1
Advantys STBApplication Note
Everett Kimball
How to use Advantys STB with a Micrologix 1500 + DeviceNet scanner
3
Advantys STBApplication Note
Everett Kimball
• By using the Advantys configuration software it is very simple to export a configuration specific Island node into RSNetWorx for use with Rockwell masters.The complexity of the island does not matter,whether you have CANext devices such as drives or valve blocks ,regular island extensions or HMI words the configured exported file contains all the data with the proper transmission type already chosen. This makes integration a simple export (out of the Advantys Configuration Software) followed by a simple 1 file import (into RSNetWorx) there by saving lots of commissioning and configuration time and effort.
4
Advantys STBApplication Note
Everett Kimball
• For this example we used the following Advantys STB hardware
1. NDN2212 Devicenet NIM2. PDT 3100 24vdc3. STBDDI3725 16 channel discrete
input4. STBDDO3705 16 channel discrete
output5. STBART0200 2 channel RTD input6. STBACO1225 2 channel 4-20mA
output7. XMP100 termination plate 8. XBE2100 CANext connected via
CAN open to the ATV31 VFD
5
Advantys STBApplication Note
Everett Kimball
• After assembling the modules in the Advantys Configuration software and performing a successful build, we can now export this configuration as a single file to be placed into RSNetWorx (this same export can be used with other manufacturers masters as well as the Sycon configuration software)
• Under the edit tab you find the export utility with the name of the Island file you are going to export (in this case the Island is named “integration”)
6
Advantys STBApplication Note
Everett Kimball
• Now choose a path to export the EDS file to.
• Some Masters have character limits on the title of an EDS so you can choose to use a short file descriptor
• Click the ok button and your configuration specific file will export to your designated path
9
Advantys STBApplication Note
Everett Kimball
From RS Networx chooseThe EDS Wizard and register The exported node specific EDS file from the Advantys Configuration software
10
Advantys STBApplication Note
Everett Kimball
Register the EDS as a singleFile. Browse for the path and Click next
12
Advantys STBApplication Note
Everett Kimball
This will place the node specificEDS file of our sample island intoThe” Communication Adapters”Sub folder in the catalog section
13
Advantys STBApplication Note
Everett Kimball
This will check the file for errorsBefore registering
14
Advantys STBApplication Note
Everett Kimball
From RSNetWorx choose your Scanner Module. In this case we will choose the 1769-SDN for the Micrologix 1500 PLC. The steps that follow would be similar for any other Rockwell Master chosen.
15
Advantys STBApplication Note
Everett Kimball
Now choose the importedEDS file. We know thatThis configuration had 18 Bytes of input and 10 bytesOf output data
16
Advantys STBApplication Note
Everett Kimball
Double click on the Scanner moduleAnd add the Advantys node to the Scan list and you are done
17
Advantys STBApplication Note
Everett Kimball
Here is the output data from our node in word formatAbove.(The numeration corresponds to the addressOf the Advantys modules on the backplane ,32Being the ATV31)
18
Advantys STBApplication Note
Everett Kimball
Here is our input data form our node in word format (the numeration corresponds to the module location on the Advantys backplane ,S is for Devicenet status word And 32 is the ATV31)