PROJECT: Sample Balance Report #3 LOCATION: 5140 Diligent Drive, Melink City, AK 99705 ARCHITECT: Architects R' Us Edison Engineers PROJECT NUMBER: P1001021 GEN. CONTRACTOR: We Build'm Better CERTIFIED TEST ADJUST BALANCE REPORT "THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIROMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST- ADJUST-BALANCE REPORT PROJECT SUMMARY." www.melinkcorp.com [email protected] 1/0/1900 1/0/1900 5140 River Valley Road, Milford, Ohio 45150 USA Phone: (513) 965-7300 Fax: (513) 965-7350 1/0/1900 T & B ENGINEER: Stephen K. Melink, PE 6/30/2016 ORIGINAL VISIT DATE: MECH. ENGINEER:

CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

Embed Size (px)

Citation preview

Page 1: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

PROJECT: Sample Balance Report #3

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

ARCHITECT: Architects R' Us

Edison Engineers

PROJECT NUMBER: P1001021

GEN. CONTRACTOR: We Build'm Better

CERTIFIED TEST ADJUST BALANCE REPORT

"THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS

AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE

CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING,

ADJUSTING, AND BALANCING OF ENVIROMENTAL SYSTEMS. ANY VARIANCES FROM

DESIGN QUANTITES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST-

ADJUST-BALANCE REPORT PROJECT SUMMARY."

www.melinkcorp.com • [email protected]

1/0/1900

1/0/1900

5140 River Valley Road, Milford, Ohio 45150 USA

Phone: (513) 965-7300 • Fax: (513) 965-7350

1/0/1900

T & B ENGINEER: Stephen K. Melink, PE

6/30/2016ORIGINAL VISIT DATE:

MECH. ENGINEER:

Page 2: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

TABLE OF CONTENTS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

Page 3: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

ABBREVIATIONS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

ABBREVIATIONS

AHU - Air Handling Unit AMP - Amperage BP - Building Pressure CFM - Cubic Feet/Minute EF - Exhaust Fan EH - Entry Heater ERU - Energy Recycling Unit ESP - External Static Pressure FLA - Full Load Amperage HP - Horse Power HZ - Hertz KH - Kitchen Hood KW - Kilowatt

MUA - Makeup Air Unit Volts - Voltage OA - Outside Air RA - Return Air RPM - Revolutions Per Minute RTU - Roof Top Unit SF - Supply Fan / Safety Factor SP - Static Pressure VAV - Variable Air Volume WC - Water Column

Page 4: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

MELINK CREDENTIALS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

Page 5: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

Fax: NA

Marcus Mills

Fax: NA

E-mail: [email protected]

MECH. CONTRACTOR:

(555) 424-4244

Fax: NA

E-mail: [email protected]

E-mail: N/A

Ivan Workhard

Phone: (555) 112-2222

MELINK TECHNICIAN:

N/A

Phone:

E-mail: [email protected]

[email protected]

MELINK SERVICE ENG.: John Smith

Phone: (513) 965-7300

E-mail:

REVISIT TECHNICIAN: N/A

Fax: (513) 965-7350

Phone: N/A

Fax:

SUPERINTENDENT: Donald Duck

Phone: (555) 112-6828

E-mail:

LOCATION:

PROJECT MANAGER:

Phone:

Fax:

Sam Sampson

(555) 683-1122

NA

5140 Diligent Drive, Melink City, AK 99705

[email protected]

TEST AND BALANCE CONTACT INFORMATION

6/30/2016PROJECT: DATE: Sample Balance Report #3

Page 6: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

Calibration Date: NA

Model #: NA

Serial #: NA

Serial #:

Alnor

EBT721-ME

91206032

FLOW HOOD:

TEST AND BALANCE EQUIPMENT INFORMATION

6/30/2016PROJECT: DATE: Sample Balance Report #3

5140 Diligent Drive, Melink City, AK 99705LOCATION:

Model #:

PITOT TUBE: NA

08/10/13

NA

Model #: NA

Calibration Date:

VANE ANEMOMETER:

NA

NA

Fluke

Serial #:

Calibration Date:

1808425

TACHOMETER:

VOLTMETER / AMPMETER:

322

Serial #: 10830582

08/10/13

Model #:

Calibration Date:

Serial #: NA

NACalibration Date:

08/10/13

MANOMETER: NA

Model #: NA

Calibration Date:

MONARCH

Model #: PT99

Serial #:

Page 7: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

The following corrections were performed by Melink and/or the contractors on-site.

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

FIELD SUMMARY: CORRECTIONS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

This air balance report is based on actual field readings and measurements taken from the store’s HVAC

systems during operation. All systems were also balanced to within +/- 10% of design unless noted otherwise.

Page 8: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

N/A N/A

Melink recommends revisiting this store due to the deficiencies listed above.

Project Manager: Please contact Melink in order to authorize the revisit.

YesRevisit necessary? 30-60 days after opening? Before opening?

The following list details the remaining deficiencies of the store’s HVAC and exhaust systems. These

corrections are necessary to comply with the design specifications.

DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

FIELD SUMMARY: PUNCH LIST

PROJECT: Sample Balance Report #3

Page 9: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

The following list details the remaining deficiencies of the store’s HVAC and exhaust systems. These

corrections are necessary to comply with the design specifications.

DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

FIELD SUMMARY: PUNCH LIST

PROJECT: Sample Balance Report #3

Project Manager: Please contact Melink in order to authorize the revisit.

Melink recommends revisiting this store due to the deficiencies listed above.

Revisit necessary? Yes 30-60 days after opening? N/A Before opening? N/A

Page 10: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

The following list details the recommendations for improving comfort and energy efficiency. These items are

not requirements of the design specifications.

FIELD SUMMARY: RECOMMENDATIONS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

Page 11: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

5140 Diligent Drive, Melink City, AK 99705

PROJECT: Sample Balance Report #3

PHOTOS

DATE: 6/30/2016

Picture 2: Rubber grommets are not installed.Picture 1: Gas lines are not painted.

LOCATION:

Picture 4: Condensate drains are not installed.

Picture 6: Grease filters are installed.

Picture 3: Electrical penetrations are not sealed.

Picture 5: Grease traps are installed.

Page 12: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

5140 Diligent Drive, Melink City, AK 99705

PROJECT: Sample Balance Report #3

PHOTOS

DATE: 6/30/2016

LOCATION:

Picture 9: EF-6 VSC is set and marked. Picture 10: RRU filters are installed.

Picture 7: Supply diffusers are insulated. Picture 8: Dampers are flagged.

Page 13: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

STANDARD 1 2 3 1 2

Verify proper unit locations √ √ √ √ √Verify units marked for easy identification X X X X X

Inspect units • Unit sealed and properly seated to roof curb X X X X X

• Unit nameplate data matches design √ √ √ X X

• Motor nameplate data matches design N/A N/A N/A N/A N/A

• No unusual vibration or noise √ √ √ √ √

• All filters installed, clean and secure √ √ √ √ √ • Condenser coil clean and free of damage √ √ √ √ √

• Evaporator coil clean and free of damage √ √ √ √ √

• Gas cocks turned on √ √ √ √ √ • Gas pipe painted X X X X X

• Condensate drain lines properly installed X X X X X

• P-Traps properly installed X X X X X

• Drain lines properly sloped X X X X X

Remove unit access panels

• Panels open freely and fully √ √ √ √ √

• Panels latch securely √ √ √ √ √

• Belts properly tensioned and free of damage N/A N/A √ √ √

• Pulleys properly aligned N/A N/A √ √ √

• Blower wheel clean and free of damage √ √ √ √ √

• Control transformer wired for correct voltage √ √ √ √ √

Check disconnect switches and covers

• Verify on/off disconnects work √ √ √ √ √

• Verify voltage input correct √ √ √ √ √

• Verify switch covers installed √ √ √ √ √

Power-on diagnostic check

• Fans operating in correct rotation √ √ √ √ √

• Compressors operating in correct rotation √ √ √ √ √

• No unusual vibration or noise √ √ √ √ √

Outside air (OA) dampers

• Outside air dampers installed and operational N/A N/A √ √ √

• Ensure slightly positive building pressure N/A N/A √ √ √

• Position marked for reference N/A N/A √ N/A N/A

• Sticker affixed to unit to preclude tampering √ √ √ √ √

RTU RRU

STATUSDESCRIPTION

ROOFTOP INSPECTION

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

Page 14: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

ROOFTOP INSPECTION

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

STANDARD 1 2 3 4 5 6

Verify proper unit locations √ √ √ √ √ √

Verify units marked for easy identification X X X X X X

Inspect units

• Unit sealed and properly seated to roof curb √ √ √ √ X X

• Unit nameplate data matches design √ √ √ √ √ √

• Motor nameplate data matches design √ √ √ √ √ √

• No unusual vibration or noise √ √ √ √ √ √

Exhaust fans (EF)

• Transition from exhaust duct to fan installed √ √ √ √ √ √

• Duct continuously welded and liquid tight √ √ √ √ √ N/A

• Fan hinged and opened for easy access √ √ √ √ N/A N/A

• Grease traps properly installed √ √ √ √ N/A N/A

Remove unit access panels

• Panels open freely and fully √ √ √ √ √ √

• Panels latch securely √ √ √ √ √ √

• Belts properly tensioned and free of damage √ √ √ √ N/A N/A

• Pulleys properly aligned √ √ √ √ N/A N/A

• Blower wheel clean and free of damage √ √ √ √ √ √

Check disconnect switches and covers

• Verify on/off disconnects work √ √ √ √ √ √

• Verify voltage input correct √ √ √ √ √ √

• Verify switch covers installed √ √ √ √ √ √

Power-on diagnostic check

• Fans operating in correct rotation √ √ √ √ √ √

EF

DESCRIPTION STATUS

Page 15: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

STANDARD

Supply duct system 1 2 3 1 2

• Ductwork is installed as per design √ √ √ √ √ • All volume dampers are properly installed √ √ √ X √

• Dampers are accessible and operable √ √ √ X √

• Ductwork is properly covered with insulation, √ √ √ √ √ and insulation is secure

• Tops of diffusers are properly insulated √ √ √ √ √

• Installed diffusers match design √ √ X √ √

Exhaust duct system 1 2 3 4 5 6 • Cleanouts are installed where applicable √ √ √ √ N/A N/A • Fire wrap is installed on duct as specified √ √ √ √ N/A N/A

• Horizontal duct is sloped as specified √ √ √ √ N/A N/A

• Welds appear to be liquid tight √ √ √ √ N/A N/A

RTU

EF

ABOVE CEILING INSPECTION

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

RRU

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

DESCRIPTION STATUS

Page 16: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

STANDARD

Thermostats 1 2 3 1 2

• Remote sensor is installed in its correct location √ √ √ √ √ • Remote sensor is wired to the proper thermostat √ √ √ √ √

• Thermostat is wired to the correct unit √ √ √ √ √

• Thermostat has proper operation √ √ √ √ √ • Thermostat is programmed correctly N/A N/A N/A N/A N/A

• Unit was cycled to verify proper operation √ √ √ √ √

• Heating mode tested satisfactorily √ √ √ √ √

• Cooling mode tested satisfactorily √ √ √ √ √

Exhaust hoods 1 2 3 4 5 • Grease cups are installed √ √ √ √ N/A

• All grease filters are installed √ √ √ √ N/A

• Filters are of correct type and size √ √ √ √ N/A

• Cooking appliances are operating X X X X N/A

• Cooking appliances properly located under hoods √ √ √ √ N/A • Smoke capture is satisfactory X X X X N/A

Comfort

• Noticeable drafts?

• Comfort is good in all areas?

Communication

• Final results were discussed with:

–Superintendent

–Project manager

–Store manager (if applicable)

• A punch list of deficiencies was provided to:

–Superintendent and/or operations

–Project manager

–Store manager (if applicable)

• Business card was left on site with contact info. Yes

KH

RTU

N/A

Yes

Yes

N/A

Yes

Yes

No

STATUS

Yes

BELOW CEILING INSPECTION

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

RRU

5140 Diligent Drive, Melink City, AK 99705LOCATION:

DESCRIPTION

Page 17: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

CFM

CFM

W.C.

FINAL BUILDING BALANCE = 808

FINAL BUILDING PRESSURE = +0.016''

DESIGN TOTAL + 8800 DESIGN TOTAL – 8580

FINAL TOTAL + 11406 FINAL TOTAL – 10598

220DESIGN BUILDING BALANCE =

600

Design

N/ARTU-1

RTU-2

4745 EF-5

EF-6

N/A EF-2

634 EF-3

6027 EF-4

MAKE-UP AIR EXHAUST AIR

Final

N/A EF-1

875

800

805

3800

4400

( IN CFM )

RRU-1

N/A

793

RRU-2

3396

1420

3150

1200

BUILDING AIR BALANCE

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

932

2283

RTU-3

TEST RESULTS

1774

Final Design

1750

Page 18: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

AMPS

EF-5 6.4 EF-5 6.4

EF-6 3.9 EF-6 3.1

EF-2 3.3 EF-2 3.3

EFFICIENCY 3%

TOTAL + 39.9 TOTAL – 38.9

MOTOR AMP SAVINGS 1.0

EF-4 1.5 EF-4 1.3

RTU-2 2.2 RTU-2 2.9

RTU-3 4.2 RTU-3 3.8

EF-3 1.8 EF-3 1.6

RRU-1 6.7 RRU-1 6.7

RRU-2 5.6 RRU-2 5.6

EF-1 2.1 EF-1 1.9

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

MOTOR LOAD SUMMARY

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

TEST RESULTS

( IN AMPS )

INITIAL FINAL

RTU-1 2.2 RTU-1 2.2

Page 19: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

DESIGN DATA

EQUIP. DATA

TEST DATA

EXTERNAL S.P.

OPERATING AMPS 2.92.8

N/A

75%

2373

0.44''

1.9 2.1

MOTOR HERTZ

SUPPLY CFM

RETURN CFM

RET/SUCT/ DISCHARGE 0.23'' 0.22'' 0.70'' 0.15''

3185

0.37''

N/A

N/A

208/3 208/3

1

N/A

N/A

3.1

0.42''

N/A

6027

0

5

1725

N/A

N/A

6/30/2016

0.60''

N/A

4.1 3.7 3.7

1VL40 x 5/8"

AK64 x 1"

AX35

N/A

778 739

209 208

4400

100%

RRU240F3

20

RRU-1

Kitchen

0

DATE:

6

RTU-3

Kitchen

2400

1720

600

25%

4400

YHC072F3

RTU-2

Bar Dining

RTU-1

Dining / R.R.

3200

1300

Marathon

N/A

EBM Papst

N/A

3200

1200

1900

59%

YHC092F3

208/3

7.5

7.5

208/3

N/A

Trane

6027

100%

BX81

N/A

636 636

209 208

N/A

Not Listed

8.5 NA

2372

72%

N/A

3303

1011

208 208

2.6

VOLTS / PHASE

Trane

YHC092F3RLA

208/3 208/3

N/A

Trane

YHC092F3RLA

134710233L134710246L

N/A

Trane

YHC072F3RLA

134612436L

SHEAVE CENTERLINE

• RPM

• VOLTS / PHASE

• FLA / SF

MOTOR SHEAVE

FAN SHEAVE

BELT(S)

NA

208/3

Direct Drive

Direct Drive

Direct Drive

N/A

5.0

1725

1VL40 x 7/8"

19" x 1 3/16"

208/3

Direct Drive

1.5

Not Listed

8.5 NA

ROOFTOP UNITS (RTU) DATA

PROJECT:

LOCATION:

UNIT MFR.

RETURN CFM

EXTERNAL S.P.

OUTSIDE AIR CFM

OUTSIDE AIR RATIO %

N/A

YHC092F3

7.5

N/A

N/A

MODEL NUMBER

CAPACITY (TONS)

SUPPLY CFM

RRU240E3NEAA

134411454D

1900

59%

EBM Papst

N/A

N/A

FAN HP

Sample Balance Report #3

5140 Diligent Drive, Melink City, AK 99705

OUTSIDE AIR CFM

OUTSIDE AIR RATIO %

6.8 6.4 6.9

209

RPM - INITIAL / FINAL

ACTUAL VOLTS

FAN RPM

• RATED TONS

FAN MOTOR

• MODEL NO.

• SERIAL NO.

• HP

• MODEL NO.

Direct Drive

Direct Drive

N/A

4.9 VDC 4.9 VDC

634

893

0.22'' 0.76''

19%

5.0 VDC 5.7 VDC

3314

2667

0.00'' 0.20'' 0.42''0.31'' 0.58'' 0.29''

Marathon

20

16.7

7.5

208 208

6

209 208

N/A

208

Page 20: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

6/30/2016DATE:

ROOFTOP UNITS (RTU) DATA

PROJECT:

LOCATION:

Sample Balance Report #3

5140 Diligent Drive, Melink City, AK 99705

DESIGN DATA

EQUIP. DATA

TEST DATA

OUTSIDE AIR RATIO % 100%

OUTSIDE AIR CFM 4745

SUPPLY CFM 4745

RETURN CFM 0

MOTOR SHEAVE 1VL40 x 7/8"

FAN SHEAVE BK110 x 1 3/16"

SHEAVE CENTERLINE N/A

209 208 208ACTUAL VOLTS

RPM - INITIAL / FINAL 540 540

BELT(S) BX68

EXTERNAL S.P. 0.572''

MOTOR HERTZ N/A

RET/SUCT/ DISCHARGE

5.40 5.70

0.00 0.28 0.57

OPERATING AMPS

• RPM 1725

• VOLTS / PHASE

• FLA / SF 9.4 1.2

208/3

• MODEL NO. N/A

• HP 3

• RATED TONS 15

FAN MOTOR Marathon

• MODEL NO. RRU180E3NOAA

• SERIAL NO. 134411488D

OUTSIDE AIR CFM 3800

UNIT MFR. Trane

FAN HP N/A

VOLTS / PHASE

FAN RPM N/A

208/3

OUTSIDE AIR RATIO % 100%

EXTERNAL S.P. N/A

MODEL NUMBER RRU180F3

CAPACITY (TONS) 15

RETURN CFM 0

O/A RTU's 1 & 2

SUPPLY CFM

RRU-2

3800

5.60

Page 21: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

SYSTEM:

OUTSIDE AIR RATIO %

SUPPLY AIR CFM

RETURN AIR CFM

OUTSIDE AIR CFM

OUTLET SIZE

N/A

N/A

N/A

300

N/A

301

N/A

N/A 300

Dining

280

310

185

300

300

4-Way

4-Way

4-Way

AIR DISTRIBUTION DATA

PROJECT: Sample Balance Report #3 DATE:

FINAL

CFM

3200

1300

1900

59%

280

N/A

N/A

N/A

1300N/A

Dining / R.R.

R1A

1J

Dining

1B

1C

1D

1K

1E

1F

1G

1H

N/A

CFM

PRELIM

285

291

326

306

319

316

291

346

306

285

280

6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

NO.

RTU-1

329 329

N/A

N/A

1802-Way

1011

185

DESIGN

1A

AREA SERVED

Dining 300

CFMTYPE

4-Way

1I

Dining

Dining

Dining

Dining

Men's Restroom

Hallway

319

329

4-Way

4-Way

1L

4-Way

4-Way

332

120

167

160

Return Grille

332

169

167

172

306

Women's Restroom

Dining

Dining

Dining

4-Way

4-Way

NA

4-Way

72%

3300 3303

1011

2372

Page 22: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

AIR DISTRIBUTION DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

SYSTEM:

OUTSIDE AIR RATIO %

SUPPLY AIR CFM

RETURN AIR CFM

OUTSIDE AIR CFM

59% 75%

R2A Bar Return Grille N/A 600 NA 427

R2B Bar Return Grille N/A 600 NA 466

AREA SERVED TYPE OUTLET SIZE CFM CFM CFM

2A Bar Dining 4-Way

2B

2G Bar Dining 4-Way N/A 500 378 434

2H Bar Dining

2C Vestibule 3-Way N/A 200 250 287

2D Hostess 4-Way N/A 200 274 315

4-Way N/A 500 326 374

N/A

RTU-2 Bar Dining

4-Way

N/A 300

2E Bar Dining 4-Way N/A 500

2F Bar Dining N/A 500

2I Bar Dining 4-Way

NO.

Bar Dining 4-Way N/A 300

DESIGN

303

358

3200 2772 3185

1200 893

PRELIM FINAL

1900

348

200 251 289

264

2373

311

415 477

303

Page 23: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

AIR DISTRIBUTION DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

SYSTEM:

1720 2667

600 634

25% 19%

2400 3737 3314SUPPLY AIR CFM

RETURN AIR CFM

OUTSIDE AIR CFM

OUTSIDE AIR RATIO %

R3B Kitchen Return Grille N/A 1400 NA 2441

R3A Office Return Grille N/A 320 NA 226

3F Kitchen Prep Perforated NA 450 848 720

3D Storage 4-Way NA 450 739 578

3E Kitchen Prep 4-Way NA 450 632 537

3B Receiving 3-Way NA 280 512 435

3C Kitchen Prep 3-Way NA 450 369 503

NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM

3A Office 1-Way NA 320 637 541

RTU-3 Kitchen

DESIGN PRELIM FINAL

Page 24: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

AIR DISTRIBUTION DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

SYSTEM:

OUTSIDE AIR RATIO %

SUPPLY AIR CFM

RETURN AIR CFM

OUTSIDE AIR CFM

RR1I Service Line 3-Way N/A 250 555 555

RR1J Cookline Perforated N/A 650 728 728

RR1G Cookline Perforated N/A 650 794 794

RR1H Cookline Perforated N/A 650 861 861

RR1E Cookline Perforated N/A 650 981 981

RR1F Service Line 3-Way N/A 250 520 520

RR1C Service Line 3-Way N/A 250 253 253

RR1D Cookline Perforated N/A 650 437 437

RRU-1 Kitchen

DESIGN PRELIM FINAL

NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM

RR1A Dishwasher Perforated N/A 200

RR1B Dishwasher Perforated N/A

4400 6027 6027

0 0

4400

200 422 422

100% 100%

6027

476 476

Page 25: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

AIR DISTRIBUTION DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

SYSTEM:

0 0

3800 4745

100% 100%

3800 4745 4745SUPPLY AIR CFM

RETURN AIR CFM

OUTSIDE AIR CFM

OUTSIDE AIR RATIO %

Unit Total: 4745

RRU2B O/A RTU-2 N/A N/A 1900 NA 2373

NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM

RRU2A O/A RTU-1 N/A N/A 1900 NA 2372

RRU-2 O/A RTU's 1 & 2

DESIGN PRELIM FINAL

Page 26: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

AIR DISTRIBUTION DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

SYSTEM:

Ceiling Grille

E6E Women's Restroom Ceiling Grille N/A 135 232 143

Women's Restroom

E6C Women's Restroom

E6B Men's Restroom

E6A Men's Restroom

805

Ceiling Grille N/A

EXHAUST AIR CFM

Ceiling Grille N/A

135

Restrooms

135

135

AREA SERVED

E6D

N/A

Ceiling Grille N/A

DESIGN PRELIM FINAL

TYPE INLET SIZE CFM CFM CFM

EF-6

328

NO.

265 289 245

1190 793

182 125

147

159 133

Page 27: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

DESIGN DATA

EQUIP. DATA

TEST DATA

ACTUAL VOLTS 208 209 208 208 209

3.3 1.6 1.7

208 208 209

EXHAUST CFM 1774 3396 1420 932

N/A N/A N/A

EXTERNAL S.P. N/A N/A N/A N/A

SUCTION / DISCHARGE N/A N/A N/A N/A N/A

MOTOR HERTZ N/A N/A N/A N/A

SHEAVE CENTERLINE N/A N/A N/A

1.5

N/A

RPM - INITIAL / FINAL 1174 1073 1089 1089 1102 905 1586 1487

1.3 1.4 1.3

208

OPERATING AMPS 1.9 1.9 1.9 3.4

FAN SHEAVE AK54 x 3/4" AK54 x 3/4" AK54 x 3/4" AK39 x 3/4"

BELT(S) AX23 AX25 AX23 AX19

MOTOR SHEAVE 1VL40 x 5/8" 1VL40 x 5/8" 1VL40 x 5/8" 1VL40 x 5/8"

• FLA / SF 3.3 1.15 4.7 1.15 2.7

• RPM 1730 1720 1735 1730

• VOLTS / PHASE

1.15 1.8 1.15

• MODEL NO. N/A N/A N/A N/A

• HP 1 1 1/2 3/4 1/2

FAN MOTOR Weg Weg Weg Weg

• MODEL NO. NCA14FA NCA16FA NCA14FA NCA8FA

• SERIAL NO. 1889365 1889365 1889365 1889365

FAN RPM N/A N/A N/A N/A

UNIT MFR. Captive-Aire Captive-Aire Captive-Aire Captive-Aire

FAN HP 1 1 1/2 3/4 1/2

VOLTS / PHASE

EXTERNAL S.P. 1.0'' 1.0'' 1.0'' 1.0''

208/3 208/3 208/3 208/3

EXHAUST FAN (EF) DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

MODEL NUMBER NCA14FA NCA16FA NCA14FA NCA8FA

EXHAUST CFM 1750 3150 1200 875

EF-1 EF-2 EF-3 EF-4

KH-1 KH-2 KH-3 KH-4

208/3 208/3 208/3 208/3

3.2

208 208 209

Page 28: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

EXHAUST FAN (EF) DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

DESIGN DATA

EQUIP. DATA

TEST DATA

EXHAUST CFM 2283 793

EXTERNAL S.P. N/A N/A

MOTOR HERTZ N/A N/A

SUCTION / DISCHARGE N/A N/A N/A N/A

OPERATING AMPS 6.4 NA NA 3.1 NA NA

ACTUAL VOLTS 119 NA NA 119 NA NA

RPM - INITIAL / FINAL VSC VSC VSC VSC

BELT(S) Direct Drive Direct Drive

SHEAVE CENTERLINE N/A N/A

MOTOR SHEAVE Direct Drive Direct Drive

FAN SHEAVE Direct Drive Direct Drive

• FLA / SF 8.1 1.0 4.0 NA

• VOLTS / PHASE 115/1 115/1

• HP 1/2 1/4

• RPM 1625 1625

FAN MOTOR Marathon Marathon

• MODEL NO. N/A N/A

• MODEL NO. DU50HFA DR30HFA

• SERIAL NO. 1889365 1889365

FAN RPM N/A N/A

UNIT MFR. Captive-Aire Captive-Aire

MODEL NUMBER DU50HFA DR30HFA

VOLTS / PHASE 120/1 120/1

EXTERNAL S.P. 0.75'' 0.5''

FAN HP 1/2 1/4

Dishwasher Restrooms

EXHAUST CFM 800 805

EF-5 EF-6

Page 29: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

DESIGN DATA

EQUIP. DATA

A

B

C

D

E

F

TEST DATA

A

B

C

D

E

F

HOOD MFR.

• MODEL NO.

N/A

Kleen-Gard Kleen-Gard Kleen-Gard

N/A

N/A

Captive-Aire

N/A

Captive-Aire

5424 ND-2

Wall Canopy

N/A

EXHAUST CFM

BALANCE RATIO %

LOCATION:

Captive-Aire

5424 ND-2

Captive-Aire

Fryers Oven Broiler

N/A

KH-1 KH-2

3150

N/A N/A

N/A

Steamer

1200 875

4824 ND-2

1750

N/A

FILTER HEIGHT

FILTER MFR.

N/A

16

N/A

Kleen-Gard

N/A

5140 Diligent Drive, Melink City, AK 99705

MAKE-UP CFM

KH-4

FILTER LENGTHS

Wall Canopy Wall Canopy

N/A

KH-3

5424 ND-2

-2-

16

-1- -2--1-

16

-1-

KITCHEN HOOD (KH) DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

MUA OPEN. TYPE

MUA WIDTH/LENGTH

Wall Canopy

N/A

N/A

• HOOD TYPE

MUA OPEN. DIR.

N/A

N/A

N/A

N/A N/A N/A

16

N/A

932

148

-1-

138

-2-

132

141

N/A

235

with filter

sizes

above

with filter

velocities

below

249

-2-

N/A

-2-

Correlates

EXH. AVG. FPM

MUA CFM

MUA AVG. FPM

EXHAUST CFM

BALANCE RATIO %

16 16

-1- -2-

N/A

20

16

20

Correlates

-1-

20

20

20

16

20 16

16

20

N/A N/A N/A

1774 3396 1420

245

137

N/AN/A N/A

232

202

204

214

N/A

226 298

232

308

16

20

16 16 16

N/A

20

-2-

20

16

N/AN/A

147

152

163

-1- -2-

150

-1-

319

Page 30: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

KITCHEN HOOD (KH) DATA

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

DESIGN DATA

EQUIP. DATA

A

B

C

D

E

F

TEST DATA

A

B

C

D

E

F

BALANCE RATIO %

Correlates

with filter

sizes

above

EXH. CFM

MUA CFM

FILTER MFR.

2283

N/A

N/A

below

MUA AVG. FPM

EXH. AVG. FPM

with filter

12

Correlates

12

HOOD MFR. Captive-Aire

4224 VHB

N/A

N/AMUA WIDTH/LENGTH

• MODEL NO.

• HOOD TYPE

velocities

MUA OPEN. TYPE

N/A

Raw Opening

MUA OPEN. DIR.

FILTER HEIGHT

FILTER LENGTHS

MAKE-UP CFM

EXHAUST CFM

BALANCE RATIO %

N/A

KH-5

N/A

800

2283

-1- -2-

N/A

Dishwasher

Wall Canopy

-1- -2-

N/A

Page 31: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

EQUIP. DATA

PROGRAM

OCCUPIED

UNOCCUPIED

SETUP

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

THERMOSTAT SETTINGS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

Kitchen

MANUFACTURER.

MODEL. NUMBER

LOCATION

RRU-1

Kitchen

Carolina Products Inc.

N/A

Controlled by CPI Controlled by CPI Controlled by CPIHEAT ° F

COOL ° F

START TIME (Primary)

On

Controlled by CPI

RTU-1 RTU-2 RTU-3

Dining / R.R. Bar Dining Kitchen

Carolina Products Inc. Carolina Products Inc. Carolina Products Inc.

N/A N/A N/A

Kitchen Kitchen Kitchen

Controlled by CPI

START TIME (Secondary)

FAN

Remote

Locked

START TIME (Secondary)

HEAT °F

SENSOR

LOCK-OUT

Controlled by CPI Controlled by CPI Controlled by CPI

On On On

Remote Remote Remote

Locked Locked Locked

COOL °F

START TIME (Primary)

Page 32: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

LOCATION: 5140 Diligent Drive, Melink City, AK 99705

THERMOSTAT SETTINGS

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

EQUIP. DATA

PROGRAM

OCCUPIED

UNOCCUPIED

SETUP

MODEL. NUMBER N/A

MANUFACTURER. Carolina Products Inc.

RRU-2

O/A RTU's 1 & 2

HEAT ° F Controlled by CPI

LOCATION Kitchen

START TIME (Primary)

COOL ° F

HEAT °F Controlled by CPI

START TIME (Secondary)

START TIME (Primary)

COOL °F

FAN On

START TIME (Secondary)

LOCK-OUT Locked

SENSOR Remote

Page 33: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

���� NLOCATION: 5140 Diligent Drive, Melink City, AK 99705

BUILDING AND ROOFTOP LAYOUT

PROJECT: Sample Balance Report #3 DATE: 6/30/2016

Page 34: CERTIFIED TEST ADJUST BALANCE REPORT - Melink … · TACHOMETER: VOLTMETER / AMPMETER: 322 Serial #: 10830582 08/10 ... This air balance report is based on actual field readings …

���� NLOCATION: 5140 Diligent Drive, Melink City, AK 99705

BUILDING AND ROOFTOP LAYOUT

PROJECT: Sample Balance Report #3 DATE: 6/30/2016