER

NEMA 3R PULLBOXINSTALLED ON BACK OF

(E) DISTRIBUTION BOARD

(E) 4000A MAIN SWITCHBOARDWITH 2000A MAIN CIRCUIT

BREAKER 480Y/277V 3PH 4W

225-Y

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

S

IT

EP

LN

- 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

ELECTRICAL SITE

PLAN

E1.1

1

SCALE: 1" = 30'-0"

GENERAL NOTES

ELECTRICAL SITE PLAN

CONSTRUCTION NOTES

ELECTRICAL SITE

PLAN

E1.1

1E2.1

2

SCALE: 1/4" = 1'-0"

(E) ELECT. SERVICE AREA

2E1.1

LP-9

3E1.1

2

SCALE: 1/4" = 1'-0"

(N) ELECT. SERVICE AREA

2

3

1

0

2

3

1

0

2310

2

3

1

0

2

3

1

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

2

3

2

0

3

4

4

1(TYPICALFOR ALL )

1(TYPICALFOR ALL )

1(TYPICALFOR ALL )

5(TYPICALFOR ALL )

2

2

2

2

1(TYPICALFOR ALL ) SPIDERBOX

SPIDERBOX

SPIDERBOX

SPIDERBOX

SPIDERBOX

7

7

7

7

8

F3

F3

F3

F3

F3F3

F3F3

F3

F3

F3

F3

F3

F3

F3

5(TYPICALFOR ALL )

9(TYP.)

5E4.1

3 5E4.1

2

6

6

6

EVENT TENT (PROVIDEDBY OTHERS)

10

10

1. COORDINATE LIGHT FIXTURE LOCATIONS AND LIGHT SWITCHLOCATIONS, COLOR, AND STYLE WITH COUNTY OF RIVERSIDE.

2. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE NEMA 3R.

3. ALL EXTERIOR RECEPTACLE OUTLETS SHALL BE GFCI TYPE.

4. CONTRACTOR SHALL WEATHERPROOF ALL EXPOSED LIGHTINGFIXTURE ELECTRICAL CONNECTION POINTS.

MOUNT LUMINAIRE ON POST AT 8'-0" ABOVE GRADE. PROVIDEWEATHERPROOF JUNCTION BOX ON BACK OF FIXTURE, ROUTE CONDUITTO TOP OF POLE AND LAND IN JUNCTION BOX ON TOP OF POLE. ROUTE SOCORD BETWEEN JUNCTION BOXES OVERHEAD ON TOP OF POLES. TAKECARE AS TO MOUNT IN A WAY THAT WILL NOT IMPEDE PROGRESS UNDERPOLE AND SO CORDS.

PROVIDE SO CORD FROM JUNCTION BOX WITH 5-20R CAP TO SPIDERBOX .PROVIDE ALL NECESSARY COMPONENTS TO MOUNT TO POLES AND TOKEEP SO CORD FROM BECOMING A TIP HAZARD.

DIRECT BURIAL POWER PEDESTAL. BURY BOTTOM OF PEDESTAL 25"BELOW GRADE PER MANUFACTURERS SPECIFICATIONS WITHCONDUCTORS SWEEPING IN AT NO LESS THAN A 7" BEND RADIUS FROMPULLBOX.

PULLBOX TO BE CLOSE ENOUGH TO SAFE OFF CONDUCTORS AFTEREVENT FOR STORAGE OF CONDUCTOR ENDS. CONTRACTOR TO ADDSIGNAGE AT PANEL 'LP' INDICATING CONDUCTORS ARE STORED INPULLBOX FOR LATER USE AND PROVIDE CIRCUIT BREAKER WITHLOCK-OFF CAPABILITY.

PROVIDE 3/16" DIAMETER AIRCRAFT CABLE TO STRING LIGHTING ON ANDALL NECESSARY COMPONENTS FOR SAFELY MOUNTING STRING LIGHTING.

TEMPORARY RESTROOM BUILDING TO BE CONNECTED TO SPIDERBOX VIANEMA 5-30P (PROVIDED BY CAL-STATE SITE SERVICES). LOAD TO BE SPLITBETWEEN SPIDERBOXES.

SPIDERBOX TO BE PROVIDED WITH A MINIMUM OF (6) NEMA 5-20R GFCIRECEPTACLES.

SPIDERBOX TO BE PROVIDED WITH A MINIMUM OF (3) NEMA L5-30R & (4)NEMA 5-20R GFCI RECEPTACLES.

POSTS ARE TO BE OWNER FURNISHED OWNER INSTALLED. VERIFY WITHCOUNTY PRIOR TO CONSTRUCTION START.

SINGLE POLE SWITCH(ES) IN LOCKABLE BOX TO CONTROL STRING ANDPOLE MOUNTED LIGHTING. CONTRACTOR TO VERIFY LOCATION ANDWHICH LIGHTING COMPONENTS THEY WOULD LIKE SWITCHED WITHRIVERSIDE COUNTY PRIOR TO ORDERING BOX(ES) AS TO DETERMINECORRECT SIZE AND NUMBER OF SWITCHES REQUIRED.

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

F

LP

LN

- 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

ENLARGED EVENT

AREA

E2.1

1

SCALE: 3/32" = 1'-0"

GENERAL NOTES

ENLARGED EVENT AREA

CONSTRUCTION NOTES

3

1

2

UNISTRUT MOUNTING DETAIL

5

4

8

7

6

11

10

9 PRE-CAST CONCRETE PULLBOX (OFCI)

TRENCH (OFOI) AND CONDUIT (CFCI) DETAIL

SERVICE & DISTRIBUTION GROUNDING DETAIL

RV TYPE POWER PEDESTAL

-

-

-

-

-

-

TRAFFIC PLATE NOTE:

PROVIDE STEEL DIAMOND PLATESTEEL LIDS WITH TRAXPLATESLIP RESISTANT SURFACELOCKABLE COVERMANUFACTURED BY JENSEN METALTECH.

TRAFFIC COVER(SEE NOTE ABOVE

TYPICAL KNOCKOUT 20"X 20"

CABLE RACK (TYPICAL)

TYPICAL KNOCKOUT8" X 16"

3/4" DIA PULL IRONTYPICAL FOR ALL

PULL BOXES

NOTES:

1. DEPTH OF PULLBOX MAY VERY. PROVIDE EXTENSION SECTIONSAS REQUIRED TO CLEAR EXISTING UNDERGROUND UTILITIES.

2. PROVIDE JENSEN PRECAST CONCRETE PULLBOXES, WITH"LOCKLID" LID, FURNISH AND INSTALL CABLE RACKS ON WALLINDICATED. EACH RACK SHALL BE EQUIPPED WITH THREEPORCELAIN CABLE HOLDERS ON A VERTICAL STEEL MOUNTINGBAR. BOLT HOLES SHALL BE PRECAST. PULLBOXES SHALL BEEQUIPPED WITH STAINLESS STEEL FLATHEAD SCREWS AND SELFCLEANING HOLES. LOOP ALL CABLES AROUND THE LONGESTLENGTH IN THE PULLBOX 2' x 3' PULLBOX SHALL BE QUICKSETSERIES 1000.

3. PROVIDE PULL ROPE FOR ALL SPARE CONDUITS.

4. SEAL OFF AND GROUT ALL CONDUIT KNOCKOUT PENETRATIONSAND SPARE CONDUIT OPENINGS.

5. ALL CONDUCTORS ENTERING UNDERGROUND PULL BOX SHALLBE LABELED WHERE CONDUCTOR IS BEING FED AND WHERECONDUCTOR IS BEING TERMINATED.

6. ALL CONDUCTORS SHALL BE NEATLY ORGANIZED.

SECTION B

FIN. GRADE

SET PULL BOX 1" ABOVETOP OF FINISH GRADE

SEE NOTE 1

5/ 8"Øx10 GROUND RODGROUND ALL STEELRACKS, PULL IRON,COVER ETC.

30 CU. FT. OF 1" CRUSHEDROCK

6" DRAIN COVER FLUSH W/DRAIN HOLE

6" COMPACT SAND

6" 6"

36"

48"

4"

POWER

24"DRAIN HOLE (TYPICAL)

6"

18"18"

18"

-B

36"

MAGNETIC TAPE(CFCI)

95% COMPACTION EARTHENBACK FILL (OFOI)

12" MINIMUM

24" MINIMUM

12"

1. PROVIDE/INSTALL UNISTRUT NUTS, STUDNUTS, SCREWS, WASHERS, LOCK WASHERS,ETC. FOR MOUNTING OF UNISTRUTCHANNELS AND PLATES. (CFCI)

5'-0"

24"

AS REQUIRED

PANEL 'HP'(OFCI)

NOTES:

HILTI KWI BOLT TZ ESR-1917 1/2"ø WITH3 1/2" MIN. EMBEDMENT. TWO PERSTRUT. USE STAINLESS STEEL BOTLS.(CFCI)

GROUNDING ELECTRODECONDUCTOR. SIZE PER C.E.C.250.66.

NEUTRAL BUS

GROUND BUSN G

EXISTING SERVICE ENTRANCE EQUIPMENT PANELBOARD OR SWITCH TRANSFORMER PANELBOARD OR SWITCH

NEUTRAL

GENERAL NOTES:

1. SEE ELECTRICAL SINGLE LINE DIAGRAM FORCONDUCTOR AND CONDUIT SIZE.

2. ALL NEUTRAL BUSSES TO BE ISOLATED.

3. PROVIDE SEPARATE GROUND BUS.

4. FERROUS METAL RACEWAYS ANDENCLOSURES FOR GROUNDING ELECTRODECONDUCTORS SHALL BE BONDED AT EACHEND OF THE RACEWAY OR ENCLOSURE TOTHE GROUNDING ELECTRODE ORGROUNDING ELECTRODE CONDUCTOR. C.E.C.250.64(E).

5. A COMMON GROUNDING ELECTRODECONDUCTOR FOR MULTIPLE SEPARATELYDERIVED SYSTEMS SHALL BE PERMITTED FORMEANS OF CONNECTING THE GROUNDEDCONDUCTOR OF EACH SEPARATELY DERIVEDSYSTEM TO THE GROUNDING ELECTRODE.C.E.C. 250.30(A)(6).

SUPPLY SIDEBONDING JUMPER.SIZE PER C.E.C.250.102(C)(1).

NEAREST GROUNDING ELECTRODETO BE ONE OF THE FOLLOWING:

METAL UNDERGROUND WATER PIPE,BUILDING STEEL. PER C.E.C.

250.30(A)(4).

N/G

NEUTRAL

N G

CONDUIT(TYP.)

SUPPLY SIDE BONDINGJUMPER. SIZE PER C.E.C.

250.102(C)

EQUIPMENT GROUNDINGCONDUCTOR. SIZE PER C.E.C. 250.122.

EQUIPMENT GROUNDINGCONDUCTOR. SIZE PER C.E.C. 250.122

GROUND BUS(TYP.)

NEUTRAL

GROUNDING ELECTRODECONDUCTOR. SIZE PER C.E.C. 250.66.

NEUTRAL BUS(TYP.)

BONDING JUMPER TO ALL OF THE FOLLOWING WHEREEXISTS IN THE AREA OF THE SEPARATELY DERIVEDSYSTEM: METAL WATER PIPE, BUILDING STEEL PERC.E.C. 250.104(D). SIZE BONDING JUMPER PER C.E.C.250.66.

SUPPLY SIDEBONDING JUMPER.

SIZE PER C.E.C.250.102(C)(1).

SYSTEM BONDING JUMPER.SIZE PER C.E.C. 250.102(C)(1).

MAIN BOUNDINGJUMPER

SIZE PER C.E.C.250.102(C)(1).

MAIN GROUND BUS INTERSYSTEMBONDING TERMINATION (AS APPLICABLE).REFER TO BUILDING AND GROUNDSYSTEM DETAIL

GROUND ELECTRODE CONDUCTOR TO UFERGROUND (1#4/0 GROUND WIRE TO 20' OR LONGERREBAR IN CONCRETE) CEC 250.52(A)(3).BOND TO BUILDING STEEL. CEC 250.52(A)(2).BOND TO METAL UNDERGROUND WATER PIPE INDIRECT CONTACT WITH EARTH FOR 10' OR LONGERWITHIN 5' OF BUILDING ENTRANCE CEC 250.52(A)(1)& 250.68(C)(1).BOND TO TELECOM SYSTEM EQUIPMENT

RIGID CONDUIT SEE PLAN FORSIZE & QUANTITY (CFCI)

1/2"ØHILTI KB II(ICC# ESR-1917) EXPANSIONANCHORS W/MIN 31

4" EMBEDEACH CORNER, 1 AT EACH CORNER (4TOTAL MIN.) (CFCI)

AS REQUIRED

PANEL 'LP'(OFCI)

4"

6" MIN. TOEDGE OF PAD

PRE-FAB CONCRETE PAD.(CFCI)

P1000 UNISTRUTRACK (CFCI)

GRADE

TO "MTS" TO POWERPEDESTALS

3" MIN.3" MIN.

GRADE

112.5kVA TRANSFORMER(OFCI)

GRC RISER WITH 40MIL TAPE (CFCI)

GRC RISER WITH 40MIL TAPE (CFCI)

RIGID CONDUIT SEE PLAN FORSIZE & QUANTITY (CFCI)

P1000 UNISTRUT POSTAND BASE ASSEMBLEDPER MANUFACTURER'SRECOMMENDATION. (CFCI)

ELECTRICALPANELBOARD (OFCI)

SHD 40 PVC(CFCI)

SHD 40 PVC(CFCI)

COUPLER(CFCI)

COUPLER(CFCI)

POWER BANK - SEEPLAN FOR FOR SIZE

AND QUANTITY(CFCI)

GRC RISER WITH 40MIL TAPE (CFCI)

SHD 40 PVC(CFCI)

COUPLER(CFCI)

25"

6.25"

42"

GRADE

100A 120/208V 1PH 3WPOWER PEDESTAL(OFCI)

GENERAL NOTES:

1. CONTRACTOR SHALL EXTEND CONDUIT AND/ OR ADJUSTTRENCH DEPTH TO SWEEP UNDERNEATH PEDESTAL ASTO MAINTAIN 7" BEND RADIUS OF CABLES.

SCALE: NONE

SCALE: NONE

SCALE: NONE

EARTHEN BACK FILL (OFOI)

PRE-FAB CONCRETE PAD.(CFCI)

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

D

ET

L - 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

ELECTRICAL DETAILS

E3.1

ELECTRICAL SPECIFICATIONSPART 1 GENERAL

1.01 SCOPE OF WORK

A. WORK COVERED BY THIS SECTION CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES, AND MATERIALS, UNLESS OTHERWISE SPECIFIED, ANDIN PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF A COMPLETE AND OPERABLE ELECTRICAL SYSTEM AS REQUIRED BY THESESPECIFICATIONS AND AS INDICATED ON THE DRAWINGS.

B. THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND SPECIFICATIONS IN A MANNER TO BE FULLY COGNIZANT OF ALL WORK REQUIRED UNDER THISSECTION.

1.02 GENERAL REQUIREMENTS

A. WORK DONE UNDER THIS SECTION SHALL COMPLY WITH THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE, NEC (NATIONAL ELECTRICALCODE), THE STATE OF CALIFORNIA TITLE 24, THE STATE BUILDING STANDARDS, (OSHA) OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, AND TOANY APPLICABLE LOCAL JURISDICTIONAL REQUIREMENTS. IN CASE OF CONFLICT BETWEEN REQUIREMENT, THE MOST RESTRICTIVE SHALL APPLY.

1.03 ELECTRICAL CONTRACTOR'S RESPONSIBILITY

A. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS. CONTRACTOR SHALL CHECK THEDRAWINGS OF THE OTHER TRADES AND SHALL CAREFULLY READ THE ENTIRE SPECIFICATIONS AND DETERMINE HIS RESPONSIBILITIES.

B. BEFORE SUBMITTING THE BID, THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FULLY ACQUAINT HIMSELF WITH EXISTING CONDITIONS. ITIS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE EQUIPMENT AND ASSOCIATED WIRING IN SUCH A MANNER AS TO CONFORM WITH THEEXISTING STRUCTURE OF THE BUILDING, AVOID OBSTRUCTIONS, AND MEET APPLICABLE CODE REQUIREMENTS.

C. THE INTENT OF THESE DRAWINGS IS TO DESCRIBE A COMPLETE AND OPERABLE SYSTEM. WHERE EXISTING CONDITIONS DIFFER FROM DRAWINGS,ADJUSTMENT SHALL BE MADE AND ALLOWANCES INCLUDED FOR ALL NECESSARY EQUIPMENT TO COMPLETE ALL PARTS OF THE DRAWINGS ANDSPECIFICATIONS. BRING ANY QUESTIONS TO THE ARCHITECT OR ENGINEER'S ATTENTION PRIOR TO BIDDING.

D. WHEREVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT, DEVICES, CIRCUIT BREAKERS, ETC., ARISES ON THE DRAWINGAND/OR SPECIFICATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THESTRICTEST CONDITION NOTED ON DRAWINGS AND/OR IN SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS AS REQUIRED BY THEOWNER AND ENGINEER.

1.04 WORK NOT INCLUDED

A. CERTAIN LABOR, MATERIALS, OR EQUIPMENT MAY BE FURNISHED UNDER OTHER CONTRACTS BY THE OWNER. WHEN SUCH IS THE CASE, THE EXTENT,SOURCE, AND DESCRIPTION OF THESE ITEMS WILL BE INDICATED ON THE DRAWINGS OR DESCRIBED IN THE SPECIFICATIONS. UNLESS OTHERWISENOTED, ALL LABOR, MATERIALS AND EQUIPMENT FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHALL BE PROVIDED UNDER THISSECTION OF THESE SPECIFICATIONS.

1.05 SPECIAL REQUIREMENTS

A. THE DRAWINGS INDICATE GENERAL ARRANGEMENT OF CIRCUITS, OUTLETS, LOCATIONS OF MOTOR CONTROLLERS WITH DISCONNECTS, PANELBOARDS,CONDUIT ROUTING, AND OTHER WORK. INFORMATION SHOWN ON THE DRAWINGS IS ESSENTIALLY DIAGRAMMATIC; HOWEVER, RECIRCUITING ORRELOCATING ELECTRICAL EQUIPMENT WILL NOT BE PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ENGINEER.

1.06 SUBMITTALS

A. AFTER AWARD OF THE CONTRACT AND BEFORE ANY MATERIALS ARE DELIVERED TO THE JOB SITE, A COMPLETE LIST OF ALL MATERIALS PROPOSED TOBE FURNISHED AND INSTALLED UNDER THIS SECTION MUST BE PROVIDED.

B. SUBMIT TO THE ENGINEER FOR APPROVAL ONE PRINT AND ONE REPRODUCIBLE OF ALL LIGHTING FIXTURES, SWITCHGEAR, PANELBOARDS, MOTORCONTROL CENTERS, TRANSFORMERS, AND MOTOR STARTERS. SHOP DRAWINGS SHALL INCLUDE MANUFACTURER'S PRINTED INFORMATION FOR EACHOF THESE ITEMS IDENTIFIED ON THE DRAWINGS. THE INFORMATION SHALL INCLUDE, AS MINIMUM, OVERALL DIMENSIONS, WEIGHT, PHASE, VOLTAGERATINGS, WIRING DIAGRAMS, AND NAMEPLATE DATA.

1.07 STANDARDS AND MATERIALS

A. ALL MATERIALS SHALL CONFORM WITH THE CURRENT APPLICABLE INDUSTRY STANDARDS, NEMA (NATIONAL ELECTRICAL MANUFACTURER'SASSOCIATION), ANSI (AMERICAN NATIONAL STANDARDS INSTITUTE), IPCEA (INSULATED POWER CABLE ENGINEERS ASSOCIATION), IEEE (INSTITUTE OFELECTRICAL AND ELECTRONIC ENGINEERS), NATIONAL ELECTRICAL SAFETY CODE.

B. UNLESS OTHERWISE INDICATED, ALL MATERIALS SHALL BE UNDERWRITERS LABORATORIES LISTED AND LABELED, OR CERTIFIED BY A NATIONALLYRECOGNIZED TESTING LABORATORY.

C. WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL MECHANICAL EFFICIENCY. DEFECTIVE AND DAMAGED MATERIALSSHALL BE REPLACED OR REPAIRED PRIOR TO FINAL APPROVAL AND ACCEPTANCE. THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE WHENTHEY ARE MORE STRINGENT THAN CODES, STATUTES, OR ORDINANCES IN EFFECT. APPLICABLE CODES, STANDARDS, ORDINANCES, AND STATUTES TAKEPRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH THE DRAWINGS OR SPECIFICATIONS.

1.08 DELIVERY AND STORAGE OF MATERIALS

A. THE CONTRACTOR SHALL INVESTIGATE EACH SPACE IN THE BUILDING THROUGH WHICH EQUIPMENT MUST PASS TO REACH ITS FINAL LOCATIONS. IFNECESSARY, THE MANUFACTURER SHALL BE REQUIRED TO SHIP HIS MATERIAL IN SECTIONS, SIZED TO PERMIT PASSING THROUGH SUCH RESTRICTEDAREAS IN THE BUILDING.

B. THE CONTRACTOR SHALL RETAIN IN HIS POSSESSION AND SHALL BE RESPONSIBLE FOR ALL PORTABLE AND DETACHABLE PARTS OF PORTIONS OFINSTALLATIONS SUCH AS FUSES, KEY LOCKS, ADAPTERS, BLOCKING CLIPS, AND INSERTS UNTIL FINAL COMPLETION OF WORK. THESE PARTS SHALL BEDELIVERED TO THE OWNER UPON COMPLETION OF THE WORK.

PART 2 PRODUCTS

2.01 EQUIPMENT AND MATERIALS

A. ALL MATERIALS FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE NEW, FREE FROM DEFECTS, AND SHALL BE GUARANTEED FOR A PERIODOF ONE (1) YEAR FROM DATE OF ACCEPTANCE OF THE WORK. SHOULD ANY TROUBLE DEVELOP DURING THEIR PERIOD DUE TO DEFECTIVE MATERIALSOR FAULTY WORKMANSHIP, THE CONTRACTOR SHALL FURNISH ALL NECESSARY MATERIALS AND LABOR TO CORRECT THE TROUBLE WITHOUT ANY COSTTO THE OWNER. ANY DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP NOTED AT THE TIME OF INSTALLATION SHALL BE CORRECTED IMMEDIATELY TOTHE SATISFACTION OF THE OWNER.

B. ALL MAJOR EQUIPMENT COMPONENTS SHALL HAVE THE MANUFACTURER'S NAME, ADDRESS, MODEL NUMBER, AND SERIAL NUMBER PERMANENTLYATTACHED IN A CONSPICUOUS MANNER.

2.02 CONDUIT

A. PROVIDE RACEWAYS AS INDICATED ON THE DRAWINGS AND AS HEREIN SPECIFIED. CONDUITS SHALL BE RIGID STEEL "GRC" (THICK WALL) GALVANIZED;ELECTRICAL METALLIC TUBING "EMT" (THIN WALL); FLEXIBLE STEEL, GALVANIZED; LIQUID-TIGHT, FLEXIBLE STEEL CONDUIT WITH GROUND BOND;ALUMINUM CONDUIT; OR SCHEDULE 40 PVC.

B. ALL EMPTY CONDUITS (CO) SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE INDICATED ON THE DRAWING.

C. WHERE CONDUIT CROSSES AN EXPANSION JOINT, PROVIDE APPROVED FITTINGS WHICH ALLOW DEFLECTIONS EQUIVALENT TO TWICE THE MOVEMENTALLOWED BY THE DESIGN.

2.03 CONDUCTORS

A. PROVIDE A COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY SYSTEMS AS SHOWN ON THE DRAWINGS AND THEN HEREIN SPECIFIED.

B. LIGHTING AND POWER CONDUCTORS SHALL BE COPPER, 600 VOLT, TYPE THWN/THHN, NO. 12 MINIMUM UNLESS OTHERWISE NOTED.

C. CONTROL CONDUCTORS SHALL BE 600V, TYPE THWN/THHN, NO.14 MINIMUM SIZE UNLESS OTHERWISE NOTED.

2.04 FITTINGS

A. CONNECTOR, COUPLING, LOCKNUT, BUSHINGS AND CAPS USED WITH RIGID CONDUIT SHALL BE STEEL, THREADED AND GALVANIZED. BUSHINGS SHALL BEINSULATED.

B. EMT FITTINGS, CONNECTORS AND COUPLINGS SHALL BE STEEL, ZINC, OR CADMIUM PLATED, COMPRESSION TYPE, WITH INSULATED THROAT.

C. FLEXIBLE STEEL CONDUIT CONNECTORS SHALL BE TWIST-IN-TYPE WITH INSULATED THROAT. THE FINISH SHALL BE ZINC OR CADMIUM PLATING.

D. EMT CONDUIT FITTINGS SHALL BE THE COMPRESSION TYPE; SET SCREW FITTINGS SHALL NOT BE USED.

2.05 JUNCTION AND PULL BOXES

A. FOR INTERIOR DRY LOCATIONS, BOXES SHALL BE GALVANIZED ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE WITH REMOVABLE, MACHINE SCREWSECURED COVERS.

B. FOR EXTERIOR WET LOCATIONS, BOXES SHALL BE NEMA 3R OR NEMA 4 RATED, GASKET MACHINE SCREW SECURED COVERS.

C. INGROUND PULLBOXES SHALL BE CONCRETE ELECTRICAL PULL BOX WITH LID APPROPRIATE FOR INSTALLATION LOCATION. SIZE PULLBOX PER NECREQUIREMENTS.

D. ALL BOXES SHALL BE SIZED FOR THE NUMBER AND SIZES OF CONDUCTORS AND CONDUITS ENTERING THE BOX AND EQUIPPED WITH PLASTER RINGSWHERE REQUIRED.

2.06 OUTLET BOXES

A. FOR FIXTURES, BOXES SHALL BE GALVANIZED, ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE EQUIPPED WITH 3/8" FIXTURE STUDS AND PLASTER RINGSWHERE REQUIRED.

B. FOR CONVENIENCE OUTLETS, WALL SWITCHES, OR OTHER DEVICES, OUTLET BOXES SHALL BE GALVANIZED ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE4"X4"X1-1/2" MINIMUM.

C. FOR LOCATIONS WHERE STANDARD BOXES ARE NOT SUITABLE, SPECIAL BOXES SHALL BE DESIGNED TO FIT SPACE OR MEET OTHER REQUIREMENTS ANDSUBMITTED FOR APPROVAL.

2.07 SWITCHES

A. ALL DEVICES SHALL CONFORM TO NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) STANDARDS AND SHALL BE UNDERWRITERS'LABORATORIES, INC., (UL) LISTED AND LABELED AND SHALL BE "SPECIFICATION GRADE," MEETING THE REQUIREMENTS OF FEDERAL SPECIFICATIONWS-896-E, FOR SWITCHES.

1. WALL SWITCHES SHALL BE SPECIFICATION COMMERCIAL GRADE (MINIMUM), FULLY ENCLOSED, QUIET-TYPE TUMBLER SWITCHES RATED 20 AMPERES,120/277-VOLT, BAKELITE OR COMPOSITION, BACK AND SIDE WIRED, BUMPER PAD, FULL RATING FOR INDUCTIVE OR NON-INDUCTIVE LOADS ANDINCANDESCENT OR FLUORESCENT LIGHTING LOADS.

2. SINGLE POLE SWITCHES: G.E. 59511, HUBBELL #1221, ARROW #1991 OR PASS & SEYMOUR 20AC1.

3. THREE-WAY QUIET SWITCHES: G.E. 59531, HUBBELL #1223, ARROW #1993 OR PASS& SEYMOUR 20AC3.

4. ALL SWITCHES SHALL BE OF THE SAME MANUFACTURE.

5. 2.10 PANELBOARDS

A. FURNISH AND INSTALL ALL BRANCH CIRCUIT PANELBOARDS AS HEREINAFTER SPECIFIED AND AS SHOWN ON THE DRAWINGS. PANELBOARDS SHALL BEOF THE DEAD FRONT SAFETY TYPE EQUIPPED WITH THE THERMAL MAGNETIC 40°C CIRCUIT BREAKERS.

B. CIRCUIT BREAKERS SHALL BE RATED MINIMUM 10,000 AMPS RMS SYMMETRICAL INTERRUPTING CAPACITY AND SHALL BE THE NUMBER OF POLES ANDCURRENT CAPACITY AS INDICATED ON THE PANEL SCHEDULE. BRANCH CIRCUIT PANELBOARDS SHALL BE SQUARE-D OR EATON/CUTLER HAMMER WITHLUGS UL LISTED FOR USE WITH 75°C WIRE.

C. DOOR SHALL HAVE A PLASTIC COVERED DIRECTORY FRAME WITH A TYPED IDENTIFICATION CARD OR ALL CIRCUIT AND PANEL NUMBERS FOR BRANCH

CIRCUIT PANELBOARDS.

D. PROVIDE NAMEPLATE FOR ALL PANELBOARDS, ENGRAVED WHITE LETTERS ON BLACK BACKGROUND INSTALL NAME PLATES ON THE TRIM ABOVE DOOR.

E. ALL WIRING SHALL BE NEATLY ARRANGED AND LACED TOGETHER.

F. BUS BARS SHALL BE RECTANGULAR IN CROSS SECTION CONSTRUCTED OF COPPER. NEUTRAL AND GROUND BUSES SHALL BE FULL SIZE. 2.11b EXTERIOR LIGHTING FIXTURES

A. FURNISH, INSTALL AND WIRE LIGHTING FIXTURES SCHEDULED OR INDICATED BY TYPE DESIGNATION ON THE DRAWINGS. IF TYPE DESIGNATION ISOMITTED, FIXTURES SHALL BE OF THE SAME TYPE AS SHOWN ON ELECTRICAL DRAWINGS FOR SIMILAR USAGE. VERIFY BEFORE PURCHASE ANDINSTALLATION. NO ALTERNATIVE FIXTURES WILL BE ACCEPTED.

B. LOCATIONS OF FIXTURES ON ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. VERIFY LOCATION AND SPACING WITH LANDSCAPE/CIVIL DRAWINGS ANDOTHER REFERENCE DATA BEFORE PURCHASING. REVIEW SITE CONDITIONS PRIOR TO INSTALLATION.

C. VERIFY ALL FINISHES WITH OWNER, REGARDLESS OF THE CATALOG PREFIXES AND SUFFIXES SHOWN, FURNISH FIXTURES WITH THE PROPER SUPPORTSAND OTHER MISCELLANEOUS APPURTENANCES OR PROPERLY COORDINATE WITH SAID FINISHES.

D. OUTDOOR FIXTURES WITH VENT HOLES SHALL HAVE WIRE MESH SCREENS IN THE VENT HOLES.

E. REPLACE BLEMISHED, DAMAGED OR UNSATISFACTORY FIXTURES AT NO ADDITIONAL COST TO THE OWNER AND IN A MANNER SATISFACTORY TO THEENGINEER.

F. LAMPS

2. LAMPS SHALL BE NEW AND OF WATTAGE AND TYPE INDICATED OR AS REQUIRED FOR THE PARTICULAR FIXTURE INSTALLED.

I. POLES AND BRACKETS

1. FURNISH MOUNTING BRACKETS AND ARMS ASSOCIATED WITH MOUNTING TO POLES AND LUMINAIRES AS AN ASSEMBLY.

J. LED LIGHT FIXTURES

A. GENERAL:

1. LED LIGHT FIXTURES SHALL BE IN ACCORDANCE WITH IES, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND AS SPECIFIED.2. LED LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES (ROHS)-COMPLIANT.3. LED DRIVERS SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED:

a. MINIMUM EFFICIENCY: 85% AT FULL LOAD.b. MINIMUM OPERATING AMBIENT TEMPERATURE: -20 DEG C. (-4 DEG F.)c. INPUT VOLTAGE: 120 - 277V (±10%) AT 60 HZ.

d. INTEGRAL SHORT CIRCUIT, OPEN CIRCUIT, AND OVERLOAD PROTECTION.

e. POWER FACTOR: >=0.95.

f. TOTAL HARMONIC DISTORTION: <=20%.

g. COMPLY WITH FCC 47 CFR PART 15.

4. LED MODULES SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED:

a. COMPLY WITH IES LM-79 AND LM-80 REQUIREMENTS.

b. MINIMUM CRI 80 AND COLOR TEMPERATURE 4000K UNLESS OTHERWISE SPECIFIED IN LUMINAIRE SCHEDULE.

c. MINIMUM RATED LIFE: 50,000 HOURS PER IES L70.

d. LIGHT OUTPUT LUMENS AS INDICATED IN THE LUMINAIRE SCHEDULE.

2.13 CIRCUIT AND MOTOR DISCONNECTS

A. DISCONNECT (SAFETY) SWITCHES SHALL BE FUSED, HEAVY DUTY TYPE SWITCHES MEETING NEMA SPECIFICATIONS. SWITCHES SHALL BE PROVIDED WITHREJECTION TYPE FUSE BLOCKS. PROVIDE SWITCHES WITH THE NUMBER OF POLES, THE VOLTAGE, CURRENT AND HORSEPOWER RATINGS AS REQUIRED.PROVIDE EXTERNALLY OPERABLE QUICK-MAKE, QUICK-BREAK TYPE MECHANISM WITH COVER INTERLOCK AND PADLOCKABLE IN EITHER THE OPEN ORCLOSED POSITION.

B. SWITCHES SHALL BE NEMA 3R (RAIN TIGHT ENCLOSURE) WHERE INDICATED TO BE OUTDOORS WEATHERPROOF.

C. PROVIDE NAMEPLATE INDICATING EQUIPMENT SERVED. ALL GENERAL SNAP SWITCHES OPERATING MOTOR LOADS SHALL BE HORSEPOWER RATED OR BERATED AT LEAST 125% OF THE FULL LOAD CURRENT.

2.14 TRANSFORMERS

A. UNLESS OTHERWISE SPECIFIED, DRY TYPE TRANSFORMERS SHALL BE IN ACCORDANCE WITH NEMA, NEC AND AS SHOWN ON THE DRAWINGS.TRANSFORMERS SHALL BE UL LISTED OR LABELED.

B. DRY TYPE TRANSFORMERS SHALL HAVE THE FOLLOWING FEATURES:

2. SELF-COOLED BY NATURAL CONVECTION, ISOLATING WINDINGS, INDOOR, DRY TYPE. AUTOTRANSFORMERS WILL NOT BE ACCEPTED.

3. RATING SHALL BE AS SHOWN ON THE DRAWINGS.

4. TRANSFORMERS SHALL HAVE COPPER OR ALUMINUM WINDINGS.

5. RATINGS SHOWN ON THE DRAWINGS ARE FOR CONTINUOUS-DUTY WITHOUT THE USE OF COOLING FANS.

6. TRANSFORMERS 30 KVA AND LARGER: UL RATED 220 DEGREES C SYSTEM HAVING AN AVERAGE MAXIMUM RISE BY RESISTANCE OF 150 DEGREES C IN AMAXIMUM AMBIENT OF 40 DEGREES C.

7. TRANSFORMERS BELOW 30 KVA: SAME AS FOR 30 KVA AND LARGER OR UL RATED 185 DEGREES C SYSTEM HAVING AN AVERAGE MAXIMUM RISE BYRESISTANCE OF 115 DEGREES C IN A MAXIMUM AMBIENT OF 40 DEGREES C.

8. PRIMARY AND SECONDARY TAP CONNECTIONS SHALL BE BRAZED OR PRESSURE TYPE.

9. CERTIFIED SOUND LEVELS DETERMINED IN ACCORDANCE WITH NEMA, SHALL NOT EXCEED THE FOLLOWING:

TRANSFORMER RATING SOUND LEVEL RATING0 - 9 KVA 40 DB10 - 50 KVA 45 DB51 - 150 KVA 50 DB151 - 300 KVA 55 DB301 - 500 KVA 60 DB

10. SINGLE PHASE TRANSFORMERS RATED 15 KVA THROUGH 25 KVA SHALL HAVE TWO, 5 PERCENT FULL CAPACITY TAPS BELOW NORMAL RATED PRIMARYVOLTAGE. ALL TRANSFORMERS RATED 30 KVA AND LARGER SHALL HAVE TWO, 2-1/2 PERCENT FULL CAPACITY TAPS ABOVE, AND FOUR, 2-1/2 PERCENTFULL CAPACITY TAPS BELOW NORMAL RATED PRIMARY VOLTAGE.

11. CORE ASSEMBLIES SHALL BE GROUNDED TO THEIR ENCLOSURES BY ADEQUATE FLEXIBLE GROUND STRAPS.

12. OUTDOOR ENCLOSURES SHALL BE NEMA 3R.

13. TEMPERATURE RISE AT HOTTEST SPOT SHALL CONFORM TO NEMA STANDARDS, AND SHALL NOT BAKE AND PEEL OFF THE ENCLOSURE PAINT AFTER THETRANSFORMER HAS BEEN PLACED IN SERVICE.

14. VENTILATION OPENINGS SHALL PREVENT ACCIDENTAL ACCESS TO LIVE COMPONENTS.

C. COPPER COILS - NEUTRALS SHALL CARRY AT LEAST 200% OF NORMAL PHASE CURRENT.

D. MINIMUM EFFICIENCY DESIGNED TO SUPPLY CIRCUITS WITH A HARMONIC PROFILE EQUAL TO OR LESS THAN A K FACTOR OF 13 WITHOUT EXCEEDINGSPECIFIED TEMPERATURE RISE. TRANSFORMERS WITH K FACTOR OF 13 SHALL BE PROVIDED, IF K FACTOR IS NOT SHOWN ON CONTRACT DRAWINGS.TABLE BELOW APPLIES TO K-13 TRANSFORMERS ONLY.

E. INSTALLATION OF TRANSFORMERS SHALL BE IN ACCORDANCE WITH THE NEC, AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER AND AS SHOWNON THE DRAWINGS.

F. INSTALL THE TRANSFORMERS WITH ADEQUATE CLEARANCE AT A MINIMUM OF 6 INCHES FROM WALL AND ADJACENT EQUIPMENT FOR AIR CIRCULATIONTO REMOVE THE HEAT PRODUCED BY TRANSFORMERS.

G. TRANSFORMERS SHALL MEET THE DOE ENERGY EFFICIENCY REQUIREMENTS LISTED IN 10 CFR 431.

2.15 ELECTRICAL CONNECTIONS

A. UNLESS OTHERWISE NOTED, ALL WIRING FOR MOTORS, STARTERS, CONTROLS, AND EQUIPMENT SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.WHERE MOTORS FOR MECHANICAL EQUIPMENT ARE FURNISHED BY OTHER DIVISIONS, WIRING SHALL BE THE RESPONSIBILITY OF THE ELECTRICALCONTRACTOR, EXCEPT WHERE WIRED INTEGRALLY WITH THE EQUIPMENT.

2.16 SUPPORTING DEVICES

A. ALL EQUIPMENT CONDUITS SHALL BE SUPPORTED, ANCHORED AND BRACED IN ACCORDANCE WITH THE MOST STRINGENT CODES AND REQUIREMENTS.COMPLY WITH CHAPTER 23 OF THE LATEST CBC (CALIFORNIA BUILDING CODE).

PART 3 EXECUTION

3.01 WORKMANSHIP AND COMPLETION OF INSTALLATION

A. WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL AND MECHANICAL EFFICIENCY. DEFECTIVE AND DAMAGEDMATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL INTERPRETATIONS INCLUDED. ANY DEFICIENCY PERTAINING TO EITHER WORKMANSHIPOR MATERIALS FOUND BY THE OWNER/ENGINEER SHALL BE CORRECTED WITHOUT ADDITIONAL COST TO THE OWNER.

B. THE CONTRACTOR SHALL MAINTAIN ON JOB SITE A SET OF THE WORKING DRAWINGS WHICH SHALL BE UPDATED DAILY IN DETAIL FOR WORKACCOMPLISHED. UPON COMPLETION OF THE WORK, A SET OF REPRODUCIBLE CONTRACT DRAWINGS SHALL BE OBTAINED FROM THE GENERALCONTRACTOR AND ALL CHANGES AS NOTED ON THE RECORD SET OF PRINTS SHALL BE INCORPORATED THEREON WITH RED INK IN A NEAT, LEGIBLE,UNDERSTANDABLE AND PROFESSIONAL MANNER.

C. ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY CLEANED, AND ALL RESIDUE REMOVEDFROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHEDCONDITION.

3.02 PREPARATION COORDINATION.

A. THE CONTRACTOR SHALL COORDINATE THIS WORK WITH ALL OTHER CONTRACTORS FURNISHING LABOR, MATERIALS AND WORK, SO THAT THE WORK ASWHOLE SHALL BE EXECUTED AND COMPLETED WITHOUT CONFLICT OR DELAY.

B. EXAMINE THE DRAWINGS AND SPECIFICATIONS AND DETERMINE THE WORK TO BE PERFORMED BY THE ELECTRICAL, MECHANICAL AND OTHER TRADES.PROVIDE THE TYPE AND AMOUNT OF ELECTRICAL MATERIALS AND EQUIPMENT NECESSARY TO PLACE THIS WORK IN PROPER OPERATION, COMPLETELYWIRED TESTED AND READY FOR USE. THIS SHALL INCLUDE ALL CONDUIT, WIRE, DISCONNECTS, RELAYS, AND OTHER DEVICES FOR THE REQUIREDOPERATION SEQUENCE OF ALL ELECTRICAL, MECHANICAL, AND OTHER SYSTEMS OR EQUIPMENT.

C. PERFORM ALL WORK IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO THE OCCUPANTS, NOR INTERFERE WITH THEACTIVITIES IN THE AREA.

D. THE CONTRACTOR SHALL COORDINATE AND SCHEDULE EACH POWER INTERRUPTION WITH OWNER, AND SHALL PROVIDE AT LEAST TWO WEEKS NOTICEOF PROPOSED INTERRUPTION AND WORK TO BE ACCOMPLISHED.

3.03 TRENCHING AND BACKFILLING

A. OWNER SHALL PERFORM ALL SUCH TRENCHING AND BACKFILLING IN ACCORDANCE WITH DRAWING DETAILS.

3.05 INSTALLATION

A. WORKMANSHIP IS TO BE NEAT, BY EXPERIENCED WORKMEN WITH ADEQUATE SUPERVISION, AND IN LINE WITH NORMAL INDUSTRY WORK PRACTICES.

B. MAINTAIN WORKING CLEARANCE AROUND ELECTRICAL EQUIPMENT, IN ACCORDANCE WITH CODE REQUIREMENTS AS A MINIMUM.

C. WHERE LIGHTING FIXTURES AND OTHER ELECTRICAL ITEMS ARE SHOWN IN CONFLICT WITH LOCATIONS OF STRUCTURAL MEMBERS AND MECHANICAL OROTHER EQUIPMENT, FURNISH AND INSTALL ALL REQUIRED SUPPORTS AND WIRING TO CLEAR THE ENCROACHMENT.

D. VERIFY LOCATION OF EACH OUTLET FOR POWER AND EACH LIGHTING FIXTURE WITH OWNER PRIOR TO ROUGH-IN. INCLUDE IN BID COST OF RELOCATINGEACH ITEM WITHIN TEN-FEET RADIUS OF ITS INDICATED LOCATION.

E. ALL CONDUIT TO BE RUN CONCEALED UNLESS OTHERWISE NOTED. NO CONDUITS SHALL BE PERMITTED IN CONCRETE SLAB, MASONRY WALLS UNLESSSPECIFICALLY SO INDICATED. CONDUIT SHALL BE RUN SO AS NOT TO INTERFERE WITH OTHER PIPING FIXTURES OR EQUIPMENT.

F. WHERE ALLOWED, EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS, OR INTERSECTIONOF VERTICAL PLANES AND CEILINGS.

G. ALL POWER WIRING SHALL BE INSTALLED IN CONDUIT UNLESS NOTED OTHERWISE.

H. ALL WIRES FOR ALL SYSTEMS SHALL BE CONTINUOUS FROM SWITCH TO TERMINAL OR FURTHEST OUTLET. NO JOINTS SHALL BE MADE EXCEPT IN PULL,JUNCTION OR OUTLET BOXES, OR IN PANEL OR SWITCHBOARD GUTTERS.

3.06 GROUNDING

A. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AS INDICATED ON DRAWINGS AND AS REQUIRED BY THE LATEST EDITION OF APPLICABLE CODES.

B. FURNISH AND INSTALL ALL GROUNDING CONDUCTORS, CONDUIT AND CLAMPS. THE SIZE OF THE GROUNDING CONDUCTORS SHALL BE NOT LESS THANTHAT SPECIFIED IN THE NEC.

C. BUILDING GROUNDING SYSTEM RESISTANCE TO GROUND SHALL NOT EXCEED 25 OHMS.

D. EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH CODE SIZE GREEN GROUND, EQUIPMENT WIRE (PER NEC 250-95) (NOT INDICATED ON DRAWINGS)WITHIN THE SAME CONDUIT FOR ALL CIRCUITS OF PANELBOARDS.

3.07 BRANCH CIRCUITS

A. NO MORE THAN THREE BRANCH CIRCUITS PERMITTED IN ONE CONDUIT UNLESS INDICATED OTHERWISE

3.08 IDENTIFICATION

A. THE FOLLOWING ITEMS SHALL BE EQUIPPED WITH NAMEPLATES:

1. ALL MOTORS, MOTOR STARTERS, CONTROL PANELS, MOTORS CONTROL REMOTE STATIONS.

2. ALL DISCONNECT AND SAFETY SWITCHES, MAIN DISTRIBUTION PANEL FEEDER OVERCURRENT DEVICES AND SPARES, CIRCUIT EQUIPMENT IN SEPARATEENCLOSURES.

3. SPECIAL ELECTRICAL SYSTEMS SHALL BE PROPERLY IDENTIFIED AT JUNCTION AND PULL BOXES

4. ALL BRANCH CIRCUIT PANEL BOARDS SHALL HAVE IDENTIFYING ENGRAVED PLASTIC NAMEPLATES. ALSO, PROVIDE A TYPED DIRECTORY CARD FOR EACHBRANCH CIRCUIT PANELBOARD. THE CARD IS TO BE PLACED ON THE INTERIOR SIDE OF THE PANELBOARD DOOR BEHIND A CLEAR PLASTIC SHIELD. THECARD SHALL IDENTIFY EACH CIRCUIT BY NUMBER, LOAD, AND LOCATION.

5. IN GENERAL, EQUIPMENT SHALL BE IDENTIFIED AS DESIGNATED ON THE ELECTRICAL DRAWINGS. NAMEPLATES FOR PANELBOARDS AND SWITCHBOARDSSHALL INCLUDE THE PANEL DESIGNATION, VOLTAGE AND PHASE OF THE SUPPLY. THE NAME OF THE MACHINE SHALL BE THE SAME AS THE NAME USEDON ALL MOTOR STARTERS, DISCONNECTS, AND P.B STATION NAMEPLATES FOR THAT MACHINE.

B. NAMEPLATES SHALL BE FABRICATED AS FOLLOWS:

1. NAMEPLATE MATERIALS SHALL CONSIST OF 3-PLY, 1/16" LAMINATED PLASTIC WITH WHITE CORE FOR LETTERING AND BLACK BACKGROUND.

2. CAPITAL LETTERS SHALL BE USED.

3. NAMEPLATES SHALL BE FASTENED WITH CADMIUM-PLATED SELF-TAPPING NO. 6 SCREWS 1/4" LONG

4. THE MINIMUM SIZE OF ALL NAME PLATES AND LETTERING SHALL BE 3/4" HIGH BY 2" LONG WITH 1/4" LETTERS.

3.09 PROTECTION

A. USE ALL MEANS NECESSARY TO PROTECT THE WORK AND MATERIALS FROM LOSS DURING AND AFTER INSTALLATION, AND PROVIDE ADEQUATE ANDPROPER STORAGE FACILITIES DURING THE PROGRESS OF THE WORK. PROVIDE FOR THE SAFETY AND GOOD CONDITION OF ALL WORK UNTIL FINALACCEPTANCE OF THE WORK BY THE OWNER. REPLACE ALL DAMAGE OR DEFECTIVE WORK, MATERIAL, AND EQUIPMENT AT NO EXPENSE TO THE OWNERBEFORE REQUESTING FINAL ACCEPTANCE.

3.10 CLEANING OF EQUIPMENT, MATERIAL, AND PREMISES

A. SITE SHALL BE LEFT BROOM CLEAN AFTER COMPLETION OF WORK EACH DAY. UPON COMPLETION OF THE WORK, LEAVE THE PREMISES CLEAN OF ALLDIRT AND DEBRIS.

B. ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY CLEANED, AND ALL RESIDUE REMOVEDFROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHEDCONDITION.

3.11 HANDLING OF WIRE AND CABLE

A. HANDLE WIRE AND CABLE SO AS TO AVOID DAMAGE TO CONDUCTORS AND TAKE EVERY PRECAUTION TO AVOID SHARP BENDING OR SCORING OF THECABLE. CABLE SHALL NOT BE LAID NOR DRAGGED UPON THE GROUND.

B. THE CONTRACTOR SHALL BE REQUIRED TO REMOVE AND REPLACE AT HIS OWN EXPENSE ALL WIRE AND CABLE DAMAGED DUE TO IMPROPER HANDLING,AND SHALL PAY FOR THE NEW WIRE OR CABLE.

3.12 TESTING

A. THE CONTRACTOR SHALL REPLACE ALL DAMAGED OR DEFECTIVE EQUIPMENT OR WORK.

B. ALL CIRCUITS SHALL BE TESTED FOR CONTINUITY AND CIRCUIT INTEGRITY BY THE CONTRACTOR. ADJUSTMENTS SHALL BE MADE FOR CIRCUITS NOTCOMPLYING WITH TESTING CRITERIA.

1

2

3

4

5

7

PR

OJE

CT

F

OR

:

EM

PL

OY

EE

C

AM

PA

IG

N

31

12

5 IR

ON

WO

OD

A

VE

NU

E

MO

RE

NO

V

AL

LE

Y, C

A 9

25

55

6

San Bernardino, CA 92408275 W. Hospitality Lane, Suite #100 Phone: 909-890-3700

Fax: 909-890-3770Email: [email protected]

DESIGN WEST ENGINEERINGMECHANICAL ELECTRICAL ENERGY CONSULTANTS

R:\_

PR

OJE

CT

\2

02

0\2

0-0

63

U

NIT

ED

W

AY

E

VE

NT

, C

OU

NT

Y O

F R

IV

ER

SID

E\2

0-0

63

E

S

PE

CS

- 2

02

0-0

4-0

1 - JE

FF

M

UL

LE

NA

X

RIV

ER

SID

E C

OU

NT

Y

FU

ND

RA

IS

ER

E

VE

NT

03/16/2020 JWM PRELIMINARY ELECTRICAL

03/19/2020 JWM FINAL ELECTRICAL

BA

DL

AN

DS

L

AN

DF

IL

L

ELECTRICAL

SPECIFICATIONS

E4.1