51
KAILUA RWWTP TUNNEL INFLUENT 11109-1 FABRICATED SLIDE GATES PUMP STATION AND HEADWORKS ADDENDUM NO. 5 FACILITY, JOB NO. W1-13 SECTION 11109 FABRICATED SLIDE GATES PART 1--GENERAL 1.01 SUMMARY A. This section specifies the minimum requirements for corrosion-resistant fabricated slide gates (gates) for control of wastewater flow as shown on the Drawings and specified herein. Gates shall be all 316L stainless steel construction. The scope of supply shall include gate frames, slides, seals, stems, stem guides, operators, floor stands, gate enclosures where specified, and all other appurtenances, in-place and complete. Powered operators for gates are specified in Section 15185. B. EQUIPMENT LIST: Equipment provided under this section is listed in paragraph 1.04, Service Requirements. 1.02 QUALITY ASSURANCE A. REFERENCED STANDARDS: This Section incorporates by reference the latest revisions of the following documents. In case of conflict between the requirements of this Section and the listed documents, the requirements of the Contract Specifications shall prevail. Reference Title ASTM A240 Standard Specification for Chromium and Chromium- Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications ASTM A276 Standard Specification for Stainless Steel Bars and Shapes ASTM D2000 Standard Classification System for Rubber Products in Automotive Applications AWWA C561-12 Fabricated Stainless Steel Slide Gates ASTM A380 Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, Equipment, and Systems B. UNIT RESPONSIBILITY: Unit responsibility, as specified in Section 11000, is assigned to the gate manufacturer (Manufacturer) for the gates and appurtenances specified in this Section and for the powered operators specified in Section 15185.

FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

  • Upload
    others

  • View
    14

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-1 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

SECTION 11109

FABRICATED SLIDE GATES

PART 1--GENERAL

1.01 SUMMARY

A. This section specifies the minimum requirements for corrosion-resistant fabricated

slide gates (gates) for control of wastewater flow as shown on the Drawings and

specified herein. Gates shall be all 316L stainless steel construction. The scope of

supply shall include gate frames, slides, seals, stems, stem guides, operators, floor

stands, gate enclosures where specified, and all other appurtenances, in-place and

complete. Powered operators for gates are specified in Section 15185.

B. EQUIPMENT LIST: Equipment provided under this section is listed in paragraph 1.04,

Service Requirements.

1.02 QUALITY ASSURANCE

A. REFERENCED STANDARDS: This Section incorporates by reference the latest

revisions of the following documents. In case of conflict between the requirements

of this Section and the listed documents, the requirements of the Contract

Specifications shall prevail.

Reference Title

ASTM A240 Standard Specification for Chromium and Chromium-

Nickel Stainless Steel Plate, Sheet, and Strip for

Pressure Vessels and for General Applications

ASTM A276 Standard Specification for Stainless Steel Bars and

Shapes

ASTM D2000 Standard Classification System for Rubber Products in

Automotive Applications

AWWA C561-12 Fabricated Stainless Steel Slide Gates

ASTM A380 Standard Practice for Cleaning, Descaling, and

Passivation of Stainless Steel Parts, Equipment, and

Systems

B. UNIT RESPONSIBILITY: Unit responsibility, as specified in Section 11000, is assigned

to the gate manufacturer (Manufacturer) for the gates and appurtenances specified

in this Section and for the powered operators specified in Section 15185.

Page 2: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-2 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

C. All gates for this project shall be supplied by the same Manufacturer, who shall be

fully experienced, reputable and qualified in the manufacturing of the equipment

furnished and who has been fabricating gates and appurtenances for a minimum

period of 10 years.

1.03 SUBMITTALS

A. PROCEDURES: Section 01300.

B. Product information, calculations, charts and graphs demonstrating compliance with

the requirements of this Section and the Drawings.

C. Plans, elevations, sections, and details showing dimensions and mounting

requirements for each gate specified.

D. Manufacturer’s data including materials of construction, construction details of

equipment, and weight of equipment.

E. Manufacturer’s product literature.

F. Electric motor operator data, where applicable, including manufacturer's catalog

information, complete dimensional data, drive unit size, calculations substantiating

selection and wiring diagrams.

G. Certificate of unit responsibility attesting that unit responsibility has been assigned

as specified in this Section and Section 11000. No other submittal material will be

reviewed until the certificate has been received and found to be in conformance with

these requirements.

H. Results of factory testing including leak testing per AWWA C-561, Section 5.22.

I. Name, location and qualifications of the passivation shop.

J. Certification attesting that all gate components have been cleaned, passivated and

tested in accordance with the procedures described in this section

K. Manufacturer’s operation and maintenance manual defining maintenance

requirements.

1.04 SERVICE REQUIREMENTS

A. PERFORMANCE REQUIREMENTS

1. Gates are intended to isolate channels and pipes or to control water surface

elevations.

Page 3: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-3 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

2. Gates shall be designed for the Design Head specified. The Design Head is

defined as the maximum head that will be applied to the gate. The Design

Head is measured from the maximum water surface elevation to the bottom

of the gate.

3. Slides and frames shall have a safety factor of 5 with regard to ultimate

tensile, compressive and shear strength; calculations shall be submitted to

show conformance.

4. Gates shall comply with field leakage tests as defined in AWWA C561.

5. Gates shall not require exercise at a frequency of more than once per year to

meet the extended warranty requirements described in this section.

6. Gates shall be passivated prior to shipping in accordance with the

requirements of this section.

B. See the Gate Schedule for specific dimensional and design requirements.

Gate Schedule

Equipment

Number

Gate

Type a

Size

W X H b

(inches)

Frame

Type c

Frame

Mounting d

Design Head e, feet Operator

Type f

Operator Special

Seating Unseating Mount g Feature h

SG 100,001 S 48 x 48 NSC 3 4 NA E SP RB

SG 100, 002 S 48 x 48 NSC 3 4 NA E SP RB

SG 100, 101 C 42 x 80 SC 1 6.0 NA E YTT

SG 100, 109 C 42 x 60 SC 1 6.0 NA E YTT

WG 100, 111 W 96 x 24 SC 2 2.5 NA MH YA DS

SG 100, 182 S 48 x 48 SC 1 NA 3 E YTT

SG 200, 101 S 55 x 55 NSC 3 66 NA E SP

SG 200, 201 S 55 x 55 NSC 3 66 NA E SP

SG 300, 113 S 30 x 30 SC 2 10 70 i E YA EN

SG 300, 123 S 20 x 20 SC 2 10 55 i E YA EN

SG 300, 133 S 30 x 30 SC 2 10 70 i E YA EN

SG 300, 111 C 36 x 98 SC 1 7 NA E YA EN

SG 300, 121 C 36 x 98 SC 1 7 NA E YA EN

SG 300, 131 C 36 x 98 SC 1 7 NA E YA EN

SG 300, 114 S 6 x 6 NSC 2 7 NA MFN WB

SG 300, 124 S 6 x 6 NSC 2 7 NA MFN WB

SG 300, 134 S 6 x 6 NSC 2 7 NA MFN WB

SG 300, 112 C 36 x 72 SC 1 5 NA E YA EN

SG 300, 122 C 36 x 72 SC 1 5 NA E YA EN

SG 300, 132 C 36 x 72 SC 1 5 NA E YA EN

SG 300, 211 C 60 x 72 SC 1 5 NA E YA EN

SG 300, 311 C 60 x 72 SC 1 5 NA E YA EN

SG 300,161 S 48 X 48 SC 2 6 NA E YA EN

SG 300, 171 C 11.75 X 12 SC e 1 0 E YTT RB, *

SG 300, 172 C 11.75 X 12 SC e 1 0 E YTT RB, *

SG 600, 001 S 36 x 36 NSC 3 20 NA E YTT RB

SG 600, 002 S 36 x 36 NSC 3 20 NA E YTT RB

Page 4: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-4 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

Equipment

Number

Gate

Type a

Size

W X H b

(inches)

Frame

Type c

Frame

Mounting d

Design Head e, feet Operator

Type f

Operator Special

Seating Unseating Mount g Feature h

SG 600, 003 S 48 x 48 NSC 3 20 NA E YTT RB

SG 700, 101 C 42 x 84 SC 1 7 NA E YTT

SG 700, 201 C 42 x 84 SC 1 7 NA E YTT

SG 700, 103 S 6 x 6 NSC 2 12 NA MFN WB

SG 700, 203 S 6 x 6 NSC 2 12 NA MFN WB

a. C = channel, S = Sluice, W = weir

b. Nominal size of opening (aperture style gates) or channel width x slide height (channel and weir gates). See Drawings

for additional dimensional requirements.

c. SC = self contained, NSC = non self contained

d. 1 = embedded frame/sill, 2 = wall mounted with embedded sill, 3 = upper section of frame wall mounted with sill and

lower portion of frame embedded (e.g., sluice style gate mounted in channelized structure), e = flange mounted

e. Design Head is the maximum water surface elevation minus the invert elevation of the gate.

f. MH = manual hand wheel, MFN = manual 2” floor nut, E = electric motor

g. YTT = yoke-mounted torque tube, SP = structure-mounted pedestal, YA = yoke-mounted actuator, WB = wall bracket

h. RB = radius bottom, DS = dual stem, EN = stainless steel enclosure, *coordinate requirements with sluiceway mfg.

(Section 11129)

i. The unseating head indicated would be an unusual condition resulting from a closed gate on a pressurized forcemain.

For this condition, the gate would not need to seal the pipe to AWWA standards but the gate would need to withstand

the resulting force without damage to the gate or seals.

1.05 COMPONENT SIZING

A. Operating forces used for determining the strength of gate components (yokes,

frames, slides, stems, slide nut pockets, and other load-bearing members) shall be

based on the sum of the guide friction force (computed using an opening breakaway

friction factor of 0.2) and the weight of slide and stem.

B. When the gate is in motion, the operating forces shall be based on the sum of the

frictional force (using a guide friction factor of 0.25) and the weight of slide and

stem.

1.06 EXTENDED WARRANTY

A. In addition to the warranty specified in Section 01740, the Manufacturer must

provide a special extended warranty for gates and appurtenances (excluding electric

operators) with all of the conditions listed below:

1. The Manufacturer shall guarantee the gates, when installed and operated as

recommended by the Manufacturer, trouble-free operation for a period of 10-

years starting at the date of delivery of equipment to the project site.

2. If, during the warranty period, the the gate fails to meet the specified

requirements, the Manufacturer shall remedy the problem at no cost or

refund the material and installation cost for a replacement gate.

Page 5: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-5 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

3. Leakage during the warranty period shall be within the limits defined in

AWWA C561. The manufacturer shall provide labor cost and materials

required for seal replacement to remedy excess leakage.

4. Gate slides shall be free of sticking or binding and move freely via operator

input without damaging equipment when exercise of the gate slides is limited

to once per year. Exercising is defined as fully opening and closing the gate

once.

5. Any gate component with evidence of corrosion affecting the function or

service life of the component shall be replaced free of charge during the

warranty period.

6. Electric operators associated with gates will be covered under the normal

warranty requirements defined in Section 01740.

1.07 PICKLING AND PASSIVATION OF STAINLESS STEEL

A. GENERAL:

1. Equipment specified under this section shall be cleaned, descaled and

passivated in accordance with methods defined in ASTM A380 – Standard

Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts,

and the specific requirements of this section.

2. For purposes of this section, passivation is defined as the removal of

exogenous iron or iron compounds from the surface of stainless steel by

means of treatment with an acid solution that will remove the surface

contamination but will not significantly affect the stainless steel itself.

3. The processes specified in this section shall be performed in an

environmentally controlled shop with at least 5-years experience performing

nitric-hydrofluoric acid solution pickling in compliance with all state and

federal laws. The equipment manufacturer shall submit the name and

qualifications of the passivation shop in accordance with the submittal

requirements of Section 01300 prior to shipping parts for passivation.

4. Equipment components that bolt together shall be disassembled prior to

passivation treatment to allow for effective circulation and removal of

cleaning solutions.

5. All fasteners and anchor bolts required for assembly and mounting of

equipment shall be batch processed at the passivation shop, then dried and

sealed in plastic bags and labeled. Fasteners shall conform to the

requirements of Section 11000.

Page 6: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-6 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

6. The use of “fabricator’s crayons” shall be prohibited during fabrication of

equipment as these marks may prevent proper passivation.

B. PASSIVATION PROCESS REQUIREMENTS:

1. The processes required for proper passivation shall include precleaning,

chemical descaling, neutralization, post-cleaning inspection, testing,

certification, and protection as defined below.

a. Precleaning – Precleaning required for the removal of all grease, oil,

paint, soil, grit and other gross contaminants preparatory to the

fabrication process shall be accomplished by vapor degreasing,

immersion or spray application of alkaline or emulsion cleaners,

steam, or high pressure water jetting.

b. Chemical Descaling –Chemical descaling (pickling) shall be

accomplished by immersion bath or spray application of a nitric-

hydrofluoric acid solution to produce a matt white, pristine

appearance. The acid solution and process used shall conform to

Code B, Table A1.1, ASTM A380.

c. Neutralization – The chemical reactions of the pickling media shall

be stopped by rinsing of the part with a 10 percent soda ash solution

for a minimum of 30-minutes followed by a water bath using high

pressure water jetting. The pH of the wetted part surface shall be

same as the water used for rinsing.

d. Post Cleaning Inspection – Post treatment inspection of the

chemically pickled and neutralized part shall exhibit a clean surface

with no signs of etching, pitting, or frosting resulting from the pickling

procedure.

e. Testing – The passivated part shall be tested for the presence or

absence of free iron with a solution of potassium ferricyanide as

defined in Verification Test Practice E, ASTM A967. The test solution

shall be mixed and used within 24-hours or less and applied with

sterile cotton swabs. The test result shall indicate an absence of free

iron on the surface of the part.

f. Certification – All parts passivated shall be certified by an officer of

both the manufacturer and the passivating shop as having been

cleaned and passivated and tested in accordance with the

procedures described in this section. Test results shall indicate an

absence of free iron on all passivated surfaces. The Certification

shall be submitted to the City prior to shipping the equipment to the

project site. Equipment that is not certified will not be accepted.

Page 7: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-7 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

g. Protection – Protection shall be provided by applying shrink wrap to

all parts of the equipment sufficient to prevent exposure of

passivated surfaces to contaminants during handling, shipping and

installation. Protected equipment shall be tagged with highly visible

warning signs stating the equipment has been passivated and shall

only be opened by authorized personnel. Equipment arriving at the

project site without proper protection will require retesting for the

presence of free iron and re-passivation if free iron is detected.

C. Assembly of equipment following passivation – If assembly of bolted parts is

required following passivation, it shall be done at the manufacturing facility under

clean conditions such that the parts will not be contaminated with exogenous iron or

iron compounds. Following assembly, retest for the presence of free iron per ASTM

A967 and treat any contaminated areas with citric acid solution. Equipment

requiring assembly shall be re-shrink wrapped sufficient to prevent exposure of

passivated surfaces to contaminants during handling, shipping and installation.

D. WITNESS OF PASSIVATION PROCESS:

1. The City retains the right to witness the stainless steel passivation process.

Provide at least 30-days notice to the Officer-in-Charge prior to start of

passivation process.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. Gates shall be all stainless steel construction. Acceptable manufacturers include

the following:

1. Stainless steel slide gate manufacturers:

a. Whipps, Inc. Athol, Massachusetts

b. Fontaine International Corporation, Orange Massachusetts

d. Waterman Industries, Exeter California

B. The manufacturer’s standard models or products may require modifications to

conform to specified requirements.

Page 8: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-8 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

2.02 MATERIALS

A. Materials of construction shall be as follows:

Component Material

Slide ASTM A240 Type 316L stainless steel

Frame ASTM A276 Type 316L stainless steel

Slide Seats ASTM D4020 UHMW Polyethylene

Seating faces or seals ASTM D4020 UHMW PE

Stem and supports ASTM A276 Type 316 stainless steel

Fasteners, adjusting

hardware, and anchors

ASTM A276 Type 316 stainless steel

Yoke ASTM A276 Type 316L stainless steel

Flush bottom seal Resilient synthetic rubber bonded to frame or ASTM

D2000 neoprene

Pedestal/Torque Tube ASTM A276 Type 316L stainless steel

Enclosure ASTM A276 Type 316L stainless steel

2.03 FEATURES

A. GENERAL:

1. Mounting requirements as shown on the Drawings and specified in this

section.

2. Unless otherwise indicated, provide gates with rising stems with clear,

graduated plastic covers in accordance with AWWA C561.

3. Weir gates having a width greater than 60 inches shall have dual stems

mechanically linked to a common operator.

4. Stainless Steel Passivation: All stainless steel components to be cleaned,

descaled, and passivated after fabrication in accordance with ASTM A380

and the specific requirements of this section. .

B. SLIDE:

1. Slides shall consist of steel plate reinforced with steel members welded to

the plate. Minimum thickness of the steel plate shall be ¼”.

Page 9: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-9 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

2. Slides shall be reinforced with horizontal stiffeners welded to vertical

stiffeners. Slides shall not deflect more than 1/1000 of the span of the gate

under the design head.

3. Gates with an opening width x design head of 80’ or greater shall

incorporate a 3”minimum structural edge extended into the guide grove or

design equivalent.

4. The slide manufacturer shall submit drawings and comprehensive design

criteria to substantiate that the maximum deflection for each slide has not

exceeded 1/1000 of the span regardless of the type used. Comprehensive

safety factor calculations shall include bending moments, buckling stress,

and bonding stress with thermal expansion factors. Safety factors shall be

calculated for the slide under the maximum head indicated in this section,

and for shear at the slide/seal interface.

C. FRAME:

1. Guide frames extending above operating floors or slabs shall be self-

contained and sufficiently strong so that no further support or reinforcement

is required. Frames for self-contained gates shall be designed for maximum

loads imposed by gate operators in the stalled condition plus the weight of

the slide, stem, torque tube or pedestal, and operator.

2. The yoke shall be formed by two structural members welded at the top of the

guides to provide a one-piece rigid frame and configured to enable slide

removal without removing the yoke. The yoke shall be designed to support

the maximum stall force applied by the operator in addition to the weight of

the stem, torque tube or pedestal, and operator where this equipment is

being supported at the yoke.

3. The frame shall be designed with a minimum factor of safety of 4 with regard

to ultimate tensile, compressive, and shear strength.

4. Wall-mounted frames shall be the flanged type. Guides for wall mounted

frames shall be formed from one plate with wrap around gussets. Bolted

together guides are not accepted.

5. Embedded frame gates shall be installed in block-out recesses formed in the

channel walls and floor.

6. Thimble-mounted gates shall be drilled to match the wall thimble. Wall

thimbles shall conform to AWWA C561.

Page 10: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-10 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

D. SEALS:

1. Gates shall incorporate factory-set self-adjusting seals utilizing a sealing

surface of UHMW PE to achieve the leakage rates specified. Self adjusting

seals shall not require adjustment and shall be replaceable without removing

the guide frame.

2. All moving contact surfaces shall be incompatible to each other thereby

minimizing sticking or jamming.

3. Seals sandwiched between bolted together guide members are not

acceptable.

E. STEMS:

1. All stems shall be of the rising type unless otherwise specified.

2. Provide stem diameter to withstand at least twice the rated output of the

electric operator or the manual operator at 40-pounds pull. Stems shall be

minimum 1-1/2-inch diameter.

3. Stem guides shall be provided at intervals necessary to maintain a

slenderness ratio (L/R) of the unsupported stem length of less than 200,

where R is the radius of gyration of the stem.

4. Stems shall be designed to withstand tensile and compressive loads that

occur under maximum operating conditions. Design for compressive loading

shall meet AISC code where K=1 with a minimum safety Factor of 2 to 1.

5. Stem sections shall be joined together by solid couplings, threaded and

keyed to the stems. All couplings of the same size shall be interchangeable.

6. The threaded portion of the stem shall have dual lead, machine rolled, full

depth ACME type threading with a 16 micro-inch finish or better. Stub

threads are not acceptable.

7. Stems shall be fixed to the slide by a threaded and keyed assembly into a

lifting nut attached to the disc in a lifting bracket, which is bolted to the disc.

The bolts securing the bracket shall be in tension and not shear.

8. Yoke-supported stems shall be provided with a torque between the top of the

yoke and the operator constructed of 316L SS. The torque tube shall have

appropriate flanges at the top and bottom for mounting to the operator and

yoke, and be sized and constructed to provide lateral support to the stem

between the yoke and the operator. Torque tubes shall be provided with

UHMW stem guides at appropriate intervals to provide lateral support to the

Page 11: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-11 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

stem. Torque tubes shall be equipped with tabs for bolting lateral supports;

the dimensions and location of the tabs shall be determined by the

manufacturer and coordinated during the submittal review process.

F. OPERATORS:

1. See Gate Schedule for operator requirements.

2. Unless otherwise indicated, manual operators shall meet requirements of

AWWA C561 as appropriate.

3. Yoke-supported operators shall be provided with 316 SS pedestals between

the top of the yoke and the operator. See drawings for length requirements.

4. Unless otherwise indicated and whenever possible, operator base shall be

set 42” above the walking surface.

5. Electric operators are specified in Section 15185.

G. ENCLOSURES:

1. Gates isolating pipes and channels within the headworks structure shall be

equipped with all stainless steel enclosures for odor control purposes.

2. Enclosures shall be designed and fabricated by the gate manufacturer.

Submit drawings prior to fabrication.

3. Enclosures shall be essentially air tight and designed to withstand negative

pressure of 0.3” WC imposed by the odor control system drawing air from

below the channel covers.

4. Enclosures shall be compatible with specified electric actuators and shall be

removable without removing the actuator.

5. Enclosure face panels shall be removable from one side. Removable

panels shall be provided in sections weighing no more than 30-pounds

each. Provide handles for lifting the removable face panels.

2.04 FACTORY TESTING

A. Conduct shop performance test per AWWA C563 or AWWA C561 as applicable.

Gates SG 200, 101 and SG 200, 201 shall be factory leak tested, all other gates

to be field leak tested following installation. Submit written report of results to

Officer-in-Charge.

Page 12: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 11109-12 FABRICATED SLIDE GATES

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

B. The City retains the right to witness the stainless steel preparation and passivation

process. Provide at least 30-days notice to Officer-in-Charge prior to start of

passivation process for gates and appurtenances.

PART 3--EXECUTION

3.01 INSTALLATION

A. Install gates and appurtenances in accordance with manufacturer’s instruction and

as shown on the Drawings.

B. For embedded gates, fill blockouts along guide frames and gate sill with grout

following installation.

C. Provide all 316 SS anchors; size anchors in accordance with the design

requirements specified in this section and in accordance with Sections 01900,

05501, and 11000.

D. Proper handling shall incorporate all practices described in Section 8.5 – Protection

of Cleaned Surfaces, ASTM A380. Passivated parts contaminated due to improper

handling and installation will require retesting for the presence of free iron and re-

passivation if free iron is detected.

3.02 FIELD TESTING

A. Operation and Leakage Tests: In accordance with AWWA C563 or AWWA C 561 as

appropriate.

3.03 TRAINING

A. Provide four hours of training as specified in Section 01660. Training shall be

certified on Form 11000-B specified in Section 01999.

3.04 MEASUREMENT AND PAYMENT

A. Fabricated slide gates shall not be paid for directly, but shall be considered

incidental and included in the lump sum bids for the respective items in the Proposal

Schedule.

**END OF SECTION**

Page 13: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-1 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

SECTION 16850

FIRE ALARM SYSTEM

PART 1 GENERAL

1.01 SUMMARY

A. This Section specifies the minimum equipment to be furnished by the Contractor to

provide system functionality and performance required for a distributed digital fire

monitoring and control system for the Tunnel Influent Pump Station (TIPS) Building.

The fire alarm system (FAS) at the TIPS Building shall include an information

management personal computer, digital fire control panel(s), remote annunciation

panels, conventional and addressable low voltage analog detecting devices,

supervisory devices, NFPA 820 ventilation monitoring device interfaces, devices to

open the elevator disconnects, and notification appliances. The FAS shall monitor

required parameters and initiate required local and remote responses as directed by

the Authority Having Jurisdiction (AHJ). The Contractor shall turn over to the City a

fully operational FAS that is in full compliance with national and local codes and has

been approved by the AHJ. Any additional fire alarm equipment, panels, devices,

appliances, detection devices, mounting equipment, cabling or other FAS related

hardware or software required by the AHJ, shall be supplied, programmed, tested,

installed and commissioned by the Contractor at no additional cost to the City.

B. The TIPS Building FAS shall have a Master Fire Control Panel (MFCP) and Fire

Annunciation Panel (FAP), located in the TIPS building as shown in the contract

drawings, with additional Fire Control Panels (FCPs) as required. FAS control panels

shall communicate with hardwired inputs and outputs for monitoring and alarming

within the building (and zones as appropriate), and shall communicate all FAS points

with each other on a peer to peer network as required. All FAS database points shall

be accessible from the MFCP regardless of origination node. The MFCP shall

automatically retransmit all building alarms to the remote monitoring site(s) over

redundant telephone lines, as approved by the AHJ.

C. Provide engineering services to design and build the FAS, with the required products

that meet the minimum system functionality and performance as specified herein, in

accordance with NFPA and Factory Mutual DS 5-48, and as required to gain the

approval of the AHJ. If conflicts arise, the more stringent requirement shall apply to

the design. Programming services include the design and implementation of FAS

software and hardware, network device configuration, interface protocol

programming, and on-site support for installation, testing and commissioning of the

system.

D. Equipment List: The Contractor system design shall include all of the devices,

appliances, and equipment required to meet the performance and functionality

specified herein and gain approval of the AHJ. As a minimum, provide the following

fire control and fire alarm panels:

Page 14: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-2 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

Item Equipment No.

Kailua TIPS Master Fire Control Panel MFCP 200,980

Kailua TIPS Fire Annunciation Panel FAP 200,981

Kailua TIPS Fire Control Panel(s) As required

1.02 QUALITY ASSURANCE

A. Referenced Standards: This Section incorporates by reference the latest revisions of

the following documents. In case of conflict between the requirements of this

Section and the listed documents, the requirements of the Contract Specifications

shall prevail.

Reference Title

ASME A17.1

FM AG

Safety Code for Elevators and Escalators

Factory Mutual (FM) Approval Guide

IFC 2006 International Fire Code

ICC IMC International Code Council – International Mechanical Code

NFPA 1 Honolulu Fire Code with amendments

NFPA 13 Standard for the Installation of Sprinkler Systems

NFPA 70 National Electrical Code

NFPA 72 National Fire Alarm Code

NFPA 90A Standard for the Installation of Air Conditioning and Ventilating

Systems

NFPA 92 Standard for Smoke Control Systems

NFPA 101 Life Safety Code

NFPA 820 Standard for Fire Protection in Wastewater Treatment and

Collection Facilities

UL 38 Manually Activated Signaling Boxes

UL 268 Smoke Detectors.

UL 268A Smoke Detectors (HVAC)

UL 1971 Standard for Visual Signaling Appliances

UL 346 Waterflow Indicators for Fire Protective Signaling Systems

UL 464 Audible Signal Appliances

UL 497B Protectors for Data Communication and Fire Alarm Circuits

UL 521 Heat Detectors for Fire Protective Signaling Systems

UL 864 Control Units for Fire Protective Signaling System

Page 15: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-3 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

Reference Title

UL 1076 Security

UL 1971 Visual Signaling Appliances

B. System Responsibility:

1. Contractor is responsible to provide the FAS design, programming,

installation and commissioning work that meets the requirements as

specified herein and on the Drawings, per NFPA codes and as approved by

the Authority Having Jurisdiction. The FAS design, installation and

commission work shall be provided by a FAS contractor that meets the

qualifications of this Section.

2. Contractor shall include all required fees for submission and review in their bid

price.

3. The Contractor shall provide on-site design reviews with the Officer-in-Charge

and shall provide on-site assistance, direction, and coordination during

installation, functional check-out, start-up, and commissioning of systems,

and as needed through project closeout. In addition, the Contractor shall

warrant the system and provide services for preventive and emergency

maintenance for a period of 365 days after the acceptance of the system by

the Authority Having Jurisdiction.

C. FAS Contractor Qualifications:

1. FAS contractor shall be regularly engaged in the design and installation of fire

alarm systems of similar scope and complexity, and have a local installation

and service organization experienced with the specified and submitted

equipment (where local is considered to be within 50 miles of the job site).

2. Upon completion of the installation, the Contractor shall certify that the final

system meets UL listing requirements.

3. The FAS contractor shall be qualified and certified to maintain ongoing

certification of the completed system to the UL installed system listing.

4. The FAS contractor shall provide a minimum of three references whose

systems are of similar complexity, have been designed and installed during

the past 5 years, and are currently in full operation.

5. The FAS Contractor’s qualified staff and support organization shall include:

a. Fire protection design engineer that:

1) Is currently registered as a Fire Protection Professional

Engineer with the State of Hawaii

2) Is a factory-trained and certified representative capable of

supervising software development and documentation,

Page 16: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-4 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

installation, field adjustments, preoperational testing, on-site

system testing, and final certification for the FAS provided.

3) Has a minimum of 5 years experience managing the design,

integration and installation of similarly sized FAS projects

4) Has intimate knowledge of the applicable codes including

International Building Code, National Fire Protection

Association, Uniform Fire Code, Hawaii State, and City and

County of Honolulu, HI fire, electrical and building codes.

b. Officer-in-Charge to manage the system design, approval and

procurement, and to provide on-site management of the system

staging, delivery, installation, testing and commissioning.

c. Current National Institute for Certification of Engineering

Technologies (NICET) Level III Technician to provide on-site

installation, application configuration, testing and commissioning

services.

d. Trainer with a minimum of 3 years experience training operators,

programmers, and maintenance staff on the supplied FAS equipment.

1.03 SUBMITTALS

A. PROCEDURES: In addition to the procedures specified in Section 01300, the

following general requirements include:

1. FAS design and equipment submittals shall be submitted as a complete

package for review by a licensed engineer. Upon receipt of comments, make

resubmissions as required to obtain approval.

2. FAS design drawings and calculations shall bear the imprint stamp of a

registered fire protection engineer responsible for the design and drawings.

B. Items to be Submitted for This Specification:

1. Provide copies of all FAS Contractor required licenses and bonds as required

by the State of Hawaii.

2. AutoCAD Format Drawings: Provide complete drawings which include the

following:

a. Drawings prepared on a computer-aided drafting (CAD) system and

delivered in an 11- by 17-inch drawing size and shall be complete

with borders and title blocks clearly identifying the project name and

scope. Electronic CAD drawing files shall be provided in “.DWG” file

format and submitted on DVD or CD media.

b. Drawing format in current version of AutoCAD, no older than 2013

version.

Page 17: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-5 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

3. Drawings: Provide the following updated and new drawings:

a. FAS one-line block diagram.

b. Floor plans showing all equipment and raceways, marked for size,

conductor count, type and percentage of allowable NEC fill used.

c. Panel layout drawings.

d. Panel wiring diagrams

e Connection diagrams

f. Interconnection diagrams

g. Elementary diagrams

h. Loop diagrams

i. Provide a FAS function matrix that illustrates alarm input/out events

in association with initiation devices. Matrix summary shall include

system supervisory and trouble output functions and any departures,

exceptions, variances, or substitutions from these specifications

and/or drawings at time of bid.

4. Manufacturer and Contractor’s data:

a. Provide catalog cut sheets for all material and equipment, installation

requirements, mounting dimensions, processors, network interfaces,

hardwired I/O, communication and power cabling and any other

equipment provided as part of the FAS. Include manufacturer’s

environmental compatibility charts for product selected, supervisory

power usage, alarm power usage, physical dimensions, and finish and

mounting requirements. Catalog cuts shall be edited to show only the

items, options, model numbers, and information that apply.

b. Provide FAS contractor qualifications.

5. System description, showing how the equipment operates as an integrated

system to meet the performance requirements specified herein, including

analysis and calculations used in sizing equipment required by the FAS. The

following information shall be supplied as a minimum:

a. Complete bill of materials which includes site equipment and system

configuration descriptions.

b. Operating system software, application software and software

configuration descriptions.

c. FAS network protocol descriptions with data flow diagrams.

Page 18: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-6 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

d. Third-party interface protocol, application, and system configuration

descriptions for communicating all required data and device status

information to third-party systems (KAI-PCS or KAN-PCS and auxiliary

systems) using BACnet, Modbus TCP, or approved protocol.

e. Start-up operations.

f. System expansion capability and method of implementation.

g. System power requirements (including supervisory and alarm power

requirements for all equipment). Include justification for power supply

ratings showing power requirements for each of the system power

supplies.

h. Battery capacity calculations.

i. Voltage drop calculations for wiring runs demonstrating worst-case

condition.

j. Submit manufacturer’s requirements for testing circuits and device

addresses prior to connecting to control panel.

k. System certifications.

l. Seismic design drawings, calculations, and data as specified in

Section 01900.

m. All FAS conductor colors for approval by the Officer-in-Charge prior to

installation.

n. System operation description including method of operation and

supervision of each type of circuit and sequence of operations for all

manually and automatically initiated system inputs and outputs. A list

of all input and output points in the system shall be provided with a

label indicating location or use of initiation device circuit, notification

appliance circuit, relay, sensor, and auxiliary control circuits.

6. Test Schedule and Procedures

a. Submit for approval, a testing schedule and step by step instructions

with anticipated results that demonstrate the required FAS functions

and performance for all tests specified in Section 01660.

b. Submit a formal manufacturer’s written requirements for testing

circuits and device addresses. Submit the Acceptance Test Plan (ATP)

for testing of the entire FAS and components in accordance with the

NFPA and this specification. Including requirements for testing

circuits and device addresses (for intelligent devices and

conventional device interface modules) submitted prior to connecting

to control panel. At a minimum the following tests shall be required:

device address, usage (alarm, supervisory, etc.), environmental

Page 19: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-7 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

compensation, temperature ratings for thermal detectors, and smoke

detector sensitivities. This requirement shall need approval before

any wiring is connected to the control panel.

c. Submit for approval, a testing schedule and step by step instructions

with anticipated results that demonstrate the required FAS functions

and performance.

d. Provide a record of all field test results.

7. Training Schedule and Documentation: Submit training schedule and

documentation to the Officer-in-Charge. Training documentation shall include

lesson plans and training manuals for the training phases that outline the

training subject matter. The training documentation shall include examples of

the training program materials, qualifications of the training instructor(s).

Schedule should minimize impairments to the plant operations and show the

duration of each training element.

8. Contract Close-out Submittals: In addition to the O&M manual requirements

in Section 01730, provide the following:

a. Functional Design Manual: It shall include a description of hardware

and software functions, interfaces, and requirements for all system

operating modes.

b. Hardware Manual: The manual shall describe all equipment

furnished including:

1) General description and specifications

2) Installation and check-out procedures

3) Equipment electrical schematics to the component level

4) System layout drawings and schematics

5) Manufacturer’s recommended spare parts list identifying

sources of supply

c. Software Manual: The software manual shall describe the functions

of all software and shall include all other information necessary to

enable proper loading, testing, and operation. The manual shall

include:

1) Definition of terms and functions

2) Use of system and applications software

3) Initialization, start-up, and shutdown

4) Alarm reports

5) Periodic and ad-hoc reports generation

6) Data base format and data entry requirements

7) Directory of all disk files

Page 20: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-8 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

d. Operator’s Manual: The operator’s manual shall fully explain all

procedures and instructions for the operation of the system including:

1) Computers and peripherals

2) System start-up and shutdown procedures

3) Use of system, command, and applications software

4) Recovery and restart procedures

5) Graphic alarm presentations

6) Data entry

7) Operator commands

8) Alarm and trouble event messages and reprinting formats

9) System access requirements

e. Maintenance Manual: The maintenance manual shall include:

1) Descriptions of maintenance for all equipment including

inspection, periodic preventive maintenance, fault diagnosis,

and repair or replacement of defective components.

2) Manufacturer’s recommended spare parts list.

3) Provide names, addresses, and telephone number of

qualified service organizations and staff.

f. Provide signed certification by the fire alarm system manufacturer

showing that their product comply with the requested requirement.

g. Provide system’s field testing records.

h. As-Built Drawings: Provide record drawings as specified in Section

01720. Record drawings shall be prepared by an individual

experienced with the work specified herein.

1.04 SEISMIC ANCHORAGE AND STRUCTURAL DATA:

A. Mechanical, instrumentation and control, electrical, nonstructural systems,

components, and elements permanently attached to the structure shall be anchored

and braced to resist seismic forces. Contractor shall design the structural

components, seismic attachment, braces, and anchors to the structure for all parts

or elements of the mechanical and electrical systems in accordance with Section

01900.

1.05 SHIPMENT, STORAGE, AND HANDLING

A. In addition to the requirements of Section 17000, the Contractor shall:

1. Deliver products to the project properly identified with names, model

numbers, types, grades, compliance labels, and similar information needed

for distinct identifications; adequately packaged and protected to prevent

damage during shipment, storage, and handling.

2. Provide on-site storage as allocated in the contract documents for equipment

and materials. Storage for electronic equipment, enclosures, cabinets,

Page 21: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-9 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

cabling and other non-conduit materials shall be in an environmentally

controlled area (70 degrees F, 50 percent RH). Off-site storage is acceptable

if authorized in writing by the Officer-in-Charge.

3. Protect stored equipment and materials from damage. Conduit and wiring

shall be stored in bundles covered with plastic covers. Conduit and other

equipment showing signs of rust or other moisture damage shall be removed

from site and replaced at no cost to City.

PART 2 PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. All equipment furnished shall be new and the latest state-of-the-art products of a

single manufacturer engaged in the manufacturing and sale of fire alarm systems

and detection devices for over five years. In addition, all equipment shall:

1. Be UL listed as a product of a single manufacturer under appropriate

category.

2. Not be modified or installed to alter or void UL label or listing.

3. Be approved by the AHJ, when required by state or local codes.

B. Acceptable fire alarm systems manufacturers include:

1. Simplex Grinnell, 4100U

2. Johnson Controls, JCI640

3. Siemens Firefinder Intelligent Fire Detection System

4. Or approved substitute

C. Substitutions: All proposed substitutions shall meet the product specified herein and

the requirements specified in Section 01300.

2.02 GENERAL SYSTEM AND OPERATIONAL REQUIREMENTS

A. The FAS shall consist of FAS application software to provide controlling, reporting,

and monitoring on graphical displays on all MFCP, FCPs, and FAPs.

B. The FAS shall be listed by UL for configuration as an approved NFPA fire alarm and

fire sprinkler releasing system. The system and its components shall also be UUKL

listed for use in a smoke control system. The FAS shall communicate with the Fire

Dampers system (Section 15912), fire suppression sprinkler system (Section

15330), and other systems identified herein, in Section 17500, and required by the

AHJ.

Page 22: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-10 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

C. The FAS shall be a microprocessor based detection and notification system having

the following:

1. Interactive, stand-alone, intelligent controllers capable of monitoring and

controlling hardwired and networked dynamic field I/O from the master MFCP

and all additional FCPs (as required) distributed throughout the Tunnel

Influent Pump Station process area communicating over the FAS serial

network (Ethernet preferred).

2. The FAS software shall allow for loading and editing instructions and

operating sequences as necessary. The FAS shall be capable of on-site

programming to accommodate system expansion and facilitate changes in

operation. All software operations shall be stored in a non-volatile

programmable memory within the fire alarm control unit. Loss of primary and

secondary power shall not erase the instructions stored in memory. FAS shall

be capable of storing dual configuration programs with one active and one in

reserve. Panel shall be capable of full system operation when downloading a

new configuration simultaneously.

3. The system shall include a history log as a means to recall alarms and trouble

conditions in chronological order for the purpose of recreating an event

history. Separate alarm and trouble history logs shall be provided.

4. The FAS shall include required patch panels, network switches, relays,

indicator lamps, wiring, wiring terminal blocks, and other devices, indicators,

equipment and accessories including, but not limited to:

a. Audible and visual notification alarm circuit zone control for the entire

facility.

b. Status indicators for sprinkling system water flow and valve devices.

c. Additional status or control functions as required.

5. Each intelligent addressable device and conventional device intelligent

interface shall cause a predetermined zone alarm at the fire panel located

within the building. The FAS shall display a map of the buildings floor plans,

indicating the location of the active fire alarm device and location of the fire

panel (You Are Here) so the responding fire personnel’s location is shown

relative to the active fire alarm device.

6. The FCP (MFCP) processors shall allow for loading or editing special

instructions and operating sequences as required and shall support on-site

programming to accommodate user modifications.

7. All system cards and modules shall be upgradeable by simply downloading

the latest module firmware using flash memory or comparable technology.

8. Provide a means, via a network port, to plug-in a laptop, log-in from a remote

site (over Internet or dial-up modem) to access diagnostic programs. Provide

Page 23: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-11 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

diagnostics and maintenance reporting software that is capable of retrieving

information selectively from the MFCP or any FCP on the network.

9. Power supplies, backup batteries or uninterruptible power supplies, wiring,

raceways, mounting equipment, enclosures, devices, software and hardware,

and miscellaneous equipment required for a complete operating system.

10. Walk-Test System Testing:

a. Provide a minimum of eight programmable pass-code-protected one

person testing groups, such that only a portion of the system need be

disabled during testing. The actuation of the ‘enable one person test’

program at the control unit shall activate the ‘one person testing

mode’ of the system as follows:

1) Bypass the telephone circuit connections and any

suppression release circuits for the testing group.

2) Bypass the control relay functions associated with the testing

group.

3) The control unit shall continue to indicate any trouble

conditions.

4) The alarm activation of any initiating device in the testing

group shall cause the audible notification appliances

assigned only to that group to sound a code to identify the

device or zone.

5) The control unit shall automatically reset itself after signaling

is complete.

6) Any opening of an initiating or notification appliance circuit

wiring shall cause the audible signals to sound for 4 seconds

indicating the trouble condition.

D. MFCP and FCP Operator Interface: The operator interface (OI) screen shall be a

minimum of a 6-inch LCD screen and shall:

1. Provide a graphical user interface with the capability to display large text

characters, hazmat icons and building maps easily readable and fully

representative of the plant areas.

2. Use standard NFPA 170 symbols for all devices, equipment, hazards and

people in the alarmed area; systems without this graphical display capability

shall supply a UL-listed graphics software package capable of providing

standard NFPA symbols with the FAS system.

3. Use a touch screen, menu driven interface or pushbuttons with a minimum of

four tabs for Supervisory, Alarms, Trouble, and Security.

4. Provide direct control of all FAS devices.

5. Provide scrolling and zoom capabilities.

6. Provide power supply loading display(s).

Page 24: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-12 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

7. Provide TROUBLE display for each supervised circuit

8. Provide ALARM display readout for each alarm initiating addressable device.

Do not require entry of device address numbers for alarmed device to be

viewed.

9. At the MFCP, provide system-wide FAS alarm log, trouble log, acknowledged

event log, silenced alarm log, and reset event log.

10. Be capable of recalling in chronological order alarm log, trouble log,

acknowledged event log, silenced alarm log, and reset event log for the

purpose of recreating an event history.

E. FAS Event Conditions:

1. Signal Priority: There shall be four priority levels with Fire Alarm events being

the highest priority. Supervisory and Trouble events shall be categories into

the second, third, and forth priority with the higher priority taking precedence

over the lower one regardless of which occurred first.

2. All events shall be annunciated at the FCP and the FAP remote annunciator

panel, indicating location and type of device.

3. Seamless Operation. Signals from zones shall not prevent or interfere with

each other, so that, the activation of an addressable device does not prevent

the receipt of signals from subsequent addressable device activations.

4. Zones shall be manually re-settable from the FAS once the devices are

restored to normal.

5. Provide single key access to graphical displays of event conditions with detail

screens dedicated to the event which provides additional text messages and

details about the event.

6. FAS Alarm Condition:

a. Activate fire alarm audible horns, visual strobes, and automatic

control devices.

b. Energize the ANSI 117-1 signal with synchronized audible alarms

(horns and/or bells) and synchronized strobes throughout the facility.

c. Transmit alarm information to the remote monitoring site.

Automatically route alarm, signal to a remote central station service

transmitter provided under another contract.

d. Transmit alarm information indicating the zone, zone location and

type of device in alarm for display and logging at the FCPs and MFCP.

Page 25: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-13 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

e. Retransmit alarm information to the KAI-PCS (as applicable) and

auxiliary systems as required herein, in Section 17500, and as

required by the AHJ.

f. Initiate shaft pressurization upon activation of a smoke detector

adjacent to the stair or a sprinkler water flow switch.

1) Open dampers DPR 200,750, DPR 200,751, DPR 200,753,

and DPR 200,754.

2) After a delay of 15 seconds (adjustable), start fans SF

200,731, SF 200,732, SF 200,739, and SF 200,740.

3) Fans shall not shut down and dampers close until the

relevant MFCP or FCP is manually reset.

g. When the sprinkler flow is greater than the theoretical maximum flow

from the smallest sized orifice sprinkler installed, actuate the

dedicated sprinkler system water flow alarm.

h. Initiate elevator functions in accordance with ASME/ANSI A17.1

including the following:

1) Elevator Recall, primary and alternate level

2) Pre-Action Sprinkler Valve

3) Activate the elevator cab annunciator.

4) Shunt Trip main elevator power supply.

i. Flash visual signals on display until activation of either a system reset

or alarm silence switch, configurable by user.

j. Silence audible signals from the fire alarm control panel when the

alarm silence switch is activated.

k. Record the alarm condition description, time of occurrence and

initiating device to the KAI-PCS (as applicable), log to the FAS history

log.

l. Activate contact for status to the KAI-PCS.

7. Supervisory Condition:

a. A supervisory signal will be initiated under following conditions:

1) Main sprinkler valve is closed.

2) Post indicator valve is closed.

3) Any sprinkler or standpipe OS&Y valve is closed.

4) Loss of ventilation fans, as required by NFPA 820.

5) Any other conditions required by code or AHJ.

b. Activate supervisory audible and dedicated visual signals at the FCP

and FAPs.

Page 26: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-14 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

c. Transmit alarm information to the remote monitoring site.

Automatically route supervisory signal to a remote central station

service transmitter.

d. Silence audible signals when acknowledged from the FAS by the

supervisory acknowledge switch.

e. Record the supervisory condition description, time of occurrence and

initiating device to the KAI-PCS (as applicable), log to the FAS history

log.

f. When the supervisory condition returns to normal, clear the

supervisory LED and return to normal.

g. Activate contact for status to the KAI-PCS.

8. Trouble Condition:

a. Trouble signal will be initiated under following conditions:

1) Open connection on an initiation or alarm indicating circuit.

2) Open connection in wiring to MFCP, FCP or FAP.

3) Ground fault condition.

4) Auxiliary manual control switch out of normal position.

5) Loss of 120V operating power to FCP or FAS, or notification

appliance.

6) Low or no battery voltage condition.

7) Any other conditions required by code or AHJ.

b. Transmit alarm information to the remote monitoring site.

Automatically route trouble signal to a remote central station service

transmitter provided under another contract.

c. Silence trouble audible signals from the MFCP or the associated FCPs

if in a different building.

d. Flash visual signals on display until activation of either a system reset

or the trouble condition is corrected.

e. Trouble conditions that have been restored to normal shall be

automatically removed from the trouble display queue and not

require operator intervention. This feature shall be software

selectable and shall not preclude the logging of trouble events to the

historical file.

f. Trouble condition for primary system power failure to the FAS shall be

automatically delayed for 60 seconds to eliminate spurious reports as

a result of power fluctuations.

Page 27: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-15 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

g. Record the trouble condition description, time of occurrence and

initiating device to the FAS history log, to the KAI-PCS (as applicable).

h. Activate contact for status to the KAI-PCS.

9. Standalone Duct Alarm Condition:

a. De-energize air-handling equipment via duct detectors integral

contact.

b. Activate associated annunciator for system trouble and alarms.

c. Fan shall be reset by the key switch.

2.03 FIRE ALARM SYSTEM CONTROL PANELS FCP (MFCP)

A. General:

1. Comply with UL 864, Control Units for Fire Protective Signaling Systems.

2. Master Fire Control Panel (MFCP) shall:

a. Communicate over a Ethernet network with its associated remote Fire

Annunciation Panel (FAP).

b. Monitor the status all area FCP monitored points and control

commands. MFCP shall retransmit all FAS monitoring points and

control commands to the remote monitoring site over telephone

and/or network connections.

c. Communicate with all hardwired detection devices and audible/visual

alarm appliances.

d. Automatically retransmit all site alarms with remote monitoring sites

over redundant local telephone lines as approved by the AHJ.

e. Ethernet Network Interface:

1) Capability to communicate with the Plant Control System (KAI-

PCS) over an Ethernet network utilizing a Plant Control System

vendor BACnet, Modbus TCP, or an approved open system

protocol. An approved open protocol is one that is supported

by multiple manufacturers, capable of exchanging data and

the required information with the specified third-party

systems and is acceptable to the Officer-in-Charge.

2) This interface shall provide in the future monitoring of all

detailed status information available on the fire alarm system

network to the KAI-PCS . Detailed information shall include,

but not be limited to, Alarm, Supervisory, and Trouble

conditions, time stamped alarm and event logs, system

status, individual addressable point status, auxiliary function

Page 28: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-16 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

status, circuit status, and values associated with the

monitoring functions. All MFCP and area FCP monitored

points shall be available for integration into the KAI-PCS (as

applicable) and auxiliary systems.

3. The MFCP and FCPs shall be a distributed modular, microprocessor-based,

state-of-the-art fire alarm system for processing initiation device information,

control function calculations, and generating the programmed output

response. System response time from initiation device detection to output

response shall not exceed 4 seconds maximum. MFCP and FCPs shall:

a. Each FCP shall be capable of connecting to, communicating with,

controlling and/or monitoring a minimum of 2,000 points, where one

point equals 1 input or output hardwired to the FCP. In addition each

FCP shall be capable of displaying all monitored I/O that originates

from another node on the FAS network.

b. The MFCP or FCP processor shall control the signaling from the

initiation devices reporting alarms and trouble conditions to the FAP

displays and other alarm indicating appliances. Provide non-

interfering type alarm circuits, so that a second device can be

annunciated simultaneously or within 3 seconds following the first

device.

c. Provide RS-232-C or USB ports for local communications and printing.

4. System Reset

a. The "System Reset" button shall be used to return the system to its

normal state. Display messages shall provide operator assurance of

the sequential steps ("IN PROGRESS", "RESET COMPLETED") as they

occur. The system shall verify all circuits or devices are restored prior

to resetting the FAS to avoid the potential for re-alarming the system.

The display message shall indicate "ALARM PRESENT, SYSTEM RESET

ABORTED."

b. Should an alarm condition continue, the FAS will remain in an

alarmed state.

5. A manual evacuation (drill) switch shall be provided to operate the

notification appliances without causing other control circuits to be activated.

6. All audio operations shall be activated by the system software so that any

required future changes can be facilitated by authorized personnel without

any component rewiring or hardware additions.

7. Monitor incoming power to all FCPs and MFCP and provide an LED to monitor

incoming power on/off status, and charging voltage and amps.

Page 29: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-17 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

B. Provide the following components as needed with the FCPs to meet the requirements

specified herein:

1. Auxiliary electronically re-settable fused output card with a minimum of 2A

@24VDC output, with programmable disconnect operation for 4-wire detector

reset.

2. Auxiliary SPDT relay that is a minimum of 2A @32VDC, programmable as a

trouble relay, either as normally energized or de-energized, or as an auxiliary

control.

3. Auxiliary Form C relay circuits (contacts rated at a minimum of 2A @ 24VDC,

resistive), programmable for trouble, alarm, supervisory of other fire response

functions, and capable of switching up to ½ A @ 120VAC, inductive.

4. Supervised serial communication channel for control and monitoring of

remotely located annunciators and I/O panels.

5. Modular Network Communications Card.

6. Service Port Modem for dial in passcode access to all fire control panel

information.

7. Intelligent Remote Battery Charger for charging up to 110Ah batteries.

8. Power Supplies with integral intelligent Notification Appliance Circuit Class B

for system expansion.

C. FCP (MFCP) Signal Wiring:

1. The system card cage shall accommodate mounting of all system cards, field

wiring, and panel inter-card power, communication buses, and other support

hardware required for a fully functional panel. The card cage shall hold the

system’s cards and have capability of connecting multiple card cages to meet

system demands.

2. Signal wiring/transmission shall be hard-wired, using separate individual

circuits for each zone of alarm operation as required for addressable signal

transmission, dedicated to fire alarm service only.

3. FAS connections for initiating and notification appliance circuits shall be

Class B. Signaling line circuits shall be Class A.

4. Circuit supervision shall detect and indicate circuit faults by initiating a

trouble signal at the FCP. There shall be a distinctive audible tone and

alphanumeric annunciation associated with trouble signal.

5. I/O subsystem includes individual supervisory and alarm relays in each circuit

arranged so that ground or open condition in any circuit or group of circuits,

will not affect proper operation of the remaining circuits.

Page 30: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-18 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

6. All module wiring shall be to terminal blocks. The terminal blocks shall be

color coded to prevent accidental crossing of wiring. Circuit design shall

incorporate 10 percent spare capacity for future expansion of modules and

module wiring.

D. Distributed Module Operation: FCP shall support the following remotely located

modules through a Style 4 (Class B) supervised serial communications channel:

1. Addressable Signaling Line Circuits (ASLC)

2. Initiating Device Circuits (IDC)

3. Notification Appliance Circuits (NAC)

4. Auxiliary Control Circuits (ACC)

5. Graphic Annunciator LED/Switch Control Modules

E. FAS Monitoring of Analog Smoke Sensors:

1. FAS shall individually monitor sensors for calibration, sensitivity, and alarm

condition, and shall individually adjust for sensitivity. The control unit shall

determine the condition of each sensor by comparing the sensor value to the

stored values.

2. The FAS shall maintain a moving average of the sensor's smoke chamber

value to automatically compensate for dust, dirt, and other conditions that

could affect detection operations.

3. Photoelectric Smoke Sensors shall have selectable sensitivity levels ranging

from 0.5% to 3.0%, programmed and monitored from the FAS.

4. The FAS shall provide sensor sensitivity testing reports that meet NFPA 72

calibrated test method requirements. The reports shall be recorded to the

FAS history log, to the KAI PCS (as applicable) for annual recording and

logging of the calibration maintenance schedule.

5. The FAS shall automatically indicate when an individual sensor needs

cleaning.

6. The FAS shall continuously perform an automatic self-test on each sensor

which will check sensor electronics and ensure the accuracy of the values

being transmitted. Any sensor that fails this test shall indicate a "SELF TEST

ABNORMAL" trouble condition.]

7. Multi-Sensors shall combine photoelectric smoke sensing and heat sensing

technologies. An alarm shall be determined by either smoke detection or

heat detection, selectable as fixed temperature or fixed with selectable rate-

of-rise; or based on an analysis of the combination of smoke and heat

activity.

8. Magnet test activation of smoke sensors shall be distinguished by its label

and history log entry as being activated by a magnet.

Page 31: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-19 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

F. FAS Monitoring of the Fire Suppression System:

1. Activation of a water flow switch shall initiate general alarm operations.

2. The activation of any sprinkler valve supervisory switch shall activate system

supervisory operations.

3. Water flow switch and sprinkler valve supervisory switch shall be capable of

existing on the same initiating zone. Activation of either device shall distinctly

report which device is in alarm on the initiating zone.

G. Alarm/Trouble Log: Log shall be capable of logging and storing 300 events in an

alarm log and 300 events in a trouble log. Events shall be stored in a battery backed

RAM (or alternative approved NVRAM), and shall include time and date of event

occurrences. Logged data shall be accessible to the OI for display, to the network

printer for reporting logged data, and shall be exportable in standard Microsoft Excel

or Access format to the KAI-PCS (as applicable) via the Ethernet interface.

H. MFCP Automatic Dial-up:

1. Provide all software and hardware modules, wiring, power supplies,

terminations, and appliances required to connect the MFCP to redundant

basic interface telephone lines dedicated to FAS service.

2. Automatic call-out dialer initiated upon:

a. Any FAS fire alarm condition

b. Operation of any supervisory or trouble condition

c. Or any other condition required by code.

3. Automatic dialer shall provide the capability of dialing up to eight pre-

programmed telephone numbers.

4. A voice message shall report the area in alarm.

I. Power Supply/Battery Charger:

1. A dedicated 120 VAC circuit shall be required from the area electrical room

panelboard to the integral 24 VDC power supply/battery charger in the MFCP

and FCPs. All circuits requiring system-operating power shall be 24 VDC and

shall be individually fused at the control unit. The system power

supply/charger shall be sized for the specific system. The power supply shall

be filtered and regulated. The system power supply shall be sized so that it

has the capability to accommodate a 25 percent expansion of the FAS. The

system power supply shall have four NO/NC relays: common alarm, common

trouble and two user defined programmable relays. The power supply shall

be rated for 120 VAC 60 Hz.

2. The battery charger programmable microprocessor shall control charging with

user selected charging rates and battery sizes. A thermistor for monitoring

battery temperature to control charging rate shall be utilized.

Page 32: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-20 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

3. Automatic transfer from AC to battery power shall be instantaneous when AC

voltage drops to a point where it is not sufficient for normal operation.

4. The power supply shall have a plug for an AC adapter cable, which allows a

technician to plug in a laptop computer for uploading or downloading

program information or test equipment.

5. Shall provide analog voltage and ammeter values for display on the FCP

(MFCP).

J. Batteries:

1. Low maintenance sealed type suitable for fire alarm system use.

2. Capable of operating the maximum normal load of the associated MFCP, FCP

or FAP for 24 hours, after which, it shall be capable of operating the load for

15 minutes if an alarm is generated.

3. Sized for 125 percent of the total maximum number of devices that can be

connected to the MFCP, FCP and FAPs (not just the installed number of

devices).

4. The system batteries shall be supervised so that a low battery or a depleted

battery condition, or disconnection of the battery shall be displayed at the

FCP for the specific fault type.

5. When a depleted battery condition exists, prevent subsequent activation of

Notification Appliance Circuits.

6. Support 100% of addressable devices in alarm or operated at the same time,

under both primary (incoming power) and secondary (battery) power

conditions.

7. Loss of incoming power shall sound a trouble signal at the FCP.

2.04 FIRE ALARM SYSTEM NETWORK

A. MFCP and FCPs shall communicate over a serial network capable of automatically

forming a sub-network with all common interactions of monitoring and control

remaining intact should a group of FCPs become isolated from the rest of the FAS

network due to fault conditions.

B. A single open, ground, or short on a network communication loop shall not degrade

network communications. Network shall maintain communication throughout all

nodes. The status of the communication link shall be reported.

C. If the FAS is provided with Ethernet network switches, they shall:

1. Perform transparent bridging at full wire speed of all internal network

communications and all external network communication interfaces.

Page 33: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-21 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

2. Reside in each area FCP and MFCP.

3. UL 864 listed for fire alarm system application.

4. High voltage tested:

a. 6,000V supply line transients.

b. 2,400V signal circuit transients.

c. 5,000V input voltage surge.

d. 115 percent rated voltage overload.

5. Provided with 25 percent spare 10/100 Mbps RJ-45 connector ports.

D. FAS Network Cabling:

1. The FAS network shall run from the area FCPs to the MFCP as shown on the

Drawings.

2. The use of raceways installed as specified in Division 16, shall be permitted if

acceptable to the AHJ and approved by the Officer-in-Charge prior to

installation.

3. Contractor shall be responsible for providing all network cabling and

equipment required to complete the FAS network.

4. Include all network communication cable and equipment required for

communications between the FCPs and the associated FAPs. Use of

raceways, installed by the Contractor as specified in Division 16, to complete

the remote network connections, shall be permitted if acceptable to the AHJ

and approved by the Officer-in-Charge prior to installation.

2.05 FIRE ALARM DEVICE PROGRAMMING AND LOOP TESTER

A. FCP Device Programmer and Loop Testing: The device programming unit shall be

used to test and verify the correct connection of devices. Communications and

confirmation of the tested device is independent of the current functioning of the

tested device. It provides device addresses, identifies ground faults and shorts, and

provides a summary of the quantity of each device type on the tested loop.

2.06 FIRE ALARM ANNUNCIATION PANELS (FAP)

A. Remote Fire Annunciation Panels (FAPs) shall be provide as required by NFPA, IBC

and AHJ, and shall:

1. Provide where required a remote LCD FAP with the same "look and feel" as

the FCP operator interface. The remote FAP shall use the same Primary

Acknowledge, Silence, and Reset Keys, Status LEDs and LCD display as the

MFCP and FCPs.

Page 34: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-22 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

2. Operator keys shall be key switch enabled to prevent unauthorized use. The

key shall only be removable in the disabled position. Acknowledge, Silence

and Reset operation shall be the same as the FCP.

3. FAP shall include a keypad for entering and executing control commands.

4. Annunciator shall have provided with four programmable control switches

and associated LEDs.

5. Remote FAPs shall be housed in a separate wall mounted enclosure suitable

for its environment located at or near the main entrance to each building as

required by code and approved by the AHJ.

B. Annunciator Displays:

1. FAPs shall display all information required by code and approved by the AHJ

including all alarms active in the associated FCP or MFCP.

2. Should an abnormal condition be detected the appropriate LED (Alarm,

Supervisory or Trouble) shall flash. The unit audible signal shall pulse for

alarm conditions and sound steady for trouble and supervisory conditions.

3. The LCD shall display the following information relative to the abnormal

condition of a point in the system:

a. Custom location label.

b. Type of device (e.g., smoke, heat, waterflow).

c. Point status (e.g., alarm, trouble).

2.07 SYSTEM ENCLOSURES

A. Provide wall-mounted steel enclosures sized to hold all MFCP, FCP or FAP circuit

boards, devices, modules and accessories with space for an additional 15 percent

future expansion. Enclosure must be sized to fit within the allowable wall space

available and not exceed 3 feet high x 2 feet wide. Larger panels may be approved by

the Officer-in-Charge prior to procurement or installation.

B. The enclosures shall be provided with transparent locking doors for viewing LED

indicators, operator displays, and other required components and indicators. Provide

enclosure color as required by the local AHJ. The outer doors shall be capable of

being a left-hand open or a right-hand open. The inner door shall have a left-hand

opening. System enclosure doors shall provide ventilation for the modules or cards

in the enclosure, where required.

C. The enclosure shall protect components from electromagnetic fields to ensure that

the FAS and all subsystems operate in their intended electromagnetic environment,

without either causing or suffering from harmful interference because of

electromagnetic emissions or component response.

D. The enclosures shall be suitable for the environmental conditions and area

classification in which they are installed.

Page 35: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-23 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

E. FCP (MFCP) Rack and Enclosure:

1. All power-limited field wiring shall be physically separated from all non-power-

limited internal wiring.

2. The rack and components shall be mounted in wall mounted panels suitable

for the environmental conditions and area classification.

3. MFCP, FCP and FAP enclosures and cabinets shall be suitable to meet all

applicable seismic requirements as specified in Section 01900 for and

certified for application, as required.

2.08 INITIATION DEVICES

A. General:

1. In addition to NFPA, IBC and AHJ detection device requirements, smoke

detectors shall be provided in all electrical rooms, computer rooms, control

rooms, telephone closets, and above all equipment as required.

2. Intelligent initiation devices used in non-classified areas shall:

a. Be microprocessor based addressable devices. The programmable

bases shall be programmable to allow the relay and sounder bases to

operate independently of their associated sensor. Sensors include a

communication transmitter and receiver in the mounting base having

a unique identification and capability for status reporting to the FCP.

Sensor address shall be located in base to eliminate false addressing

when replacing sensors.

b. Have an LED on the sensor or sensor base that flashes each time it is

scanned by the FCP. In alarm condition, the sensor base LED shall be

on steady. Sensors which do not provide visible indication of an

abnormal condition at the sensor location are not acceptable.

c. Have a magnetically actuated test switch for easy alarm testing at

each sensor location.

d. Be provided with printed labels which contain the complete circuit

and device numbers.

e. Detector wiring shall not require any special shielded cable.

3. Conventional initiation devices used in classified areas shall:

a. Be manufactured as explosion proof sensors for hazardous areas.

b. Be supplied with the appropriate bases and intrinsically safe modules

as required.

Page 36: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-24 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

c. Have a magnetically actuated test switch for easy alarm testing at

each sensor location.

d. Be provided with printed labels which contain the complete circuit

and device numbers.

e. Panels shall be rated for area classification as specified in Section

16000.

f. Be supplied with the required addressable circuit interface module for

each conventional initiating device circuit that connects to an

intelligent FCP or MFCP circuit and is capable of the following:

g. Provide a device programming tool which programs the intelligent

devices functions, device addresses, and tests the loop wiring for

grounds, opens, and shorts.

B. Smoke Detector:

1. The smoke detector shall be an intelligent digital photoelectric detector with a

programmable thermal detector that is software addressable without

mechanical switches that complies with UL 268. Sensor and associated

electronic components shall be mounted in a module that connects a fixed

base with a twist-locking plug connection. Removal of the detector head shall

interrupt the supervisory circuit of the fire alarm detection loop and cause a

trouble signal at the FCP.

2. Smoke detectors shall be listed for use as open area protective coverage, in

duct installation and duct sampling assembly installation, and shall be

insensitive to air velocity changes.

3. The smoke detector communications shall allow the detector to provide an

alarm input to the system and an alarm output from the system within 4

seconds.

4. Smoke detectors shall be programmable for a minimum of 11 unique

environmental fire profiles that shall eliminate the possibility of false

indications caused by dust, moisture, RFI/EMI, chemical fumes, and air

movement; while factoring in conditions of ambient temperature rise,

obscuration rate changes, and hot/cold smoke phenomenon into the alarm

decision to give the earliest possible real alarm condition report.

5. Smoke detector shall be capable of providing three distinct outputs to the

control panel. The outputs shall be from an input of smoke obscuration, a

thermal condition, or a combination of obscuration and thermal conditions.

6. The smoke detector shall be designed to automatically eliminate calibration

errors associated with contamination or field cleaning of the chamber.

7. Each photoelectric smoke detector shall be scanned by the FCP for its type

identification to prevent inadvertent substitution of another sensor type.

Page 37: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-25 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

Upon detection of a "wrong device", the FCP shall operate with the installed

photoelectric sensor at the default alarm settings of 2.5% obscuration, but

shall indicate a "Wrong Device" trouble condition.

8. Smoke detector shall be self-restoring and not require resetting or

readjustment after actuation to restore normal operation.

9. Removal of the sensor head for cleaning shall not require the setting of

addresses.

10. Each sensor base shall contain an LED that will flash each time it is scanned

by the FCP. In alarm condition, the sensor base LED shall be on steady.

Detector wiring shall not require any special shielded cable.

11. Sensors include a communication transmitter and receiver in the mounting

base having a unique identification and capability for status reporting to the

FCP. Sensor address shall be located in base to eliminate false addressing

when replacing sensors.

12. Provide a smoke detectors for activating smoke control.

C. Thermal Detector:

1. Thermal Sensor: Sealed rate compensated; 200-deg F temperature setting

except as indicated.

2. Thermal sensor shall be of the epoxy encapsulated electronic design. It shall

be thermistor-based, rate-compensated, self-restoring and shall not be

affected by thermal lag.

3. The thermal detectors shall have a listed spacing for coverage up to 2,500

square feet and shall be installed according to the requirements of NFPA 72

for open area coverage.

D. Duct-Mounted Smoke Detector:

1. For duct-mounted detectors, the smoke detector shall be an intelligent digital

photoelectric detector with a programmable thermal detector that is software

addressable without mechanical switches. Environmental compensation,

programmable sensitivity settings, status testing, and monitoring of sensor

dirt accumulation for the duct sensor shall be provided by the FCP.

2. Duct-mounted smoke detectors shall be listed for use as open area

protective coverage, in duct installation and sampling assembly installation,

and shall be insensitive to air velocity changes.

3. The duct-mounted smoke detector communications shall provide alarm input

to the system and alarm output from the system within 4 seconds.

4. The duct-mounted smoke detector shall support the use of a remote test

switch, relay, or LED remote indicator.

Page 38: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-26 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

5. Duct-mounted smoke detector sampling tube shall be designed and

dimensioned as recommended by the manufacturer for the specific duct size

and installation conditions where applied. Sensor includes relay as required

for fan shutdown.

6. The duct-mounted smoke detector shall be mounted in a duct detector

housing listed for that purpose.

a. Duct Housing shall provide a relay control trouble indicator Yellow

LED.

b. Duct Housing shall have a transparent cover to monitor for the

presence of smoke. Cover shall secure to housing by means of four

captive fastening screws.

c. Duct Housing shall provide two Test Ports for measuring airflow and

for testing. These ports will allow aerosol injection in order to test the

activation of the duct smoke sensor.

d. Duct Housing shall provide a magnetic test area and Red sensor

status LED.

e. For maintenance purposes, it shall be possible to clean the duct

housing sampling tubes by accessing them through the duct housing

front cover.

f. Each duct sensor shall have a Remote Test Station with an alarm LED

and test switch.

g. The Duct Housing shall provide a supervised relay driver circuit for

driving up to 15 relays with a single "Form C" contact rated at a

minimum of 7A@ 28VDC or 10A@ 120VAC. This auxiliary relay output

shall be fully programmable. Relay shall be mounted within 3 feet of

HVAC control circuit.

h. Where indicated, provide NEMA 4X weatherproof duct housing

enclosure shall provide for the circulation of conditioned air around

the internally mounted addressable duct sensor housing to maintain

the sensor housing at its rated temperature range. The housing shall

be UL Listed to Standard 268A.

E. Manual Station:

1. Double-action type push/pull, red LEXAN, with molded, raised-letter operating

instructions of contrasting color. Station will mechanically latch upon

operation and remain so until manually reset by opening with a key common

with the control units.

2. Provide flush- or surface-mounted, as required. Surface-mounted stations

shall be mounted using a manufacturer's prescribed matching red enamel

outlet box.

Page 39: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-27 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

3. Where required, provide a tamperproof, clear LEXAN shield and red frame

that easily fits over manual pull stations. When shield is lifted to gain access

to the station, a battery powered piercing warning horn shall be activated.

The horn shall be silenced by lowering and realigning the shield. The horn

shall provide 85dB at 10 feet and shall be powered by a 9 VDC battery.

4. Manual stations shall contain the intelligence for reporting address, identity,

alarm and trouble conditions to the MFCP or FCP.

5. The manual station communications shall allow the station to provide alarm

input to the system and alarm output from the system within less than

4 seconds.

6. The manual station shall be equipped with terminal strip and pressure style

screw terminals for the connection of field wiring.

F. Addressable Circuit Interface Modules:

1. Addressable Circuit Interface Modules: Arrange to monitor one or more

system components that are not otherwise equipped for addressable

communication. Modules shall be used for monitoring of waterflow, valve

supervisory, non-addressable devices, and for control of evacuation

indicating appliances and HVAC AHU systems, and shall include:

a. Alphanumeric message display.

b. Alarm verification.

c. Walk test capability.

d. No mechanical address programming required.

e. Circuits are power limited as required by NEC 760.

f. UL listed for application.

2. Addressable Circuit Interface Modules will include cover plates to allow

surface or flush mounting. Modules will receive their operating power from

the signaling line or a separate two wire pair running from an appropriate

power supply as required.

3. There shall be the following types of modules:

a. Type 1: Monitor Circuit Interface Module:

1) For conventional 2-wire smoke detector and/or contact

device monitoring with Class B or Class A wiring supervision.

The supervision of the zone wiring will be Class B. This

module will communicate status (normal, alarm, trouble) to

the FCP.

2) For conventional 4-wire smoke detector with Class B wiring

supervision. The module will provide detector reset capability

and over-current power protection for the 4-wire detector. This

module will communicate status (normal, alarm, trouble) to

the FCP.

Page 40: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-28 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

b. Type 2: Line Powered Monitor Circuit Interface Module

1) This type of module is an individually addressable module

that has both its power and its communications supplied by

the two wire multiplexing signaling line circuit. It provides

location specific addressability to an initiating device by

monitoring normally open dry contacts. This module shall

have the capability of communicating four zone status

conditions (normal, alarm, current limited, trouble) to the FCP.

2) This module shall provide location specific addressability for

up to five initiating devices by monitoring normally closed or

normally open dry contact security devices. The module shall

communicate four zone status conditions (open, normal,

abnormal, and short). The two-wire signaling line circuit shall

supply power and communications to the module.

c. Type 3: Single Address Multi-Point Interface Modules

1) This multipoint module shall provide location specific

addressability for four initiating circuits and control two output

relays from a single address. Inputs shall provide supervised

monitoring of normally open, dry contacts and be capable of

communicating four zone status conditions (normal, open,

current limited, and short). The input circuits and output relay

operation shall be controlled independently and disabled

separately.

2) This dual point module shall provide a supervised multi-state

input and a relay output, using a single address. The input

shall provide supervised monitoring of two normally open, dry

contacts with a single point and be capable of communicating

four zone status conditions (normal, open, current limited,

and short). The two-wire signaling line circuit shall supply

power and communications to the module.

3) This dual point module shall monitor an unsupervised

normally open, dry contact with one point and control an

output relay with the other point, using a single address. The

two-wire signaling line circuit shall supply power and

communications to the module.

d. Type 4: Line Powered Control Circuit Interface Module shall provide

control and status tracking of a Form "C" contact. The two-wire

signaling line circuit shall supply power and communications to the

module.

4. All Circuit Interface Modules shall be supervised and uniquely identified by

the FCP. Module identification shall be transmitted to the FCP for processing

according to the program instructions. Modules shall have an on-board LED

to provide an indication that the module is powered and communicating with

the FCP. The LEDs shall provide a troubleshooting aid since the LED blinks

on poll whenever the peripheral is powered and communicating.

Page 41: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-29 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

G. Sprinkler System Sensor:

1. The following TIPS Building sprinkler sensors shall be monitored by the FAS:

a. Sprinkler water flow switches shall be as specified in Section 15330,

not included in FAS requirements.

b. Pressure switch shall be as specified in Section 15330, not included

in FAS requirements.

c. Supervisory switches as specified in Section 15330, not included in

FAS requirements.

d. Exterior alarm bell as specified in Section 15330, not included in FAS

requirements.

e. Heat detectors within 2 feet of sprinkler heads to disconnect elevator

main line power supply before application of water.

2. The MFCP shall receive and process water flow, pressure and supervisory

alarms and transmit them to the Plant Control System.

2.9 NOTIFICATION APPLIANCE

A. Horn Only: The horn shall have a minimum sound pressure level of 100 dBA @

24VDC. For all NEMA 4X environments, horns shall be UL Listed and FM Approved

with a NEMA 4X Rating, and the horn shall be surface mounted with its incorporated

back box to maintain its NEMA 4X Rating.

B. Visible/Only: Strobe shall be listed to UL 1971. The V/O shall consist of a xenon flash

tube and associated lens/reflector system. The V/O enclosure shall mount directly to

standard single gang, double gang or 4" square electrical box, without the use of

special adapters or trim rings. V/O appliances shall be provided with Multi candela

flash intensities of 15cd, 75cd , and 110cd.

C. Audible/Visible: Combination Audible/Visible (A/V) Notification Appliances shall be

listed to UL 1971 and UL 464. The strobe light shall consist of a xenon flash tube

and associated lens/reflector system. Provide a Multi Candela devices with different

flash intensities of 15CD, 75CD, 110CD . The horn shall have a minimum sound

pressure level of 85 dBA @ 24VDC. The audible/visible enclosure shall mount directly

to standard single gang, double gang or 4" square electrical box, without the use of

special adapters or trim rings.

D. Notification Appliance Circuit provides synchronization of strobes at a rate of 1 Hz

and operates horns with a Temporal Code Pattern operation. The circuit shall provide

the capability to silence the audible signals, while the strobes continue to flash, over

a single pair of wires. The capability to synchronize multiple notification appliance

circuits shall be provided.

Page 42: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-30 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

E. Bell: Where required, provide wiring and connections to a 10-inch bell connected to a

non-silenceable circuit for activation by the sprinkler system. The bell shall be

provided as specified in Section 15330.

F. Furnish the necessary accessories.

2.10 NOTIFICATION APPLIANCE CIRCUIT (NAC) POWER EXTENDED

A. The FAS networked NAC Power Extender panel shall be a stand-alone panel capable

of powering a minimum of 4 notification appliance circuits. Notification appliance

circuits shall be Class B Style Y rated at 2 amps each. Panel shall provide capability

to be expanded to 8 notification appliance circuits.

B. The internal power supply & battery charger shall be capable of charging up 12 Ah

batteries internally mounted or 18 Ah batteries mounted in an external cabinet.

C. The addressable NAC Extender Panel shall be capable of controlling each output NAC

for general alarm or selective area notification.

D. Up to five NAC extender panels can be connected on a single FAS network channel.

E. Alarms from the FCP shall signal the NAC power extender panel to activate. The panel

shall monitor itself and each of its NACs for trouble conditions and shall report

trouble conditions to the FCP.

2.11 MISCELLANEOUS DEVICES

A. Isolated Loop Circuit Protector (Transient Suppression):

1. Hybrid solid state high performance suppression system. Do not use gas

tubes, spark gaps or other suppression system components which might

short or crowbar the line resulting in interruption of normal power flow to

connected loads.

2. Line-to-line response time of less than 1 nanosecond capable of accepting a

2000A (8 x 20 μsec pulse) at 28V.

3. Line-to-ground response time of less than 1 nanosecond capable of

accepting a 2000A (8 x 20 μsec pulse) to earth.

4. Shield-to-ground shall be capable of accepting a 5000A (10 x 50 μsec pulse)

to earth.

5. Standard: UL 497B.

B. Combustible Gas Detectors:

1. Provide additional components and wiring as required for connection to the

FAS to monitor excessive concentrations of combustible gases (exceeding the

lower explosive limits – LEL) for hazardous areas as required by NFPA 820,

as shown on the drawings and as listed in Section 17217. LEL

Page 43: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-31 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

instrumentation, local alarm panels, and wiring to the Plant Control System

are provided in other sections.

C. Loss of Ventilation:

1. Provide additional components and wiring as required for connection to the

FAS to monitor loss of ventilation fans as required by NFPA 820 and as

shown on the drawings.

2.12 SMOKE CONTROL PANEL (SCP)

A. The SCP shall control the stair pressurization system in the stair shafts. It shall use a

graphic annunciator to display the status of each air handling unit and fan – on, off,

or fault. Air flow switches shall be used to verify that fans are properly functioning.

Limit switches shall be installed on the dampers to ensure that they are properly

open before fans are turned on.

2.13 SERVICES

A. The FAS contractor or FAS manufacturer shall offer for the City’s consideration at the

time of FAS submittal, a priced inspection, maintenance, testing, and repair contract

in full compliance with the requirements of NFPA 72 for a period of 5 years

commencing after formal acceptance of the FAS by the Officer-in-Charge.

B. Provide quarterly routine maintenance on-site visits by factory trained National

Institute for Certification of Engineering Technologies (NICET) Level III certified

technicians at times scheduled in advance with City. The minimum maintenance and

testing services shall include adjusting and/or replacing defective parts and

components with original manufacturer’s replacement parts and components, and

any other routine and warranty work required.

C. Provide biannual routine maintenance on-site visits by factory trained National

Institute for Certification of Engineering Technologies (NICET) Level III certified

technicians at times scheduled in advance with City. Include the following minimum

maintenance and testing services:

1. Sensitivity reading and logging for each smoke sensor.

2. Threshold adjustments to maintain proper sensitivity for each smoke sensor.

3. Threshold adjustment to any smoke sensor that has alarmed the system

without the presence of particles of combustion.

4. Cleaning or replacement of each smoke detector or sensor within the system.

5. Functional testing of each smoke detector or sensor using the manufacturer's

calibrated test tool.

6. Written documentation of all testing, cleaning, replacing, threshold

adjustment, and sensitivity reading for each smoke detector or sensor device

within the system.

Page 44: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-32 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

D. Perform emergency service within 24 hours of notification of system trouble with a

factory trained National Institute for Certification of Engineering Technologies (NICET)

Level III certified technicians. Adjust and replace defective parts and components

with original manufacturer’s replacement parts, components and supplies.

E. Perform services not classified as routine maintenance as warranty work when

authorized by City. Compensation for additional services must be agreed upon in

writing prior to performing services.

F. Maintenance and repair contract renewal proposal for an additional one-year shall be

delivered to the City no later than 60 days prior to the expiration of the existing

contract.

G. FAS contractor shall provide a five years service for a 24 hours a day / 7 days a week

monitoring service of the Tunnel Influent Pump Station FAS which shall begin as part

of the Acceptance Test Plan (ATP) of the FAS.

2.14 SPARE PARTS

A. Procedures: Section 01750.

B. Manufacturer’s recommended spare parts shall be provided as part of this Contract

at the completion of the acceptance test. Provided spare parts shall not be less than

10 percent for each system component, annunciation device, or sensor provided,

including all strobe units, horn units, smoke detectors, fire detectors, flame

detectors, and detector or sensor bases.

PART 3 EXECUTION

3.01 GENERAL DESIGN

A. Prepare design that meets the requirements specified herein, and local, state and

national codes and regulations, and submit to the AHJ for approval.

B. Final system design shall be accepted and approved by the Officer-in-Charge and the

AHJ.

3.02 GENERAL INSTALLATION

A. FAS raceway and wiring for initiating, miscellaneous and automatic control devices

and notification appliances shall be installed in accordance with applicable NFPA and

local fire jurisdiction standards and manufacturer’s recommendations.

B. Wiring shall be non-armor jacketed fire protective signaling rated cable in

conduit. Where conduit is used, installation shall be per the requirements specified

in Division 16 unless those requirements are in conflict with applicable code

requirements. In that case, the code requirements shall prevail. The Officer-in-

Charge will provide a response to this request based on an evaluation of future

needs and the revised fill per the requested additional cables.

Page 45: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-33 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

C. FAS fiber optic cable provided and installed as required by Section 16890, can be

used to complete FAS network communications if acceptable to the AHJ and

specifically allowed in writing by the Officer-in-Charge prior to installation.

D. Perform work in accordance with the requirements of NFPA 70 and NFPA 72. All work

to be done in a skillful and workmanlike manner. Installation personnel shall be

supervised by persons who are qualified and experienced in the installation,

inspection and testing of provided fire alarm system.

E. Install all components as indicated on the approved design drawings and in

accordance with the manufacturer’s wiring diagrams, instructions and

recommendations. No modifications or rearrangements shall be made from the

approved design without the prior approval of the Officer-in-Charge.

F. Installation of equipment and devices that pertain to other work in contract shall be

closely coordinated with appropriate subcontractors.

1. Fire dampers, conduit and wiring not included in the FAS specification shall

be monitored and/or controlled by the FAS.

2. Duct detector devices, conduit, and wiring not included in the FAS

specification shall be monitored and/or controlled by the MFCP or FCP.

3. Sprinkler alarms and indication devices, conduit and wiring not included in

the FAS specification shall be monitored and/or controlled by the MFCP or

FCP.

4. Connect conduit and wiring for the fire dampers, duct detectors, and sprinkler

alarms at the FAS.

5. Rolling fire door smoke and fire detection devices, conduit, and wiring as

required by code or the AHJ.

6. In addition to NFPA requirements, smoke detectors shall be required in all

electrical rooms, computer rooms, control rooms, telephone closets and

above all equipment as required.

7. Other devices required by code for AHJ approval.

G. Upon completion of installation, submit a Certificate of Compliance to the Officer-in-

Charge in accordance with NFPA 72 that is the most current edition, adopted and

approved by the AHJ.

H. All materials, appliances, equipment, or devices shall be new, UL listed and Factory

Mutual approved for use in the intended application. All individual components and

composite systems shall be designed and installed for continuous operation without

undue heating or change in rated values.

I. The MFCP, area FCPs, and any other Ethernet connected devices shall request IP

addresses and subnet masks from the Officer-in-Charge prior to the commencement

Page 46: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-34 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

of programming, and the City assigned IP addresses shall be programmed in

Ethernet networked devices.

3.03 JUNCTION BOXES, ENCLOSURES, AND WIRING DEVICES

A. Cable and Raceways:

1. Install cable and raceways in accordance with Section 16110.

2. Install network and signal wiring cable as specified in Section 16120 and

required to meet code.

B. Junction boxes, enclosures and wiring devices shall be installed as specified in

Section 16110, and shall include as a minimum:

1. Junction boxes shall be installed plumb and firmly in position.

2. Extension rings with blank covers shall be installed on junction boxes where

required.

3. Junction boxes served by concealed conduit shall be flush mounted.

4. The inside and outside of all boxes are to be painted red.

C. Upon initial installation, all wiring outlets, junction, pull, and outlet boxes shall have

dust covers installed. Dust covers shall not be removed until wiring installation when

permanent dust covers or devices are installed.

D. All installed cabinets and devices shall be sealed in plastic for protection until final

acceptance testing has commenced.

E. "Fire Alarm System" decal or silk-screened label shall be applied to all junction box

covers. Inside of the junction boxes shall be painted red.

F. Mounting height for equipment and devices as indicated below unless otherwise

indicated on the submitted and approved drawings.

1. Manual pull stations: 48 inches to top

2. Notification appliances: 80 to 96 inches to bottom

3. Control panels: 72 inches to top

4. Stand-alone Duct Detector Annunciators: 54 inches

G. A surge suppressor shall be installed on all metallic circuits entering or exiting a

building and connected to a control panel. Surge suppressors shall be used to

protect panels from lightning. Surge suppressors shall be provided for and

compatible with FAS alarm circuits, FAS alarm panel communications, and 70V audio

circuits. Surge suppressors shall be wired and bonded to building grounding system.

Surge suppressors shall be as specified in Section 16422. As a minimum, furnish

and install minimum 6 AWG ground wire from surge suppressors to building

grounding system.

Page 47: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-35 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

H. Wiring within subpanels shall be arranged and routed to allow accessibility to

equipment for adjustment and maintenance.

3.04 CONDUCTORS

A. Each conductor shall be identified with alphanumeric wire markers at each terminal

point. Attach permanent heat shrink wire markers within 2 inches of the wire

termination. Marker legends shall be visible.

B. Minimum Sizes for Conductors:

1. 120 VAC and power supply connections: 12 gauge minimum.

2. Low-voltage general alarm circuits: 14 gauge minimum.

3. Low-voltage signal initiating circuits: 18 gauge minimum.

4. Annunciator and data communication circuits: As required by manufacturer,

UL listed.

5. Use larger wire sizes when recommended by equipment manufacturer and

per voltage drop calculations.

C. All wiring shall be supplied and installed in compliance with the requirements of the

National Electric Code, NFPA 70, Article 760, and the manufacturer.

D. In-line splices are not permitted. All connectors shall be installed in conformance

with the manufacturer’s recommendations.

E. Crimp-on type spade lugs shall be used for terminations of stranded conductors to

binder screw or stud type terminals. Spade lugs shall have upset legs and insulation

sleeves sized for the conductors.

F. Install conductors that adhere to the approved color code for FAS conductors. Color-

code fire alarm conductors differently from the normal building power wiring. Use on

color code for alarm initiating device circuits wiring and a different color code for

supervisory circuits. Color-code notification appliance circuits differently from alarm-

initiating circuits.

G. All cable runs shall be run at right angles to building walls, supported from structure

at intervals not exceeding 3 feet and, where installed in environmental air plenums,

be rated for such use and tied/supported by components listed for environmental air

plenums installation.

H. Install isolated loop circuit protectors on all fire alarm data communication circuits

that extend beyond a building via aerial or underground methods. The isolated loop

circuit protector shall be located as close as practicable to the point at which the

circuits leave or enter a building. See Section 16422.

Page 48: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-36 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

3.05 DEVICES

A. Devices and Appliances:

1. Fasten equipment to structural members of building or metal supports

attached to structure or to concrete surfaces.

2. Cover all smoke detectors with plastic bags immediately after installation to

maintain cleanliness.

B. Relays and other devices to be mounted in auxiliary panels shall be securely

fastened to avoid false indications and failures due to shock or vibration.

C. All devices and appliances shall be mounted to or in an approved electrical box.

D. Water flow and valve position devices shall be furnished and installed as specified in

Division 15.

3.06 FIELD QUALITY CONTROL

A. The system I/O shall be tested on an individual circuit basis for opens, shorts, and

communications with all addressable devices installed before connection to the

control panel. Systems without this capability shall have a test panel installed for

initial testing and maintenance purposes to eliminate short or long term damage to

the control panel. For systems that require an installed test panel shall replace the

test panel and proceed with complete testing, after the initial testing.

B. All alarm initiating devices shall be observed and logged for correct zone and

sensitivity. These devices and their bases shall be tagged with adhesive tags located

in an area not visible when installed, showing the initials of the installing technician

and date.

C. Wiring runs shall be tested for continuity, short circuits, and grounds before system is

energized. Resistance, current, and voltage readings shall be made and recorded as

work progresses. The Contractor shall schedule all testing with the Officer-in-Charge

and AHJ.

D. A systematic record, submitted in advance of any testing for approval, shall be

maintained for all readings using schedules or charts of tests and measurements.

Areas shall be provided on the logging form for readings, dates, and witnesses.

E. The acceptance inspector shall be notified a minimum of seven days before the start

of the required tests. All items found at variance with this specification during testing

or inspection by the acceptance inspector shall be recorded and corrected. Any

device or system requiring correction shall be retested.

F. Completed test reports shall be delivered to the acceptance inspector.

G. The installing contractor shall make instruments, tools, and labor required to conduct

the system tests available.

Page 49: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-37 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

H. The following equipment shall be a minimum for conducting the tests:

1. Ladders and scaffolds as required to access all installed equipment.

2. Multimeter for reading voltage, current, and resistance.

3. Two-way radios and flashlights.

4. A manufacturer-recommended device for measuring air flow through air duct

smoke detector sampling assemblies.

5. Decibel meter.

6. All test instruments shall be calibrated to references traceable to the National

Institute of Standards and Technology and shall have a current calibration

sticker showing date of calibration, deviation from standard, name of

calibration laboratory and technician, and date of recalibration.

3.07 TESTING

A. Test system in accordance with these specifications and state and local fire

authorities’ requirements and in accordance with NFPA 72, state and local codes and

manufacturer's requirements.

B. Determine through pretesting the conformance of the system to the requirements

specified herein. Correct deficiencies observed in pretesting by replacing

malfunctioning or damaged items with new, and retest until satisfactory performance

and conditions are achieved.

C. Prior to commencement of the ATP, the Contractor shall prepare a complete listing of

all device labels for alphanumeric annunciator displays.

D. Acceptance Test Plan (ATP) for testing the FAS components and installation will be

prepared by the Contractor in accordance with NFPA 72, this Specification, and

Section 01660. Provide a 10-minimum notice in writing when the system is ready for

final acceptance. The Contractor shall be responsible for the performance of the

ATP, demonstrating the function of the system and verifying the correct operation of

all system components, circuits, and programming.

1. At a minimum, test the required: device, address, usage (Alarm, Supervisory,

etc.), environmental compensation, temperature ratings for thermal

detectors, and smoke detector sensitivities and any other manufacturer

recommended circuit tests, and device address testing.

2. Test the FAS wiring to show the following results and the system

subsequence operation. Coordinate tests with the appropriate equipment

vendors.

Page 50: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-38 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

a. Primary power

b. Backup battery power after the primary power has been

disconnected.

c. Operation of system notification circuits and appliances to

demonstrate correct functionality and that the audio and visual levels

meet required standards.

d. Demonstrate the correct messages at the MFCP, FCPs, and FAPs.

e. Verify FAS off-site reporting of alarm, supervisory, and trouble events.

f. Test all detector alarm operation using heat and/or canned smoke.

g. Test all combustible gas (LEL) detector alarm operation per Section

17217.

h. Test sprinkler water flow and valve supervisory switches by letting the

water flow and manually operating the valve.

i. Test actuation of HVAC smoke and plenum dampers (as required) for

proper operation.

j. Test elevator functions.

k. Test stair pressurization functions.

E. A program matrix shall be prepared by the Contractor referencing each alarm input to

every output function affected as a result of an alarm condition on that input.

F. The AHJ acceptance inspector shall use the system record drawings in combination

with the documents as specified within this Section during the testing procedure to

verify operation as programmed. In conducting the ATP, the AHJ acceptance

inspector may request demonstration of any or all input and output functions.

G. Correct deficiencies identified during ATP and completely retest to verify system

compliance with the specifications and applicable standards.

H. In addition to the testing specified, the Contractor shall perform any additional

testing or retesting required by the AHJ.

3.08 TRAINING

A. A factory-authorized service representative shall conduct training courses as

specified in Section 01660, for personnel designated by City. The training shall be

oriented to the specific system being installed under this contract.

Page 51: FABRICATED SLIDE GATES passivated in accordance with methods defined in ASTM A380 – Standard Practice for Cleaning, Descaling, and Passivation of Stainless Steel Parts, and the specific

KAILUA RWWTP TUNNEL INFLUENT 16850-39 FIRE ALARM SYSTEM

PUMP STATION AND HEADWORKS ADDENDUM NO. 5

FACILITY, JOB NO. W1-13

B. Training manuals shall be delivered for each trainee with two additional copies

delivered for archiving at the project site. The manuals shall include an agenda,

defined objectives for each lesson, and a detailed description of the subject matter

for each lesson.

C. The Contractor shall furnish audiovisual equipment and other training materials and

supplies as necessary. Where the Contractor presents portions of the course by

audiovisual material, copies of the audiovisual material shall be delivered to the

Officer-in-Charge on the same media as that used during the training session.

D. A minimum of 12 hours of training shall be provided including: one 4-hour training

classes shall be provided that covers FAS operations and two 4-hour classes that

cover FAS instrumentation and control maintenance. Provide access to either the live

FAS or a simulated FAS that is representative of the live system and integrate into all

training classes. Training shall occur over two consecutive days and shall be for 8 to

12 people. The City will provide a classroom at the Kailua Regional Wastewater

Treatment Plant for training.

E. Training shall be certified on Form 11000-B specified in Section 01999.

3.09 MEASUREMENT AND PAYMENT

A. The cost for the Fire Alarm System in this Section shall not be paid for directly, but shall

be considered incidental and included in the lump sum bids for the respective items in

the Proposal Schedule.

**END OF SECTION**