PROJECT: Sample Balance Report #3
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
ARCHITECT: Architects R' Us
Edison Engineers
PROJECT NUMBER: P1001021
GEN. CONTRACTOR: We Build'm Better
CERTIFIED TEST ADJUST BALANCE REPORT
"THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS
AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE
CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING,
ADJUSTING, AND BALANCING OF ENVIROMENTAL SYSTEMS. ANY VARIANCES FROM
DESIGN QUANTITES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST-
ADJUST-BALANCE REPORT PROJECT SUMMARY."
www.melinkcorp.com • [email protected]
1/0/1900
1/0/1900
5140 River Valley Road, Milford, Ohio 45150 USA
Phone: (513) 965-7300 • Fax: (513) 965-7350
1/0/1900
T & B ENGINEER: Stephen K. Melink, PE
6/30/2016ORIGINAL VISIT DATE:
MECH. ENGINEER:
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
TABLE OF CONTENTS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
ABBREVIATIONS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
ABBREVIATIONS
AHU - Air Handling Unit AMP - Amperage BP - Building Pressure CFM - Cubic Feet/Minute EF - Exhaust Fan EH - Entry Heater ERU - Energy Recycling Unit ESP - External Static Pressure FLA - Full Load Amperage HP - Horse Power HZ - Hertz KH - Kitchen Hood KW - Kilowatt
MUA - Makeup Air Unit Volts - Voltage OA - Outside Air RA - Return Air RPM - Revolutions Per Minute RTU - Roof Top Unit SF - Supply Fan / Safety Factor SP - Static Pressure VAV - Variable Air Volume WC - Water Column
MELINK CREDENTIALS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
Fax: NA
Marcus Mills
Fax: NA
E-mail: [email protected]
MECH. CONTRACTOR:
(555) 424-4244
Fax: NA
E-mail: [email protected]
E-mail: N/A
Ivan Workhard
Phone: (555) 112-2222
MELINK TECHNICIAN:
N/A
Phone:
E-mail: [email protected]
MELINK SERVICE ENG.: John Smith
Phone: (513) 965-7300
E-mail:
REVISIT TECHNICIAN: N/A
Fax: (513) 965-7350
Phone: N/A
Fax:
SUPERINTENDENT: Donald Duck
Phone: (555) 112-6828
E-mail:
LOCATION:
PROJECT MANAGER:
Phone:
Fax:
Sam Sampson
(555) 683-1122
NA
5140 Diligent Drive, Melink City, AK 99705
TEST AND BALANCE CONTACT INFORMATION
6/30/2016PROJECT: DATE: Sample Balance Report #3
Calibration Date: NA
Model #: NA
Serial #: NA
Serial #:
Alnor
EBT721-ME
91206032
FLOW HOOD:
TEST AND BALANCE EQUIPMENT INFORMATION
6/30/2016PROJECT: DATE: Sample Balance Report #3
5140 Diligent Drive, Melink City, AK 99705LOCATION:
Model #:
PITOT TUBE: NA
08/10/13
NA
Model #: NA
Calibration Date:
VANE ANEMOMETER:
NA
NA
Fluke
Serial #:
Calibration Date:
1808425
TACHOMETER:
VOLTMETER / AMPMETER:
322
Serial #: 10830582
08/10/13
Model #:
Calibration Date:
Serial #: NA
NACalibration Date:
08/10/13
MANOMETER: NA
Model #: NA
Calibration Date:
MONARCH
Model #: PT99
Serial #:
The following corrections were performed by Melink and/or the contractors on-site.
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
FIELD SUMMARY: CORRECTIONS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
This air balance report is based on actual field readings and measurements taken from the store’s HVAC
systems during operation. All systems were also balanced to within +/- 10% of design unless noted otherwise.
N/A N/A
Melink recommends revisiting this store due to the deficiencies listed above.
Project Manager: Please contact Melink in order to authorize the revisit.
YesRevisit necessary? 30-60 days after opening? Before opening?
The following list details the remaining deficiencies of the store’s HVAC and exhaust systems. These
corrections are necessary to comply with the design specifications.
DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
FIELD SUMMARY: PUNCH LIST
PROJECT: Sample Balance Report #3
The following list details the remaining deficiencies of the store’s HVAC and exhaust systems. These
corrections are necessary to comply with the design specifications.
DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
FIELD SUMMARY: PUNCH LIST
PROJECT: Sample Balance Report #3
Project Manager: Please contact Melink in order to authorize the revisit.
Melink recommends revisiting this store due to the deficiencies listed above.
Revisit necessary? Yes 30-60 days after opening? N/A Before opening? N/A
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
The following list details the recommendations for improving comfort and energy efficiency. These items are
not requirements of the design specifications.
FIELD SUMMARY: RECOMMENDATIONS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
5140 Diligent Drive, Melink City, AK 99705
PROJECT: Sample Balance Report #3
PHOTOS
DATE: 6/30/2016
Picture 2: Rubber grommets are not installed.Picture 1: Gas lines are not painted.
LOCATION:
Picture 4: Condensate drains are not installed.
Picture 6: Grease filters are installed.
Picture 3: Electrical penetrations are not sealed.
Picture 5: Grease traps are installed.
5140 Diligent Drive, Melink City, AK 99705
PROJECT: Sample Balance Report #3
PHOTOS
DATE: 6/30/2016
LOCATION:
Picture 9: EF-6 VSC is set and marked. Picture 10: RRU filters are installed.
Picture 7: Supply diffusers are insulated. Picture 8: Dampers are flagged.
STANDARD 1 2 3 1 2
Verify proper unit locations √ √ √ √ √Verify units marked for easy identification X X X X X
Inspect units • Unit sealed and properly seated to roof curb X X X X X
• Unit nameplate data matches design √ √ √ X X
• Motor nameplate data matches design N/A N/A N/A N/A N/A
• No unusual vibration or noise √ √ √ √ √
• All filters installed, clean and secure √ √ √ √ √ • Condenser coil clean and free of damage √ √ √ √ √
• Evaporator coil clean and free of damage √ √ √ √ √
• Gas cocks turned on √ √ √ √ √ • Gas pipe painted X X X X X
• Condensate drain lines properly installed X X X X X
• P-Traps properly installed X X X X X
• Drain lines properly sloped X X X X X
Remove unit access panels
• Panels open freely and fully √ √ √ √ √
• Panels latch securely √ √ √ √ √
• Belts properly tensioned and free of damage N/A N/A √ √ √
• Pulleys properly aligned N/A N/A √ √ √
• Blower wheel clean and free of damage √ √ √ √ √
• Control transformer wired for correct voltage √ √ √ √ √
Check disconnect switches and covers
• Verify on/off disconnects work √ √ √ √ √
• Verify voltage input correct √ √ √ √ √
• Verify switch covers installed √ √ √ √ √
Power-on diagnostic check
• Fans operating in correct rotation √ √ √ √ √
• Compressors operating in correct rotation √ √ √ √ √
• No unusual vibration or noise √ √ √ √ √
Outside air (OA) dampers
• Outside air dampers installed and operational N/A N/A √ √ √
• Ensure slightly positive building pressure N/A N/A √ √ √
• Position marked for reference N/A N/A √ N/A N/A
• Sticker affixed to unit to preclude tampering √ √ √ √ √
RTU RRU
STATUSDESCRIPTION
ROOFTOP INSPECTION
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
ROOFTOP INSPECTION
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
STANDARD 1 2 3 4 5 6
Verify proper unit locations √ √ √ √ √ √
Verify units marked for easy identification X X X X X X
Inspect units
• Unit sealed and properly seated to roof curb √ √ √ √ X X
• Unit nameplate data matches design √ √ √ √ √ √
• Motor nameplate data matches design √ √ √ √ √ √
• No unusual vibration or noise √ √ √ √ √ √
Exhaust fans (EF)
• Transition from exhaust duct to fan installed √ √ √ √ √ √
• Duct continuously welded and liquid tight √ √ √ √ √ N/A
• Fan hinged and opened for easy access √ √ √ √ N/A N/A
• Grease traps properly installed √ √ √ √ N/A N/A
Remove unit access panels
• Panels open freely and fully √ √ √ √ √ √
• Panels latch securely √ √ √ √ √ √
• Belts properly tensioned and free of damage √ √ √ √ N/A N/A
• Pulleys properly aligned √ √ √ √ N/A N/A
• Blower wheel clean and free of damage √ √ √ √ √ √
Check disconnect switches and covers
• Verify on/off disconnects work √ √ √ √ √ √
• Verify voltage input correct √ √ √ √ √ √
• Verify switch covers installed √ √ √ √ √ √
Power-on diagnostic check
• Fans operating in correct rotation √ √ √ √ √ √
EF
DESCRIPTION STATUS
STANDARD
Supply duct system 1 2 3 1 2
• Ductwork is installed as per design √ √ √ √ √ • All volume dampers are properly installed √ √ √ X √
• Dampers are accessible and operable √ √ √ X √
• Ductwork is properly covered with insulation, √ √ √ √ √ and insulation is secure
• Tops of diffusers are properly insulated √ √ √ √ √
• Installed diffusers match design √ √ X √ √
Exhaust duct system 1 2 3 4 5 6 • Cleanouts are installed where applicable √ √ √ √ N/A N/A • Fire wrap is installed on duct as specified √ √ √ √ N/A N/A
• Horizontal duct is sloped as specified √ √ √ √ N/A N/A
• Welds appear to be liquid tight √ √ √ √ N/A N/A
RTU
EF
ABOVE CEILING INSPECTION
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
RRU
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
DESCRIPTION STATUS
STANDARD
Thermostats 1 2 3 1 2
• Remote sensor is installed in its correct location √ √ √ √ √ • Remote sensor is wired to the proper thermostat √ √ √ √ √
• Thermostat is wired to the correct unit √ √ √ √ √
• Thermostat has proper operation √ √ √ √ √ • Thermostat is programmed correctly N/A N/A N/A N/A N/A
• Unit was cycled to verify proper operation √ √ √ √ √
• Heating mode tested satisfactorily √ √ √ √ √
• Cooling mode tested satisfactorily √ √ √ √ √
Exhaust hoods 1 2 3 4 5 • Grease cups are installed √ √ √ √ N/A
• All grease filters are installed √ √ √ √ N/A
• Filters are of correct type and size √ √ √ √ N/A
• Cooking appliances are operating X X X X N/A
• Cooking appliances properly located under hoods √ √ √ √ N/A • Smoke capture is satisfactory X X X X N/A
Comfort
• Noticeable drafts?
• Comfort is good in all areas?
Communication
• Final results were discussed with:
–Superintendent
–Project manager
–Store manager (if applicable)
• A punch list of deficiencies was provided to:
–Superintendent and/or operations
–Project manager
–Store manager (if applicable)
• Business card was left on site with contact info. Yes
KH
RTU
N/A
Yes
Yes
N/A
Yes
Yes
No
STATUS
Yes
BELOW CEILING INSPECTION
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
RRU
5140 Diligent Drive, Melink City, AK 99705LOCATION:
DESCRIPTION
CFM
CFM
W.C.
FINAL BUILDING BALANCE = 808
FINAL BUILDING PRESSURE = +0.016''
DESIGN TOTAL + 8800 DESIGN TOTAL – 8580
FINAL TOTAL + 11406 FINAL TOTAL – 10598
220DESIGN BUILDING BALANCE =
600
Design
N/ARTU-1
RTU-2
4745 EF-5
EF-6
N/A EF-2
634 EF-3
6027 EF-4
MAKE-UP AIR EXHAUST AIR
Final
N/A EF-1
875
800
805
3800
4400
( IN CFM )
RRU-1
N/A
793
RRU-2
3396
1420
3150
1200
BUILDING AIR BALANCE
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
932
2283
RTU-3
TEST RESULTS
1774
Final Design
1750
AMPS
EF-5 6.4 EF-5 6.4
EF-6 3.9 EF-6 3.1
EF-2 3.3 EF-2 3.3
EFFICIENCY 3%
TOTAL + 39.9 TOTAL – 38.9
MOTOR AMP SAVINGS 1.0
EF-4 1.5 EF-4 1.3
RTU-2 2.2 RTU-2 2.9
RTU-3 4.2 RTU-3 3.8
EF-3 1.8 EF-3 1.6
RRU-1 6.7 RRU-1 6.7
RRU-2 5.6 RRU-2 5.6
EF-1 2.1 EF-1 1.9
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
MOTOR LOAD SUMMARY
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
TEST RESULTS
( IN AMPS )
INITIAL FINAL
RTU-1 2.2 RTU-1 2.2
DESIGN DATA
EQUIP. DATA
TEST DATA
EXTERNAL S.P.
OPERATING AMPS 2.92.8
N/A
75%
2373
0.44''
1.9 2.1
MOTOR HERTZ
SUPPLY CFM
RETURN CFM
RET/SUCT/ DISCHARGE 0.23'' 0.22'' 0.70'' 0.15''
3185
0.37''
N/A
N/A
208/3 208/3
1
N/A
N/A
3.1
0.42''
N/A
6027
0
5
1725
N/A
N/A
6/30/2016
0.60''
N/A
4.1 3.7 3.7
1VL40 x 5/8"
AK64 x 1"
AX35
N/A
778 739
209 208
4400
100%
RRU240F3
20
RRU-1
Kitchen
0
DATE:
6
RTU-3
Kitchen
2400
1720
600
25%
4400
YHC072F3
RTU-2
Bar Dining
RTU-1
Dining / R.R.
3200
1300
Marathon
N/A
EBM Papst
N/A
3200
1200
1900
59%
YHC092F3
208/3
7.5
7.5
208/3
N/A
Trane
6027
100%
BX81
N/A
636 636
209 208
N/A
Not Listed
8.5 NA
2372
72%
N/A
3303
1011
208 208
2.6
VOLTS / PHASE
Trane
YHC092F3RLA
208/3 208/3
N/A
Trane
YHC092F3RLA
134710233L134710246L
N/A
Trane
YHC072F3RLA
134612436L
SHEAVE CENTERLINE
• RPM
• VOLTS / PHASE
• FLA / SF
MOTOR SHEAVE
FAN SHEAVE
BELT(S)
NA
208/3
Direct Drive
Direct Drive
Direct Drive
N/A
5.0
1725
1VL40 x 7/8"
19" x 1 3/16"
208/3
Direct Drive
1.5
Not Listed
8.5 NA
ROOFTOP UNITS (RTU) DATA
PROJECT:
LOCATION:
UNIT MFR.
RETURN CFM
EXTERNAL S.P.
OUTSIDE AIR CFM
OUTSIDE AIR RATIO %
N/A
YHC092F3
7.5
N/A
N/A
MODEL NUMBER
CAPACITY (TONS)
SUPPLY CFM
RRU240E3NEAA
134411454D
1900
59%
EBM Papst
N/A
N/A
FAN HP
Sample Balance Report #3
5140 Diligent Drive, Melink City, AK 99705
OUTSIDE AIR CFM
OUTSIDE AIR RATIO %
6.8 6.4 6.9
209
RPM - INITIAL / FINAL
ACTUAL VOLTS
FAN RPM
• RATED TONS
FAN MOTOR
• MODEL NO.
• SERIAL NO.
• HP
• MODEL NO.
Direct Drive
Direct Drive
N/A
4.9 VDC 4.9 VDC
634
893
0.22'' 0.76''
19%
5.0 VDC 5.7 VDC
3314
2667
0.00'' 0.20'' 0.42''0.31'' 0.58'' 0.29''
Marathon
20
16.7
7.5
208 208
6
209 208
N/A
208
6/30/2016DATE:
ROOFTOP UNITS (RTU) DATA
PROJECT:
LOCATION:
Sample Balance Report #3
5140 Diligent Drive, Melink City, AK 99705
DESIGN DATA
EQUIP. DATA
TEST DATA
OUTSIDE AIR RATIO % 100%
OUTSIDE AIR CFM 4745
SUPPLY CFM 4745
RETURN CFM 0
MOTOR SHEAVE 1VL40 x 7/8"
FAN SHEAVE BK110 x 1 3/16"
SHEAVE CENTERLINE N/A
209 208 208ACTUAL VOLTS
RPM - INITIAL / FINAL 540 540
BELT(S) BX68
EXTERNAL S.P. 0.572''
MOTOR HERTZ N/A
RET/SUCT/ DISCHARGE
5.40 5.70
0.00 0.28 0.57
OPERATING AMPS
• RPM 1725
• VOLTS / PHASE
• FLA / SF 9.4 1.2
208/3
• MODEL NO. N/A
• HP 3
• RATED TONS 15
FAN MOTOR Marathon
• MODEL NO. RRU180E3NOAA
• SERIAL NO. 134411488D
OUTSIDE AIR CFM 3800
UNIT MFR. Trane
FAN HP N/A
VOLTS / PHASE
FAN RPM N/A
208/3
OUTSIDE AIR RATIO % 100%
EXTERNAL S.P. N/A
MODEL NUMBER RRU180F3
CAPACITY (TONS) 15
RETURN CFM 0
O/A RTU's 1 & 2
SUPPLY CFM
RRU-2
3800
5.60
SYSTEM:
OUTSIDE AIR RATIO %
SUPPLY AIR CFM
RETURN AIR CFM
OUTSIDE AIR CFM
OUTLET SIZE
N/A
N/A
N/A
300
N/A
301
N/A
N/A 300
Dining
280
310
185
300
300
4-Way
4-Way
4-Way
AIR DISTRIBUTION DATA
PROJECT: Sample Balance Report #3 DATE:
FINAL
CFM
3200
1300
1900
59%
280
N/A
N/A
N/A
1300N/A
Dining / R.R.
R1A
1J
Dining
1B
1C
1D
1K
1E
1F
1G
1H
N/A
CFM
PRELIM
285
291
326
306
319
316
291
346
306
285
280
6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
NO.
RTU-1
329 329
N/A
N/A
1802-Way
1011
185
DESIGN
1A
AREA SERVED
Dining 300
CFMTYPE
4-Way
1I
Dining
Dining
Dining
Dining
Men's Restroom
Hallway
319
329
4-Way
4-Way
1L
4-Way
4-Way
332
120
167
160
Return Grille
332
169
167
172
306
Women's Restroom
Dining
Dining
Dining
4-Way
4-Way
NA
4-Way
72%
3300 3303
1011
2372
AIR DISTRIBUTION DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
SYSTEM:
OUTSIDE AIR RATIO %
SUPPLY AIR CFM
RETURN AIR CFM
OUTSIDE AIR CFM
59% 75%
R2A Bar Return Grille N/A 600 NA 427
R2B Bar Return Grille N/A 600 NA 466
AREA SERVED TYPE OUTLET SIZE CFM CFM CFM
2A Bar Dining 4-Way
2B
2G Bar Dining 4-Way N/A 500 378 434
2H Bar Dining
2C Vestibule 3-Way N/A 200 250 287
2D Hostess 4-Way N/A 200 274 315
4-Way N/A 500 326 374
N/A
RTU-2 Bar Dining
4-Way
N/A 300
2E Bar Dining 4-Way N/A 500
2F Bar Dining N/A 500
2I Bar Dining 4-Way
NO.
Bar Dining 4-Way N/A 300
DESIGN
303
358
3200 2772 3185
1200 893
PRELIM FINAL
1900
348
200 251 289
264
2373
311
415 477
303
AIR DISTRIBUTION DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
SYSTEM:
1720 2667
600 634
25% 19%
2400 3737 3314SUPPLY AIR CFM
RETURN AIR CFM
OUTSIDE AIR CFM
OUTSIDE AIR RATIO %
R3B Kitchen Return Grille N/A 1400 NA 2441
R3A Office Return Grille N/A 320 NA 226
3F Kitchen Prep Perforated NA 450 848 720
3D Storage 4-Way NA 450 739 578
3E Kitchen Prep 4-Way NA 450 632 537
3B Receiving 3-Way NA 280 512 435
3C Kitchen Prep 3-Way NA 450 369 503
NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM
3A Office 1-Way NA 320 637 541
RTU-3 Kitchen
DESIGN PRELIM FINAL
AIR DISTRIBUTION DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
SYSTEM:
OUTSIDE AIR RATIO %
SUPPLY AIR CFM
RETURN AIR CFM
OUTSIDE AIR CFM
RR1I Service Line 3-Way N/A 250 555 555
RR1J Cookline Perforated N/A 650 728 728
RR1G Cookline Perforated N/A 650 794 794
RR1H Cookline Perforated N/A 650 861 861
RR1E Cookline Perforated N/A 650 981 981
RR1F Service Line 3-Way N/A 250 520 520
RR1C Service Line 3-Way N/A 250 253 253
RR1D Cookline Perforated N/A 650 437 437
RRU-1 Kitchen
DESIGN PRELIM FINAL
NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM
RR1A Dishwasher Perforated N/A 200
RR1B Dishwasher Perforated N/A
4400 6027 6027
0 0
4400
200 422 422
100% 100%
6027
476 476
AIR DISTRIBUTION DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
SYSTEM:
0 0
3800 4745
100% 100%
3800 4745 4745SUPPLY AIR CFM
RETURN AIR CFM
OUTSIDE AIR CFM
OUTSIDE AIR RATIO %
Unit Total: 4745
RRU2B O/A RTU-2 N/A N/A 1900 NA 2373
NO. AREA SERVED TYPE OUTLET SIZE CFM CFM CFM
RRU2A O/A RTU-1 N/A N/A 1900 NA 2372
RRU-2 O/A RTU's 1 & 2
DESIGN PRELIM FINAL
AIR DISTRIBUTION DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
SYSTEM:
Ceiling Grille
E6E Women's Restroom Ceiling Grille N/A 135 232 143
Women's Restroom
E6C Women's Restroom
E6B Men's Restroom
E6A Men's Restroom
805
Ceiling Grille N/A
EXHAUST AIR CFM
Ceiling Grille N/A
135
Restrooms
135
135
AREA SERVED
E6D
N/A
Ceiling Grille N/A
DESIGN PRELIM FINAL
TYPE INLET SIZE CFM CFM CFM
EF-6
328
NO.
265 289 245
1190 793
182 125
147
159 133
DESIGN DATA
EQUIP. DATA
TEST DATA
ACTUAL VOLTS 208 209 208 208 209
3.3 1.6 1.7
208 208 209
EXHAUST CFM 1774 3396 1420 932
N/A N/A N/A
EXTERNAL S.P. N/A N/A N/A N/A
SUCTION / DISCHARGE N/A N/A N/A N/A N/A
MOTOR HERTZ N/A N/A N/A N/A
SHEAVE CENTERLINE N/A N/A N/A
1.5
N/A
RPM - INITIAL / FINAL 1174 1073 1089 1089 1102 905 1586 1487
1.3 1.4 1.3
208
OPERATING AMPS 1.9 1.9 1.9 3.4
FAN SHEAVE AK54 x 3/4" AK54 x 3/4" AK54 x 3/4" AK39 x 3/4"
BELT(S) AX23 AX25 AX23 AX19
MOTOR SHEAVE 1VL40 x 5/8" 1VL40 x 5/8" 1VL40 x 5/8" 1VL40 x 5/8"
• FLA / SF 3.3 1.15 4.7 1.15 2.7
• RPM 1730 1720 1735 1730
• VOLTS / PHASE
1.15 1.8 1.15
• MODEL NO. N/A N/A N/A N/A
• HP 1 1 1/2 3/4 1/2
FAN MOTOR Weg Weg Weg Weg
• MODEL NO. NCA14FA NCA16FA NCA14FA NCA8FA
• SERIAL NO. 1889365 1889365 1889365 1889365
FAN RPM N/A N/A N/A N/A
UNIT MFR. Captive-Aire Captive-Aire Captive-Aire Captive-Aire
FAN HP 1 1 1/2 3/4 1/2
VOLTS / PHASE
EXTERNAL S.P. 1.0'' 1.0'' 1.0'' 1.0''
208/3 208/3 208/3 208/3
EXHAUST FAN (EF) DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
MODEL NUMBER NCA14FA NCA16FA NCA14FA NCA8FA
EXHAUST CFM 1750 3150 1200 875
EF-1 EF-2 EF-3 EF-4
KH-1 KH-2 KH-3 KH-4
208/3 208/3 208/3 208/3
3.2
208 208 209
EXHAUST FAN (EF) DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
DESIGN DATA
EQUIP. DATA
TEST DATA
EXHAUST CFM 2283 793
EXTERNAL S.P. N/A N/A
MOTOR HERTZ N/A N/A
SUCTION / DISCHARGE N/A N/A N/A N/A
OPERATING AMPS 6.4 NA NA 3.1 NA NA
ACTUAL VOLTS 119 NA NA 119 NA NA
RPM - INITIAL / FINAL VSC VSC VSC VSC
BELT(S) Direct Drive Direct Drive
SHEAVE CENTERLINE N/A N/A
MOTOR SHEAVE Direct Drive Direct Drive
FAN SHEAVE Direct Drive Direct Drive
• FLA / SF 8.1 1.0 4.0 NA
• VOLTS / PHASE 115/1 115/1
• HP 1/2 1/4
• RPM 1625 1625
FAN MOTOR Marathon Marathon
• MODEL NO. N/A N/A
• MODEL NO. DU50HFA DR30HFA
• SERIAL NO. 1889365 1889365
FAN RPM N/A N/A
UNIT MFR. Captive-Aire Captive-Aire
MODEL NUMBER DU50HFA DR30HFA
VOLTS / PHASE 120/1 120/1
EXTERNAL S.P. 0.75'' 0.5''
FAN HP 1/2 1/4
Dishwasher Restrooms
EXHAUST CFM 800 805
EF-5 EF-6
DESIGN DATA
EQUIP. DATA
A
B
C
D
E
F
TEST DATA
A
B
C
D
E
F
HOOD MFR.
• MODEL NO.
N/A
Kleen-Gard Kleen-Gard Kleen-Gard
N/A
N/A
Captive-Aire
N/A
Captive-Aire
5424 ND-2
Wall Canopy
N/A
EXHAUST CFM
BALANCE RATIO %
LOCATION:
Captive-Aire
5424 ND-2
Captive-Aire
Fryers Oven Broiler
N/A
KH-1 KH-2
3150
N/A N/A
N/A
Steamer
1200 875
4824 ND-2
1750
N/A
FILTER HEIGHT
FILTER MFR.
N/A
16
N/A
Kleen-Gard
N/A
5140 Diligent Drive, Melink City, AK 99705
MAKE-UP CFM
KH-4
FILTER LENGTHS
Wall Canopy Wall Canopy
N/A
KH-3
5424 ND-2
-2-
16
-1- -2--1-
16
-1-
KITCHEN HOOD (KH) DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
MUA OPEN. TYPE
MUA WIDTH/LENGTH
Wall Canopy
N/A
N/A
• HOOD TYPE
MUA OPEN. DIR.
N/A
N/A
N/A
N/A N/A N/A
16
N/A
932
148
-1-
138
-2-
132
141
N/A
235
with filter
sizes
above
with filter
velocities
below
249
-2-
N/A
-2-
Correlates
EXH. AVG. FPM
MUA CFM
MUA AVG. FPM
EXHAUST CFM
BALANCE RATIO %
16 16
-1- -2-
N/A
20
16
20
Correlates
-1-
20
20
20
16
20 16
16
20
N/A N/A N/A
1774 3396 1420
245
137
N/AN/A N/A
232
202
204
214
N/A
226 298
232
308
16
20
16 16 16
N/A
20
-2-
20
16
N/AN/A
147
152
163
-1- -2-
150
-1-
319
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
KITCHEN HOOD (KH) DATA
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
DESIGN DATA
EQUIP. DATA
A
B
C
D
E
F
TEST DATA
A
B
C
D
E
F
BALANCE RATIO %
Correlates
with filter
sizes
above
EXH. CFM
MUA CFM
FILTER MFR.
2283
N/A
N/A
below
MUA AVG. FPM
EXH. AVG. FPM
with filter
12
Correlates
12
HOOD MFR. Captive-Aire
4224 VHB
N/A
N/AMUA WIDTH/LENGTH
• MODEL NO.
• HOOD TYPE
velocities
MUA OPEN. TYPE
N/A
Raw Opening
MUA OPEN. DIR.
FILTER HEIGHT
FILTER LENGTHS
MAKE-UP CFM
EXHAUST CFM
BALANCE RATIO %
N/A
KH-5
N/A
800
2283
-1- -2-
N/A
Dishwasher
Wall Canopy
-1- -2-
N/A
EQUIP. DATA
PROGRAM
OCCUPIED
UNOCCUPIED
SETUP
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
THERMOSTAT SETTINGS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
Kitchen
MANUFACTURER.
MODEL. NUMBER
LOCATION
RRU-1
Kitchen
Carolina Products Inc.
N/A
Controlled by CPI Controlled by CPI Controlled by CPIHEAT ° F
COOL ° F
START TIME (Primary)
On
Controlled by CPI
RTU-1 RTU-2 RTU-3
Dining / R.R. Bar Dining Kitchen
Carolina Products Inc. Carolina Products Inc. Carolina Products Inc.
N/A N/A N/A
Kitchen Kitchen Kitchen
Controlled by CPI
START TIME (Secondary)
FAN
Remote
Locked
START TIME (Secondary)
HEAT °F
SENSOR
LOCK-OUT
Controlled by CPI Controlled by CPI Controlled by CPI
On On On
Remote Remote Remote
Locked Locked Locked
COOL °F
START TIME (Primary)
LOCATION: 5140 Diligent Drive, Melink City, AK 99705
THERMOSTAT SETTINGS
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
EQUIP. DATA
PROGRAM
OCCUPIED
UNOCCUPIED
SETUP
MODEL. NUMBER N/A
MANUFACTURER. Carolina Products Inc.
RRU-2
O/A RTU's 1 & 2
HEAT ° F Controlled by CPI
LOCATION Kitchen
START TIME (Primary)
COOL ° F
HEAT °F Controlled by CPI
START TIME (Secondary)
START TIME (Primary)
COOL °F
FAN On
START TIME (Secondary)
LOCK-OUT Locked
SENSOR Remote
���� NLOCATION: 5140 Diligent Drive, Melink City, AK 99705
BUILDING AND ROOFTOP LAYOUT
PROJECT: Sample Balance Report #3 DATE: 6/30/2016
���� NLOCATION: 5140 Diligent Drive, Melink City, AK 99705
BUILDING AND ROOFTOP LAYOUT
PROJECT: Sample Balance Report #3 DATE: 6/30/2016