Trame Rapport
Page 22/30
Hng PhmPhone: 01649397068Mobile:
Installation calculation report
New_projectFull
Project information
Name:capdienhathekhuvucnhatro
Place:hanoi
Customername:-
Revision:-
Content41Project description
41.1Project general settings
41.2Settings for wiring device calculation
41.3List of loads
62Installation general design
62.1List of devices
143Calculation notes
143.1Source circuits
233.2Generator circuits
233.3LV Source circuits
243.4UPS circuits
243.5Surge Arrester circuits
243.6Capacitor bank circuits
243.7Feeder circuits
253.8LV Transformer circuits
273.9Couplers circuits
273.10Generic load circuits
273.11Lighting load circuits
283.12Power socket load circuits
283.13Motor starter combination
293.14Busbar circuits
293.15Busbar trunking system circuits
293.16Busbar trunking system circuits
293.17Lighting Busbar trunking system circuits
1 Project description
1.1 Project general settingsInstallation standardIEC60364
Calculation standardTR50480
Circuit breaker standardIEC 60947-2
Frequency50 Hz
1.2 Settings for wiring device calculationMaximal CSA300 mm
1.3 List of loads
1.3.1 Generic loadsNameSr (kVA)Pr (kW)Ir (A)CosNbrPolarityNon linear loadTHDi 3 (%)
AA 171.821.827.871161Ph+NNo0
AA 31114.33111Ph+NNo0
AA 17 (1)1.821.827.871161Ph+NNo0
AA 17 (1) (1)1.821.822.621163Ph+NNo0
1.3.2 Power socketsNameSr (kVA)Pr (kW)Ir (A)CosNbrPolarityNon linear loadTHDi 3 (%)
AA 133.683.6815.9111Ph+NNo0
AA 253.683.6815.9121Ph+NNo0
1.3.3 Lighting distribution
NameType of lampP Lamp (W) P ballast (W)Nb of lamp/lightNb of light
EA 6Metal iodine704.519
EA 7Metal iodine704.519
EA 8Metal iodine704.519
EA 9Fluorescent with electronic ballast364.515
EA 10Fluorescent with electronic ballast364.515
EA 11Fluorescent with electronic ballast184.5110
EA 12Fluorescent with electronic ballast184.5110
EA 18Fluorescent with electronic ballast364.516
EA 20Metal iodine704.514
EA 18 (1)Fluorescent with electronic ballast364.516
EA 18 (1) (1)Fluorescent with electronic ballast364.516
1.3.4 Motor loadsNameSr (kVA)Pr (kW)Ir (A)CosNbrPolarityNon linear loadTHDi 3 (%)
MA 302.492.123.60.8513PhNo0
2 Installation general design2.1 List of devices2.1.1 MV/LV transformer
NameNbrRangeInsulationSr (kVA)ukrT (%)ConnectionU2 (V)SEARb (m)
TA 01TrihalDry-type1606D420TN-S10000
2.1.2 LV switchboards and busbarSwitchboard nameRangeRating (A)IP
UC 2No preference0.00Undefined
UC 5No preference0.00Undefined
UC 16No preference0.00Undefined
UC 22No preference0.00Undefined
UC 29No preference0.00Undefined
UC 16 (1)No preference0.00Undefined
UC 16 (1) (1)No preference0.00Undefined
Busbar nameSwitchboard nameKsPolaritySEAEquipotential bounding
WC 1UC 213Ph+NTN-SWith
WC 4UC 513Ph+NTN-SWithout
WC 15UC 1613Ph+NTN-SWithout
WC 21UC 2213Ph+NTN-SWithout
WC 28UC 2913Ph+NTN-SWithout
WC 15 (1)UC 16 (1)13Ph+NTN-SWithout
WC 15 (1) (1)UC 16 (1) (1)13Ph+NTN-SWithout
2.1.3 Circuit breakerNameNbrRange - DesignationRating (A)PolesTrip unit/CurveRCDRCD class
QA 01Compact NSX - NSX250B2504P4dMicrologic 5.2 ARH197PA
QA 31Acti9 iC60 - iC60N164P4dCRH99MA
QA 61Acti9 iC60 - iC60N42P1dCRH99MA
QA 71Acti9 iC60 - iC60N42P1dCRH99MA
QA 81Acti9 iC60 - iC60N42P1dCRH99MA
QA 91Acti9 iC60 - iC60N12P1dCRH99MA
QA 101Acti9 iC60 - iC60N12P1dCRH99MA
QA 111Acti9 iC60 - iC60L1.62P2dCRH99MA
QA 121Acti9 iC60 - iC60L1.62P2dCRH99MA
QA 131Acti9 iC60 - iC60N162P1dCRH10MA
QA 141Acti9 iC60 - iC60N324P4dCRH99MA
QA 1716Acti9 iC60 - iC60N102P1dCRH10MA
QA 181Acti9 iC60 - iC60L1.62P2dCRH99MA
QA 191Acti9 iC60 - iC60N164P4dCRH99MA
QA 201Acti9 iC60 - iC60L1.62P2dCRH99MA
QA 252Acti9 iC60 - iC60N162P1dCRH10MA
QA 271Acti9 iC60 - iC60N104P4dCRH99MA
QA 301Acti9 P25M - P25M43P3dMRH10MA
QA 311Acti9 iC60 - iC60N62P1dCRH10MA
QA 17 (1)16Acti9 iC60 - iC60N102P1dCRH10MA
QA 18 (1)1Acti9 iC60 - iC60L1.62P2dCRH99MA
QA 14 (1)1Acti9 iC60 - iC60N324P4dCRH99MA
QA 17 (1) (1)16Acti9 iC60 - iC60N34P4dCRH10MA
QA 18 (1) (1)1Acti9 iC60 - iC60L1.62P2dCRH99MA
QA 14 (1) (1)1Acti9 iC60 - iC60N324P4dCRH99MA
2.1.4 Transmission busbar trunking system scheduleNameNbrIncomerFeederL (m)RangeRating (A)
WD 31QA 3WC 43KTC1000
WD 141QA 14WC 154KTC1000
WD 191QA 19WC 214KTC1000
WD 14 (1)1QA 14 (1)WC 15 (1)4KTC1000
WD 14 (1) (1)1QA 14 (1) (1)WC 15 (1) (1)4KTC1000
2.1.5 Cable scheduleNameNbrIncomerFeederTypeInsulationL (m)L1/L2/L3NPE/PEN
WD 01TA 0QA 0Multi-coreXLPE3002x185 Copper2x185 Copper 1x185 Copper
WD 121QA 12EA 12Multi-corePVC201x1.5 Copper1x1.5 Copper 1x4 Copper
WD 101QA 10EA 10Multi-corePVC201x1.5 Copper1x1.5 Copper 1x4 Copper
WD 81QA 8EA 8Multi-corePVC171x1.5 Copper1x1.5 Copper 1x4 Copper
WD 71QA 7EA 7Multi-corePVC171x1.5 Copper1x1.5 Copper 1x4 Copper
WD 61QA 6EA 6Multi-corePVC171x1.5 Copper1x1.5 Copper 1x4 Copper
WD 311QA 31AA 31Multi-coreXLPE101x1.5 Copper1x1.5 Copper 1x4 Copper
WD 201QA 20EA 20Multi-corePVC101x1.5 Copper1x1.5 Copper 1x4 Copper
WD 131QA 13AA 13Multi-corePVC101x2.5 Copper1x2.5 Copper 1x4 Copper
WD 111QA 11EA 11Multi-corePVC71x1.5 Copper1x1.5 Copper 1x4 Copper
WD 91QA 9EA 9Multi-corePVC71x1.5 Copper1x1.5 Copper 1x4 Copper
WD 18 (1) (1)1QA 18 (1) (1)EA 18 (1) (1)Multi-corePVC51x1.5 Copper1x1.5 Copper 1x4 Copper
WD 17 (1) (1)16QA 17 (1) (1)AA 17 (1) (1)Multi-corePVC51x1.5 Copper1x1.5 Copper 1x4 Copper
WD 18 (1)1QA 18 (1)EA 18 (1)Multi-corePVC51x1.5 Copper1x1.5 Copper 1x4 Copper
WD 17 (1)16QA 17 (1)AA 17 (1)Multi-corePVC51x1.5 Copper1x1.5 Copper 1x4 Copper
WD 301QA 30MA 30Multi-coreXLPE51x1.5 Copper1x4 Copper
WD 271QA 27WC 28Multi-coreXLPE51x1.5 Copper1x1.5 Copper 1x4 Copper
WD 252QA 25AA 25Multi-corePVC51x2.5 Copper1x2.5 Copper 1x4 Copper
WD 181QA 18EA 18Multi-corePVC51x1.5 Copper1x1.5 Copper 1x4 Copper
WD 1716QA 17AA 17Multi-corePVC51x1.5 Copper1x1.5 Copper 1x4 Copper
2.1.6 MV CableNameNbrDesignationCSA (mm)Icc (A)In (A)Un (kV)
MVWD 01NA1 x 185 Al16.435324
3 Calculation notes3.1 Source circuits3.1.1 Circuit Source 0MV power supplyW 0
Max. upstream short circuit power500 MVA
Min. upstream short circuit power100 MVA
MV CableMVWD 0
Parameters
Length10 m
Type of cableSingle core
Ib5 A
Nb of conductor per phase1
Cross section area1 x 185 Al mm
CoreAluminium
Short circuit withstand16.4 kA
Assigned voltage20 kV
Insulation voltage24 kV
MV/LV transformerTA 0
RangeTrihal
TechnologyDry-type
Rated power160 kVA
ukrT6 %
Type of lossesNormal
PkrT2.35 kW
System earthing arrangementTN-S
MV ConnectionD
LV Connectionyn
No load secondary voltage Ur0420V
Ur LV400V
Rb (neutral grounding)NA
Ra (mass grounding)NA
Sizing informationUkrT and PkrT calculated by system
CableWD 0
Parameters
Length300 m
Max lengthNA
Installation method31EMulti-core cables on vertical perforated tray
Type of cableMulti-core
Nb of additional touching circuits0
InsulationXLPE
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib231 A
Sizing constraintVoltage drop
The CSA of cable WD 0 has been increased from 35 to 2*185 to comply with the voltage drop in the circuit.
Sized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor0.88
Standard table referenceB-52-20
User correction factor1
Overall factor0.88
Selected phase
Cross section area2x185 mm
CoreCopper
Iz under real conditions803 A
Selected neutral
Cross section area2x185 mm
CoreCopper
Iz under real conditions803 A
Selected PE
Cross section area1x185 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.823.313.822.171.982.500.00
Synthesis for all operating mode
(kA)3.823.313.822.171.982.500.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Circuit breakerQA 0
Ib231 A
Distance from originNA
Sizing InformationSized by system
RangeCompact NSX
DesignationNSX250B
Circuit breaker rating250 A
Breaking capacity25 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationMicrologic 5.2 A
Trip unit rating250 A
Long delay settings
Ir231 A
Tr16 s
Short delay settings
Isd current1502 A
Tsd0 s
Instantaneous tripping
Ii current3000 A
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
NADiscrimination can't be determinated : no upstream Lv Breaker
RCD designationRH197P
ClassA
In30000 mA
Break Time4.7 s
t4.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 1281.00] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
NADiscrimination not analyzed
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)66.62976.47666.34010
Synthesis for all operating mode
(A)66.62976.47666.34010
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9571.957
UL1L2 (%)2.2592.259
UL2L3 (%)2.2662.266
UL3L1 (%)2.2652.265
UL1N (%)1.9561.956
UL2N (%)1.9571.957
UL3N (%)1.9681.968
3.2 Feeder circuits3.2.1 Circuit Feeder circuit 27Circuit breakerQA 27
Ib7.14 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating10 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating10 A
Long delay settings
Ir10 A
TrNA
Short delay settings
Isd current80 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0NSX250BMicrologic 5.2 A250 A / 4P4dFull Discrimination
RCD designationRH99M
ClassA
In10000 mA
Break Time1.2 s
t1 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 667.87] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH197P (QA 0)Full Discrimination
CableWD 27
Parameters
Length5 m
Max lengthNA
Installation method31EMulti-core cables on horizontal perforated tray
Type of cableMulti-core
Nb of additional touching circuits0
InsulationXLPE
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib7 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-20
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions23 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions23 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.541.370.951.340.00
Synthesis for all operating mode
(kA)3.072.662.541.370.951.340.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Design current
IL1 IL2IL3IN
Operating mode Normal
(A)3.6003.6007.1373.54
Synthesis for all operating mode
(A)3.6003.6007.1373.54
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.1950.238
UL1L2 (%)2.3800.121
UL2L3 (%)2.4640.198
UL3L1 (%)2.4630.198
UL1N (%)2.1810.226
UL2N (%)2.1830.226
UL3N (%)2.3270.359
3.2.2 Circuit Feeder circuit 3Circuit breakerQA 3
Ib15.9 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating16 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating16 A
Long delay settings
Ir16 A
TrNA
Short delay settings
Isd current128 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0NSX250BMicrologic 5.2 A250 A / 4P4dFull Discrimination
RCD designationRH99M
ClassA
In10000 mA
Break Time1.2 s
t1 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 1254.29] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH197P (QA 0)Full Discrimination
Transmission buswayWD 3
Parameters
Length3 m
Max lengthNA
Installation methodStandard
Ambient temperature35 C
Level of third harmonic THDI0 %
Ib16 A
Sizing InformationSized with Ir
Correction factors
Temperature factor 1
Installation method factor 1
Type of protection factor 1
User defined factor1
Selected busway
DesignationKTC1000
Rating1000
PE typeStandard PE
IP55
IK08
CoreCopper
Icw50 kA
Ip110 kA
Reinforced short circuit withstandNA
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.542.222.082.510.00
Synthesis for all operating mode
(kA)3.072.662.542.222.082.510.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Design current
IL1 IL2IL3IN
Operating mode Normal
(A)3.22615.9353.65112.5
Synthesis for all operating mode
(A)3.22615.9353.65112.5
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9580.001
UL1L2 (%)2.2590.001
UL2L3 (%)2.2670.001
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)1.9590.002
UL3N (%)1.9680.001
3.2.3 Circuit Feeder circuit 14Circuit breakerQA 14
Ib28.3 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating32 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating32 A
Long delay settings
Ir32 A
TrNA
Short delay settings
Isd current256 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0NSX250BMicrologic 5.2 A250 A / 4P4dFull Discrimination
RCD designationRH99M
ClassA
In10000 mA
Break Time1.2 s
t1 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 1245.60] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH197P (QA 0)Full Discrimination
Transmission buswayWD 14
Parameters
Length4 m
Max lengthNA
Installation methodStandard
Ambient temperature35 C
Level of third harmonic THDI0 %
Ib28 A
Sizing InformationSized with Ir
Correction factors
Temperature factor 1
Installation method factor 1
Type of protection factor 1
User defined factor1
Selected busway
DesignationKTC1000
Rating1000
PE typeStandard PE
IP55
IK08
CoreCopper
Icw50 kA
Ip110 kA
Reinforced short circuit withstandNA
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.542.212.082.490.00
Synthesis for all operating mode
(kA)3.072.662.542.212.082.490.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Design current
IL1 IL2IL3IN
Operating mode Normal
(A)23.61724.29528.3404.42
Synthesis for all operating mode
(A)23.61724.29528.3404.42
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9590.002
UL1L2 (%)2.2610.002
UL2L3 (%)2.2680.003
UL3L1 (%)2.2680.003
UL1N (%)1.9590.004
UL2N (%)1.9610.004
UL3N (%)1.9730.005
3.2.4 Circuit Feeder circuit 19Circuit breakerQA 19
Ib15.9 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating16 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating16 A
Long delay settings
Ir16 A
TrNA
Short delay settings
Isd current128 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0NSX250BMicrologic 5.2 A250 A / 4P4dFull Discrimination
RCD designationRH99M
ClassA
In10000 mA
Break Time1.2 s
t1 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 1245.60] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH197P (QA 0)Full Discrimination
Transmission buswayWD 19
Parameters
Length4 m
Max lengthNA
Installation methodStandard
Ambient temperature35 C
Level of third harmonic THDI0 %
Ib16 A
Sizing InformationSized with Ir
Correction factors
Temperature factor 1
Installation method factor 1
Type of protection factor 1
User defined factor1
Selected busway
DesignationKTC1000
Rating1000
PE typeStandard PE
IP55
IK08
CoreCopper
Icw50 kA
Ip110 kA
Reinforced short circuit withstandNA
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.542.212.082.490.00
Synthesis for all operating mode
(kA)3.072.662.542.212.082.490.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Design current
IL1 IL2IL3IN
Operating mode Normal
(A)15.93515.9351.43414.5
Synthesis for all operating mode
(A)15.93515.9351.43414.5
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9580.001
UL1L2 (%)2.2600.002
UL2L3 (%)2.2670.001
UL3L1 (%)2.2660.001
UL1N (%)1.9580.003
UL2N (%)1.9590.003
UL3N (%)1.9680.000
3.2.5 Circuit Feeder circuit 14 (1)Circuit breakerQA 14 (1)
Ib28.3 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating32 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating32 A
Long delay settings
Ir32 A
TrNA
Short delay settings
Isd current256 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0NSX250BMicrologic 5.2 A250 A / 4P4dFull Discrimination
RCD designationRH99M
ClassA
In10000 mA
Break Time1.2 s
t1 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 1245.60] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH197P (QA 0)Full Discrimination
Transmission buswayWD 14 (1)
Parameters
Length4 m
Max lengthNA
Installation methodStandard
Ambient temperature35 C
Level of third harmonic THDI0 %
Ib28 A
Sizing InformationSized with Ir
Correction factors
Temperature factor 1
Installation method factor 1
Type of protection factor 1
User defined factor1
Selected busway
DesignationKTC1000
Rating1000
PE typeStandard PE
IP55
IK08
CoreCopper
Icw50 kA
Ip110 kA
Reinforced short circuit withstandNA
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.542.212.082.490.00
Synthesis for all operating mode
(kA)3.072.662.542.212.082.490.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Design current
IL1 IL2IL3IN
Operating mode Normal
(A)23.61724.29528.3404.42
Synthesis for all operating mode
(A)23.61724.29528.3404.42
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9590.002
UL1L2 (%)2.2610.002
UL2L3 (%)2.2680.003
UL3L1 (%)2.2680.003
UL1N (%)1.9590.004
UL2N (%)1.9610.004
UL3N (%)1.9730.005
3.2.6 Circuit Feeder circuit 14 (1) (1)Circuit breakerQA 14 (1) (1)
Ib25.9 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating32 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating32 A
Long delay settings
Ir32 A
TrNA
Short delay settings
Isd current256 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 0NSX250BMicrologic 5.2 A250 A / 4P4dFull Discrimination
RCD designationRH99M
ClassA
In10000 mA
Break Time1.2 s
t1 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 1245.60] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH197P (QA 0)Full Discrimination
Transmission buswayWD 14 (1) (1)
Parameters
Length4 m
Max lengthNA
Installation methodStandard
Ambient temperature35 C
Level of third harmonic THDI0 %
Ib26 A
Sizing InformationSized with Ir
Correction factors
Temperature factor 1
Installation method factor 1
Type of protection factor 1
User defined factor1
Selected busway
DesignationKTC1000
Rating1000
PE typeStandard PE
IP55
IK08
CoreCopper
Icw50 kA
Ip110 kA
Reinforced short circuit withstandNA
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.542.212.082.490.00
Synthesis for all operating mode
(kA)3.072.662.542.212.082.490.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Design current
IL1 IL2IL3IN
Operating mode Normal
(A)25.19125.19125.8700.679
Synthesis for all operating mode
(A)25.19125.19125.8700.679
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9590.002
UL1L2 (%)2.2610.002
UL2L3 (%)2.2680.003
UL3L1 (%)2.2680.003
UL1N (%)1.9600.004
UL2N (%)1.9610.004
UL3N (%)1.9720.004
3.3 Generic load circuits3.3.1 Circuit Load 17Circuit breakerQA 17
Ib7.87 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating10 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating10 A
Long delay settings
Ir10 A
TrNA
Short delay settings
Isd current80 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 14iC60NC32 A / 4P4d260 A
RCD designationRH10M
ClassA
In300 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.40] s
Normative required sensitivity[0.00 ; 681.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 14)Full Discrimination
CableWD 17
Parameters
Length5 m
Max length42.4 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib8 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.410.991.360.00
Synthesis for all operating mode
(kA)3.072.662.531.410.991.360.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeAA 17
U400 V
S1.82 kVA
P1.82 kW
I7.87 A
cos1
Polarity1Ph+N
Phase connectionAuto
Number of circuit16
Ku (Normal)1
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0007.87
Synthesis for all operating mode
(A)0.0000.0000.0007.87
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.2120.252
UL1L2 (%)2.2610.000
UL2L3 (%)2.2680.000
UL3L1 (%)2.2680.000
UL1N (%)2.4640.505
UL2N (%)2.4660.505
UL3N (%)2.4770.505
Synthesis for all operating mode
U3L (%)2.212
UL1L2 (%)2.261
UL2L3 (%)2.268
UL3L1 (%)2.268
UL1N (%)2.464
UL2N (%)2.466
UL3N (%)2.477
3.3.2 Circuit Load 31Circuit breakerQA 31
Ib4.33 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating6 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating6 A
Long delay settings
Ir6 A
TrNA
Short delay settings
Isd current48 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 27iC60NC10 A / 4P4d80 A
RCD designationRH10M
ClassA
In300 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.40] s
Normative required sensitivity[0.00 ; 296.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 27)Full Discrimination
CableWD 31
Parameters
Length10 m
Max length62.6 m
Installation method31EMulti-core cables on horizontal perforated tray
Type of cableMulti-core
Nb of additional touching circuits0
InsulationXLPE
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib4 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-20
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions26 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions26 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)2.111.821.330.670.410.590.00
Synthesis for all operating mode
(kA)2.111.821.330.670.410.590.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeAA 31
U400 V
S1 kVA
P1 kW
I4.33 A
cos1
Polarity1Ph+N
Phase connectionAuto
Number of circuit1
Ku (Normal)1
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0004.33
Synthesis for all operating mode
(A)0.0000.0000.0004.33
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.4910.296
UL1L2 (%)2.3800.000
UL2L3 (%)2.4640.000
UL3L1 (%)2.4630.000
UL1N (%)2.1810.000
UL2N (%)2.1830.000
UL3N (%)2.9190.592
Synthesis for all operating mode
U3L (%)2.491
UL1L2 (%)2.380
UL2L3 (%)2.464
UL3L1 (%)2.463
UL1N (%)2.181
UL2N (%)2.183
UL3N (%)2.919
3.3.3 Circuit Load 17 (1)Circuit breakerQA 17 (1)
Ib7.87 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating10 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating10 A
Long delay settings
Ir10 A
TrNA
Short delay settings
Isd current80 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 14 (1)iC60NC32 A / 4P4d260 A
RCD designationRH10M
ClassA
In300 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.40] s
Normative required sensitivity[0.00 ; 681.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 14 (1))Full Discrimination
CableWD 17 (1)
Parameters
Length5 m
Max length42.4 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib8 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.410.991.360.00
Synthesis for all operating mode
(kA)3.072.662.531.410.991.360.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeAA 17 (1)
U400 V
S1.82 kVA
P1.82 kW
I7.87 A
cos1
Polarity1Ph+N
Phase connectionAuto
Number of circuit16
Ku (Normal)1
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0007.87
Synthesis for all operating mode
(A)0.0000.0000.0007.87
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.2120.252
UL1L2 (%)2.2610.000
UL2L3 (%)2.2680.000
UL3L1 (%)2.2680.000
UL1N (%)2.4640.505
UL2N (%)2.4660.505
UL3N (%)2.4770.505
Synthesis for all operating mode
U3L (%)2.212
UL1L2 (%)2.261
UL2L3 (%)2.268
UL3L1 (%)2.268
UL1N (%)2.464
UL2N (%)2.466
UL3N (%)2.477
3.3.4 Circuit Load 17 (1) (1)Circuit breakerQA 17 (1) (1)
Ib2.62 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating3 A
Breaking capacity50 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole4P4d
Trip unit designationC
Trip unit rating3 A
Long delay settings
Ir3 A
TrNA
Short delay settings
Isd current24 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 14 (1) (1)iC60NC32 A / 4P4d480 A
RCD designationRH10M
ClassA
In300 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.20] s
Normative required sensitivity[0.00 ; 681.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 14 (1) (1))Full Discrimination
CableWD 17 (1) (1)
Parameters
Length5 m
Max length256 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib3 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions13 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions13 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.410.991.360.00
Synthesis for all operating mode
(kA)3.072.662.531.410.991.360.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeAA 17 (1) (1)
U400 V
S1.82 kVA
P1.82 kW
I2.62 A
cos1
Polarity3Ph+N
Phase connection
Number of circuit16
Ku (Normal)1
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)2.6242.6242.6240
Synthesis for all operating mode
(A)2.6242.6242.6240
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.0430.084
UL1L2 (%)2.3580.097
UL2L3 (%)2.3660.097
UL3L1 (%)2.3650.097
UL1N (%)2.0440.084
UL2N (%)2.0450.084
UL3N (%)2.0560.084
Synthesis for all operating mode
U3L (%)2.043
UL1L2 (%)2.358
UL2L3 (%)2.366
UL3L1 (%)2.365
UL1N (%)2.044
UL2N (%)2.045
UL3N (%)2.056
3.4 Lighting load circuits3.4.1 Circuit Load 6Circuit breakerQA 6
Ib3.23 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating4 A
Breaking capacity50 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating4 A
Long delay settings
Ir4 A
TrNA
Short delay settings
Isd current32 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d130 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 279.88] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 6
Parameters
Length17 m
Max length120 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib3 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.540.640.390.560.00
Synthesis for all operating mode
(kA)3.072.662.540.640.390.560.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 6
U400 V
S0.745 kVA
P0.67 kW
I3.23 A
cos0.9
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesMetal iodine
Nb of luminaries9
Nb of lights/luminaries1
Lights power70 W
Ballast power4.5 W
Ia5.81 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0003.23
Synthesis for all operating mode
(A)0.0000.0000.0003.23
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.2750.317
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)1.9590.000
UL3N (%)2.6030.635
Synthesis for all operating mode
U3L (%)2.275
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)1.956
UL2N (%)1.959
UL3N (%)2.603
3.4.2 Circuit Load 7Circuit breakerQA 7
Ib3.23 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating4 A
Breaking capacity50 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating4 A
Long delay settings
Ir4 A
TrNA
Short delay settings
Isd current32 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d130 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 279.88] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 7
Parameters
Length17 m
Max length120 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib3 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.540.640.390.560.00
Synthesis for all operating mode
(kA)3.072.662.540.640.390.560.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 7
U400 V
S0.745 kVA
P0.67 kW
I3.23 A
cos0.9
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesMetal iodine
Nb of luminaries9
Nb of lights/luminaries1
Lights power70 W
Ballast power4.5 W
Ia5.81 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0003.23
Synthesis for all operating mode
(A)0.0000.0000.0003.23
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.2750.317
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)2.5930.635
UL3N (%)1.9680.000
Synthesis for all operating mode
U3L (%)2.275
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)1.956
UL2N (%)2.593
UL3N (%)1.968
3.4.3 Circuit Load 8Circuit breakerQA 8
Ib3.23 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating4 A
Breaking capacity50 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating4 A
Long delay settings
Ir4 A
TrNA
Short delay settings
Isd current32 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d130 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 279.88] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 8
Parameters
Length17 m
Max length120 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib3 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.540.640.390.560.00
Synthesis for all operating mode
(kA)3.072.662.540.640.390.560.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 8
U400 V
S0.745 kVA
P0.67 kW
I3.23 A
cos0.9
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesMetal iodine
Nb of luminaries9
Nb of lights/luminaries1
Lights power70 W
Ballast power4.5 W
Ia5.81 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0003.23
Synthesis for all operating mode
(A)0.0000.0000.0003.23
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.2750.317
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)2.5910.635
UL2N (%)1.9590.000
UL3N (%)1.9680.000
Synthesis for all operating mode
U3L (%)2.275
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)2.591
UL2N (%)1.959
UL3N (%)1.968
3.4.4 Circuit Load 9Circuit breakerQA 9
Ib0.943 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating1 A
Breaking capacity50 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating1 A
Long delay settings
Ir1 A
TrNA
Short delay settings
Isd current8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d370 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 557.38] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 9
Parameters
Length7 m
Max length485 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.541.190.791.110.00
Synthesis for all operating mode
(kA)3.072.662.541.190.791.110.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 9
U400 V
S0.218 kVA
P0.202 kW
I0.943 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries5
Nb of lights/luminaries1
Lights power36 W
Ballast power4.5 W
Ia0.943 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0000.943
Synthesis for all operating mode
(A)0.0000.0000.0000.943
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9970.039
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)1.9590.000
UL3N (%)2.0470.079
Synthesis for all operating mode
U3L (%)1.997
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)1.956
UL2N (%)1.959
UL3N (%)2.047
3.4.5 Circuit Load 10Circuit breakerQA 10
Ib0.943 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating1 A
Breaking capacity50 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating1 A
Long delay settings
Ir1 A
TrNA
Short delay settings
Isd current8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d370 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 242.72] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 10
Parameters
Length20 m
Max length485 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.540.560.340.490.00
Synthesis for all operating mode
(kA)3.072.662.540.560.340.490.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 10
U400 V
S0.218 kVA
P0.202 kW
I0.943 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries5
Nb of lights/luminaries1
Lights power36 W
Ballast power4.5 W
Ia0.943 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0000.943
Synthesis for all operating mode
(A)0.0000.0000.0000.943
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.0700.113
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)2.1840.225
UL3N (%)1.9680.000
Synthesis for all operating mode
U3L (%)2.070
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)1.956
UL2N (%)2.184
UL3N (%)1.968
3.4.6 Circuit Load 11Circuit breakerQA 11
Ib1.05 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60L
Circuit breaker rating1.6 A
Breaking capacity100 kA
TNS One pole breaking capacity100 kA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P2d
Trip unit designationC
Trip unit rating1.6 A
Long delay settings
Ir1.6 A
TrNA
Short delay settings
Isd current12.8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d128 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 557.38] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 11
Parameters
Length7 m
Max length302 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.541.190.791.110.00
Synthesis for all operating mode
(kA)3.072.662.541.190.791.110.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 11
U400 V
S0.242 kVA
P0.225 kW
I1.05 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries10
Nb of lights/luminaries1
Lights power18 W
Ballast power4.5 W
Ia1.05 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0001.05
Synthesis for all operating mode
(A)0.0000.0000.0001.05
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.0020.044
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)2.0440.088
UL2N (%)1.9590.000
UL3N (%)1.9680.000
Synthesis for all operating mode
U3L (%)2.002
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)2.044
UL2N (%)1.959
UL3N (%)1.968
3.4.7 Circuit Load 12Circuit breakerQA 12
Ib1.05 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60L
Circuit breaker rating1.6 A
Breaking capacity100 kA
TNS One pole breaking capacity100 kA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P2d
Trip unit designationC
Trip unit rating1.6 A
Long delay settings
Ir1.6 A
TrNA
Short delay settings
Isd current12.8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4d128 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 242.72] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 12
Parameters
Length20 m
Max length302 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.540.560.340.490.00
Synthesis for all operating mode
(kA)3.072.662.540.560.340.490.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 12
U400 V
S0.242 kVA
P0.225 kW
I1.05 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries10
Nb of lights/luminaries1
Lights power18 W
Ballast power4.5 W
Ia1.05 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0001.05
Synthesis for all operating mode
(A)0.0000.0000.0001.05
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.0830.125
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)1.9590.000
UL3N (%)2.2190.250
Synthesis for all operating mode
U3L (%)2.083
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)1.956
UL2N (%)1.959
UL3N (%)2.219
3.4.8 Circuit Load 18Circuit breakerQA 18
Ib1.13 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60L
Circuit breaker rating1.6 A
Breaking capacity100 kA
TNS One pole breaking capacity100 kA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P2d
Trip unit designationC
Trip unit rating1.6 A
Long delay settings
Ir1.6 A
TrNA
Short delay settings
Isd current12.8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 14iC60NC32 A / 4P4d256 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 681.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 14)Full Discrimination
CableWD 18
Parameters
Length5 m
Max length302 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.410.991.360.00
Synthesis for all operating mode
(kA)3.072.662.531.410.991.360.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 18
U400 V
S0.261 kVA
P0.243 kW
I1.13 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries6
Nb of lights/luminaries1
Lights power36 W
Ballast power4.5 W
Ia1.13 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0001.13
Synthesis for all operating mode
(A)0.0000.0000.0001.13
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9930.034
UL1L2 (%)2.2610.000
UL2L3 (%)2.2680.000
UL3L1 (%)2.2680.000
UL1N (%)1.9590.000
UL2N (%)2.0280.068
UL3N (%)1.9730.000
Synthesis for all operating mode
U3L (%)1.993
UL1L2 (%)2.261
UL2L3 (%)2.268
UL3L1 (%)2.268
UL1N (%)1.959
UL2N (%)2.028
UL3N (%)1.973
3.4.9 Circuit Load 20Circuit breakerQA 20
Ib1.43 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60L
Circuit breaker rating1.6 A
Breaking capacity100 kA
TNS One pole breaking capacity100 kA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P2d
Trip unit designationC
Trip unit rating1.6 A
Long delay settings
Ir1.6 A
TrNA
Short delay settings
Isd current12.8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 19iC60NC16 A / 4P4d128 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 430.87] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 19)Full Discrimination
CableWD 20
Parameters
Length10 m
Max length302 m
Installation method21CMulti-core cables fixed directly under a wooden ceiling
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor0.95
Standard table referenceB-52-17
User correction factor1
Overall factor0.95
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions18.5 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions18.5 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.530.950.600.860.00
Synthesis for all operating mode
(kA)3.072.662.530.950.600.860.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 20
U400 V
S0.331 kVA
P0.298 kW
I1.43 A
cos0.9
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesMetal iodine
Nb of luminaries4
Nb of lights/luminaries1
Lights power70 W
Ballast power4.5 W
Ia2.58 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0001.43
Synthesis for all operating mode
(A)0.0000.0000.0001.43
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.0410.083
UL1L2 (%)2.2600.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2660.000
UL1N (%)1.9580.000
UL2N (%)1.9590.000
UL3N (%)2.1340.166
Synthesis for all operating mode
U3L (%)2.041
UL1L2 (%)2.260
UL2L3 (%)2.267
UL3L1 (%)2.266
UL1N (%)1.958
UL2N (%)1.959
UL3N (%)2.134
3.4.10 Circuit Load 18 (1)Circuit breakerQA 18 (1)
Ib1.13 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60L
Circuit breaker rating1.6 A
Breaking capacity100 kA
TNS One pole breaking capacity100 kA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P2d
Trip unit designationC
Trip unit rating1.6 A
Long delay settings
Ir1.6 A
TrNA
Short delay settings
Isd current12.8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 14 (1)iC60NC32 A / 4P4d256 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 681.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 14 (1))Full Discrimination
CableWD 18 (1)
Parameters
Length5 m
Max length302 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.410.991.360.00
Synthesis for all operating mode
(kA)3.072.662.531.410.991.360.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 18 (1)
U400 V
S0.261 kVA
P0.243 kW
I1.13 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries6
Nb of lights/luminaries1
Lights power36 W
Ballast power4.5 W
Ia1.13 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0001.13
Synthesis for all operating mode
(A)0.0000.0000.0001.13
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9930.034
UL1L2 (%)2.2610.000
UL2L3 (%)2.2680.000
UL3L1 (%)2.2680.000
UL1N (%)1.9590.000
UL2N (%)2.0280.068
UL3N (%)1.9730.000
Synthesis for all operating mode
U3L (%)1.993
UL1L2 (%)2.261
UL2L3 (%)2.268
UL3L1 (%)2.268
UL1N (%)1.959
UL2N (%)2.028
UL3N (%)1.973
3.4.11 Circuit Load 18 (1) (1)Circuit breakerQA 18 (1) (1)
Ib1.13 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60L
Circuit breaker rating1.6 A
Breaking capacity100 kA
TNS One pole breaking capacity100 kA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P2d
Trip unit designationC
Trip unit rating1.6 A
Long delay settings
Ir1.6 A
TrNA
Short delay settings
Isd current12.8 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 14 (1) (1)iC60NC32 A / 4P4d256 A
RCD designationRH99M
ClassA
In3000 mA
Break Time0.65 s
t0.5 s
DiscriminationNA
Normative required break time[0.00 ; 5.00] s
Normative required sensitivity[0.03 ; 681.34] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 14 (1) (1))Full Discrimination
CableWD 18 (1) (1)
Parameters
Length5 m
Max length302 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib1 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected neutral
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions14 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.410.991.360.00
Synthesis for all operating mode
(kA)3.072.662.531.410.991.360.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeEA 18 (1) (1)
U400 V
S0.261 kVA
P0.243 kW
I1.13 A
cos0.93
Ku (Normal)1
Number of circuit1
Polarity1Ph+N
Phase connectionAuto
Type of luminariesFluorescent with electronic ballast
Nb of luminaries6
Nb of lights/luminaries1
Lights power36 W
Ballast power4.5 W
Ia1.13 A
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.0001.13
Synthesis for all operating mode
(A)0.0000.0000.0001.13
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)1.9930.034
UL1L2 (%)2.2610.000
UL2L3 (%)2.2680.000
UL3L1 (%)2.2680.000
UL1N (%)1.9600.000
UL2N (%)1.9610.000
UL3N (%)2.0400.068
Synthesis for all operating mode
U3L (%)1.993
UL1L2 (%)2.261
UL2L3 (%)2.268
UL3L1 (%)2.268
UL1N (%)1.960
UL2N (%)1.961
UL3N (%)2.040
3.5 Power socket load circuits3.5.1 Circuit Load 13Circuit breakerQA 13
Ib15.9 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating16 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating16 A
Long delay settings
Ir16 A
TrNA
Short delay settings
Isd current128 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 3iC60NC16 A / 4P4dNo Discrimination
RCD designationRH10M
ClassA
In30 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.40] s
Normative required sensitivity[0.01 ; 0.03] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 3)Full Discrimination
CableWD 13
Parameters
Length10 m
Max length43 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib16 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x2.5 mm
CoreCopper
Iz under real conditions18.5 A
Selected neutral
Cross section area1x2.5 mm
CoreCopper
Iz under real conditions18.5 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.541.290.881.100.00
Synthesis for all operating mode
(kA)3.072.662.541.290.881.100.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeAA 13
U400 V
S3.68 kVA
P3.68 kW
I15.9 A
cos1
Polarity1Ph+N
Phase connectionAuto
Number of circuit1
Ku (Normal)1
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.00015.9
Synthesis for all operating mode
(A)0.0000.0000.00015.9
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.5710.613
UL1L2 (%)2.2590.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2650.000
UL1N (%)1.9560.000
UL2N (%)3.1851.226
UL3N (%)1.9680.000
Synthesis for all operating mode
U3L (%)2.571
UL1L2 (%)2.259
UL2L3 (%)2.267
UL3L1 (%)2.265
UL1N (%)1.956
UL2N (%)3.185
UL3N (%)1.968
3.5.2 Circuit Load 25Circuit breakerQA 25
Ib15.9 A
Distance from originNA
Sizing InformationSized by system
RangeActi9 iC60
DesignationiC60N
Circuit breaker rating16 A
Breaking capacity10 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole2P1d
Trip unit designationC
Trip unit rating16 A
Long delay settings
Ir16 A
TrNA
Short delay settings
Isd current128 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 19iC60NC16 A / 4P4dNo Discrimination
RCD designationRH10M
ClassA
In30 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.40] s
Normative required sensitivity[0.01 ; 0.03] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 19)Full Discrimination
CableWD 25
Parameters
Length5 m
Max length43 m
Installation method2A2Multi-core cables in conduit in a thermally insulated wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationPVC
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib16 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x2.5 mm
CoreCopper
Iz under real conditions18.5 A
Selected neutral
Cross section area1x2.5 mm
CoreCopper
Iz under real conditions18.5 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)3.072.662.531.691.291.610.00
Synthesis for all operating mode
(kA)3.072.662.531.691.291.610.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.ChargeAA 25
U400 V
S3.68 kVA
P3.68 kW
I15.9 A
cos1
Polarity1Ph+N
Phase connectionAuto
Number of circuit2
Ku (Normal)1
Harmonic generatorNo
THDI30
Sensitivity to over voltageNA
Design current
IL1 IL2IL3IN
Operating mode Normal
(A)0.0000.0000.00015.9
Synthesis for all operating mode
(A)0.0000.0000.00015.9
Voltage drop
Cumulated from upstreamCircuit
Operating mode Normal
U3L (%)2.2650.307
UL1L2 (%)2.2600.000
UL2L3 (%)2.2670.000
UL3L1 (%)2.2660.000
UL1N (%)2.5710.613
UL2N (%)2.5720.613
UL3N (%)1.9680.000
Synthesis for all operating mode
U3L (%)2.265
UL1L2 (%)2.260
UL2L3 (%)2.267
UL3L1 (%)2.266
UL1N (%)2.571
UL2N (%)2.572
UL3N (%)1.968
3.6 Motor starter combination
3.6.1 Circuit Motor Load 30Circuit breakerQA 30
IbNA
Distance from originNA
Sizing InformationSized by system
RangeActi9 P25M
DesignationP25M
Circuit breaker rating4 A
Breaking capacity150 kA
TNS One pole breaking capacityNA
IT One pole breaking capacityNA
Reinforced breaking capacityNA
Pole & protected pole3P3d
Trip unit designationM
Trip unit rating4 A
Long delay settings
Ir4 A
TrNA
Short delay settings
Isd current51 A
TsdNA
Instantaneous tripping
Ii currentNA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
QA 27iC60NC10 A / 4P4d17 A
RCD designationRH10M
ClassA
In300 mA
Break Time0.03 s
t0 s
DiscriminationNA
Normative required break time[0.00 ; 0.20] s
Normative required sensitivity[0.00 ; 414.00] mA
Discrimination Results
UpStream Discrimination Limit
Operating mode Normal
RH99M (QA 27)Full Discrimination
ContactorLC1K06
DesignationLC1K06
Type of coordinationT1
CableWD 30
Parameters
Length5 m
Max length189 m
Installation method20Cmulti-core cables fixed on or spaced less than 03 x cable diameter from a wooden wall
Type of cableMulti-core
Nb of additional touching circuits0
InsulationXLPE
Ambient temperature30 C
Level of third harmonic THDI0 %
Ib4 A
Sizing constraintIz
Sizing InformationSized with Ir
Correction factors
Temperature factor1
Standard table referenceB-52-14
Soil thermal resistivity factor1
Standard table referenceB-52-16
Loaded neutral factor1
Standard table referenceE-52-1
Touching conductor factor1
Standard table referenceB-52-17
User correction factor1
Overall factor1
Selected phase
Cross section area1x1.5 mm
CoreCopper
Iz under real conditions22 A
Selected PE
Cross section area1x4 mm
CoreCopper
Short circuit current
Ik3max Ik2maxIk1maxIk2minIk1minIefIef2min
Operating mode Normal
(kA)2.111.820.000.910.000.830.00
Synthesis for all operating mode
(kA)2.111.820.000.910.000.830.00
Calculation results in accordance with CENELEC technical report TR50480.
All assumptions and device choices are the user's responsibility.Asynchronous LV MotorMA 30
Startup typeDirect
U400 V
Mechanical power1.5 kW
Startup current Id/Ir6
Transient current Id/Ir