Class C Cargo Compartment ULD Suppression Agent Penetration Test. Second IMLBTCM Audience >. Harry Webster, FAA Fire Safety Br. September 9, 2014. Purpose. To determine the infiltration rate of Halon 1301 into a standard LD3 ULD. “Quick Look”, more rigorous tests to follow. Background. - PowerPoint PPT Presentation

Citation preview

Page 1: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Presented to:

By:

Date:

Federal AviationAdministrationClass C Cargo

Compartment ULD Suppression Agent Penetration Test

Second IMLBTCMAudience>

Harry Webster, FAA Fire Safety Br.

September 9, 2014

Page 2: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

2

Purpose

• To determine the infiltration rate of Halon 1301 into a standard LD3 ULD.

• “Quick Look”, more rigorous tests to follow

Page 3: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

3

Background

• Halon 1301 has been shown to be effective in suppressing the electrolyte fire associated with lithium-ion cells in thermal runaway.

• Halon 1301 has been shown to be an effective explosion suppressant.

• The effectiveness of the agent is predicated on the agent concentration and proximity to the fire.

Page 4: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

4

Why this is an issue

• Lithium-ion battery fires originating in ULD’s may not be exposed to the full concentration of Halon 1301.

• Potential for the explosive build up of unburned electrolyte gases.

Page 5: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

5

Test Setup

• Measure Halon concentration – Inside the environmental chamber– Inside the closed LD3– 20” above the floor

• Volumes– Chamber volume: 284 cubic feet– LD3 volume: 160 cubic feet

Page 6: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

6

Test Setup

Page 7: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

7

Results

• Test 1– Initial chamber concentration: 12.33%– Time to 5% concentration in LD3: 7:11 minutes

• Test 2– Initial chamber concentration: 8.93%– Time to 5% concentration in LD3: 11:04 minutes

Page 8: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

8

Additional Tests• Tests will be

conducted to measure the ability of Class C cargo compartment fire suppression agent to penetrate into standard AKE cargo containers.

Page 9: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

9

Additional Tests

• Aluminum AKE containers with flexible door coverings have been ordered. These types of containers are typical of what is used in many Class C cargo compartments.

• FE25 (HFC-125) will be used as a surrogate gas for Halon 1301. Gas concentrations will be measured in the compartment outside of the containers and within the containers

Page 10: Class C Cargo Compartment ULD Suppression Agent Penetration Test

Federal AviationAdministration

10

Additional Tests

• Variables include– Container loading– Simulated battery fire