ELSEVIER SO950-4230(96)00014-9 J. Loss Prev. Process Ind. Vol. 9. No. 3. pp. 231-240, 19% Copyright 0 1996 Elsevier Science Ltd Printed in Great Britain. All rights reserved 0950-4230/96 $15.00 + 0.00 Protection of equipment engulfed in a pool fire Eul&lia Planas-Cuchi*, Joaquim Casal*, Antonio Lancia? and Leo Bordignon? *Centre d’Estudis de Rise Tecnolbgic (CERTEC), Department of Chemical Engineering of the Universitat Politkcnica de Catalunya-Institut d’Estudis Catalans, Diagonal 647, 08028 Barcelona, Catalonia, Spain i_Tecsa Ricerca & Innovazzione, via Aldo Moro 1, Scanzorosciate (BG), Italy Received 1 I February 1996 When process equipment is engulfed in a fire, the protection system should extinguish the fire and simultaneously cool the equipment. Therefore, the behaviour of equipment engulfed in a fire, as well as its eventual influence on the fire, should be known. In this article, experimental data from pool fires of hexane (4 m2) and kerosene (12 mZ) are discussed. The evolution of the fire up to its full engulfment is studied, as is the evolution of temperatures at different points of a tank engulfed in it. The heat release rates under the different operating conditions are studied. A method is developed to calculate the maximum combustion rate, both for the developing stage and for the fully developed fire. The hindering effect of the tank on the fire is discussed and quantified in terms of ‘efficiency of hindered combustion’. Copyright 0 1996 Elsevier Science Ltd Keywords: pool fire; foam and water; cooling; extinguishing; modelling Certain industrial installations are designed according to an extremely compact lay-out. Off-shore oil platforms and some sections of chemical process plants exhibit a high density of equipment which, in the event of certain incidents, can lead to dangerous situations and can sig- nificantly complicate the management of emergency pro- cedures’. In such installations, moreover, there are usu- ally large inventories of hazardous materials, and protection systems with a high degree of reliability and efficiency must be provided. If flammable materials are processed or stored, a good fire protection system must be installed. Such a system should be able to cover two objectives simultaneously: extinguishing or at least con- trolling the fire and, furthermore, cooling the structures and the equipment. This second scope is very important, in some cases even more than the first one, as the effect of fire on certain equipment can result in further loss of containment of flammable substances and hence in the escalation of the accident scenario. In order to cover these two objectives there are vari- ous possibilities. In the conventional approach, cooling and extinguishing are addressed by two different sys- tems: water deluge systems and foam systems, the spec- ific features of water and foam thus being used separ- ately. Water is the most commonly used fire extinguishing agent; it has a high specific heat and very high latent heat of vaporization, and furthermore it is usually available at a low cost. However, the use of water also has several disadvantages, the main one resulting from its relatively high density, higher than that of most hydrocarbon fuels. Furthermore, hydrocarbons are also immiscible with water; therefore, in the event of a pool fire water will neither cover the burning fuel - thus extinguishing or reducing the fire - nor mix and dilute it. The hydro- carbon will maintain a lighter burning layer, and in some cases water may even flash (if it enters a hot mass of fuel) and spread fuel. If a cover for the burning surface is required - and this will help significantly in the control of the fire - foam solutions must be used. However, foam agents are much more expensive than water and, moreover, they are available in much smaller amounts. One interesting approach consists, therefore, in using a single deluge system which discharges foaming solution for a given minimum time and then continues discharging water. Such systems, known as ‘foam and water deluge systems’, should discharge a kind of foam which is fluid enough to behave like water for cooling purposes but stable enough to possess useful extinguishing properties in spill fires. Foam and water deluge systems are quite advantageous, especially for off-shore oil platforms and processing plants, due to the possibility of achieving fast fire control, the simplifi- cation of plant structure and operating procedures and the resulting reduction in the costs of the system. This work discusses the behaviour of a typical piece of equipment (a tank) during the development and 231

Protection of Equipment Engulfed in a Pool Fire

Embed Size (px)

DESCRIPTION

Protection of equipment

Citation preview

  • ELSEVIER SO950-4230(96)00014-9

    J. Loss Prev. Process Ind. Vol. 9. No. 3. pp. 231-240, 19% Copyright 0 1996 Elsevier Science Ltd

    Printed in Great Britain. All rights reserved 0950-4230/96 $15.00 + 0.00

    Protection of equipment engulfed in a pool fire

    Eul&lia Planas-Cuchi*, Joaquim Casal*, Antonio Lancia? and Leo Bordignon? *Centre dEstudis de Rise Tecnolbgic (CERTEC), Department of Chemical Engineering of the Universitat Politkcnica de Catalunya-Institut dEstudis Catalans, Diagonal 647, 08028 Barcelona, Catalonia, Spain i_Tecsa Ricerca & Innovazzione, via Aldo Moro 1, Scanzorosciate (BG), Italy

    Received 1 I February 1996

    When process equipment is engulfed in a fire, the protection system should extinguish the fire and simultaneously cool the equipment. Therefore, the behaviour of equipment engulfed in a fire, as well as its eventual influence on the fire, should be known. In this article, experimental data from pool fires of hexane (4 m2) and kerosene (12 mZ) are discussed. The evolution of the fire up to its full engulfment is studied, as is the evolution of temperatures at different points of a tank engulfed in it. The heat release rates under the different operating conditions are studied. A method is developed to calculate the maximum combustion rate, both for the developing stage and for the fully developed fire. The hindering effect of the tank on the fire is discussed and quantified in terms of efficiency of hindered combustion. Copyright 0 1996 Elsevier Science Ltd

    Keywords: pool fire; foam and water; cooling; extinguishing; modelling

    Certain industrial installations are designed according to an extremely compact lay-out. Off-shore oil platforms and some sections of chemical process plants exhibit a high density of equipment which, in the event of certain incidents, can lead to dangerous situations and can sig- nificantly complicate the management of emergency pro- cedures. In such installations, moreover, there are usu- ally large inventories of hazardous materials, and protection systems with a high degree of reliability and efficiency must be provided. If flammable materials are processed or stored, a good fire protection system must be installed. Such a system should be able to cover two objectives simultaneously: extinguishing or at least con- trolling the fire and, furthermore, cooling the structures and the equipment. This second scope is very important, in some cases even more than the first one, as the effect of fire on certain equipment can result in further loss of containment of flammable substances and hence in the escalation of the accident scenario.

    In order to cover these two objectives there are vari- ous possibilities. In the conventional approach, cooling and extinguishing are addressed by two different sys- tems: water deluge systems and foam systems, the spec- ific features of water and foam thus being used separ- ately.

    Water is the most commonly used fire extinguishing agent; it has a high specific heat and very high latent heat of vaporization, and furthermore it is usually available at

    a low cost. However, the use of water also has several disadvantages, the main one resulting from its relatively high density, higher than that of most hydrocarbon fuels. Furthermore, hydrocarbons are also immiscible with water; therefore, in the event of a pool fire water will neither cover the burning fuel - thus extinguishing or reducing the fire - nor mix and dilute it. The hydro- carbon will maintain a lighter burning layer, and in some cases water may even flash (if it enters a hot mass of fuel) and spread fuel. If a cover for the burning surface is required - and this will help significantly in the control of the fire - foam solutions must be used. However, foam agents are much more expensive than water and, moreover, they are available in much smaller amounts.

    One interesting approach consists, therefore, in using a single deluge system which discharges foaming solution for a given minimum time and then continues discharging water. Such systems, known as foam and water deluge systems, should discharge a kind of foam which is fluid enough to behave like water for cooling purposes but stable enough to possess useful extinguishing properties in spill fires. Foam and water deluge systems are quite advantageous, especially for off-shore oil platforms and processing plants, due to the possibility of achieving fast fire control, the simplifi- cation of plant structure and operating procedures and the resulting reduction in the costs of the system.

    This work discusses the behaviour of a typical piece of equipment (a tank) during the development and

    231

  • alnpow leluaw!Jadxa aql 01 13adSaJ ~I!M sJalawo!peJ aql40 uo!ysod (q) :sgJoa u! sa!Jas Isal ale3s-lln4 aq~ ~04 pasn dn-yoow WJOpeld aw 40 aJnvnJ3s (a) L alnhj

    ( p!Ml 01 - 0) PZ J~HUJO!pe~

    1 $J/MI OZ - 01 LZ Jwawo!pe~

    1 zw/Ml 01 - 0) gz Jal~wo!P~~

    yuei atjl~o ap!s $saM aql uo pale301 Saldno3oWJaq~ aql 01 pUOdSaJJO3 SasaqluaJed u! sJaqwnu aql SaldnO3OWJaql yuel 40 Guyo!gsod 2 arn@j

    we3 zz . u PZ 3-M 9 16% GLCLL LZ

    QEJauat) *atug 30 uoypun3 v SE aIdnoDowayl y3ea 103 aw pue 11s auofzmouu1 2g amaDw ss3aL - mu pm pun SUIU 11~ 103 pallold SBM (s.xaIyuuds aq~ 30 uoyzlado vds vsxm vds oavs SKY WWI ayl4 PadoIaAap ayl 01 snoyAaJd Isa] arfl 30 a)nuytu lsly aq %.ynp) amI ,su1.1o3~ld 110 aloqs33o 103 uralsAs a&yap JawM -wadwa~30 uoynIoAa aqi spawamwatu Itz)uawI.radxa 30 PW mod, u-681~~1 SI-HL IDafoti 383 aw 30 7~0~ AqliqicmpoldaJ put! A1yqcgal aq A3paA 01 laplo III -aww3 aql U~IM paKiallo9 alaM mp ptz,uatuuadxg

    7.uoo3 30 lady e II? paIpzlsuj slalawolpvl aaJy1 ayl 30 uogsod aql s~oys

    (q)l a.4n8!d *lawi Quo 8uIsn auop sm uoymgxa aql 5 1 pm pi sisal II! ~vq~ aluasqo 01 wvodw! s! I! tl a1qv.z ul paluasa.td as\? sisal @!a asay 30 szgsua$atznzq~ aqJ @I ~1 30 aDy.ms B ~I!M) auasolay qiy mo3 pm2 @.I p 30 aayns Iood I? qii~) auexaq ~I!M pawoyad aJaM

    sisal mod *(amwadwal SE%) slu!od pzrrralxa mo3 IV pam

    -seaw wM amle.wIwai a~owaqwg !(z am8?& gut.3 am

    qll~ (a.ry aql qsp&gxa pw) Ilids aq laAo3 djsnoaw)

    -Inwys pw 11100~ 01 laplo uy pal~no~d aq 01 luawdyba

    ayl 30 am3ms av 01~0 dpDaI!p pinjj &u~ooD aw a&q:, -sip speaq hds a.xow .IO au0 qD!qM us su~a$sks asoqj -a*! stualsrCs dwds Java pw ureo3 30 paluasald 0s~ s! dpnls v .paprAoJd azrr $u ~1 pm $u p %U!.uW?au.I auas -olay put! amxaq 30 saIy Iood u10.13 paugqo tmp pmar_u -uadxg *pa3@ua sr oy qD!qM ui aJy Iood a 30 uoyugxa

    ye la !yzvyweuejd *g :aJ!J load e u! paj@ua juawdinba 40 uogc)aJoJd ZEZ

  • Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al. 233

    Table 1 Description of the selected experiments

    Pool area S.A.R3* Deluge flow Test number (m*) Fuel Extinction agent Sprinklers configuration (Lmin-.m-*) (I.min-)

    12 4 Hexane Foam two SPKOl125 14.2 246 13 4 Hexane Foam two SPK0/125+SPY0/90 14.2+ 296 14 4 Hexane Water two SPK0/125+SPY0/90 14.2+ 296 15 4 Hexane Water two SPKOf125 14.2 246 88 12 Kerosene Foam two SPK0/125+SPY0/90 14.2+ 296 89 12 Kerosene Foam two SPK1/90+SPY0/90 14.2+ 296 90 12 Kerosene Foam two SPK0/125 6.5 112 91 12 Kerosene Foam two SPKl/l ?O 6.5 112

    Surface application rate

    speaking, the results for the hexane pools (4 m2) showed a practically linear trend, essentially identical for the first three tests; run number 15 showed slightly higher values with respect to the rest of the results, although the trend was similar. For the kerosene pools the results were parabolic rather than linear; this can be attributed to the fact that the development of fire over the whole surface of the pool (in this case 12 m2) was slower.

    The data obtained from the radiometers have been used to plot the variation of radiation intensity as a func- tion of time (Figure 3). As can be observed, after approximately 40 s the fire can be considered to be fully developed, and with a practically stationary regime (the time required to reach this condition was more than 60 s for the 12 m2 kerosene pool fires); typical oscillations exist, which must be related to the turbulence of the fire and to the variability of the shape, size and orientation of flames as a function of time. Later on, the decrease of radiation intensity shows the effects of the start-up of the extinction system. The action of the foam-water mixture caused a significant decrease in the size of the flames, which finally led to the complete extinction of the pool fire as it became covered with a stable layer of foam.

    Evolution of temperature

    As the fire proceeds, the equipment engulfed in it - a tank in this work - will undergo an increase in tempera- ture which will be a function of the evolution and size

    4.5

    4

    3.5

    T3

    E 2.5

    j2

    z! 1.5

    1

    0.5

    0

    Radiometer 26

    -Radiometer 27

    0 50 100 150 200 250

    time (s)

    Figure3 Variation of the radiation intensity as a function of time for test number 13 (4 m*, hexane)

    of the flames, and also of the location of the measuring point; those zones exposed to flame impingement will undergo stronger heating than those which are not in direct contact with them. On the other hand, after the start-up of the cooling/extinguishing system, different behaviour will be observed depending on the existence or otherwise of a water/foam layer on that particular zone of the equipment surface. The analysis of the experimental results indicates the existence of five dif- ferent situations or steps4, which are discussed in the following paragraphs.

    Initial step (development of the jire) The first step corresponds to the development of the fire and takes place over the first minute (approximately). Figure 4 shows the variation of temperature as a function of time, at diverse measuring points, for two of the tests. Temperature increases approximately linearly with time, the slope depending on the location of the point and on the impingement of the flames on that point. In one minute, the temperature at the bottom of the tank increases from room temperature to more than 350C while in the lower zone of the sides it does not exceed 250C and at the top the maximum temperature is 125C.

    From the data plotted in Figure 4(b) it can be seen that the temperatures registered by the thermocouples located in the upper sides of the tank show a degree of scattering. This must be attributed to the fact that the fire was not exactly symmetrical owing to turbulences and the arrangement of the module walls. Thus, although theoretically all the thermocouples should show the same behaviour (as in Figure 4(a)), the induced wind and the radiation from the heated walls caused these differences between the measurement points.

    For the 12 m2 pool fires (Figure 4(c)), the scattering is less noticeable and the temperatures are higher, because in this case the engulfment of the tank in the fire is more complete, and therefore the impingement of the flames on its walls has a greater influence. As in Figure 4(a), the bottom of the tank (Figure 4(d)) for the 12 mz pool fires shows the same behaviour for all the thermocouples.

    The evolution of the temperature at different points of the tank as a function of time has also been plotted in Figure 5. The experimental points show clearly how the bottom of the tank undergoes the most intense heat- ing action, due to the greater exposure to the flames.

  • 234 Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al.

    8) 400 I

    350 -- JiE& 17 11 5 . 300 -- g250 --

    t

    200 -- 0

    150 -- 4 l-

    100 -- e 8 0 Thermocouple 5

    50 -- I 0 Thermocouple 11 A htmocouple 17

    O-1

    b) 300 I

    250

    A

    A

    0

    A 0 0 Thermocouple 7

    0 Thermocouple 13

    A Themwouple 19

    a

    m Thermocouple 3

    . Thermocouple 9

    0 Thermocouple 15

    I 8 50 0 8 f 04 I

    0 10 20 ti: (*)

    40 50 60 0 10 20 30 40 50 60 time (8)

    )-f~ d 3501 1 !FA 17 11 5 0 0 0

    0

    0

    A A

    A

    250

    0 Ttwmpcoupb 7

    0 Thermocouple 13

    0 llwrrmcoupb 15

    A a l 0 n

    a Therwcoupb 11 0

    0 A A

    A 0 0

    A

    8 -200

    f j 150

    100

    P 0 q n

    8 8 i a A O o

    4 8 0

    50

    04 1

    0 10 20 30 40 50 90

    time (8)

    04 4

    0 10 20 30 40 50 90 time(s)

    Figure4 Tank temperature during the first minute. (a) Test number 13 (4m *, hexane), tank bottom; (b) test number 13 (4 m*, hexane), upper tank laterals; (c) test number 91 (12 m*, kerosene), tank bottom; (d) test number 91 (12 m*, kerosene), upper tank lat- erals

    Operation of the extinguishing system The evolution of the fire during its development and dur- ing the extinguishing process can be seen schematically in Figure 6, obtained from a film. In the initial steps the fire increases rapidly, soon engulfing the whole tank. The shape of the flames is variable, as usually happens with relatively large fires. As flame length increases, so do the turbulence and mobility of the flames.

    From the moment at which the extinction system is started, a significant increase in the turbulence of the flames is observed, together with the existence of wind from the west side; as a consequence, the flames move towards the east side (see Figure 6)4. Therefore, the west side of the tank is less influenced by the flames (the surface area undergoing flame impingement decreases significantly) and consequently the temperatures meas- ured here are lower.

    After reaching a maximum, the temperature at the various measuring points of the tank starts to decrease; in the plot of temperature versus time, a negative slope is obtained. This situation corresponds to the moment at which the cooling effect of water/foam starts, i.e. when

    I92an

    +t=6a

    -a-t-wr -A-tear -et421

    -A-t**

    -o-t=9or

    h 300.. 42 j 250.. 200.-

    i 150.. Q

    k im.. 50 .. 0 04 0 8

    0 60 im 150 200 HeisM (cm)

    Figure5 Evolution of tank temperature at different time instants as a function of height. Test number 89 (12 m*, kerosene)

  • Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al. 235

    Test no1 2 Test no1 2

    Time = 10s Time = 20 8

    Test no1 2

    Time = 30 s

    Test no1 2 Time = 40 s

    Test no1 2 Time = 50 s

    n4

    Test no1 2 Test no1 2 Time = 120s Time = 1802

    Test no1 2 Time = 60 s

    Figure 6 Evolution of the fire during its development and dur- ing the extinguishing process. Test number 12 (4 m*, hexane)

    the mixture reaches that measuring point. In any event, while the tank surface continues to be exposed to flame impingement, temperature will decrease slowly, although the size of the fire decreases significantly after the start-up of the deluge system.

    Later on, as the pool gradually gets covered by the foam, the height of the flames gets less and less and they no longer impinge on the tank wall. Now the cooling action of the water is stronger and the temperature decreases dramatically, with a steep negative slope in the plot of temperature versus time. Finally, when the fire is extinguished and the extinguishing system is stopped, a slight increase in temperature is again observed due to the heating caused by the radiation from the hot walls of the experimental module.

    This process establishes in a relatively clear way the existence of five stages in the evolution of temperature at the various points of the tank wall (Figure 7)4. The first one, which corresponds to the initial development of the fire, is characterized by a rapid increase in temperature; in the plot of temperature versus time a practically

    A 8 300

    2 250 a [ 200

    j 150

    0 50 100 150 200 250 300 350 400 tlrne (s)

    Figure 7 Stages of the temperature evolution at the lower tank laterals (thermocouple 6). Test number 12 (4 m2, hexane)

    straight line is obtained with a steep slope (the heating rate depends on the location - at the bottom of the tank values of the order of 3.6Cs were registered). In the second stage, which corresponds to a fully developed pool fire, temperature continues to increase but at a slower rate and with a trend which is no longer linear; in this stage a considerable wind appeared in all the tests. The third stage initiates with the start-up of the cooling/extinguishing system. The temperature starts to decrease - its maximum value having been reached at the transition between these two steps - gradually, at an approximately constant rate. The fourth stage corre- sponds to a situation in which, due to the blanketing action of the foam over the pool, the magnitude of the flames has decreased considerably and they no longer reach the point in the tank where the temperature is being measured. Now the heat balance is clearly influ- enced by the dominant mechanism of the foam/water cooling, with a relatively weak heat input by radiation; thus, temperature decreases abruptly, following an approximately linear trend. Finally, once the fire is extin- guished, gentle heating is observed.

    The existence of these five stages was observed only in certain conditions during the experimental tests. In other cases some of the intermediate stages were not found, depending on the point at which the temperature was being measured. This happened, for example, when the influence of flames on the tank wall ceased at the same moment that the cooling mixture reached that parti- cular point. Stage 3 does not exist and just after reaching its maximum value the temperature decreases abruptly to very low values, and afterwards continues to fall very gradually (see Figure 8). For the whole system, this situ- ation would correspond to an immediate extinction of the pool fire. This case, which would be the best one from the point of view of controlling the emergency, in practice implies conditions which can only be found at certain points of real installations.

    At the bottom of the tank, however, flame impinge- ment existed practically throughout the experimental test, finishing only when the fire was extinguished. Fur- thermore, this zone was never reached by the cooling mixture in the various tests that were carried out. This

  • 236 Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al.

    350

    300

    _

    250 1

    g e! B 200

    i 150

    I- 100

    50

    5 01

    0 50 100 150 200 250 300 350 400

    time (s)

    Figure 8 Stages of temperature evolution at the lower tank lat- erals (thermocouple 12). Test number 12 (4 m2, hexane)

    is why slope changes are smoother and therefore the temperature values are higher up to the extinction of the fire (Figure 9).

    Heat released from the pool fire

    Probably the best way to follow the development and evolution of the pool fire is to measure the heat released by the combustion. For a pool fire of a given fuel, the heat release rate is a function of the combustion rate and of the combustion efficiency. The heat release rate will rise rapidly in the initial moments, while the fire is developing and the size of the flames is increasing, and after that it will have an approximately constant value once the fire is completely developed. Nevertheless, for pool fires of a relatively large size, this second stage - which would correspond to a stationary state if no changes or external actions were imposed on the sys- tem - is characterized by significant variations in flame size and shape.

    The evolution of the heat release rate as a function of time will be therefore a way to identify the moment at which the pool fire is completely developed. In the following paragraphs the experimental results of the

    700

    600

    500

    E g! 400

    E p 300

    8 200

    100

    0

    l-

    !Gi4 5

    B B

    hod , c -F

    0 50 100 150 200 250 time (s)

    Figure9 Temperature evolution at the tank bottom Figure 10 Total heat release rate evolution as a function of (thermocouple 5). Test number 91 (23 m2, hexane) time for test number 13 (4 ma, hexane)

    overall heat release rate and of the heat released by con- vection are discussed.

    Overall heat released The heat released during each test was measured as a function of time by using the adiabatic calorimeter. The plot of overall heat release rate versus time (Figure 10) shows a steep rise at first, with a characteristic change in slope at approximately 30 s; from this moment the heat release rate still increases, but more gradually, up to a maximum-value (fully developed fire). For a 4 m* pool fire of hexane, the heat release rate increased from zero at ignition (t = 0) to rates of the order of 5 100 kW after 30 s. For the kerosene pool fires (12 m*), the heat release rate increased to rates of the order of 16 600 after 60 s. When the deluge system was activated, the heat release rate decreased rapidly until the extinction of the fire. In those cases in which only water was used for the extinction (tests 14 and 15), the heat release rate also decreased after the activation of the deluge system, but a few seconds later the fire revived.

    Heat released by convection The heat released from a fire is essentially divided into two fractions, one transferred by convection and the other transmitted by radiation. Both contributions can be determined separately and independently from Q,,. The heat released by convection can be obtained from the flow rate and temperature of the gases produced in the combustion:

    . I, Q c-cm = iv*moke * cp x AT,,, . (1) During the experimental tests, these data were measured by the calorimeter and treated in such a way as to give continuously the value of Q,,,,. The trend of the evol- ution of the heat released by convection as a function of time is similar to that corresponding to the overall heat release rate: for the pool fire of 4 m* a gradual increase in the heat released, with a steep slope during the first 30 s; later on, a more gradual increase is observed - with some scattering caused by the turbulence and irregularity associated with the phenomenon - until the maximum value (steady state) is reached at approximately 60 s.

    Ooo I 6000 +

    7

    0 3o 50 100 150 200 250

    time (s)

  • Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al. 237

    After this moment, a sudden fall can be observed due to the start-up of the extinguishing system.

    The 12 m2 pool fires (Figure 11) show an increase in the heat released, with a steep slope, during the first 60 s, after which the extinction system is activated. In this case the steady state was not reached, i.e. the fire was still developing when the sprinklers were activated. It can be observed that after that moment the heat release rate displays an approximately constant value for a cer- tain period, with a steep fall afterwards; this can be attri- buted to the difficulties in extinguishing the fire.

    In this equation, the first term on the right-hand side corresponds to the heat transferred by conduction; this is a boundary effect, significant only for pools with a few centimetres in diameter and, therefore, negligible here. The second term is the heat transferred by convec- tion, also negligible for the large pools studied in this work. For pools with a diameter of 1 m or more, the radiation mechanism is the only one which is really important. Therefore, in this work the rate at which heat is transferred to the pool is given by:

    For hexane pool fires of 4 m*, the heat released by convection was approximately 57% of the overall heat released. In the case of kerosene, this fraction was approximately 65%. The kerosene fires gave rise to larger amounts of dark smoke, i.e. the fire was less bright and the amount of heat transmitted by radiation was cor- respondingly lower.

    ri - = D F(q - c)(l - eekd) . (n&/4)

    The theoretical combustion rate can be obtained from this expression and from the heat required to evaporate the fuel. As combustion rate increases with pool size, for a pool of infinite diameter, the maximum combustion rate is obtained:

    Discussion

    Most communications published on hydrocarbon pool fires deal with fully developed fires, and very little infor- mation is to be found on the initial unsteady state, when the fire is developing. This is why there is no equation available in the literature to predict the evolution of flame temperature during the initial development of a fire. Moreover, when relatively large equipment is engulfed in a pool fire, it should have a disturbing effect on the flames as compared to a free surface pool fire; again, this aspect has not been studied by those authors who have worked in this field5-8.

    and for a pool fire of finite diameter: . N m f=h;max (1 -emM).

    From equation (4) it can be inferred that during the initial development of the fire (unsteady state) the com- bustion rate will change with time, as will flame tem- perature. Moreover, flame temperature will also change with height.

    In the following paragraphs this effect is studied. In order to calculate the theoretical (maximum) combustion rate in both an unsteady and a steady state, a semiempir- ical expression is derived from the treatment of exper- imental data. Accordingly, the heat transfer rate from the fire to the pool is given by the following expression:

    The experimental data have shown that during the development of a pool fire the flame temperature changes with time according to an expression of this type:

    t Tf @A = (b + &) (f-5)

    where a and b are parameters which can depend on height. The values obtained for the different operating conditions are given in Table 2.

    rd 214 Heat bv convection Heat by conduction

    + oF(G - c)( 1 - emkd) . keat by radiation

    7000 0

    )C t 6000 --

    0" 5000 --

    0

    4000 -- 0 00

    0

    3000 -- 0

    0

    2000 -- 0

    1000 -- 0

    0

    ocr :

    0 b %O 08 0 coo Q,

    80 0

    rprinklers diwUon

    0 30 60 00 120 150 180 210 240

    time (s)

    Figure 11 Heat released by convection as a function of time for test number 90 (12 m2, kerosene)

    Table 2 Values a and b for different operating conditions

    Hexane Kerosene (4 m2) (12 m*)

    a 0.000851 (0.000465-0.000188h~ b ~0.0034+0.021 h) (0.0347+0.0114h)

    Equation (5) was used to calculate the flame tem- perature just above the pool surface (h = 0). However, it must be taken into account that this temperature corre- sponds to the central axis of the flame. Flame tempera- ture decreases over the radius, from flame axis to periph- ery; at the flame boundary, the temperature is approximately 50% (in terms of temperature increase with respect to room temperature*) of the temperature

    * rR - T, = 0.5 x (Tr- TJ, then r, = 0.5 x CT,+ T,). The average temperature at a given height can be determined, as a function of temperature at flame boundary and room temperature, from the following expression: T,,= (T, + T,)/Z. In this work, a room temperature of 293K has been taken.

  • 238 Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al.

    at the axislo. Thus, the average flame temperature at a given height is approximately

    T,, = 0.75 . Tf + 73.25 (7)

    By introducing this equation, together with equation (6), into equation (5), it is possible to obtain a semiempirical expression for the calculation of the combustion rate dur- ing the non-stationary regime:

    riz(t) = FU

    [(

    t

    AK + c,(T,-T,) 0.75(b+at) + 73.25 4 (8)

    -I - c (l-e-).

    1

    The heat release rate can be obtained as * n Q t,,fa, = m; AH, . (9)

    As in this case the view factor value between the fire and the pool is unity and the mass loss rate can be determined from equation (8); the rate at which heat is released can be calculated from the following relation- ship:

    This expression gives the maximum heat release rate, i.e. that corresponding to the combustion of all the fuel evaporated. However, in an accidental fire, not all the fuel is burnt, i.e. combustion efficiency is not 100%. Fig- ure 12 shows the experimental values for a fire of 4 m2, as well as those calculated by the method proposed in the aforementioned paragraphs. As can be observed, experimental values are fairly lower than the theoretical ones. Taking into account the fact that the combustion can be hindered by the existence of the engulfed equip- ment, two different combustion efficiencies can be defined. First of all, the combustion efficiency,

    Heat released in the combustion of a free surface pool

    = Heat released in the case of complete combustion of all the fuel evaporated

    (11)

    14000

    12000

    E s

    10000

    E

    8 0000 I

    ; 6000

    +f

    E 4000 2000

    0 7

    0 lo 20 30 40 50 60

    time(s)

    ;5

    I

    0 10 20 30 40 50 60

    time (s)

    Figure 12 Total heat release rate, experimental and theoreti- Figure 13 Efficiency of hindered combustion as a function of cal, as a function of time for test number 13 (4 m*, hexane) time for test number 13 (4 m*, hexane)

    0 0

    0

    0

    0

    0 o 0 0 O 0

    00 0 0

    0 0

    0

    0 0

    pi

    When there is equipment engulfed in the fire, this equip- ment has a hindering or obstructing effect on the fire, thus a hindering factor can be defined as the ratio between the heat released in the combustion of a pool fire with an obstacle (for example, a tank) and that released in the same pool fire with a free surface:

    Heat released in the combustion

    5= of a pool with an obstacle

    Heat released in the combustion of the same pool without any obstacle

    (12)

    5 would have a maximum value of 1 in those cases in which the influence of the obstacle is negligible, and decreasing values as the hindering effect increases (i.e. as the size of the equipment as compared to that of the pool increases).

    Finally, the efficiency of hindered combustion can be defined as the ratio between the heat released in the combustion of a hindered pool and the maximum tbeor- etical heat which could be released if the combustion was complete and non-obstructed:

    %bst = 77 x 5 =

    Heat released in the combustion of a hindered pool

    (13)

    Heat released in the complete combustion of all * the fuel evaporated in a free pool

    Figure 13 shows the value of q&r for the data shown in Figure 12 (pool fire of 4 m2 with a tank engulfed in it); the experimental data corresponding to the initial moments have a certain lack of accuracy due to the variability of fire spreading and increasing in this first step. Therefore, the VdUeS of qObSI are significant only over the region of Figure 13, in which they are approximately constant. For this set of values, the efficiency of hindered combustion is approximately 47%, considerably lower than the values found in the literature for free surface pool fires.

    The hindering effect of equipment engulfed in the fire can be observed from the data plotted in Figure 14, corresponding to a pool fire of hexane. For this hydro-

    co -I

  • Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al. 239

    12000

    E 10000

    c

    t 8000

    P

    ; 6000

    between the flames and the tank wall practically throughout the run, and the cooling fluid never reached this zone. Instead, as height increased the temperature reached was lower and the effect of the cooling fluid (after the start-up of the deluge system) was far greater.

    0

    0 10 20 30 40 50 60

    time(s)

    Figure 14 Total heat release rate as a function of time for tests number 13 and 9 (4 m2. hexane. with and without tank respectively). The horizontal line cor;esponds to the theoretical heat release rate at steady-state, calculated according to Bab- rauskass equation

    At a given point, the complete process followed five different steps. The first one corresponded to strong heat- ing, followed by a second stage in which the temperature still increased but at a slower rate (in this step, induced wind was already noticeable). Immediately after the start-up of the deluge system, the temperature started to decrease, but very slowly (third step); there was still flame impingement, although the height of the flames was already decreasing. Once the cooling fluid reached that particular point, the temperature decreased dramati- cally (fourth step) up to the extinction of the fire. After- wards, the temperature increased slightly due to the radi- ation from the hot walls of the experimental module. In certain zones of the tank only some of these steps were observed, depending on the existence or otherwise of flame impingement and on the contact or lack of it with the cooling fluid.

    carbon, combustion efficiency in free surface pool fires of 92% has been proposed in the literature. Figure 14 shows experimental data corresponding to the heat release rate for the pool fire with and without a tank engulfed in it. Furthermore, the maximum theoretical heat release rate (77 = 100%) has also been plotted, calcu- lated according to the method explained in the previous paragraphs. To check this method, the following data can be considered: the heat release rate at steady state (pool fire of hexane, 4 m*) calculated from the combus- tion rate predicted by Babrauskass equation is 13 045 kW; by applying the new method proposed here - which can be used even during the unsteady state - a value of 13 807 kW is obtained at f = 60 s (after reaching the stationary state). The small difference (5.5% with respect to the highest value) confirms the validity of the method. In Figure 14 it can be seen that for a free sur- face pool fire, the steady state would be reached after approximately 45 s, with a combustion efficiency of approximately 88%.

    Conclusions

    The experimental data obtained have allowed the study of the evolution of a pool fire from its beginning up to its complete development. As the sizes of the pool fires were relatively large (4 m* and 12 m*), both the shape and size of the flames were relatively variable. This was even more important after the start-up of the deluge sys- tem, as a relatively strong wind was induced. In these conditions, the fire was moved towards one of the sides and this gave rise to an asymmetrical evolution of the temperatures of the equipment engulfed in the pool fire, with flame impingement essentially on the bottom and on one of the sides.

    Concerning the heating of this equipment, its tem- perature increased following an approximately linear trend, at a velocity which depended on the location of the measuring point. Thus, the highest temperatures were measured at the bottom of the tank (approximately 300C in 1 min). In this zone, there was direct contact

    Concerning the heat released by the fire, the exper- imental results were significantly lower than the theoreti- cal values which should be expected. A method has been developed to calculate the maximum combustion rate, both for the developing stage (unsteady state) and for the fully developed fire. This has allowed comparison between the theoretical values and the experimental data with and without a tank in the fire. It has been found that the heat release rate is significantly lower when there is a tank engulfed in the fire; the existence of this equip- ment is in fact an obstacle for the flames. Thus, both a hindering factor and an efficiency of hindered com- bustion have been defined. The values of qobsr are sig- nificantly lower than those corresponding to the combus- tion efficiency of a free surface pool, this being a clear effect of the hindering consequence of the engulfed equipment.

    The results obtained show the advantages of a sys- tem with the objective - from the first moment - of sim- ultaneously cooling the equipment and extinguishing the fire. Covering these two aspects with a single deluge sys- tem can be very useful in providing a rapid solution to certain emergencies which can be encountered in the process industries.

    Acknowledgements

    Two of the authors @P.-C. and J.C.) gratefully acknowledge partial financial support from the Univer- sities and Research Commission of the Generditut (Catalan government).

    References 1. Wighus, R. J. Loss Prev. Process hi. 1994, 7, 305-309 2. Foam and Water Deluge Systems for Off-Shore Oil Platforms,

    Project Summary Report, Ek Contract: TH-X125/89-IT 3. Fixed Water Surav and Deluge Protection for Oil and Chemical

    Plant, IRI Info-m&ion IM.12r2.1.2, 3 June, 1991 4. Casal, J., Planas, E., Lancia, A. and Bordignon, L. in Fire engin-

    eering and emergency planning. Research and application, ed: R. Barham, Chapman and Hall, London, 19%. PD 209-217

    5. Aydemir, N. k., Magapu, V. K., Sousa, A. k: M. and Venart, J. E. S. J. Hazardous Materials 1988, 20, 239-262

  • 240 Protection of equipment engulfed in a pool fire: E. Planas-Cuchi et al.

    6. Bainbridge, B. L. and Keltner, N. R. J. Hazardous Materials 1988, 20,214o

    7. Beynon, G. V., Cowley, L. T., Small, L. M. and Williams, I. J. Hazardous Materials 1988,20, 227-238

    8. Birk, A. M. J. of Hazardous Materials 1988, 20, 197-225 9. Mudan, K. S. hog. Energy. Combust. Sci. 1984, 10, 59-80

    10. Heskestad, G. F. Safety J. 1984, 7, 25 11. Tewarson, A. SFPE handbook of fire protection engineering,

    Chap. 13, Section 1, 1.179-1.199, 1st edn, NFPA, 1990 12. Babrauskas, V. Fire Tech. 1983, 19, 251

    Nomenclature ah

    CP d F H Ah, AH, k

    Parameters in equation 5 Specific heat of the generated gases (kJ Pool diameter (m) View factor (dimensionless) Convection coefficient (kW me2 . K-) Heat of combustion (kJ kg-) Heat of vaporization (kJ . kg-) Extinction coefficient (m-l)

    kg- . K-1)

    T L1 Tb Tf TR

    0

    5

    Thermal conductivity of the pool walls (kW . m-r K-r) Combustion rate (kg. m-* s-r) Maximum combustion rate (kg. m-*. s-l) Flow rate of the gases produced in the combustion (kg . m-* s-l) Heat transfer rate (kW) Heat transfer rate per unit surface (kW . m-*) Heat released by convection (kW . mdZ) Total heat release rate emitted during the fuel combus- tion (kW . m-*) Time (s) Room temperature (K) Average temperature of flames at a given height (K) Boiling temperature of the fuel (K) Centreline flame temperature (K) Temperature at flame boundary (K) Temperature rise of the smoke (K)

    Combustion efficiency Efficiency of hindered combustion Stefan-Boltzmann constant (= 5.67 . 10-r? kW m-* a K4) Hindering factor