105
JOINT BASE ELMENDORF-RICHARDSON STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 WATER DISTRIBUTION SYSTEMS 2021 714 FOURTH AVENUE, SUITE 100 FAIRBANKS, ALASKA PO Box 74040 FAIRBANKS, AK 99707 (907) 455-1500 www.doyonutilities.com

DIVISION 60 WATER DISTRIBUTION SYSTEMS...JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS 2021 1 Doyon Utilities, LLC SECTION 60.01

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • JOINT BASE ELMENDORF-RICHARDSON STANDARD CONSTRUCTION SPECIFICATIONS

    AND DETAILS

    DIVISION 60 WATER DISTRIBUTION

    SYSTEMS

    2021

    714 FOURTH AVENUE, SUITE 100 FAIRBANKS, ALASKA

    PO Box 74040 FAIRBANKS, AK 99707

    (907) 455-1500

    www.doyonutilities.com

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 i Doyon Utilities, LLC

    TABLE OF CONTENTS

    SECTION 60.01 - GENERAL .......................................................................................... 1

    Article 60.01.1 - Scope, Applicability, and Content of Specifications ....................................... 1

    Article 60.01.2 - Safety ............................................................................................................. 1

    Article 60.01.3 - Alaska Department of Environmental Conservation (ADEC) Approvals ........ 1

    Article 60.01.4 - Applicable Standards ..................................................................................... 2

    Article 60.01.5 - Contaminated Material ................................................................................... 3

    Article 60.01.6 - JBER Access Privileges for Contractor Personnel ......................................... 3

    Article 60.01.7 - Inspection, Notices, and Official Communications ......................................... 3

    Article 60.01.8 - Utility Locations and Dig Clearance Permit Requirements ............................ 4

    Article 60.01.9 - Hot Work Permit Requirements ..................................................................... 5

    Article 60.01.10 - Fire Hydrant Use Permit Requirements ....................................................... 5

    Article 60.01.11 - Submittals .................................................................................................... 5

    Article 60.01.12 - Permanent Materials Furnished by Doyon Utilities and by Contractor ......... 6

    Article 60.01.13 - Other Division Requirements ....................................................................... 6

    Article 60.01.14 - Water Shutdown Scheduling and Duration .................................................. 8

    Article 60.01.15 - Wastewater and/or Water System Valve Operation ..................................... 8

    Article 60.01.16 - Site Housekeeping and Clean-Up ................................................................ 8

    SECTION 60.02 - WATER LINES................................................................................... 9

    Article 60.02.1 - General .......................................................................................................... 9

    Article 60.02.2 - Material ........................................................................................................ 10

    Article 60.02.3 - Construction ................................................................................................. 15

    Article 60.02.4 - Flushing, Testing, and Disinfection .............................................................. 27

    Article 60.02.5 - Demolition .................................................................................................... 31

    SECTION 60.03 - UNDERGROUND VALVES ............................................................. 34

    Article 60.03.1 - General ........................................................................................................ 34

    Article 60.03.2 - Material ........................................................................................................ 34

    Article 60.03.3 - Construction ................................................................................................. 36

    SECTION 60.04 - FIRE HYDRANT ASSEMBLIES ...................................................... 39

    Article 60.04.1 - General ........................................................................................................ 39

    Article 60.04.2 - Material ........................................................................................................ 39

    Article 60.04.3 - Construction ................................................................................................. 41

    SECTION 60.05 - CONNECTIONS TO EXISTING WATER SYSTEMS ....................... 45

    Article 60.05.1 - General ........................................................................................................ 45

    Article 60.05.2 - Material ........................................................................................................ 45

    Article 60.05.3 - Construction ................................................................................................. 46

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 ii Doyon Utilities, LLC

    SECTION 60.06 - INTERIOR WATER SERVICES AND WATER METERS ................ 48

    Article 60.06.1 - General ........................................................................................................ 48

    Article 60.06.2 - Material ........................................................................................................ 48

    Article 60.06.3 - Construction ................................................................................................. 52

    SECTION 60.07 - WATER STORAGE TANKS ............................................................ 54

    Article 60.07.1 - General ........................................................................................................ 54

    Article 60.07.2 - Material ........................................................................................................ 54

    Article 60.07.3 - Construction ................................................................................................. 54

    SECTION 60.08 - BOOSTER STATIONS .................................................................... 55

    Article 60.08.1 - General ........................................................................................................ 55

    Article 60.08.2 - Material ........................................................................................................ 55

    Article 60.08.3 - Construction ................................................................................................. 55

    SECTION 60.09 - PRESSURE REDUCING STATIONS .............................................. 56

    Article 60.09.1 - General ........................................................................................................ 56

    Article 60.09.2 - Material ........................................................................................................ 56

    Article 60.09.3 - Construction ................................................................................................. 56

    SECTION 60.10 - TEMPORARY WATER SYSTEMS .................................................. 57

    Article 60.10.1 - General ........................................................................................................ 57

    Article 60.10.2 - Material ........................................................................................................ 57

    Article 60.10.3 - Construction ................................................................................................. 57

    SECTION 60.11 - RELOCATION OF DUCTILE IRON OR HDPE WATER LINES ...... 60

    Article 60.11.1 - General ........................................................................................................ 60

    Article 60.11.2 - Material ........................................................................................................ 60

    Article 60.11.3 - Construction ................................................................................................. 60

    SECTION 60.12 - RELOCATION OF COPPER WATER SERVICES .......................... 63

    Article 60.12.1 - General ........................................................................................................ 63

    Article 60.12.2 - Material ........................................................................................................ 63

    Article 60.12.3 - Construction ................................................................................................. 63

    SECTION 60.13 - REMOVING AND SALVAGING OF EXISTING FIRE HYDRANT ASSEMBLIES ............................................................................... 65

    Article 60.13.1 - General ........................................................................................................ 65

    Article 60.13.2 - Material ........................................................................................................ 65

    Article 60.13.3 - Construction ................................................................................................. 65

    SECTION 60.14 - REPLACEMENT, RESETTING, OR ADJUSTMENT OF VALVE BOXES ......................................................................................... 66

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 iii Doyon Utilities, LLC

    Article 60.14.1 - General ........................................................................................................ 66

    Article 60.14.2 - Material ........................................................................................................ 66

    Article 60.14.3 - Construction ................................................................................................. 66

    SECTION 60.15 - ADJUSTMENT OF KEY BOXES ..................................................... 68

    Article 60.15.1 - General ........................................................................................................ 68

    Article 60.15.2 - Material ........................................................................................................ 68

    Article 60.15.3 - Construction ................................................................................................. 68

    SECTION 60.16 - ABANDONMENT OF WATER WELLS ........................................... 69

    Article 60.16.1 - General ........................................................................................................ 69

    Article 60.16.2 - Material ........................................................................................................ 69

    Article 60.16.3 - Construction ................................................................................................. 69

    LIST OF WATER DISTRIBUTION SYSTEM STANDARD DETAILS ........................... 76

    Detail # Description

    00W6021 JBER Water Line Typical Trench Section

    00W6022 JBER Requirements for New or Rerouted Water Line Crossing of Sewer or Storm Drain

    00W6023 JBER Water Line Cast-in-Place Thrust Blocks

    00W6024 JBER Horizontal Thrust Restraint at New Ductile Iron Water Line Tie-Ins

    00W6025 JBER Horizontal Thrust Restraint in New Ductile Iron Water Lines

    00W6026 JBER 1”ø Underground Water Service

    00W6027 JBER 1-1/2“ or 2”ø Underground Water Service

    00W6028 JBER 1” to 2”ø Underground Water Service Stub-Out for Future

    00W6029 JBER Water Service Key Box Access

    00W6030 JBER Thaw Wire Connection for 1-1/2“ or 2”ø Underground Water Service

    00W6031 JBER Ductile Iron Water Line Branch Tie-In to New HDPE Water Main

    00W6032 JBER 3”ø or Larger Underground Water Service

    00W6033 JBER 4”ø or Larger Underground Fire Line

    00W6034 JBER UG 3”ø or Larger Water Service or 4”ø or Larger Fire Line Stub-Out for Future

    00W6036 JBER Water Line Railroad Crossing in Casing

    00W6041 JBER Gate Valve and Valve Box Assembly

    00W6042 JBER Fire Line Valve Indicator Post Bollards

    00W6051 JBER Single Pumper Fire Hydrant Assembly

    00W6052 JBER Double Pumper Fire Hydrant Assembly

    00W6053 JBER Fire Hydrant Bollards

    00W6071 JBER Interior 3/4 or 2”ø Potable Water Service Piping

    00W6072 JBER Interior 3/4 or 2”ø Potable Water Service Piping with Fire Line

    00W6073 JBER Interior 3”ø or Larger Potable Water Service Piping

    00W6074 JBER Interior 3”ø or Larger Potable Water Service Piping with Fire Line

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 iv Doyon Utilities, LLC

    00W6075 JBER Interior 2”ø Flush Connection on Fire Line

    00W6081 JBER Water Line Re-Route at New Sewer or Storm Drain

    00W6082 JBER Thrust Block Assembly for Water Line Re-Route at New Sewer or Storm Drain

    CHANGE LOG

    Item# Reference(s) Change

    1 Article 60.02.4 Complete section rewrite for 2021

    2 Detail 00W6035, Article 60.02.3(G) Angle markers removed

    3 60.02.3(B) Tracer wire moved from 60.02.4(E) (HDPE) to 60.02.3(B) (all water lines)

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 1 Doyon Utilities, LLC

    SECTION 60.01 - GENERAL

    Article 60.01.1 - Scope, Applicability, and Content of Specifications

    The Work covered by these Specifications consists of providing all plant, labor, equipment, supplies, material, transportation, handling and storage, and performing all operations necessary to complete new construction, modification, and/or repair of water distribution facilities operated by Doyon Utilities LLC on Joint Base Elmendorf Richardson, hereafter referred to as JBER.

    All Division 60 work shall be in accordance with the Plans, Special Provisions, Standard Details, and these Specifications. In the event of differences between the requirements contained in these various documents and specifications, the most stringent requirements, as determined by Doyon Utilities’ Authorized Representative, shall govern.

    Much of the content of this JBER Division 60 is taken from the 2009 Municipality of Anchorage Standard Specifications (MASS), but this JBER Division 60 also includes requirements not found in the 2009 MASS.

    Article 60.01.2 - Safety

    The Contractor is solely responsible for all construction-related safety and safety compliance, including, but not limited to: worker and jobsite safety; safety of Doyon Utilities employees and agents; safety of other JBER personnel and property; safety of the general public; safety of military operations; safety of wildlife and the environment; and, safety of the water distribution system, the wastewater collection system, and other utility safety.

    Water system safety includes, but is not limited to, avoidance of cross-connections between potable water systems and contamination sources, proper flushing, disinfection, and biological testing, and use of only non-toxic chemicals and materials in water systems.

    Article 60.01.3 - Alaska Department of Environmental Conservation (ADEC) Approvals

    Water distribution system construction plans, including design-build plans, and major changes to ADEC-approved plans, require ADEC approval or re-approval. Contractors submitting design–build plans, and Contractors proposing major field changes to ADEC-approved plans, shall submit plans for ADEC review and approval. A minimum of 30 calendar days shall be allowed for ADEC review. All ADEC plan review fees shall be at Contractor expense. A copy of the ADEC “Approval to Construct” and/or ADEC review comments shall be provided to Doyon Utilities’ Authorized Representative.

    If the Contractor is required to obtain an ADEC “Approval to Construct”, the Contractor shall not begin construction until “Approval to Construct” has been received from ADEC, and provided to and accepted by Doyon Utilities’ Authorized Representative.

    If the Contractor is required to obtain an ADEC “Approval to Construct”, the Contractor shall also be required to obtain an ADEC “Approval to Operate”. The system shall not be placed in operation and final payment shall not be authorized for the Contractor until “Approval to Operate” has been received from ADEC, and provided to and accepted by Doyon Utilities’ Authorized Representative.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 2 Doyon Utilities, LLC

    Article 60.01.4 - Applicable Standards

    The latest revisions of the following standards of the American Society of Testing and Materials (ASTM), the American Water Works Association (AWWA), the International Association of Plumbing and Mechanical Officials ( IAPMO), National Fire Protection Association (NFPA), and the National Sanitation Foundation (NSF) are hereby made a part of these Specifications.

    ASTM A126 .............. Gray Iron Castings for Valves, Flanges and Pipe Fittings

    ASTM B88 ................ Seamless Copper Water Tubing

    ASTM B828 ............... Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings

    ASTM B843 ............... Standard Specification for Magnesium Alloy Anodes for Cathodic Protection

    ASTM D638 .............. Standard Test Method for Tensile Properties of Plastics

    ASTM D3035 ........... Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Controlled Outside Diameter

    ASTM D3261 ........... Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing

    ASTM D3350 ........... Polyethylene Plastic Pipe and Fittings Materials

    ASTM F1055 ................... Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene and Crosslinked Polyethylene (PEX) Pipe and Tubing

    ASTM F2620 ............. Heat Fusion Joining of Polyethylene Pipe and Fittings

    AWWA A100 ............ Water Wells

    AWWA C104 ................... Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water

    AWWA C105 ............. Polyethylene Encasement for Ductile Iron Piping for Water and Other Liquids

    AWWA C111 ............. Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings

    AWWA C115 ............ Flanged Ductile-Iron Pipe with Threaded Flanges

    AWWA C151 ............ Ductile-Iron Pipe, Centrifugally Cast in Metal Molds or Sand-Lined Molds, for Water or Other Liquids

    AWWA C153 ............. Ductile-Iron Compact Fittings for Water Service

    AWWA C502 ............ Dry-Barrel Fire Hydrants

    AWWA C504 ............ Rubber-Seated Butterfly Valves

    AWWA C509 ............. Resilient-Seated Gate Valves for Water Supply Service

    AWWA C515 ............. Reduced-Wall Resilient-Seated Gate Valves for Water Supply Service

    AWWA C550 ............. Protective Epoxy Interior Coatings for Valves and Hydrants

    AWWA C600 ............ Installation of Ductile-Iron Water Mains and Their Appurtenances

    AWWA C651 ............ Disinfecting Water Mains

    AWWA C652 ............. Disinfection of Water Storage Facilities

    AWWA C800 ............ Underground Service Line Valves and Fittings

    AWWA C901 ............. Standard for Polyethylene (PE) Pressure Pipe and Tubing, ½ In. through 3 In., for Water Service

    AWWA C906 ............. Standard for Polyethylene (PE) Pressure Pipe and Fittings, 4 In. Through 63 In., for Water Distribution and Transmission

    NFPA 1 ..................... Fire Code, latest edition adopted by MOA and current local amendments

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 3 Doyon Utilities, LLC

    NFPA 13 ................... Standard for the Installation of Sprinkler Systems, latest edition

    NFPA 15 ................... Standard for Water Spray Fixed Systems for Fire Protection, latest edition

    NFPA 24 ................... Standard for the Installation of Private Fire Service Mains and Their Appurtenances, latest edition

    NFPA 25 ................... Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, latest edition

    NSF Standard 60 ...... Drinking Water System Chemicals – Health Effects

    NSF Standard 61 ...... Drinking Water System Components – Health Effects

    NSF Standard 372 .... Drinking Water System Components – Lead Content

    UPC .......................... Uniform Plumbing Code, latest edition adopted and as amended by the State of Alaska

    Article 60.01.5 - Contaminated Material

    Unless otherwise noted in the Contract Documents, neither JBER nor Doyon Utilities LLC is aware of any contaminated material within the project limits. If such material is encountered, the Contractor shall notify Doyon Utilities’ Authorized Representative immediately for direction. Unless the contamination was caused by Contractor’s operations, discovery of contaminated material will be treated as a changed condition.

    Article 60.01.6 - JBER Access Privileges for Contractor Personnel

    The Contractor shall provide Doyon Utilities LLC with a list of personnel, including Subcontractor personnel, requiring regular access to JBER, as well as required personnel identification documents as required by JBER military base security personnel, all at least 7 calendar days prior to the date that access is required. JBER access privileges for Contractor personnel are contingent on passing of background checks to the satisfaction of JBER military base security personnel.

    JBER access privileges for Contractor and Subcontractor personnel are revocable at the discretion of JBER military base security personnel.

    Denial or revocation of JBER access privileges by JBER military base security personnel for Contractor or Subcontractor personnel shall not be grounds for extra Contractor or Subcontractor compensation.

    Article 60.01.7 - Inspection, Notices, and Official Communications

    All work activities covered under this section, including but not limited to traffic maintenance, storm water pollution prevention, construction, hot tapping, water shutdowns, water line open bore flushing, hydrant barrel extension, hydrant flushing, water line pressure testing, hydrant pressure testing, disinfection, sampling and bacteriological testing, continuity testing, temporary water system work, pipe abandonment in place, well abandonment, and punch list work, are subject to inspection and acceptance by Doyon Utilities LLC. Work completed without inspection by Doyon Utilities’ Authorized Representative shall be subject to rejection.

    Unless specifically noted otherwise in this Division 60, the Contractor shall schedule water line hot tapping, open bore flushing, hydrant flushing, water line pressure testing, hydrant pressure testing, disinfection, sampling and bacteriological testing, continuity testing, temporary water system work, well abandonment, and similar activities to occur on non-holiday weekdays during normal working hours of 7:30 AM to 4 PM to facilitate inspection by Doyon Utilities’ Authorized Representative.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 4 Doyon Utilities, LLC

    Written notice of traffic lane closures and water shutdowns shall be provided to Doyon Utilities LLC and the JBER Fire Department by the Contractor at least 14 calendar days in advance.

    Written notice of traffic lane closures shall be provided to the JBER Police Department by the Contractor at least 14 calendar days in advance.

    Written notice of traffic maintenance (excluding lane closure work), storm water pollution prevention, construction, hot tapping, water line open bore flushing, hydrant flushing, water line pressure testing, hydrant pressure testing, disinfection, sampling and bacteriological testing, continuity testing, temporary water system work, well abandonment, and punch list work, and similar activities requiring inspection shall be provided to Doyon Utilities LLC by the Contractor at least 5 calendar days prior to beginning any of these operations.

    The Contractor shall notify Doyon Utilities’ Authorized Representative again in person or by e-mail one calendar day before starting any of the work listed above.

    For water shutdowns, water line open bore flushing, temporary water supply, and similar activities affecting water system customers, first written notice of these activities, acceptable to Doyon Utilities’ Authorized Representative, shall be provided by the Contractor to all affected customers and to Doyon Utilities’ Authorized Representative at least 14 calendar days prior to beginning any of these activities. A second written notice of these activities, acceptable to Doyon Utilities’ Authorized Representative, shall be provided by the Contractor to all affected customers and to Doyon Utilities’ Authorized Representative at least 24 hours prior to beginning any of these activities.

    Failure by the Contractor to provide the required notice(s) shall be grounds for issuance of a stop-work order and/or complete rejection of the work.

    If the Contractor for any reason fails to perform work, for which advance notice is required, on the originally scheduled date and time, then the full notice period(s) as specified herein shall start over again and all notices specified herein shall be provided for the new scheduled dates and times for the work.

    To be considered official and binding, all communication from and to Doyon Utilities LLC shall be in writing.

    Article 60.01.8 - Utility Locations and Dig Clearance Permit Requirements

    Prior to any excavation, the Contractor shall place a telephone, fax, or on-line locate request with Alaska Digline Inc. (Anchorage telephone - 278-3121 or 811, statewide telephone - 1-800-478-3121, statewide fax – 1-907-278-0696, on-line – http://www.akonecall.com/). Documentation of the Alaska Digline request shall be provided to Doyon Utilities’ Authorized Representative. The Contractor shall coordinate with utility company locator personnel to locate all existing utilities before digging.

    In addition to obtaining utility locations through Alaska Digline Inc., the Contractor shall obtain a Dig Clearance Permit from JBER CES (673 ABW Form 3 – BCE Work Clearance Request), and provide a copy of the fully executed Dig Clearance Permit to Doyon Utilities’ Authorized Representative. A minimum of 14 calendar shall be allowed by the Contractor for complete processing of a Dig Clearance Permit. The Contractor shall comply with all requirements of the fully executed Dig Clearance Permit.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 5 Doyon Utilities, LLC

    Article 60.01.9 - Hot Work Permit Requirements

    For any activity producing open flames, or heat or sparks sufficient to cause combustion, the Contractor obtain a hot work permit signed by the JBER Fire Department, and provide a copy of the fully executed hot work permit to Doyon Utilities’ Authorized Representative. A minimum of 14 calendar days shall be allowed by the Contractor for complete processing of a hot work permit. The Contractor shall comply with all requirements of the fully executed hot work permit.

    Article 60.01.10 - Fire Hydrant Use Permit Requirements

    Prior to use of any JBER fire hydrant for any reason other than emergency usage, the Contractor shall obtain a fire hydrant use permit from Doyon Utilities. Issuance of fire hydrant use permits is at the discretion of Doyon Utilities. A minimum of 3 working days shall be allowed by the Contractor for complete processing of a fire hydrant use permit. The Contractor shall comply with all requirements of the fully executed fire hydrant use permit.

    Article 60.01.11 - Submittals

    The Contractor shall provide paper submittals or electronic submittals, at the option of Doyon Utilities’ Authorized Representative, for review and acceptance by Doyon Utilities. Duplicate paper submittals shall be supplied in the quantities requested by Doyon Utilities’ Authorized Representative. Submittals shall clearly document compliance with Contract requirements, as well as any deviations from Contract requirements, all to the satisfaction of Doyon Utilities’ Authorized Representative. Any materials ordered and/or work done in advance of written acceptance of submittals by Doyon Utilities’ Authorized Representative is subject to rejection.

    Submittals for Doyon Utilities review and acceptance are required for the following items.

    1. ADEC “Approval to Construct” and/or ADEC review comments (as applicable).

    2. Documentation of Alaska Digline utility locate requests.

    3. Fully executed Dig Clearance Permit(s).

    4. Fully executed hot work permit(s).

    5. Submittals for all permanent materials.

    6. HDPE butt fusion lead technician resume and certificate for HDPE piping butt fusion.

    7. Post-disinfection bacteriological test results for all newly constructed water lines and all temporary water systems.

    8. Hot tap procedures and hot tap supervisor resume.

    9. Documentation from the appropriate JBER personnel regarding whether or not a backflow preventer is required in a building requiring new water meter installation by Doyon Utilities, and if a backflow preventer is required, documentation from the appropriate JBER personnel stating that the required type of backflow preventer has been successfully installed.

    10. Isometric, plan, and elevation drawings of proposed interior water service piping, and water meters.

    11. Temporary water system plans, including Contractor contact persons, 24-hour contact phone numbers, water customers’ “Permissions to Enter”, bacteriological test reports, and ADEC approvals.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 6 Doyon Utilities, LLC

    12. 14 day and 24 hour advance notifications to water customers of water shutdowns or other possible disruptions of normal water service.

    13. Work Site Traffic Supervisor certification and resume.

    14. Traffic Control Plans.

    15. Red-lined drawings.

    16. ADEC “Approval to Operate” (as applicable).

    Bacteriological test results shall be provided to Doyon Utilities’ Authorized Representative as soon as they are available from the testing laboratory. “ADEC Approval to Construct” and “Approval to Operate”, if required, shall be provided to Doyon Utilities’ Authorized Representative as soon as they are available from ADEC. Permanent material submittals shall be provided to Doyon Utilities’ Authorized Representative at least 30 calendar days prior to ordering of materials. Temporary water system plans, ADEC approvals, and bacteriological test reports for temporary water systems shall be provided at least 35, 5, and 2 days calendar days respectively prior proposed temporary system start-up. Other submittals listed above shall be provided to Doyon Utilities’ Authorized Representative at least 14 calendar days prior to the activity covered by the submittal. Completed red-lined drawings shall be submitted to Doyon Utilities’ Authorized Representative within 14 calendar days of substantial completion.

    Doyon Utilities’ Authorized Representative reserves the right to request additional submittals for other Contractor procedures and personnel qualifications.

    Article 60.01.12 - Permanent Materials Furnished by Doyon Utilities and by Contractor

    Doyon Utilities may furnish some permanent materials on some projects. When Doyon Utilities does furnish permanent material, a list of these Doyon Utilities’-provided permanent materials, and locations where these Doyon Utilities’-provided materials shall be received by the Contractor, will be provided in the Contract Documents. The Contractor shall perform a complete take-off of all permanent materials required for the Project. The Contractor shall furnish any and all permanent materials not supplied by Doyon Utilities, in order to complete the Project in accordance with the Plans, Standard Details, Special Provisions, and/or these Specifications.

    The Contractor shall be responsible for receiving, inspecting, and inventorying Doyon Utilities’-provided materials at locations specified in the Contract Documents, notifying Doyon Utilities Authorized Representative of damage, shortages, etc, loading as required, delivery to the jobsite, and unloading at the jobsite. Materials damaged during transportation to the jobsite and/or unloading at the jobsite shall be replaced at Contractor expense.

    Any surplus Doyon Utilities’-provided materials not used on a project shall remain the property of Doyon Utilities, and shall be delivered by the Contractor to the Doyon Utilities storage yard and carefully off-loaded and stored on Contractor-provided wooden pallets or other suitable dunnage.

    Article 60.01.13 - Other Division Requirements

    Except as specifically stated otherwise in the various Sections of this Division 60, the following other Divisions and Sections of these Standard Specifications are incorporated by reference into all Sections of Division 60:

    A. Storm Water Pollution Prevention, Clearing and Grubbing, Concrete and Asphalt Demolition, and Earthwork

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 7 Doyon Utilities, LLC

    The Contractor shall perform storm water pollution prevention, clearing and grubbing, concrete and asphalt demolition, earthwork, and related work in accordance with applicable sections of Division 20 - Earthwork.

    B. Wastewater Collection Facility Construction

    The Contractor shall construct wastewater collection facilities in accordance with applicable sections of Division 50 – Wastewater Collection Systems.

    C. Surface Restoration

    Unless shown otherwise on the Plans and/or Standard Details, specified otherwise in the Special Provisions, or directed otherwise by Doyon Utilities’ Authorized Representative, the Contractor shall provide the following materials as required for surface restoration:

    1. For restoration of concrete pavement, sidewalks, curb and gutter, etc. – Class AA-3 Portland cement concrete in accordance with Division 30 – Portland Cement Concrete, with concrete dimensions to match existing.

    2. For restoration of asphalt pavement - Class E asphalt pavement, 2 inches minimum compacted thickness, in accordance with Division 40 - Asphalt Surfacing, over a 2 inches minimum compacted base of leveling course in accordance with Division 20 - Earthwork.

    3. For restoration of gravel-surfaced roads, road shoulders, parking lots, etc. - Leveling course gravel surfacing, 2 inches minimum compacted thickness, in accordance with Division 20 - Earthwork.

    4. For restoration of vegetated surfaces or bare dirt surfaces not scheduled for other surface restoration - 4 inches minimum rolled thickness of topsoil and hydro-seeding with Schedule A seeding mix (for mowed areas) or Schedule D seeding mix (for unmowed areas) in accordance with Division 75 - Seeding, Landscaping, and Revegetation.

    D. Construction Surveying and Red-Lined Drawings

    The Contractor shall provide construction surveying and maintain red-lined drawings in accordance with Division 65 - JBER Construction Surveys. The red-lined drawings shall be up-dated weekly by the Contractor to the satisfaction of Doyon Utilities’ Authorized Representative. Completed red-lined drawings shall be submitted within 14 calendar days of substantial completion, for review and acceptance by Doyon Utilities’ Authorized Representative.

    E. Traffic Maintenance

    The Contractor shall provide all traffic maintenance in accordance with the Division 70 - Standard Construction Specifications, Miscellaneous, and the Manual of Uniform Traffic Control Devices, latest edition adopted by State of Alaska, and current local amendments. The Contractor is solely responsible to provide all traffic maintenance for vehicular, non-motorized, and pedestrian traffic. For any operations involving disruption of normal traffic flow, the Contractor shall provide Traffic Control Plans for review and acceptance by Doyon Utilities’ Authorized Representative. Traffic Control Plans shall be provided at least fourteen (14) calendar days prior to beginning any operations involving disruption of normal traffic flow. Acceptance of Traffic Control Plans by Doyon Utilities’ Authorized Representative is required prior to any operations involving disruption of normal traffic flow.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 8 Doyon Utilities, LLC

    Article 60.01.14 - Water Shutdown Scheduling and Duration

    Scheduling and durations of water shutdowns shall be subject to acceptance by Doyon Utilities’ Authorized Representative. No water shutdown shall exceed 6 hours in duration in any 24 hour period unless temporary water service is provided. Residential water shutdowns shall be started and completed on non-holiday weekdays between the hours of 9 AM to 3 PM. Non-residential water shutdowns shall be started and completed on days and during hours determined by Doyon Utilities’ Authorized Representative to minimize adverse consequences on JBER operations.

    See Article 60.01.7 Inspection, Notices, and Official Communications above for notification requirements for water service shutdowns.

    Article 60.01.15 - Wastewater and/or Water System Valve Operation

    Wastewater and/or water system valves shall be operated only by Doyon Utilities personnel unless others are authorized in writing in advance by Doyon Utilities’ Authorized Representative.

    Article 60.01.16 - Site Housekeeping and Clean-Up

    Littering is strictly prohibited.

    The Contractor shall clean up all construction debris as soon as possible after it is generated and store it properly in suitable containers, all to the satisfaction of Doyon Utilities’ Authorized Representative. Trash shall be disposed of weekly or more often if directed by Doyon Utilities’ Authorized Representative.

    The entire project site shall be cleaned up of all debris and litter at the end of the project and all debris and litter shall be properly disposed of, all to the satisfaction of Doyon Utilities’ Authorized Representative.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 9 Doyon Utilities, LLC

    SECTION 60.02 - WATER LINES

    Article 60.02.1 - General

    The work under this Section includes construction of underground water mains, fire hydrant assembly piping legs, fire lines, and water services. The table below provides guidance as to types of water lines covered in this Section, diameters, allowable materials, and applicable Articles within this Section:

    Types and Sizes of Water Lines, Types of Pipe, and Applicable Paragraphs in Section 60.02

    Type of Water Line

    Size of Water Line

    Type of Pipe

    Article 60.02.2 - Material

    Article 60.02.3 - Construction

    Article 60.02.4 - Flushing, Testing,

    & Disinfection

    Water Mains

    12” and Larger

    Ductile Iron

    A, D, & E A, B, C,

    F, G, & H, A, B, C, D, F,

    I, J, K, L, N, & O

    12” and Larger

    HDPE B & D A, B, D,

    F, G, & H A, B, C, D, G, H, I, J, K, M, N, & O

    Fire Lines

    4” and Larger

    Ductile Iron

    A, D, & E A, B, C,

    F, G, & H A, B, C, D, G, H, I, J, K, L, N, & O

    Water Services

    3” and Larger

    Ductile Iron

    D, & E A, B, C, F,

    G, & H A, B, C, D, F, H, I, J, K, L, N, & O

    1” to 2” Copper C, & D, A, B,

    E, F, & H A, B, C, H, G,

    I, J, N, & O

    Water Lines in Casings

    3” and Larger

    Ductile Iron

    A & E A, B, C, G, & H

    A, B, C, F, G, I, J, K, L, N, & O

    Single Pumper Hydrant

    Legs

    6” Ductile

    Iron A & D

    A, B, C, F, G, H, I, J, & K

    A, B, E, F, H, I, L, N, & O

    Double Pumper Hydrant

    Legs

    8” Ductile

    Iron A & D

    A, B, C, F, G, & H

    A, B, E, F, H, I, L, N, & O

    A fire line is a water line that originates at a water main, and has the primary purpose of providing building interior fire protection. No connections, other than those for additional fire protection, will be allowed on the fire line outside of a served building. Domestic water obtained from a fire line shall be connected and metered inside the served building.

    All piping and tubing materials, accessories, and linings exposed to potable water shall conform to NSF Standards 61 and 372. All chemicals that are used in the construction of potable water systems in such a manner that they could come in contact with potable water shall conform to NSF Standard 60.

    Refer to Standard Detail 00W6021 for additional information on water line trench sections.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 10 Doyon Utilities, LLC

    Refer to Standard Detail 00W6022 for additional information on new water crossings of wastewater collection and storm drain lines.

    Refer to Standard Details 00W6023 through 00W6025 for additional information on water line thrust restraint.

    Refer to Standard Details 00W6026 through 00W6034 for additional information on water service lines and fire lines.

    Refer to Standard Detail 00W6036 for additional information on cased water line crossings of the Alaska Railroad.

    Refer to Section 60.01 – General for additional general requirements.

    Article 60.02.2 - Material

    A. Ductile Iron Piping

    1. Ductile Iron Pipe

    Ductile iron pipe shall conform to the requirements of AWWA C151, Class 52, with cement mortar lining conforming to the requirements of AWWA C104.

    2. Ductile Iron Push-On Joint Gaskets and Restraints

    Rubber gasket joints for ductile iron pipe and fittings shall conform to the requirements of AWWA C111.

    Push-on joint restraints shall be “U.S. Pipe Field LOK®” gaskets or Doyon Utilities’ Authorized Representative accepted equal.

    3. Ductile Iron Mechanical Joint Fittings, Gaskets, Joint Restraints, and Bolting Materials

    Fittings shall have a minimum of 250 pounds pressure rating, mechanical joint, cement lined, either cast iron or ductile iron. All fittings shall conform to the requirements of AWWA C153.

    Rubber mechanical joint gasket joints shall conform to the requirements of AWWA C111.

    Mechanical joint restraints shall be “EBAA Iron MEGALUG®” or “Romac Industries RomaGrip” mechanical joint restraining glands, or Doyon Utilities’ Authorized Representative accepted equal.

    All mechanical joint T-bolts and nuts supplied with fittings and appurtenances shall conform to ASTM A242 weathering steel. All T-bolts and nuts shall be factory-coated with a blue fluoropolymer coating for corrosion resistance. T-bolts shall be of sufficient length that, when a bolt-up is complete, each bolt extends completely through and at least 1/8 inch beyond the nut, all around.

    4. Ductile Iron Flange Materials

    Field installed flanges shall be restrained flange coupling adapters, ductile iron, ASTM A536, Grade 65-45-12, fusion bonded epoxy coated and lined, Class 150 flange drilling, with break-away head restrainer bolts and heat-treated restraining lugs, “Romac RFCA” or Doyon Utilities’ Authorized Representative accepted equal.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 11 Doyon Utilities, LLC

    Field installed flanges that are not equipped with break-away head restrainer bolts and heat-treated restraining lugs, or similar restraining systems acceptable to Doyon Utilities’ Authorized Representative, shall not be allowed.

    Rubber flange gaskets shall conform to the requirements of AWWA C111/ANSI A21.11.

    Flange bolts and nuts shall be Type 304 stainless steel heavy hexagonal. All flange bolt diameters shall be 1/8 inch smaller than flange bolt hole diameters. All flange bolts shall be of sufficient length that, when a bolt-up is complete, each bolt extends completely through and at least 1/8 inch beyond the nut, all around. If stud bolts are used for flange bolt-up, the same length criteria shall apply to each end of each stud bolt.

    5. Continuity Straps, Test Leads, Exothermic Weld Materials, and Valve Box Top Sections

    Continuity straps and test leads shall be stranded Number 2 AWG copper wire with HMWPE insulation suitable for direct burial.

    Exothermic weld materials shall be “Erico Cadweld” or Doyon Utilities’ Authorized Representative accepted equal. Weld shot size shall be per manufacturer’s recommendations for the Class 52 ductile iron pipe and stranded #2 AWG copper wire.

    Thermite weld caps, “Royston Handy Cap IP” or Doyon Utilities’ Authorized Representative accepted equal, shall be provided for protection of all exothermic welds. A coal tar pitch product acceptable to Doyon Utilities’ Authorized Representative shall be provided to protect exposed bare metal not covered by thermite weld caps.

    Standard cast iron valve box top sections with “Water” covers shall be provided as needed for storage of day-lighted test leads.

    6. Polyethylene Encasement for Ductile Iron Pipe and Appurtenances

    Polyethylene encasement shall conform to the most current edition of AWWA C105/ANSI A21.5.

    B. High Density Polyethylene (HDPE) Piping

    1. General

    All HDPE pipe and fittings used on JBER potable water systems shall be certified by the manufacturer as in compliance with NSF 61 for potable water service and shall be clearly marked as being as in compliance with NSF 61 for potable water service.

    2. Butt Fusion HDPE Pipe and Fittings

    High density polyethylene pipe (HDPE) and fittings shall be manufactured to meet or exceed the requirements of ASTM D3350, AWWA C901, and AWWA C906, and shall be manufactured from PE4710 polyethylene compounds, cell classification 445574. HDPE pipe and fitting material compound shall contain color and ultraviolet (UV) stabilizer meeting or exceeding the requirements of Code C per ASTM D3350. Butt fusion fittings shall comply with ASTM D3261. All fittings shall have pressure class ratings not less than the pressure class rating of

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 12 Doyon Utilities, LLC

    the pipe to which they are joined. HDPE pipe and fittings shall be manufactured to iron pipe size equivalent outside diameter.

    HDPE pipe and fittings for water mains shall be SDR11.

    3. Electro Fusion HDPE Couplings and Fittings

    Electro-fusion couplings and fittings shall comply with ASTM F1055. Unless specifically called out on the Plans or specified in the Special Provisions, use of HDPE electro-fusion couplings and/or electro-fusion fitting shall be subject to acceptance by Doyon Utilities’ Authorized Representative on a case by case basis. All electro-fusion couplings and fittings shall have pressure class ratings not less than the pressure class rating of the pipe to which they are joined.

    4. HDPE Flange Materials

    HDPE flange adapters shall have pressure class ratings not less than the SDR and pressure rating of the pipe to which they are joined. HDPE flange adapters shall be manufactured to iron pipe size equivalent outside diameter.

    Flange back-up rings shall be Type 304 stainless steel, Class 150 flange drilling.

    Rubber flange gaskets shall conform to the requirements of AWWA C111/ANSI A21.11.

    Flange bolts and nuts shall be Type 304 stainless steel heavy hexagonal. All flange bolt diameters shall be 1/8 inch smaller than flange bolt hole diameters. All flange bolts shall be of sufficient length that, when a bolt-up is complete, each bolt extends completely through and at least 1/8 inch beyond the nut, all around. If stud bolts are used for flange bolt-up, the same length criteria shall apply to each end of each stud bolt.

    5. Tracer Wire and Tracer Wire Accessories

    Tracer Wire shall be direct bury #10 AWG solid copper clad steel wire with a 600 pound minimum breaking strength and with blue 30 mil high density high molecular weight HDPE insulation, “Copperhead Industries” or Doyon Utilities’ Authorized Representative accepted equal. Tracer wire splice connectors shall be direct bury lug type with silicone sealant, “Copperhead Industries #3WB-01”, “Copperhead Industries #SCB-01R”, or Doyon Utilities’ Authorized Representative accepted equals.

    Tracer Wire ground rods shall be ½ inch diameter by 4-foot-long copper clad steel, “Erico Copperbonded”, and Tracer Wire ground clamps shall be “Erico EK17”, or Doyon Utilities’ Authorized Representative accepted equals.

    Standard cast iron valve box top sections with “Water” covers shall be provided as needed for storage of day-lighted Tracer Wires.

    C. Copper Tubing and Accessories

    1. Copper Tubing

    Copper tubing for underground installation shall be soft drawn ASTM B88 seamless Type K.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 13 Doyon Utilities, LLC

    2. Corporation Stops

    Corporation stops shall be 85-5-5-5 ASTM B62 brass, full port ball type, 300 PSI cold water working pressure, male threaded by flare copper.

    3. Thaw Wire Connection Materials for Copper Tubing at Main Connections

    For one inch copper water services, corporation stops shall be furnished with flare nuts with integral wire connectors for connection of Number 2 thaw wire to the corporation stop.

    For 1 ½” and 2” copper water services, materials for connection of Number 2 thaw wires to service saddles shall in in accordance with the Standard Details.

    4. Curb Stops

    Curb stops shall be 85-5-5-5 ASTM B62 brass, plug type, 175 PSI cold water working pressure, flare copper both ends. Curb stops shall be designed so that the tubing downstream of the curb stop can drain back through the curb stop when the curb stop is closed. Curb stops shall be “Mueller Mark II Oriseal H-15214” or Doyon Utilities’ Authorized Representative accepted equal.

    5. Service Saddles

    Service saddles for connection of corporation stops to 30 inch or smaller nominal diameter ductile iron water mains shall be ductile iron saddle body, with two each 2 inch wide Type 304 stainless steel straps, Type 304 stainless steel bolting materials, NBR gasket, and “CC” female threaded connection, 350 PSI pressure rating, “Romac 202-NS” or Doyon Utilities’ Authorized Representative accepted equal.

    Service saddles for connection of corporation stops to 12 inch or smaller nominal diameter HDPE water mains shall be Type 304 stainless steel shell, hardware, bolting materials including spring washers, and “CC” female threaded connection, and NBR gasket, 150 PSI pressure rating, “Romac 305-H” or “Romac 306-H” or Doyon Utilities’ Authorized Representative accepted equal.

    6. Key Boxes

    Key boxes, with non-removable operating rods, shall be “Mueller 10306” or Doyon Utilities’ Authorized Representative approved equal.

    7. Thaw Wire for Copper Tubing

    Thaw wire shall be stranded Number 2 AWG copper wire with HMWPE insulation suitable for direct burial.

    D. Other Water Distribution System Materials

    1. Underground Gate and Butterfly Valves and Appurtenances

    All underground gate valves, underground butterfly valves, valve boxes, indicator posts, and appurtenances shall meet the requirements of Section 60.03 - Underground Valves.

    2. Transition Couplings for Connection of Different Water Line Materials

    Use of transition couplings is subject to acceptance by Doyon Utilities’ Authorized Representative on a case by case basis.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 14 Doyon Utilities, LLC

    Where allowed, transition couplings shall be “Romac Alpha”, “Romac Macro HP” (not approved for HDPE pipe), “Romac 501” (interior stiffening inserts required for connections of HDPE pipe), or Doyon Utilities’ Authorized Representative accepted equals, with gaskets as necessary to match piping diameters that are being joined. Transition couplings shall be NSF 61 fusion bonded epoxy coated and lined, and shall have Type 304 stainless steel fasteners.

    3. Repair Clamps

    Use of repair clamps is subject to acceptance by Doyon Utilities’ Authorized Representative on a case by case basis.

    Where allowed, repair clamps, for closure of holes in ductile iron or AC pipe, shall be “Romac SS1, SS2, or SS3” or Doyon Utilities’ Authorized Representative accepted equals.

    Where allowed, repair clamps, for closure of holes in HDPE pipe, shall be “Romac SS1-H, SS2-H, or SS3-H” or Doyon Utilities’ Authorized Representative accepted equals.

    The minimum length of a repair clamp shall be as recommended by the clamp manufacturer for the maximum operating pressure or hydrotest pressure as applicable, and the size of the pipe wall penetration being sealed.

    4. Detectable Underground Warning Tape

    Detectable underground warning tape shall be 5-mil by 6-inch wide aluminum backed blue tape with the words “Caution Buried Water Line Below”. Detectable underground warning tape shall be “Seton” or Doyon Utilities’ Authorized Representative accepted equal.

    5. Pipe Plugs for Abandoned-in-Place Tapping Saddles

    Pipe plugs, for plugging of existing tapping saddles to remain on water lines after removal of corporation stops, shall match tapping saddle material to the satisfaction of Doyon Utilities’ Authorized Representative, to reduce potential for corrosion due to dissimilar metals.

    6. Board Insulation

    Board insulation shall be provided in accordance with Division 20 – Earthwork.

    E. Materials for Water Lines in Casings

    1. Casing Spacers

    Casing spacers, for installation of ductile iron water line carrier pipe in casing pipe, shall be fabricated with Type 304 stainless steel bands, risers, and fasteners, minimum 2 inch wide HDPE runners, and 1/8 inch minimum thickness PVC liners. Casing spacer dimensions shall be such that carrier pipe centerline is within 2 inches vertical of the casing pipe centerline. Each casing spacer shall be designed and fabricated to support the weight of 10 feet of Class 52 ductile iron pipe of the required diameter, completely filled with water, with a minimum factor of safety of 2. Casing spacers shall also be designed for dynamic loads experienced during carrier pipe installation in casing. Casing spacers shall be “Calpico” or Doyon Utilities’ Authorized Representative accepted equal.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 15 Doyon Utilities, LLC

    2. Casing End Seals

    Casing end seals shall be as detailed on the Plans, as shown on the Standard Details, or as directed by Doyon Utilities’ Authorized Representative.

    Casing end seals, as shown on the Standard Details, shall be fabricated of 3 inch by 4 inch by 8 inch concrete bricks, mortar, and 1/2 inch thick by 10 inch wide neoprene padding.

    Mortar shall be composed of 1 part cement and 3 parts sand. Cement for mortar shall conform to the requirements of ASTM C150, Type II. Sand shall conform to the requirements of AASHTO M45. The addition of lime is not permitted. The use of 5 minute or fast-cure mortar is prohibited.

    Article 60.02.3 - Construction

    A. Materials Delivery, Handling, and Temporary Storage

    Pipe and appurtenances shall be delivered, unloaded, and handled and stored on the jobsite in such a manner to ensure placement in the trench in a sound, undamaged condition. Particular care shall be taken not to damage the pipe, fittings, or pipe or fitting coating or lining. Damaged pipe, fittings, coating, and/or lining shall be repaired to the satisfaction of Doyon Utilities’ Authorized Representative or pipe shall be replaced, all at Contractor expense.

    On-site storage of pipe and other materials shall be to the satisfaction of Doyon Utilities’ Authorized Representative to avoid inconvenience to the military and the general public on JBER and/or to avoid potential safety hazards such as inadvertent shifting and rolling of pipe.

    Rubber gaskets shall be protected from freezing temperatures and direct sunlight.

    B. General Installation Requirements for All Water Lines

    Also see specific requirements below for installation of ductile iron, HDPE, and copper water lines.

    1. Earthwork

    All trenching, pipe bedding, backfilling, and related work shall be in accordance with Division 20 - Earthwork.

    The Contractor shall remove and dispose of all contaminated soils encountered within the trench area. Contaminated soils shall not be re-used as fill or backfill material anywhere on JBER, but shall be disposed of in accordance with Division 20 - Earthwork.

    All water mains, fire lines, fire hydrant assembly piping, and water services shall be constructed with a minimum of 10 feet of earth cover from proposed finished grade.

    Minimum 10 foot depths for water services and fire lines shall be maintained to 5 feet horizontal inside of building footings.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 16 Doyon Utilities, LLC

    2. Pipe Installation

    The interior of all pipe and accessories shall be thoroughly cleaned of foreign matter prior to installation to the satisfaction of Doyon Utilities’ Authorized Representative.

    Cutting of pipe shall be done in a neat and workmanlike manner without damage to the pipe, coating, and/or lining to the satisfaction of Doyon Utilities’ Authorized Representative.

    Pipe and appurtenances shall be carefully lowered into the trench by means of fabric slings, wire rope chokers, rope tag lines, and other suitable lifting and rigging gear. Pipe placement, including all handling, installing in the trench, bedding, and backfilling, shall be done to the satisfaction of Doyon Utilities’ Authorized Representative.

    Where new water piping ties into an existing in-service water distribution system, all tie-in methods and materials shall be subject to acceptance by Doyon Utilities’ Authorized Representative. Tie-in work shall include thrust restraint of existing and new piping as appropriate and required to assure the integrity of the tie-in to the satisfaction of Doyon Utilities’ Authorized Representative.

    When making a tie-in to an in-service water line, a “bell hole” type sump shall be excavated at the tie-in location. Water accumulating in the sump shall be pumped down or otherwise removed so that the water level in the sump is at all times at least 2 feet below the invert level of the tie-in.

    If tie-in components will not be subjected to disinfection after completion of the tie-in, the interior surfaces of new and existing pipe, fittings, and/or valves shall be thoroughly cleaned and disinfected in accordance with AWWA C651 and all to the satisfaction of Doyon Utilities’ Authorized Representative.

    If tie-in components will not be hydrostatically tested after completion of a tie-in, and if the tie-in piping can be safely returned to service prior to backfilling, then tie-in components shall be visually inspected by the Contractor and Doyon Utilities’ Authorized Representative under normal operating conditions after tie-in work is complete but before polyethylene wrapping and/or backfill is/are placed. Any and all leaks shall be repaired to the satisfaction of Doyon Utilities’ Authorized Representative.

    When work is not in progress, open piping ends shall be securely plugged so that no trench water, earth, or other substances will enter the piping.

    All new water lines shall be marked with detectable underground warning tape. The Contractor shall install detectable underground warning tape directly above and parallel to the axis of the water line with no breaks in continuity. The Contractor shall install the locator tape 3 feet below finished grade.

    If a project includes new water main and new water services connected to the new main, new water services shall be completely installed before new water main open bore flushing, pressure testing, and disinfection are completed, and shall be flushed, pressure tested, and disinfected in the same operations as the water main.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 17 Doyon Utilities, LLC

    Care shall be exercised during construction, flushing, testing, and disinfection operations to assure that no backflow occurs from new water piping into the existing in-service water system.

    Pipe ends left for future connections shall be plugged, capped, or blind flanged, securely wrapped in polyethylene encasement, and restrained to the satisfaction of Doyon Utilities’ Authorized Representative. Ends of water piping for future connection shall be permanently marked with new vertical 4 inch by 4 inch pressure treated wood posts set directly at the end of pipes. In non-traffic areas, the 4 inch by 4 inch pressure treated wood posts shall extend at least one foot above finished grade, shall be painted blue, and shall be permanently fitted with 3-inch diameter red plastic reflectors on all four sides. In vehicular and/or pedestrian traffic areas, the 4 inch by 4 inch pressure treated wood posts shall be cut off at a depth no more than 6 inches below grade and fitted with a metal end-cap.

    3. Repair or Replacement of Damaged Pipe or Accessories

    Where pipe or other component structural integrity, mechanical integrity, coating, lining, and/or polyethylene encasement is/are damaged by the Contractor as determined by Doyon Utilities’ Authorized Representative, the damaged pipe or component shall be replaced if directed by Doyon Utilities’ Authorized Representative, or repaired if acceptable to Doyon Utilities’ Authorized Representative. All repair methods and materials shall be to the satisfaction of Doyon Utilities’ Authorized Representative. Use of repair clamps and similar devices shall not be permitted. Replacement or repair shall be at the Contractor’s expense.

    4. Tracer Wire Installation

    Tracer wire for all water line piping shall be laid directly on the top of the pipe and securely taped to the pipe at 5-foot intervals. Whenever possible, tracer wire shall be installed in continuous lengths with no splices from one end of a piping run to the other end. When allowed, splices shall be made using direct bury wire splice connectors with silicone sealant, installed in strict accordance with the manufacturer’s recommendations. The number of splices shall be minimized to the satisfaction of Doyon Utilities’ Authorized Representative.

    Buried T-connections in tracer wire may be installed on a case-by-case basis if acceptable to Doyon Utilities’ Authorized Representative. Where T-connections are allowed in tracer wire, such T-connections shall be made using direct bury lug type Tracer Wire splice connectors with silicone sealant, installed in strict accordance with the manufacturer’s recommendations.

    All Tracer Wire dead ends shall be attached to 1/2” diameter by 4-foot-long ground rods with grounding clamps.

    All tracer wires shall be brought from the pipe to finished grade and permanently stored in standard cast iron valve box top sections with “Water” covers set at locations directly over water lines as directed by Doyon Utilities’ Authorized Representative. Tracer wires shall extend 5 feet minimum above finished grade to provide accessibility for future use.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 18 Doyon Utilities, LLC

    C. Installation Requirements for Ductile Iron Water Mains and Services, Fire Lines, and Hydrant Legs

    See Article 60.02.3, paragraphs A. and B. above for additional applicable requirements.

    1. Polyethylene Encasement

    All new ductile iron pipes, fittings, associated valves, valve boxes, indicator posts, and hydrants shall be encased in polyethylene encasement. The polyethylene encasement shall be installed in strict conformance to the methods described in the most current editions of AWWA C105/ANSI A21.5 and the Ductile Iron Pipe Research Association's "A Guide for the Installation of Ductile Iron Pipe" and to the satisfaction of Doyon Utilities’ Authorized Representative. The Contractor shall use Method A of ANSI/AWWA C105/A21.5 to install polyethylene encasement.

    Existing ductile iron piping exposed for tie-ins and similar activities shall be encased in polyethylene encasement to the satisfaction of Doyon Utilities’ Authorized Representative.

    Damage to polyethylene encasement, whether occurring before, during, or after pipe installation, shall be either repaired or the piping shall be removed and the polyethylene encasement replaced, all as directed by Doyon Utilities’ Authorized Representative. Repair and/or replacement of damaged polyethylene encasement shall be at Contractor expense.

    2. Pipe Installation

    Installation and joining of ductile iron pipe shall be in accordance with the requirements of AWWA C600. Ductile iron water main and service pipe laying shall in all cases proceed by inserting the spigot end of the pipe being installed into the bell of the previously installed pipe. Each pipe shall be joined in accordance with the pipe manufacturer’s recommended standards. Each pipe shall be laid true to line and grade.

    When any ductile iron pipe push-on joints must be deflected horizontally and/or vertically to maintain the required alignment and/or grade, the actual total deflection at each joint shall not exceed two-thirds of the maximum joint deflection recommended by the pipe manufacturer.

    When ductile iron pipe push-on joints with field lock gaskets must be deflected to maintain the required alignment and/or grade, the pipe manufacturer’s recommended procedures for joint assembly and deflection shall be strictly followed to the satisfaction of Doyon Utilities’ Authorized Representative.

    All ductile iron pipe water line tie-in locations, methods, and fit-ups shall be subject to Doyon Utilities’ Authorized Representative acceptance. Tie-ins must be made in either straight runs of water line or where the water line horizontal alignment deflects 90 degrees. If a tie-in is to be made between two straight segments of water line on the same alignment, the tie-in shall be made using a push-on joint or a single mechanical joint if possible, or using a mechanical joint “long sleeve”. If a tie-in is to be made between two perpendicular segments of new water line, the tie-in shall be made using a single 90 degree bend, a single tee, or a single cross. Tie-ins at bends less than 90 degrees shall not be permitted. Tie-ins using non-restrained couplings shall not be permitted. Both water line sections at a tie-in shall

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 19 Doyon Utilities, LLC

    be restrained using thrust restraint components specified above. As applicable, tie-in work shall include restraint of existing pipe as required to assure the integrity of the tie-in to the satisfaction of Doyon Utilities’ Authorized Representative.

    3. Ductile Iron Pipe Bedding and Backfill

    Unless called out otherwise on the Plans or directed otherwise by Doyon Utilities’ Authorized Representative, pipe bedding for ductile iron piping shall meet the requirements of Class “B” bedding per Division 20 - Earthwork.

    Bedding and backfill of ductile iron piping with polyethylene encasement shall be placed and compacted with sufficient care to protect the polyethylene encasement from becoming torn, punctured, or otherwise damaged during the Work. Damage to the integrity of the polyethylene encasement shall be either repaired or the piping shall be removed and the polyethylene encasement replaced, all as directed by Doyon Utilities’ Authorized Representative. Repair and/or replacement of damaged polyethylene encasement shall be at Contractor expense.

    4. Thrust Restraint

    Thrust restraint for ductile iron pipe shall be provided by restrained pipe joints, thrust blocks, or a combination of both. Wherever possible, restrained pipe joints shall be used for thrust restraint in lieu of thrust blocks. Use of thrust blocks shall only be allowed when transitioning from existing unrestrained piping to new piping or at other locations where specifically shown on the Plans or directed by Doyon Utilities’ Authorized Representative. Thrust restraint, including restrained pipe joints and thrust blocks, shall meet or exceed requirements of the Standard Details and shall be to the satisfaction of Doyon Utilities’ Authorized Representative.

    Ductile iron pipe joint thrust restraint components for water lines, including mechanical joint restraining glands and field lock gaskets, shall be installed in strict accordance with manufacturers’ recommended procedures and to the satisfaction of Doyon Utilities’ Authorized Representative. Joint thrust restraints shall be installed as required where a new water line terminates or changes alignment utilizing a tee, cross, bend, or similar fitting.

    As applicable, tie-in work shall include restraint of existing pipe as required to assure the integrity of the tie-in to the satisfaction of Doyon Utilities’ Authorized Representative.

    5. Continuity Straps and Test Leads

    Two parallel electrical continuity straps shall be exothermically welded to ductile iron water line piping on both sides of every joint to provide redundant electrical continuity paths across the joint.

    At intervals on ductile iron water lines not to exceed 500 feet in length, sets of two parallel electrical continuity test leads shall be installed. Test lead sets shall be located so that the entire water line can be continuity tested. All test leads shall be brought to from the pipe to finished grade and permanently stored in “Water” valve boxes or standard cast iron valve box top sections with “Water” covers at all locations directed by Doyon Utilities’ Authorized Representative. Test leads shall extend one foot minimum above finished grade to provide accessibility for future use.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 20 Doyon Utilities, LLC

    Continuity straps and test leads shall be exothermically welded to a clean, dry, freshly ground bright ductile iron pipe surface. Weld quality shall be subject to acceptance by Doyon Utilities’ Authorized Representative. All welds and bare pipe surfaces are to be coated with shall be protected with thermite weld caps, “Royston Handy Cap IP” or Doyon Utilities’ Authorized Representative accepted equal, and remaining exposed bare metal surfaces shall be coated with coal tar pitch or other suitable coating, all to the satisfaction of Doyon Utilities’ Authorized Representative.

    6. Additional Installation Requirements for Ductile Iron Fire Lines and Water Services

    If a project includes new water main and new fire lines and/or water services connected to the new main, all new fire lines and water services shall be completely installed before new water main open bore flushing, pressure testing, and disinfection are completed, and shall be flushed, pressure tested, and disinfected in the same operations as the water main.

    Valves and appurtenances shall be installed in conformance with Section 60.03 – Underground Valves.

    Connections of ductile iron fire lines and water services to operational 24 inch or smaller nominal diameter ductile iron or 12 inch or smaller nominal diameter HDPE water mains shall be hot tapped in accordance with Section 60.06 - Connections to Existing Water Systems. Service line isolation valves shall be flange by mechanical joint.

    Connections of ductile iron fire lines and water services to operational HDPE main pipe larger than 12 inch nominal diameter shall be as shown on the Plans or as specified in the Special Provisions.

    The Contractor shall install fire lines and water services perpendicular to the street centerline whenever possible.

    7. Insulation

    All ductile iron fire lines, water services, and hydrant legs shall be insulated with board insulation 4 inches thick (two each 2 inch thick layers) by 4 foot minimum width, centered over the water line and extending the full length of the water line plus 2 additional feet minimum at each end. The bottom of the insulation shall be 6 inches above the top of the water line. Board insulation shall be coped as necessary to fit snugly around valve boxes, fire hydrant barrels, etc., to the satisfaction of Doyon Utilities’ Authorized Representative.

    At all water line/gravity sewer and water line/storm drain crossings where the out-to-out vertical separation at the crossing is less than 3 feet, a minimum of 4 inches of board insulation (at least two each 2 inch thick layers) shall be installed between water lines and gravity sewer lines or storm drains, as shown on the Plans, in accordance with the Standard Details and as directed by Doyon Utilities’ Authorized Representative.

    8. Installation Requirements for Ductile Iron Water Lines in Casings

    a. Casing Pipe and Placard Installation

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 21 Doyon Utilities, LLC

    Casing pipe and placards shall be installed in accordance with Division 20 – Earthwork, and with the Standard Details as applicable.

    b. Carrier Pipe Installation

    All water carrier pipe installed in casing shall be ductile iron and shall be installed on casing spacers in strict accordance with casing spacer and pipe manufacturers’ recommendations, and with the Standard Details as applicable. Casing spacers shall be installed as follows as a minimum:

    (i) At least three casing spacers per full ductile iron pipe section.

    (ii) At least two casing spacers per partial ductile iron pipe section.

    (iii) 8 foot maximum center-to-center separation between casing spacers.

    (iv) One casing spacer at 1 foot 6 inches clear from each end of the casing.

    (v) One casing spacer at 1 foot 0 inches clear on either side of each pipe joint in the casing.

    c. Continuity Straps on Carrier Pipe in Casing

    Two parallel electrical continuity straps shall be installed at each ductile iron pipe joint inside of a casing in accordance with Article 60.02.3, subparagraph C.5. above.

    d. Installation of Casing End Seals

    End seals shall be installed to close the annular spaces between water line carrier pipe and the casing pipe, and shall be as shown on the Plans, in accordance with the Standard Details, and as directed by Doyon Utilities’ Authorized Representative. As a minimum, casing end seals shall be constructed as follows:

    (i) The carrier pipe shall be tightly and securely wrapped with a double wrap of 1/2 inch thick by 10 inch wide neoprene padding or Doyon Utilities’ Authorized Representative accepted equal, so that the wrap extends one inch beyond the end of the casing.

    (ii) A concrete-brick-and-mortar bulkhead with vent and drain pipes shall be constructed in the annular space between the carrier pipe and casing pipe. The long dimensions of concrete bricks shall be laid parallel with the axis of the carrier pipe and casing pipe, with outer ends of bricks flush with the outer end of the casing.

    (iii) During brick-and-mortar bulkhead construction, Schedule 40 PVC vent and drain pipes, 1 inch nominal diameter by 10 inches long, shall be installed through each bulkhead, one installed at the top as a vent and the other installed at the bottom as a drain. Prior to backfilling, all 1 inch vent and drain pipes shall be cleaned to the satisfaction of Doyon Utilities’ Authorized Representative.

    (iv) Completed casing end seals shall be allowed to cure for a minimum of 48 hours prior to backfilling, during which time the

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 22 Doyon Utilities, LLC

    seals shall be protected from all damage to the satisfaction of Doyon Utilities’ Authorized Representative.

    (v) After a minimum of 48 hours of curing, casing end seals shall be carefully backfilled to the satisfaction of Doyon Utilities’ Authorized Representative.

    D. Installation Requirements for HDPE Water Mains

    See Article 60.02.3, paragraphs A. and B. above for additional applicable requirements.

    1. Inspection of Pipe

    The Contractor shall inspect HDPE piping for damage just prior to joining. Damage includes cuts or gouges exceeding 10% of the pipe wall thickness, kinked pipe, pipe flattened by more than 5% of round pipe diameter, or any abrasion, cuts, gouges, or other damage on the pipe interior. Damaged pipe shall be cut out and discarded at Contractor expense.

    2. Pipe Cleaning Prior to Fusion

    HDPE pipe ends and walls shall be cleaned just prior to fusion to the satisfaction of Doyon Utilities’ Authorized Representative. Only 99% isopropyl alcohol shall be used for HDPE cleaning just prior to fusion. Water, denatured alcohol, acetone, or other solvents are prohibited for HDPE pipe cleaning. No liquid of any kind shall be applied to butt fusion pipe ends after mechanical facing. Fusion surfaces shall be protected from precipitation and moisture of any kind, and shall be completely dry just prior to fusion.

    3. Butt Fusion Joining

    All HDPE pipe and fitting joint butt fusion shall conform to ASTM F2620 and the pipe manufacturer's recommendations for proper equipment and procedures. The Contractor’s lead technician for butt fusion shall provide documentation of successful completion of an 8 hour minimum certification course in HDPE piping butt fusion and a resume describing the lead person’s HDPE piping butt fusion project experience, all for review and acceptance by Doyon Utilities’ Authorized Representative. The HDPE pipe supplier shall supply a qualified representative acceptable to Doyon Utilities’ Authorized Representative to instruct the Contractor's personnel on butt fusion, and to witness the first 20 butt fusion joints.

    The Contractor shall assure that butt fusion joints are fused at the temperature and pressure and for the duration recommended by the pipe manufacturer in order to achieve maximum pressure ratings of all joints. Joints that are not fused in accordance with pipe manufacturer’s recommendations and to the satisfaction of Doyon Utilities’ Authorized Representative shall be cut out and replaced at Contractor expense.

    Up to 3 completed butt fusion joints per 1,000 feet of piping may be selected at random by Doyon Utilities’ Authorized Representative for quality assurance testing for compliance with ASTM D638. Test specimens shall be cut out at Contractor expense and shall include the selected butt fusion joint and piping on 12 inches minimum on either side of the joint. After test specimen removal, remaining piping shall be rejoined at Contractor expense. For each joint that fails compliance testing in

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 23 Doyon Utilities, LLC

    accordance with ASTM D638, 2 additional joints shall be cut out for testing, and piping shall be rejoined, all at Contractor expense.

    4. Electro-Fusion Joining

    All HDPE coupling and fitting electro-fusion shall conform to the electro-fusion coupling and fitting manufacturer's recommendations for proper equipment and procedures. The electro-fusion coupling and fitting supplier shall supply a qualified representative acceptable to Doyon Utilities’ Authorized Representative to instruct the Contractor's personnel on electro-fusion, and to witness the first 20 electro-fusion joints. Exact locations of all buried electro-fusion joints shall be noted on red-lined drawings, including stations, offsets, and GPS coordinates.

    5. Pipe Installation

    Joined HDPE pipe shall be handled using fabric straps or rubber covered wire rope chokers. Pick points shall be separated to the satisfaction of Doyon Utilities’ Authorized Representative, and shall be at least 5 feet from any piping joints.

    The temporary HDPE pipe bending radius during handling shall not be less than the minimum radius recommended by the pipe manufacturer. The permanent HDPE pipe bending radius shall not be less than twice the minimum radius recommended by the pipe manufacturer.

    Due to the flexibility of the HDPE, the Contractor shall exert due care while placing bedding and trench backfill and compacting adjacent to and over these types of pipe. All placement and compaction of bedding and trench backfill shall be per the manufacturer's recommendations and to the satisfaction of Doyon Utilities’ Authorized Representative.

    6. HDPE Water Main Bedding

    Unless called out otherwise on the Plans or Standard Details, specified otherwise herein, or directed otherwise by Doyon Utilities’ Authorized Representative, pipe bedding for HDPE pipe shall be Class “B” or Class “D” bedding per Division 20 - Earthwork. Class “B” bedding shall be required at all water/sewer and water/storm drain crossings in accordance with the Standard Details and Article 60.02.3., paragraph G. below.

    E. Installation Requirements for Copper Water Services

    See Article 60.02.3., paragraphs A. and B. above for additional applicable requirements.

    1. Copper Water Service Connections to Water Mains

    Water service connections to pre-existing operational water mains shall be made under line pressure in the main.

    Connections of 1 inch corporation stops to ductile iron piping shall be made by directly tapping the ductile iron piping wall. Connections of 1-1/2 inch and 2 inch corporation stops to ductile iron piping shall be made using service saddles.

    Connections of 1 inch, 1-1/2 inch, and 2 inch corporation stops to 12 inch or smaller nominal diameter HDPE main pipe shall be made using service saddles.

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 24 Doyon Utilities, LLC

    Connections of copper water services to operational HDPE main pipe larger than 12 inch nominal diameter shall be as shown on the Plans or as specified in the Special Provisions.

    2. Copper Water Service Installation

    Water services shall be installed perpendicular to the street centerline whenever possible.

    Copper tubing shall be installed without kinking or other damage, and to the satisfaction of Doyon Utilities’ Authorized Representative. Kinked or otherwise damaged copper tubing, as determined by Doyon Utilities’ Authorized Representative, shall be discarded and replaced at Contractor expense.

    Wherever possible, copper water services shall be installed in continuous sections with buried joints only as specifically shown on the Standard Details or directed by Doyon Utilities’ Authorized Representative. If required, underground joints in copper tubing shall be flare connections. Underground soldered joints and/or unions shall not be permitted.

    If a project includes new water main and new water services connected to the new main, new water services shall be completely installed before new water main open bore flushing, pressure testing, and disinfection are completed, and shall be flushed, pressure tested, and disinfected in the same operations as the water main.

    For copper water services stubbed out for buildings that are under construction, the water service line shall be installed from the curb stop to a point up to 5 feet inside the building footing line that is acceptable to Doyon Utilities’ Authorized Representative and, at that point inside of the footings, extended upward to 2 feet minimum above the finished grade.

    For copper water services stubbed out for future use, a copper bleeder line with a diameter equal to the service line diameter shall be connected to the curb stop, extended above the finished grade in a non-traffic area designated by Doyon Utilities’ Authorized Representative, and attached to a 4 inch by 4 inch post as shown on the Standard Details.

    Bleeders or day-lighted service line extensions shall be used for open bore flushing, disinfection, and sampling of water services for bacteriological testing. After satisfactory bacteriological testing results are obtained from new water services, all chlorine solution shall be flushed out, and bleeders and day-lighted services shall be closed off above grade as shown on the Standard Details and as directed by Doyon Utilities’ Authorized Representative.

    3. Copper Water Service Bedding

    Unless called out otherwise on the Plans or Standard Details, specified otherwise herein, or directed otherwise by Doyon Utilities’ Authorized Representative, pipe bedding for copper tubing shall meet the requirements of Class “B” bedding per Division 20 - Earthwork.

    4. Copper Water Service Thaw Wires

  • JBER STANDARD CONSTRUCTION SPECIFICATIONS AND DETAILS DIVISION 60 – WATER DISTRIBUTION SYSTEMS

    2021 25 Doyon Utilities, LLC

    A #2 stranded copper thaw wire shall be installed as shown on the Standard Details. Thaw wires shall be of lengths to extend one foot minimum above finished grade to provide accessibility for future use.

    5. Copper Water Service Insulation

    All copper water services shall be insulated with board insulation 4 inches thick (two each 2 inch thick layers) by 4 foot minimum width, centered over the water service and extending the full length of the water service plus a minimum of 2 additional feet at each end. To the extent possible, the bottom of the insulation shall be 6 inches above the top of the water service. Board insulation shall be coped as necessary to fit snugly around key boxes to the satisfaction of Doyon Utilities’ Authorized Representative.

    F. Water Line Separation Requirements from Sanitary Sewers and Storm Drains

    All water lines, including mains, fire hydrant assemblies, fire lines, and water services, shall be constructed to meet all separation requirements of 18 AAC 80.020, or the following requirements, whichever are more stringent:

    1. Water lines shall be installed at least 10 feet horizontal out-to-out from parallel sanitary sewers, storm drains, and sewer and storm drain appurtenances (including but not limited to gravity sewer mains, gravity sewer services, sewer manholes, sewer clean-outs, wastewater lift stations and force mains, storm drain mains, catch basins and catch basin leads, and storm drain manholes).

    2. Water line pipe at sanitary s