61
Grounding By ELASSAD Hakam Microelettrica Scientifica MS RESISTANCES

Grounding System Philippine

  • Upload
    lenhan

  • View
    259

  • Download
    4

Embed Size (px)

Citation preview

Page 1: Grounding System Philippine

Grounding

By ELASSAD Hakam

Microelettrica Scientifica

MS RESISTANCES

Page 2: Grounding System Philippine

ELECTRICITY

The Electricity is produced & generated

outside cities at high voltage

On Nuclear plant

On diesel ,or steam generateur

On wind or photovoltaique

On hydro plant

Page 3: Grounding System Philippine

NUCLEAR POWER PLANT

Page 4: Grounding System Philippine

Diesel Generation plant

Page 5: Grounding System Philippine

Steam power process

Page 6: Grounding System Philippine

Steam generator

Page 7: Grounding System Philippine
Page 8: Grounding System Philippine
Page 9: Grounding System Philippine

Photovoltaic plant

Page 10: Grounding System Philippine

WIND POWER PLANT

Page 11: Grounding System Philippine

Transmission & Distribution

Electricity should be transported & distributed

The transportation is made through Cables (

High voltage head over lines Transmission )

63 , 132,220 , 330 , 400 or 750 kV the voltage

vary from countries , distance , total power to be

transported Etc.

Page 12: Grounding System Philippine

Head over lines

Page 13: Grounding System Philippine

Transmission & distribution

process

Page 14: Grounding System Philippine

Sub-Station

Page 15: Grounding System Philippine

Types of Neutral Grounding in Power

Distribution

In industrial high voltage network , ground

or earth is the reference point from which

voltages are measured , a common return

path for electrical current or direct physical

connection to the earth

Page 16: Grounding System Philippine

Method of grounding (Earthing)

To determine the Earthing mode a

compromise between three requirements

–Damp over voltages

–Limit damage & disturbances cause by

the earth fault

–Provide simple selective protection

devices

Page 17: Grounding System Philippine

Criteria to Choose

Voltage level: The insulation level of material must

be in accordance with induced over voltage at the

time of Short circuit

Insulation coordination : Ground fault current will

induce locally over voltage which must be

compatible with the insulation of components

Limitation of Fault current : To reduce the

electrodynamics stress on material , limit the induced

voltage on telecommunication lines

Page 18: Grounding System Philippine

Grounding Method

Page 19: Grounding System Philippine

Insulated or Ungrounded Neutral

Ungrounded system is no longer recommended

No connection between Neutral & Ground

Page 20: Grounding System Philippine

Solidly earthed or direct Earthling

The Neutral of Transformer or

Generator is directly connected

to ground by Bus Bar

No limitation of Fault current

Is usually used in low voltage

600 V and lower

Page 21: Grounding System Philippine

Impedance fault current Limitation

There is three types

By neutral grounding

Resistor

By Neutral grounding

reactor

By tuned reactor (

Petersen coil or

ground fault

neutralizer )

Page 22: Grounding System Philippine

Through a Neutral Earthing Reactor

The Neutral of Transformer is connected to earth through a Reactor

The ground fault current should be at least 60% of the three phase fault current

Reactor grounding is not considered as an alternative to the resistor grounding

This solution is rarely used in industry or bear cities due to induced magnetic field

Page 23: Grounding System Philippine

Neutral grounding Reactor dry

type

Page 24: Grounding System Philippine

PETERSEN COIL

An Earthing reactor connected between the

neutral of a system and earth and having

relatively high value of reactance

The reactive current to earth under fault

conditions balances the capacitance current

to earth so that the earth current at the fault

is limited to practically zero

Page 25: Grounding System Philippine

Arc suppression coil

(Peterssen coil )

Page 26: Grounding System Philippine

Through a Neutral Earthing Resistor

The Neutral of Transformer is connected to

earth through a Resistor

The fault current is limited to chosen value

I f = (System Voltage /3)/R

There is two types of resistors

LOW RESISTANCE & HIGH RESISTANCE

Page 27: Grounding System Philippine

Neutral Grounding Resistor

Page 28: Grounding System Philippine

Low Resistance Grounding Connected to earth ground through low resistance

Limits ground fault current to a 20 % of 3 phase fault

current (10-3000 A)

Resistor is connected between neutral of power source

Page 29: Grounding System Philippine

High Resistance Grounded

Connected to earth ground through a high resistance

Limits ground fault current to a few amperes (1-10 A is common)

Commonly used on low voltage systems in industrial plants

Used by utilities for large generators

Page 30: Grounding System Philippine

Where Do We Ground?

Single source feeding bus

Source connected

Derive neutral with Y- or zig-zag transformer

Connect grounding resistor to this derived neutral

Page 31: Grounding System Philippine

Where Do We Ground?

Single transformer feeding bus

Transformer secondary Y connected

Connect grounding resistor to neutral of transformer

Page 32: Grounding System Philippine

Where Do We Ground?

Single generator

feeding bus

Generator Y

connected

Connect grounding

resistor to neutral

of generator

Page 33: Grounding System Philippine

Where Do We Ground?

Multiple sources feeding bus

Sources Y or connected

Derive neutral with Y- or zig-zag transformer

Connect grounding resistor to this derived neutral

Page 34: Grounding System Philippine

Where Do We Ground?

Double-ended

substation with

normally open tie

Transformers Y

connected

Connect grounding resistor to each

transformer neutral

Page 35: Grounding System Philippine
Page 36: Grounding System Philippine

NEUTRAL GROUNDING

RESISTOR

Page 37: Grounding System Philippine

Neutral Earthing Resistor

NGR is not a protection components

NGR is installed to reduce the fault current before clearing

the fault

Phase - Neutral Voltage = V = System voltage / 3

V=U/1.732

Rated fault Current = V/R ( A )

Rated time (sec)

Required Temperature Rise °K

NOTA : IEEE-32-1990 is the only existing standards to

design the resistor

Page 38: Grounding System Philippine

Rated Voltage

NGR is inserted between the Neutral of

Transformer ( secondary ) & Earth ,

The rated voltage of NGR = Phase to

Neutral Voltage = System Voltage /3

Page 39: Grounding System Philippine

Rated Fault Current

I fault= (U/3)/ R

Phase to Neutral Voltage / resistance value

In High Resistance , The fault current =1 to 10 A

In Low Resistance : The fault current = 10 to 3000A

In case of NO indication we limit the fault current to the rated current of transformer

Page 40: Grounding System Philippine

Rated Time & temperature Rise Rated time = 10 sec , 30 sec or 1 minute /hour

The time rating indicate the time that the NGR can operate under fault conditions without damage & without exceeding the specified temperature rise

385 °C for continuous rating

760°C for less than 10 minutes

As per I EEE 32 Standards ,

Page 41: Grounding System Philippine
Page 42: Grounding System Philippine

Insulation

As per IEEE 32 Standards the

applied voltage should be = 2.25 times

the line to neutral voltage + 2 kV

Page 43: Grounding System Philippine

EXTRACT FROM IEEE 32-1990

Page 44: Grounding System Philippine

Resistances material

Different kind of resistance material

1: Cast iron ( not used any more)

2: Liquid resistor ( not used any more)

Stainless Steel ( AISI 304 , 430,310,32/20 or

inconel 601 ) NiCr alloy

Page 45: Grounding System Philippine

Temperature Coefficient of resistance material

Temperature coefficient =

indicate the variation of resistivity of resistance material with temperature

Resistance material used for NGR should have a high variation of resistivity to limit the fault current & keep the voltage constant

The Stainless Steel AISI 430 is mostly used for NGR

Page 46: Grounding System Philippine
Page 47: Grounding System Philippine
Page 48: Grounding System Philippine

Protection Degree

The NGR is a passive component , resistor

will absorb the energy developed by the

current during rated time and should

evacuate it

The Best Protection Degree for NGR = IP23

Page 49: Grounding System Philippine

IP 55 type tests

Page 50: Grounding System Philippine

IP55

Page 51: Grounding System Philippine

Sub station in the desert Egypt

Page 52: Grounding System Philippine

Components can be installed into Resistor

RECOMMANDED

Current & voltage transformer

On or off load disconnectors ( contactors)

Surge Arrestors

Space heater

Lamp

Doors

NOT RECOMMANDED

Electronic devices like relays or others monitors

( temperature into resistors will reach very high level & cause

damage to electronic

Page 53: Grounding System Philippine

accessories

Page 54: Grounding System Philippine
Page 55: Grounding System Philippine
Page 56: Grounding System Philippine
Page 57: Grounding System Philippine
Page 58: Grounding System Philippine

ROUTINE & Type Tests

Routine Tests Visual Inspection

Dimensional Check

Measurement of Insulation Resistance

Measurement of Resistance

High Potential Test (Dielectric test @ 50Hz – 1min)

Page 59: Grounding System Philippine

Type Tests

As per IEEE-32 Impulse tests are not required for Resistor

Heat run tests = Temperature Rise tests , application of constant voltage during

rated time

measurement of current & resistance value at 0 sec up to end rated time

Measurement of temperature rise by application of tempearture sensor

Calculation of temperature rise tests as per following formula

R2=R1*(1+αΔθ)

α = Temperature coefficient of resistance material

Δθ = Temperature Rise

Page 60: Grounding System Philippine

Temperature Rise tests & installation of temperature sensor

Page 61: Grounding System Philippine

The End