Upload
others
View
9
Download
0
Embed Size (px)
Citation preview
www.yousung.com
Overview
Processing Speed, AccuracyImprovement· Adopt the 32bit Digital Signal Processor · Possible to measure 0.1V and 0.01A By 16Bit A/D
Converter
Parallel Operation Function· Parallel operation methods : Master/Foller and CRC
method· Possible to support parallel operation up to 8 sets of
transformer
Real-time Monitoring function· Display LED and output alarm signal in case
error occurs
7”TOUCH LCD· Providing the convenience of the user
operation
Protection elements mounted· OCR(50), OVR(59), UVR(27) Protection elements
mounted
Tap Operation of OLTC Counting Function· Count and record the number of tap operation· Possible to forecast the maintenance time for on load
tap changer
Hourly Operating function· Operation Mode supports 8· Possible to Weekdays weekend driving mode setting
IEC 61850 Communication· Offer MMS, Goose, Report signals· Reliability secure through communication redundancy· Other Company IED interoperability
The Product is automatic voltage regulator to operate the On Load Tap Changer(OLTC) on main transformer. It can control the voltage according to each load characteristics and can supporting parallel operation up to 8 sets of transformer without any additional devices and also, it can IEC 61850 Communication. So, This product is suitable for the digital substation.
◎ Processing Speed, Accuracy Improvement
◎ Parallel Operation Function
(Up to 8 sets of transformer)
◎ Real-time Monitoring Function
◎ 7inch TOUCH LCD
◎ Protection elements mounted
◎ Tap Operation of OLTC Counting Function
◎ Hourly Operating function
◎ IEC61850 Communication
KEMA certification : No. 74101864 - MOC/INC 12-01490
Features
YSVR – 2110A
Smart Automatic Voltage RegulatorFor Parallel Operation
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
YSVR – 2110A
Smart Automatic Voltage RegulatorFor Parallel Operation
Control Power Source
AC 80V ~ 264 OR DC 110 ~ 340V
Power Consumption
Under 30W at normal time,Under 50W at during operation
Rated
Voltage AC 110V
Current AC 5A
Input
Voltage 1EA
Current 1EA
Digital 22EA
Analog 4EA
Output
Control 10EA(‘a’Contact)
Alarm 10EA(‘a’Contact)
4~20mA 4EA
Communi-cation
Front RS -232(Front HMI)
Backside
OPTIC PORT(ST TYPE) × 4EA
(for IEC 61850 : 2EA, OPTION : 2EA)
LAN PORT × 1EA (for IEC 61850)
Case
Material Steel
Size 322 × 308 × 216 mm
Specification
www.yousung.com
Interlock Module DeviceYSIM-2250M
GENERAL
SPECIFICATIONS
This product is the fast programmable logic controller of 154/345kV Interlock Panel controller.This hybrid system is combine with sealed-relay and power semiconductor devices replaceto Analog keep relay in existing Panel.
THE PRODUCT
◎ Interlock Logic Function based on PLC
◎ Remote Control Function
◎ Constant monitoring System
◎ Convenient User Interface
◎ Connector Lock Type
◎ Event Record system
Control Power Source DC 125V ±20%
ContactCapacity
Input Local DC 125V
Output
Circuit BreakerControl
Power Device IGBT 1200V 25A
Sealed Relay 16A 250VAC, 125VDC
Interlock or Alarm
(Latch Relay)
8A 250VAC, 125VDC
OperatingTime
Circuit BreakerOpearation
ON Within 35ms
OFF Within 200ms
Latch RelayON Within 20ms
OFF Within 20ms
CaseMaterial Steel
Size 552 X 311.8 X 81.1(mm)
SPECIAL
FEATURES Interlock Logic Funtion based on PLC· Replace conventional interlock
c i rcui ts wi th conf igurat ion of various Interlock logics based on programmable Logic Controller
Remote Control Function· Circuit Breaker operation status
monitoring and control
Constant monitoring system· Power device, CPU, Control power
Source· Redundant input circuit monitoring
and diagnostics· Real Time temperature monitoring
inside the panel
Connector Lock Type· Space reduction and maintenance - free
Convenient User Interface· Can be monitored in real time using
the Ethernet port· Console port using a convenient
logic upload
Event Record system· Up to 256 events can be stored
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
FieldApplicationCase
Set up Interlock Module Device in 154kV ILC PANEL
Applied to Keep Relay on 154kV Panel (front)
Applied to Keep Relay on 154kV Panel(back side)
Applied new Interlock Module Device on 154kV Panel (front)
Applied new Interlock Module Device on 154kV Panel (back side)
www.yousung.com
YSSR - 0230
Control Power Source DC 125V ±20%
ContactCapacity
InputLocal DC 125V
Scada DC 24V
OutputSemiconductor IGBT 1200V 25A
Sealed Relay 5A 250VAC, 30VDC
OperatingTime
Semiconductor ON Within 16ms
Sealed Relay ON Within 20ms
Circuit BreakerTrip Within 16ms
Close Within 16ms
CaseMaterial Steel
Size 380 X 218 X 71(mm)
GENERAL
SPECIFICATIONS
The product is the fast programmable logic controller In LCP function of 25.8kV GIS.This hybrid system is combine with the sealed relay and power semiconductor devices to replace with the existing relays used in gas-insulated switchgear.
THE PRODUCT
SPECIAL
FEATURES
Semiconductor Soild Control Relay(SSCR, GIS Control Device)
◎ Interlock Logic Function based on PLC
◎ Remote Control Function
◎ RealTime Monitoring Function
◎ Convenient Program Upload
◎ Connector Lock Type
◎ Energy Saving
Interlock Logic Functionbased on PLC· Replace conventional interlock citcuits
with configuration of various Interlock Logics based on programmable Logic Controller
Remote Control Function· Possible to remotely control all contacts
the related gas insulated switchgear
RealTime Monitoring Function· Power device, CPU, Control power
source· Display LED and output alarm signal
in case of error occurs
Convenient Program Upload· Upload the program communication
port in front of outer case
Connector Lock Type· Prevent of contact failure & electric confusion
Energy Saving· Space reduction and maintenance
free
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
FieldApplicationCase
Set up SSCR in 25.8kV GIS
25.8kV GIS Control Panel with Magnetic Relay
25.8kV GIS Control Panel with Magnetic Relay
25.8kV GIS Control Panel with new SSCR
25.8kV GIS Control Panel with new SSCR
www.yousung.com
Overview
Protection Function· OCR(50/51, 50N/51N), Reclose(79), OVR(59), UVR(27), NGR(59GA, 59GT), UBOC
Measurement Function· Current(A), Voltage(V), Apparent power(AV), Active power(P), Reactive power(Q), Power Factor(PF), Frequency(F)
Monitoring and Control Function· Monitor contacts of CB/DS/ES· Remotely control contacts of CB/DS/ES
Interlock Logic Function based on PLC· Replace conventional circuits with configuration of various Interlock logics based on programmable Logic Controller
Self Diagnosis Function· Setting value, Memory(ROM/RAM/Clock), Power source,
A/D converter, In-output circuits
Event and Fault Record Function· Record all event related to protection and control· Change setting values and analyze fault data though
HMI which is offered by manufacturer· Possible to change comtrade files
IEC 61850 Communication Protocol· Offer MMS, Goose, Report signals· Setting group Support· Acquire the reliability through communication doubling· Improve the interoperability between third
- party IEDs· Obtain the IEC61850 certificate of Level A1
by KEMA (No. 74101864-MOC/INC 12-01488)· Front USB port (for PC MMI), Rear Optic
- port(for IEC 61850 Communication)
The Product is an Intelligent Electronic Device(IED) which is designed to carry out various functions such as protection, monitoring, control, measurement, interlock functions for 25.8kV GIS in digital substation and the IED uses for protecting main transformer’s secondary Main feeder/Distribution line, Sh.C, S.Tr/Bus Tie, Bus section/PT bay.
◎ Multifunctional Protection and Measurement
◎ Monitoring and Control Function
◎ Interlock Logic Function based on PLC
◎ Self Diagnosis Function
◎ Event and Fault Record Function
◎ IEC61850 Communication Protocol
KEMA Certification : NO. 74101864 – MOC/INC 12-01488)
Features
YSDPI – 9800Smart Multifunctional IED
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
Control Power Source
DC 125V ±20%
Power Consumption
Under 30W at normal time, Under 50W at during operation
Rated
Voltage 110/√3V, 190/√3V, 190/3V
Current AC 5A
InputContact
Voltage / Current
4CT, 4PC or 8PT
Digital 28EA
Analog 5EA(4~20mA x 5ea)
OutputContact
Control 14EA(‘a’Contact x 14ea)
Alarm 2EA(‘c’Contact x 2ea)
Communi-cation
Front USB port for PC HMI
Rear
OPTIC PORT(ST TYPE) × 4EA
(IEC 61850 : 2EA, OPTION : 2EA)
LAN PORT × 1EA
(for Tester)
Case
Material Steel
Size 304 × 275 × 259(mm)
Specification
YSDPI – 9800Smart Multifunctional IED
www.yousung.com
Overcurrent Relay to Prevent 96P from MalfunctionYSOC-0800A
Control Power Source DC 125±20%
Rated Current AC 5A
Input ContactCurrent 4ea(A, B, C, N-phase current)
Digital 1ea(Clear)
OutputContactControl 3ea(‘b’ contact×3ea)
Alarm 2ea(‘a’ contact×1ea, ‘b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485
Outer Case
Structure Draw Out Type
Material Steel
Size 170×226×255(mm)
GENERAL
SPECIFICATIONS
The product is an overcurrent relay to prevent malfunction of 96P relay by fault current in case of the external fault on transformer.
THE PRODUCT
■ Digital Protection Relay base on Real-Time Operation■ Overcurrent Protection Function to Prevent
Malfunction of 96P■ Easy Maintenance■ Measurement Function for each Phase Current■ Self Diagnosis Function■ Event Data Record
SPECIAL
FEATURES Digital Protection Relay base on Real-Time Operation· Adopt the 32bit digital signal processor
Self Diagnosis Function· Setting value, Memory(ROM/RAM/Clock), Power source, A/D converter, In-output circuits
Easy Maintenance·Draw out type
Measurement Function for each Phase Current
Overcurrent Protection Function to Prevent Malfunction of 96P· Instantaneous “B” contact (point) output within 15msec which the time is faster than operation time of 96P Relay
Event Data Record· Record all events related to protection and control· Offer the PC interface using the RS-232C port· Check the information of event and change setting values though HMI which is offered by manufacturer
YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-209-7411~4 Fex. 82-32-209-7415
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory
Overcurrent Relay(OCR, 50/51)
YSOC-7900A
Control Power Source DC 90~140V
Rated Current AC 5A
Input ContactCurrent 4ea(A, B, C, N-phase current)
Digital 3ea(CB-b, Trip Blocking, Clear)
Output ContactControl 5ea(‘a’ contact×4ea, ‘b’ contact×1ea)
Alarm 9ea(‘2a’ contact×8ea, ‘2b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485(option)
Outer CaseStructure Draw Out Type
Material Steel
Size 172×226×253(mm)
GENERAL
SPECIFICATIONS
The product operates by over current which occurs during power system faults and it is designed to fit with protection, monitoring, control & measurement in the distribution line.
THE PRODUCT
SPECIAL
FEATURES Overcurrent Protection Function(50/51, 50N/51N)· Adopt characteristic curves according to KEPCO and IEC standard
Unbalance Alarm Function(UBOC)
OLTC Blocking Function· Send the blocking signal to stop operating on load tap changer during reclosing(79) operates
Measurement Function for each Phase Current
Monitoring and Control Function· Monitor contacts of circuit breaker· Remotely control contacts of circuit breake
Self Diagnosis Function· Setting value, Memory(ROM/RAM/ Clock), Power source, A/D converter, In-output circuits
Fault and Event Data Record· Record event data(up to 256ea) and fault data(up to 16ea)· Change setting values and analyze fault data though HMI which is offered by manufacturer· Possible to change comtrade files
■ Overcurrent Protection Function(50/51, 50N/51N) - KEPCO and IEC standard Characteristic Curve
■ Unbalance Alarm Function(UBOC)■ OLTC Blocking Function■ Measurement Function for each Phase Current■ Monitoring and Control Function■ Self Diagnosis Function■ Fault and Event Data Record
www.yousung.com
YSOC-7900R
Control Power Source DC 90~140V
Rated Current AC 5A
Input ContactCurrent 4ea(A, B, C, N-phase current)
Digital 5ea(CB-b, Trip Blocking, Manual Lock, 43RC, Clear)
Output ContactControl 5ea(‘a’ contact×4ea, ‘1a1b’ contact×1ea)
Alarm 9ea(‘2a’ contact×8ea, ‘2b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485(option)
Outer Case
Structure Draw Out Type
Material Steel
Size 172×226×253(mm)
GENERAL
SPECIFICATIONS
The product operates by over current which occurs during power system faults and it is added reclosing function & load unbalance detection function with 50/51 relay. It is designed to fit with protection, monitoring, control & measurement in the distribution line.
THE PRODUCT
SPECIAL
FEATURES
Overcurrent Relay with Reclosing(OCR with Reclosing, 50/51/79)
■ Overcurrent Protection Function(50/51, 50N/51N) - KEPCO and IEC standard Characteristic Curve
■ Reclosing Function(79)■ Unbalance Alarm Function(UBOC)■ OLTC Blocking Function■ Monitoring and Control Function■ Self Diagnosis Function■ Fault and Event Data Record
Overcurrent Protection Function(50/51, 50N/51N)· Adopt characteristic curves according to KEPCO and IEC standard
Reclosing Function(79)· Operate up to 3 times· After one time reclosing operation through setting the internal manu, it can block the instantaneous trip· After finishing the reclosing operation, the instantaneous trip will return automatically
Unbalance Alarm Function(UBOC)
OLTC Blocking Function· Send the blocking signal to stop operating on load tap changer during reclosing(79) operates
Monitoring and Control Function· Monitor contacts of circuit breake· Remotely control contacts of circuit breaker
Measurement Function for each Phase Current
Self Diagnosis Function· Setting value, Memory(ROM/RAM/ Clock), Power source, A/D converter, In-output circuits
Fault and Event Data Record· Record event data(up to 256ea) and fault data(up to 16ea)· Change setting values and analyze fault data though HMI which is offered by manufacturer· Possible to change comtrade files
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
Control Power Source DC 90~140V
Input Contact Digital 4ea(43RC, CB-b, 50/51, Clear)
Output ContactControl 2ea(‘a’ contact×1ea, ‘1a1b’ contact×1ea)
Alarm 5ea(‘a’ contact×5ea)
Communication Front RS-232C
Outer Case Structure Draw Out Type
Material Steel
Size 172×226×177(mm)
GENERAL
SPECIFICATIONS
YSDR-8030A
Digital Reclosing Relay(Reclosing Operation, 79)
■ Reclosing Function(79)■ OLTC Blocking Function■ Self Diagnosis Function■ Circuit Breaker Operation Monitoring
Function■ Circuit Breaker Operation Counting■ Automatic Testing Function■ Setting Value Change by HMI
The product can minimize the delay time which is taken at the time of fault recovery through automatic reclosing performance, in case circuit breaker is opened when the fault occur on the power system.
THE PRODUCT
SPECIAL
FEATURES Reclosing Function(79)· Operate up to 3 times· After one time reclosing operation through setting the internal manu, it can block the instantaneous trip· After finishing the reclosing operation, the instantaneous trip will return automatically
OLTC Blocking Function· Send the blocking signal to stop operating on load tap changer during reclosing(79) operates
Self Diagnosis Function· Setting value, Memory(ROM/RAM/ Clock), Power source, A/D converter, In-output circuits
Circuit Breaker Operation Status Monitoring Function· If they are different each other through comparing the reclosing signal and the circuit breaker contact, alarm signal is output
Circuit Breaker Operation Counting · The number of count : up to 9,999
Reclosing Automatic Testing Function·Test the reclosing operation step by step automatically by setting value
Setting Value Change by HMI· Offered PC interface using the RS- 232C port· Change setting values through HMI which is offered by manufacturer
www.yousung.com
YDOV-3
Control Power Source DC 125V±20%
Rated Voltage AC 110V
Input Contact Voltage 3ea(A, B, C-phase voltage)
Output ContactControl 1ea(‘a’ contact×1ea)
Alarm 5ea(‘a’ contact×4ea, ‘b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485(option)
Outer Case
Structure Draw Out Type
Material Steel
Size 172×226×274(mm)
GENERAL
SPECIFICATIONS
The product operates against over voltage which a fault is occurred on the power equipment. It is designed to fit for protection of differential voltage method about static condenser which is used for high voltage & ultra high voltage distribution lines.
THE PRODUCT
SPECIAL
FEATURES
Overvoltage Relay for Capacitor Protection(OVR For Condenser Protection, 60)
■ Digital Protection Relay base on
Real-Time Operation■ Overvoltage Protection Function(60)■ Self Diagnosis Function■ Test Trip Function■ Fault and Event Data Record
Digital Protection Relay base on Real-Time Operation· 16bit Digital
Overvoltage Protection Function(60)· Adopt characteristic curves according to IEC standard
Self Diagnosis Function· Setting value, Memory(ROM/RAM/ Clock), Power source, A/D converter, In-output circuits· Multiple Monitor of Output Circu it
Test Trip Function· Possible to change output contacts by test mode
Fault and Event Data Record· Record event data(up to 8ea) and Fault data(up to 4ea) · Change setting values and analyze fault data though HMI which is offered by manufacturer· Possible to change comtrade files
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
The product offer the alarm output function per each channel & fault record function in case the ground fault is occurred, as it is always monitoring the leakage current in DC power supply line (P/N phase) at the power plant or the substation through CT with communication.
THE PRODUCT
DGPS-C60, C30
GENERAL
SPECIFICATIONS
Control Power Source AC 65-240V or DC 125V±20%
Rated Voltage DC 125V±10%
Input ContactVoltage 1ea(DC line voltage)
Digital 2ea(Scada Reset, Spare)
Output Contact
Signal Generator
AC 30~65V, 27.5Hz
Alarm 4ea(‘a’ contact×3ea, ‘1a1b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485×6ea
Outer CaseMaterial Steel
Size 400×191×110(mm)
DC Ground Processing System(DGPS, Leakage Current Detection Device)
■ Digital Protection Relay base on
Real-Time Operation■ Detect Fault Signal by CT with Communication■ Measurement Method by Removing Noise Signal■ Possible to Select Fault Detection
Method in Each Channel■ Possible to Extend and Select Channels■ Monitoring and Control Function by
Communication Interface
SPECIAL
FEATURES Digital Protection Relay base on Real-Time Operation· Adopt the 32bit digital signal processor
Detect Fault Signal by CT with Communication· Use RS-485 communication between DGPS to DCT· Detective current range: 1~12mA, Accuracy: ±2%· Adapt two kinds of DCT
Measurement Method by Removing Noise Signal· Adopt the measurement method which removes noise signal by learning in advance
Possible to Select Fault Detection Method in Each Channel· Absolute method, Increment method
Possible to Extend and Select Channels· Possible to select channel number from 30ea to 60ea
Monitoring and Control Function by Communication Interface· Local: RS-232C port · Remote: RS-485 port(Possible to extend DGPS up to 10ea)
www.yousung.com
The product is automatic voltage regulator to control the On Load Tap Changer(OLTC) on main transformer. It can control the voltage according to each load characteristics and also, it can adjust the voltage effectively by bus/line voltage drop as it includes Digital Voltage Meter(DVM) function too.
THE PRODUCT
SPECIAL
FEATURES
YVC-03
GENERAL
SPECIFICATIONS
Control Power Source DC 125V±20%, AC 85~245V(Option)
RatedCurrent AC 5A
Voltage AC 60~160V
Input Contact
Current 1ea
Voltage 1ea
Digital 2ea(Volt-change 1, Volt-change 2)
Output Contact
Control 2ea(‘a’ contact×2ea)
Alarm 3ea(‘a’ contact×2ea, ‘b’ contact×1ea)
Error 1ea(‘b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485
Outer Case
Structure Draw out Type
Material Steel
Size 205×240×177(mm)
Automatic Voltage Regulator(AVR, Controller for OLTC of M.Tr)
■ Processing Speed, Accuracy Improvement■ DVM Function■ Self Diagnosis Function■ Tap Operation of OLTC Counting Function■ Event Data Record■ Communication Interface
Processing Speed, Accuracy Improvement · Adopt the 32bit Digital Signal Processor · Possible to measure 0.1V and 0.01A by 16Bit A/D Converter
DVM Function · Possible to regulate voltage though the voltage of bus and feeder decrease rapidly
Self Diagnosis Function
Tap Operation of OLTC Counting Function· Count and record the number of tap operation· Possible to forecast the maintenance time for on load tap changer
Event Data Record· Record event data(up to 110ea)
Communication Interface· Offer the communication interface with the RS-232C and RS-485 port· Check the information of event and change setting values through HMI which is offered by manufacturer
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
Automatic Voltage Regulator for Parallel Operation(AVR, Controller for Parallel operation Of M.Tr)
The product is automatic voltage regulator to operate the On Load Tap Changer(OLTC) on
main transformer. It can control the voltage according to each load characteristics and can
supporting parallel operation up to 8 sets of transformer without any additional devices and
also, it can adjust the voltage effectively by bus/line voltage drop as it includes Digital Voltage
Meter(DVM) function too.
THE PRODUCT
SPECIAL
FEATURES
YVC-03P
GENERAL
SPECIFICATIONS
Control Power Source DC 125V±20%
RatedVoltage AC 60~160V
Current AC 5A
Input Contact
Voltage 1ea
Current 1ea
Digital 5ea(Volt-change 1, Volt-change 2, Parallel 1, Parallel 2, Manual)
Analog 2ea(Potentiometer, 4~20mA)
Output Contact
Control 2ea(‘1a1b’ contact×2ea)
Alarm 3ea(‘1a1b’ contact×3ea)
Error3ea(Relay fault ‘1a1b’ contact×1ea, Parallel On ‘1a1b’ contact×1ea, Parallel Fault
‘1a1b’ contact×1ea)
CommunicationFront RS-232C
Rear RS-485 for parallel operation
Outer CaseMaterial Steel
Size 230×330×90(mm)
■ Processing Speed, Accuracy Improvement■ Parallel Operation Function(up to 8 sets of transformer)■ DVM Function■ Self Diagnosis Function■ Event Data Record■ Tap Operation of OLTC Counting Function■ Communication Interface
Processing Speed, Accuracy Improvement · Adopt the 32bit Digital Signal Processor · Possible to measure 0.1V and 0.01A by 16Bit A/D Converter
Parallel Operation Function· Parallel operation methods : Master/ Follower and CRC method· Possible to support parallel operation up to 8 sets of transformer
DVM Function· Possible to regulate voltage though the voltage of bus and feeder decrease rapidly
Self Diagnosis Function
Event Data Record· Record event data(up to 110ea)
Tap Operation of OLTC Counting Function· Count and record the number of tap operation· Possible to forecast the maintenance time for on load tap changer
Communication Interface· Offer the communication interface with the RS-232C and RS-485 port· Check the information of event and change setting values through HMI which is offered by manufacturer
www.yousung.com
The product is the device which indicates the tap position on the screen by receiving BCD & Potentiometer values from Motor Drive Unit(MDU) in order to know information for tap position of On Load Tap Changer(OLTC) on main transformer and which transmits analog outputs (DC 4~20mA, 0~1mA, 0~5V, BCD) to the remote control panel or the SCADA system in central control room.
THE PRODUCT
SPECIAL
FEATURES
YSTPI-9240A~K
Various types according to In-output
Input Output Type Input Output Type
Indicator BCD
None A
Potentiometer
None F
CurrentDC 0~1mA B
CurrentDC 0~1mA G
DC 4~20mA C DC 4~20mA H
Voltage DC 0~5V D Voltage DC 0~5V I
BCD E BCD J
Converter - - - BCD BCD K
GENERAL
SPECIFICATIONS
Control Power Source AC 100~240V±10% or DC 125V±20%
Power Consumption 4W
Display Type 7 Segment LED Display(Letter height: 14.2㎜)
Display Range 1~35Tap
Allowable Input 110% of input range
Input BCD, Potentiometer
Output None, Current(0~1mA, 4~20mA), Voltage(0~5V), BCD
Structure Indicator(Panel mounting type), Converter(Din rail type)
Certification
Tap Position Indicator(TPI, Indicator for OLTC of M.Tr)
■ Various types by In-output■ Extensive Power Source Range■ Tap Setting Function■ In-output Signal Compensation Function
by Calibration■Analog Output Scale Function ■Dry Contact■CE Certification
Extensive Power Source Range· Range: AC 100~240V, 50/60Hz
Tap Setting Function· Possible to operate regardless of tap range of OLTC· Tap setting rage: Start tap 0 or 1, Maximum tap 5~35
In-output Signal Compensation Function by Calibration· Compensate errors of resistance input signal· Compensatec errors of analog output signal
Analog Output Scale Function· Possible to scale voltage and current output siganls same as tap position
Dry Contact· Offer the compatibility Improvement between other devices
www.yousung.com
Control Power Source Input 220V
Data UnitOS Windows7
Total LU Point LU-50EA
Local UnitProcessor Type DSP
Function 1sensor/LU
UHF Sensor Band Width 550MHz ~ 1.8GHz
GENERAL
SPECIFICATIONS
THE PRODUCT
SPECIAL
FEATURES
Monitoring, Analysis of UHF Bandwidth PD· Figure out the failure condition or spot through abnormal UHF PD signal
Monitoring for Extra High Voltage M.Tr., GIS, · Analyze PD Data for both M.Tr., GIS
Real Time Monitoring Function· TCP/IP Network, Remote monitoring function for a number of S/S, Access the DB Server to review or analyze the saved PD data
Type of External UHF Sensor Device · Type of External UHF Sensor Device to put in Oil Drain Valve
Adapt the Neural Network & L2-Classifier Knowledge Algorithm· The defect is figured out accurately by the Neural Network with L2-Classifier Knowledge Algorithm through prior learning
IEC 61850 HMI Communication · Adapt IEC 61850 HMI Comm. to do mutual intercommunication in digital power subsystem site
Monitoring, Analysis of Ultra-High Frequency Partial Discharge Signals for preventing the failures of M.Tr. or through External Sensor Device which put in Oil Drain Valve of M.Tr. with Acoustic Sensor Devices.
M.Tr./GIS PD DataMonitoring System
■ Monitoring of UHF Bandwidth PD■ Acoustic Sensor■ Type of External UHF Sensor Device to put in
Oil Drain Valve■ IEC61850 HMI Communication■ Remote Real Time Monitoring System■ Neural Network, L2-Classifier Knowledge Algorithm
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
HMISYSTEM Upstream HMI Screen
Total Configuration IEC 61850 Structure
[변압기 센서1]AmplitudeMax 3Avg 3
UHFBand Width 500~1500MHz
Channel 2(scalable)
AEBand Width 120~150kHz
Channel 3(+1spare)
Internal SW OS Window 7
PC SW VS.net 3.5
GENERAL
SPECIFICATIONS
THE PRODUCT
STRENGTH
UHF Sensor which is Insertion type of Oil Drain Valve· Insertion the patched type of Oil Drain Valve
AE Sensor · A magnetic attachment type to detect Acoustic Emission Signal on the external of M.Tr, GIS
Monitor PD Data of AE Signal· 120KHz Center Frequency
regardless vibration noise
Simultaneous Detection function, UHF with AE · UHF, AE Self-Trigger function
Both Channel Detection Function · Compare AE Sensor Channel – 3 Ch, UHF Sensor Channel – 2 Ch with external Noise
Monitor PD Data of UHF Bandwidth· 500~1500MHz Bandwidth · Notch Filter
Figure out the accuracy faulty location of the caused PD using by UHF Sensor with AE Sensor to check out the current status of M.Tr, GIS to help the enhanced Electric Power Supply.
Portable PD Measurement Device of M.Tr., GISYSPD-3200P
■ Adapt UHF Sensor
■ Adapt AE Sensor to localize PD Point
■ Function to save the running PD Sampling Data
■ Neural Network Self-Knowledge Algorithm
■ All-In-One Portable Device
SPECIFICATIONS · Measure UHF PD Signal on the hot line for high voltage M.Tr. · Figure out UHF PD Spot using by high sensitive Acoustic Sensor· Insertion Type of Oil Drain Valve to reduce Outer Noise · High Reliability based on Large Database during the prolonged period· User Friendly Function like as Save, Compare, Display Wave Form and Report
HMISYSTEM System Block Diagram
Sample of Screen
The Inserted UHF Sensor UHF, AE Sensor
Embedded PC Screen
Sensor Board Analysis
AE Sensor
AE Sensor
AE Sensor
AE Sensor
UHF Sensor
UHF Sensor
AE Board(Physical)
PCExt.PC
DSP
TCP/IP
UHF Board#1(Physical)
UHF Board#2(Physical)
TCP/IP
TCP/IP
DSP
DSP
AE#2(Logical)
AE#3(Logical)
AE#4(Logical)
AE#1(Logical)
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
THE PRODUCT
SPECIAL FEATURES
Protection Relay of Condenser Bank is designed to monitor, protect the capacitance of the Condenser Bank by utilizing the harmonics waves in the Live line state capacitors configured for high-voltage or low-voltage switchboard or MCC.
Condenser Protection RelayYSCR-3150
■ Real time Monitoring of Condenser Bank
■ The Measured Capacitance of Condenser Bank in Live line state
■ Monitoring, Analysis of Harmonic-Wave based on Real Time
■ Trip and Alarm Signal
Realtime Monitoring the capacitance of Condenser Bank
· Realtime monitoring by 7 Segments Algorithm
· High Speed Sampling, 512 Sample/cycle
Power Supply
· AC/DC 85 ~ 264V
Monitoring, Analysis of Harmonic-Wave based on Real Time
· 64 harmonic wave representative
Setting Value Change by HMI
· Offered PC interface using the
RJ-45 Port
· Change setting values through HMI which is offered by manufacturer
Easily Program Upload
· Provided COMM Port to upload
Measuring a various function
· Current, Voltage, Apparent Power, Effective Power, Reactive Power, Power Factor, Frequency
Easy Maintenanc
· Draw Out Type
Control Function
· Remotely control the contacts of circuit breaker
Specification Input Power AC/DC 110V, 220V Free Voltage
Frequency 60Hz
Rated
Voltage 110V
Current 5A
Output
Control 2EA
Alarm 1EA
COMM
Front RS-232(debugging type)
Real Rj-45(HMI type)
Display type Trip, Pick up, Error
Sampling 512 Sampleing
Error tolerance ±1%
Case
Material Steel
Size 237x183x259(mm)
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
THE PRODUCT
SPECIAL FEATURES
Monitor, Diagnosis154kV transmission line by circuit parameter measuring
· Monitor, Diagnosis of Linear Equation Compose of voltages resistance(R),Inductance(L)
conductance(g) and Capacitance(C) of each phase transmission line
Condition Change
The provided IEC61850 Sampled Value, MMS Comm.
· (KEMA Certification No, 74104514-MOC/INC 13-1787)
Real Time Finding Out the incipient state of the transmission line
· Reduce Facility Accident, Power Failure Damage, Recovering Damage Restoration Cost, Maintenance Costs and accident prevention in the new On-Line monitoring technology for measuring the constant line of hot-state
Real Time Monitoring· Duplexing diagnosis circuit to check
out ROM/RAM/Clock, Control Power, Comm. and Input / Output
The new concept of Electric Power Facilities which is an on-line condition monitoring method for transmission line is proposed using electrical circuit theory and IT technology. It is reasonable that the circuit parameters such as resistance(R), Inductance(L) conductance(g) and Capacitance(C) of a transmission line exposed the electrical conditions and physical state of line.
Condition Monitoring System of transmission line by online circuit parameter measuring
■ Monitor, Diagnosis 154kV transmission line by circuit parameter measuring
■ The provided IEC61850 Sampled Value, MMS Comm. (KEMA Certification No. 74104514-MOC/INC 13-1787)
■ Applied IEEE 1588 Synchronization Protocol ■ Harmonic Monitor Function■ Real Time Monitoring■ Real Time Finding Out the incipient state of
the transmission line
Harmonic Monitor Function
· Can be monitored maximum 64 Harmonic Wave
Applied IEEE 1588 Synchronization Protocol
· Very useful for building Smart Grid, Digital Power Substation by Time
Synchronization Technic.
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
HMISYSTEM
Specification
CTGIS(CB/DS/ES)
GIS(CB/DS/ES)
A. Substation
Ethernet IEC 61850
B. Substation
Ethernet
PT
PT
S.M.U S.M.UC.M.U
H.M.I
CT
Circuit-parameterMeasuring
Unit
Control Power AC 110~220V or DC-48V
Power Consumption 30W
Output Alarm 5EA(Change over contact)
Comm. FrontRS-232×1Port(admin)RJ-45×1Port(admin)
CaseMaterial
RJ-45 × 2Port(HMI:1Port, Spare : 1Port)OPTIC(LC Type, Single Mode) × 4Port
(IEC 61850:2Port, Spare:2Port)
Dimension 482.6 × 250 × 44(mm)
Synchro-phasor
Measurement Unit
Control Power DC 125V or AC 220V
Power Consumption 20W
Rated Voltage 110/√3V, 190/√3V, 190/√3V
Current AC 5A
InputV/I 4CT, 4PT
(DI) 30EA
Output Alarm 5EA(Change over contact)
Comm.
Front RS-232 Port(admin)
RearOPTIC(ST Type, Single Mode)×2port
(IEC61850:1Port, Spare:1Port)
CaseMaterial Steel
Dimension 482.6 × 221.5 × 212.5(mm)
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
www.yousung.com
LCD-type Alarm Device(YANS-L) Communication Module(YANS-COM2)
YANS-L, YANS-COM2
SPECIAL FEATURES
Alarm Device
THE PRODUCT
The product consists of touch screen, alarm device module(watchdog, converter) and communication module(converter, output, repeater). It transfers the site information to the operator by Bell, Buzzer & LED through signal processing up to 256ea
SPECIAL FEATURES
Converter Unit · The fault signal in substation convert to RS-485 signal· Possible to select “A” or “B” contacts in each channel (up to 8ea) by deep switch· Possible to select general or first-up sequence by first-up switch
Repeater Unit· Control the management of Output or User Input
Output Unit· Possible to select bell or buzzer by deep switch in each channel· Possible to connect the output unit to the lamp by connectors
Alarm Circuit Expansion· Possible to expand the number of channel up to 256ea as connection one repeater, 8ea converters and 4ea output units
Alarm Circuit Construction· Possible to check it in front of control panel by the lamp which shows communication conditions of converter, repeater and ouput unit· Possible to select the alarm circuit or the alarm circuit for communication by simple switch control
Touch Screen · Industrial PC with touch panel· Possible to display and manage information of equipment in substation· Possible to record operating data of equipment in substation
WatchDog· Monitor the normal operation of PC with touch screen · Detection of errors in Input Module· Manage input and output signals as bell and buzzer· Adopt the RS-232 port
Input Module· Connect touch screen to RS485-Multi-Drop· Monitor the analog input and transmit data · Possible to connect the input module to converters up to 32ea
Switchboard
Monitoring and Control Panel
Power Distribution Panel
Digital Reduction Mosaic Panel LCD type Digital Reduction Mosaic Panel
Ultra High Voltage Panel High/Low Voltage Panel Motor Control Center Power Distribution Panel Distribution Panel
THE PRODUCT· Mosaic PNL, Digital reduction mosaic PNL, LCD type digital reduction mosaic PNL, Concentrate monitoring and control PNL, Central monitoring and control PNL, HMI
CERTIFICATE· CE, FCC, ISO9001, ISO14001, Bid for Korean Electric Power Coporation(KEPCO)
THE PRODUCT· 22.9kV ultra high voltage PNL, Transformer PNL, High/low voltage PNL, Integrated PNL, Distribution PNL, Motor Control Center, Power distribution PNL
CERTIFICATE· ISO9001, ISO14001, Bid for Korean Electric Power Coporation(KEPCO)
www.yousung.com
YouSung, 76 GaetBeol-Ro YeonSu-Go Incheon, KoreaTel. 82-32-819-6135 Fex. 82-32-818-6137
M1803 Techno Park IT Center 32 SongDoGwaHak-Ro YeonSu-Gu Incheon,Korea 406-840Tel. 82-32-719-8798 Fex. 82-32-719-8799
70 Aenggogae-Ro 556 BeonGil YeonSu-Gu Incheon, KoreaTel. 82-32-819-8621 Fex. 82-32-819-8622
● Head Office ● R&D Center
● Factory YOUSUNG Instrument & Electric Co., Ltd.www.yousung.com
Switchboard
Protection Panel
Automatic Control Panel
Distribution Line Protection Panel UFR Panel, S․C Panel
Inverter Control Panel PLC Control Panel
THE PRODUCT· BUS protection PNL, Feeder protection PNL, Transformer protection PNL, Distribution line protection PNL, Non-ground line protection PNL, UFR PNL, S·C PNL, S·R PNL, B·F PNL
CERTIFICATE· ISO9001, ISO14001, Bid for Korean Electric Power Coporation(KEPCO)
THE PRODUCT· Inverter Control PNL, PLC Control PNL, Water-cooled Control PNL
CERTIFICATE· ISO9001, ISO14001, Bid for Korean Electric Power Coporation(KEPCO)
www.yousung.com