14
L-IOB Integration 19th October 2011, 14:40 LOYTEC electronics GmbH Alexander Bauer

20111019 1440 L-IOB Integration - LOYTEC … · NTC / PTC / Translation Table ... Microsoft PowerPoint - 20111019_1440_L-IOB_Integration.ppt Author: kpoeltl Created Date: 10/21/2011

Embed Size (px)

Citation preview

L-IOB Integration

19th October 2011, 14:40

LOYTEC electronics GmbHAlexander Bauer

Page 2LOYTEC electronics GmbH ©2011

Presenter

DI Alexander BauerResearch and developmentWith LOYTEC since 2000Product manager for

L-IOB product familyNIC709 / NIC852 / NIC-IP NIC & LPA software

ResponsibilitiesQuality management in R&DSoftware development tools

Page 3LOYTEC electronics GmbH ©2011

L-IOB I/O Module

Key featuresDevice modesModelsUser interfacesDemonstration

Overview

Page 4LOYTEC electronics GmbH ©2011

L-IOB Key Features

Universal inputs, digital inputsAnalog outputs, relays, triacs128 x 64 display with backlightManual operation using jog dialSimple device replacementSeamless integration with L-INX and L-ROC devicesStand-alone CEA-709 mode with LONMARK® certification

Page 5LOYTEC electronics GmbH ©2011

L-IOB I/O Types

UI - Universal input: 0-10VDigital: sampling rate 10msVoltage: 0-10V, sampling rate 1sCurrent: 4-20mA, sampling rate 1sResistance: 1-100kΩ, sampling rate 1s

DI - Digital input (S0)AO - Analog output: 0-12V, 10mADO - Digital output:

Relay: 6A or 16A, 250 VAC / 30 VDCTriac: 1A, 24-230 VAC

Page 6LOYTEC electronics GmbH ©2011

L-IOB Signal Interpretations

Digital and Linear Analog ModesNTC / PTC / Translation TableFrequency / Frequency Table

Pulse Count / Physical Unit CountOccupancyPulse Width Modulation (PWM)Interlocked Mode

Page 7LOYTEC electronics GmbH ©2011

LIOB-Connect Mode

Easy snap-in connection with L-INX or L-ROC devices

Required if Length > 1 m

4

Length < 50 m

...

...

Max. 4 1 4

Max. 4 5 8

Page 8LOYTEC electronics GmbH ©2011

LIOB-FT Mode

Up to 500m in free topology

2

1 2 3 4

LT-33 free

topology

8 7 6 5

24V 24V 24V 24V

Max. 4

Page 9LOYTEC electronics GmbH ©2011

Stand-alone operationLONMARK® certified interfacechangeable NV typesEasy integration into any existingCEA-709 networkGroup network variables for fast digital I/O accessSwitch mode for light andsunblind buttons

L-IOB LONMARK® Mode

Page 10LOYTEC electronics GmbH ©2011

L-IOB Models

5 (5 x Relay 16 A)8 (8 x Relay 6 A)-9 (5 x Relay 6 A,4 x Triac)

Digital Output (DO)

66-2Analog Output (AO)

--162Digital Input (DI)

6688Universal Input (UI)

LIOB-103LIOB-102LIOB-101LIOB-100

5 (4 x Relay 16 A, 1 x Relay 6 A)

8 (8 x Relay 6 A)-8 (4 x Relay 6 A,4 x Triac)

Digital Output (DO)

66-2Analog Output (AO)

--122Digital Input (DI)

6688Universal Input (UI)

LIOB-153LIOB-152LIOB-151LIOB-150

Page 11LOYTEC electronics GmbH ©2011

L-IOB User Interfaces

Local access via L-IOB LCD UIL-INX / L-ROC LCD UI with full remote access to L-IOB devicesL-INX / L-ROC Web UI (LIOB page)Configurator for I/O setup

Page 12LOYTEC electronics GmbH ©2011

AHU Demo Setup

Page 12

Global Connection

KNX IP

ZigBee

OPC XML/DA

Modbus

M-Bus

CEA-709

BACnet/IP

Page 13LOYTEC electronics GmbH ©2011

Demo Application

Same configuration in all modesLIOB-Connect/FT modes (L-INX / L-ROC)LONMARK® mode (Stand-alone LIOB-15X)

Setup of L-IOB functionsDevice settings (name, pin code, etc.)I/O settings (signal interpretation, etc.)Localization, alternative unit

Device & I/O TemplatesData point setupTest with LCD UI and Web UI

Thank you for your attention!

LOYTEC electronics GmbHAlexander BauerBlumengasse 351170 Vienna, Austria

Phone: +43 (1) 4020805-0Fax +43 (1) 4020805-99Email: [email protected]: www.loytec.com