20
roofSec Leakage Detection and Monitoring System CU018 Refernce Manual

roofSec Leakage Detection and Monitoring System CU018 · 2020. 8. 3. · - Power supply: PHOENIX CONTACTS, STEP-PS/1AC/24DC/2.5 If any parts are incorrect, missing, or damaged, contact

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • roofSec Leakage Detection and Monitoring System

    CU018 Refernce Manual

  • Table of content

    1 Hardware Setup .................................................................................................................................... 3

    1.1 System requirements .................................................................................................................... 3

    1.2 Unpack your system ...................................................................................................................... 3

    1.3 TOP VIEW ...................................................................................................................................... 3

    1.4 Front view ..................................................................................................................................... 4

    1.5 Rear view ....................................................................................................................................... 5

    1.6 Sensor cable connection ............................................................................................................... 5

    1.7 Sensor cable strain relief ............................................................................................................... 6

    2 Initial Setup ........................................................................................................................................... 7

    2.1 Install the CU018 ........................................................................................................................... 7

    2.2 Connect to the system and Log In................................................................................................. 8

    3 Web management interface ............................................................................................................... 10

    3.1 Dashboard ................................................................................................................................... 10

    3.2 NETWORK CONFIGURATION ....................................................................................................... 12

    3.2.1 Ethernet Connection ........................................................................................................... 12

    3.2.2 Wireless Connection ........................................................................................................... 14

    3.2.3 Test Connection .................................................................................................................. 14

    3.3 USER SETTINGS ........................................................................................................................... 15

    3.3.1 Authentication process ....................................................................................................... 16

    3.3.2 Authentication validation ................................................................................................... 17

    3.3.3 Activation key ...................................................................................................................... 17

    4 Manage the system ............................................................................................................................. 18

    4.1 Change the login password ......................................................................................................... 18

    4.2 Deactivate Hotspot ..................................................................................................................... 18

    4.3 Restore the Factory Default Settings .......................................................................................... 18

    5 Monitoring .......................................................................................................................................... 19

    5.1 View System Information ............................................................................................................ 19

    5.2 View/Update Wireless Stations .................................................................................................. 19

    6 Troubleshooting and debugging ......................................................................................................... 19

    6.1 Troubleshooting with the LEDs ................................................................................................... 19

    6.2 Cannot connect to the system to configure it ............................................................................ 19

    6.3 Cannot connect to the Cloud to complete the installation ........................................................ 20

  • 1 HARDWARE SETUP

    1.1 SYSTEM REQUIREMENTS Before installing the CU018 communication unit, make sure that your system includes the following:

    - The Cat5 Ethernet cable with RJ-45 connector

    - A 100-240 V, 50-60Hz AC power source

    - A web browser for configuration

    - At least on computer with TCP/IP protocol installed

    - for wired connection:

    a 10/100/1000 Mbps local area network device such as a hub or switch

    - for wireless connection:

    802.11b/g-compliant device

    1.2 UNPACK YOUR SYSTEM Your system must include

    - Leakage monitoring and detection system: CU018 communication unit device

    - Installation guide with cabling and access point setup instruction

    - Power supply: PHOENIX CONTACTS, STEP-PS/1AC/24DC/2.5

    If any parts are incorrect, missing, or damaged, contact your roofSec dealer or roofSec.

    1.3 TOP VIEW The top view of the CU018 are shown in the following figure.

    Power supply for 24VDC -/+

    Network connectivity of LAN, WLAN

    Sensor connectivity by S1, S2, S3, S4

    Reset button T1, T2

    External extension R1, R2

  • 1.4 FRONT VIEW The status LEDs and connectors on the front side of the panels are shown in the following figure.

    Power connector LAN port WLAN dongle

    LED power

  • 1.5 REAR VIEW The status LEDs and connectors on the rear side of the panels are shown in the following figure.

    Pressing the Reset button for at least 10 seconds restores the factory settings for the network

    configuration and authentication configuration.

    1.6 SENSOR CABLE CONNECTION The sensor cable wiring is very important to be done based on the given color code of the single wires

    and is shown in the following figure.

    From left to right:

    GR/GY… grey

    RT/RD… red

    OR/OG… orange

    GE/YE… yellow

    Sensor cable connectors Reset button External extension

    LED processor board

  • 1.7 SENSOR CABLE STRAIN RELIEF Make sure that you are using a strain relief that prevents the sensor cable from getting loose or

    unplugged when moved or bent as shown in the following example figure.

  • 2 INITIAL SETUP

    2.1 INSTALL THE CU018 Make sure that your Internet service is active to complete the full installation process including the

    authentication process.

    Make sure that the power supply is already properly installed and wired with the power plug of the

    CU018.

    TO INSTALL CU018

    1) Connect the Power Supply input to the line

    2) Connect the Power Supply output with the power plug of the CU018.

    This already powers up the CU018 system and you should see

    a. The power LEDs lighting green.

    b. The processor LED in red lighting up and the processor LED in green flashing

    occasionally.

    3) Connect the sensor cable SC018_100 via the CC018_50 to the CU018.

    4) The network configuration can either be done via static or dynamic IP address configuration.

  • An overview of the devices and the connection of these is shown in the following figure.

    2.2 CONNECT TO THE SYSTEM AND LOG IN

    You can connect to the CU018 web management interface to view or change its LAN, wireless access

    settings and to run the mandatory authentication process to the roofSec cloud service.

    To connect to the system via LAN and DHCP

    The CU018 is configured to have DHCP enabled by default.

    If the connected switch or access point does not provide an IP address when the LAN network cable is

    connected.

    1) Connect the Ethernet cable to the LAN port of the CU018.

    2) Connect the other end of the Ethernet cable to switch or access point.

    3) Open your switch or access point device’s web interface to retrieve the IP address that has been

    assigned to the CU018.

    4) On the computer that is connected to the same network, enter the IP address of the CU018 in

    the address field of a browser.

    A login screen displays. For further configuration see section Web management interface.

  • To connect to the system via LAN and static IP configuration

    The CU018 has a fallback LAN configuration in case of DHCP is provided and this method is well suited

    for wireless configuration.

    1) Connect the Ethernet cable to the LAN port of the CU018.

    2) Connect the other end of the Ethernet cable to the computer.

    3) Configure the computer with a static IP address of http://10.0.0.10/and a subnet mask of

    255.255.255.0.

    For help configuration a static IP address on your computer, check the instructions or online

    help that came with that computer or operating system.

    4) On the computer that is connected to the same network, enter the IP address of the CU018 in

    the address field of a browser.

    A login screen displays. For further configuration see section Web management interface.

    To connect to the system via WIFI access point

    The CU018 has a dedicated WIFI that acts as access point and provides a dedicated configuration WIFI

    network called roofSec.. This configuration allows full flexibility for the LAN/WIFI

    configuration and the authentication process.

    1) Configure your computer to update all WIFI networks and search for roofSec.

    Each CU018 provide a unique WIFI SSID name.

    For example: roofSec.b827eb1c48fe

    2) Connect to the roofSec-Portal WIFI without any password needed

    3) On the computer that is connected to the CU018 WIFI, enter http://10.3.141.1 in the address

    field of a browser.

    A login screen displays. For further configuration see section Web management interface.

    http://10.3.141.1/

  • 3 WEB MANAGEMENT INTERFACE

    The initial web management interface of the CU018 displays a login screen first.

    Enter ChangeMe for the password and click on Login.

    You will be redirected to the DASHBOARD after successfully entering the correct password.

    If you encounter problems logging into the system please check your password accordingly.

    If you still encounter problems please refer to the section on how to reset to Factory default settings.

    The configuration and authentication process can be described as follows:

    3.1 DASHBOARD The Dashboard screen gives you detailed information of the

    - Network settings via LAN Information and WIRELESS Information

    - ROOFSEC cloud server configuration and connection status

    - Account information with your activation key (also referred as code)

    The Dashboard can be used to review these settings and change them accordingly based on updates

    with respect to the network or the sensor cables.

    DASHBOARD

    NETWORK

    CONFIGURATION

    USER SETTINGS

    DASHBOARD

  • In order to start the initial configuration and authentication you have to click Continue to display the

    network configuration screen.

  • 3.2 NETWORK CONFIGURATION The network configuration screen allows you to configure your LAN and WIFI configuration in order to

    connect the CU018 to the roofSec cloud service.

    The roofSec cloud service is mandatory for a full functionality of the leakage detection and monitoring

    system.

    3.2.1 Ethernet Connection

    The Ethernet/LAN connection allows you to select between DHCP or Static IP configuration.

  • DHCP/Static IP

    By default, the Dynamic Host Configuration Protocol (DHCP) is enabled. If your LAN includes a DHCP

    server and you have enabled DHCP, the CU018 gets its IP address, subnet mask, and default gateway

    settings automatically from the DHCP server on your network when you connect the CU018 to your LAN.

    - IP Address. The IP address of your access point. The default IP address is 10.0.0.10. To change it,

    enter an unused IP address from the address range used on your LAN, or enable DHCP.

    - IP Subnet Mask. The access point calculates the subnet mask based on the IP address that you

    assign. Otherwise, you can use 255.255.255.0 (the default) as the subnet mask.

    - Default Gateway. The IP address of the gateway for your LAN. For more complex networks,

    enter the address of the router for the network segment to which the access point is connected.

    The default is 0.0.0.0.

    - DNS Server. The IP address for the primary Domain Name Server used by stations on your LAN.

    The default is 0.0.0.0.

    Click Save and Apply to take over changes applied to the Ethernet connection configuration.

    Hint: In case you have selected DHCP as your Ethernet Connection configuration,

    the static IP option is sued as failover static configuration in case no DHCP server is

    present in the network.

    Hint: In order to update network settings for you LAN configuration it may be

    required to connect and disconnect the Ethernet cable from the LAN port of the

    CU018.

  • 3.2.2 Wireless Connection

    The Wireless connection dialog allows you to connect the CU018 to wireless networks near you.

    We do not recommend this connection type and you should use it only if no LAN network is available.

    The wireless connection dialog lists all the wireless networks within the range of the CU018.

    Add WIFI network

    In order to connect to a wireless network, you have to enter the password in the Passphrase field and

    click Add.

    The successful connection to the wireless network is visualized with the checkmark on the left of the

    SSID.

    Update WIFI network

    In order to update your password, you can change the Passphrase and click Update.

    Delete WIFI network

    In order to disconnect from the wireless network, click Delete.

    3.2.3 Test Connection

    Once you have successfully configured your Ethernet connection or Wireless connection properly with a

    link to the Internet, you can test the configuration.

    - Click Test Connection

  • The result of a successful connection to the roofSec cloud service will be displayed in a separate

    information dialog as shown in the following figure.

    This does not imply that the authentication process is complete.

    3.3 USER SETTINGS The last step of the initialization process is the application of the user settings to link the sensor data of

    your building and/or roof to the corresponding building and/or roof in the roofSec cloud service

    database.

    It is mandatory that you use the correct activation key (see Activation key) for your building and/or

    roof.

  • 3.3.1 Authentication process

    You can either use your registration account information or you can use the dialog to create a new

    account as shown in the following figure.

    1) Enter valid Email.

    2) Enter the Password.

    a. Reenter the password in case of creating a new account.

    3) Enter the Activation key.

    4) Click Finish configuration.

    The configuration is validated and if successful, you will be redirected to the Dashboard.

    You have now successfully finished the configuration and authentication process of

    the network and user settings.

    The connection status dialog box informs you accordingly as Connected as shown in the following figure.

  • 3.3.2 Authentication validation

    The email, password and activation key are determined to be a unique information that belongs

    together. When you click Finish configuration, this information is validated at the roofSec cloud server

    and the result will be displayed on the screen.

    If the input parameters are invalid, a message is displayed that the login was not successful as shown in

    the following figure.

    3.3.3 Activation key

    The activation key can be found in the planning report that you get from your supplier and should be

    available at the construction site.

  • 4 MANAGE THE SYSTEM

    4.1 CHANGE THE LOGIN PASSWORD After you have successfully finished the configuration and authentication process, we recommend that

    you change the default login password to a more secure password.

    4.2 DEACTIVATE HOTSPOT The CU018 has an internal WIFI acting as hotspot for configuration. After you have successfully finished

    the configuration and authentication process, we recommend that you disable the hotspot.

    On the Dashboard page within the Wireless information dialog box, click Deactivate Hotspot.

    The Hotspot is reactivated when you reset to Factory Default Settings, see Restore the Factory Default

    Settings.

    4.3 RESTORE THE FACTORY DEFAULT SETTINGS The CU018 configuration can be reset to factory default settings.

    Pressing the Reset button for at least 10 seconds restores the factory settings for the network

    configuration and authentication configuration.

    Please note that by pressing this button to reset to Factory Default Settings, the

    system will be rebooted automatically in order to make the changes affective.

  • 5 MONITORING

    5.1 VIEW SYSTEM INFORMATION The dashboard is the main entry page.

    You get all the information on the network status, the roofSec cloud service connection status.

    5.2 VIEW/UPDATE WIRELESS STATIONS If you want to change your wireless stations settings or you want to switch to a different wireless

    station, you can always update these settings in the Network configuration page.

    In order to keep the link to the roofSec cloud service active, you need to validate the connection status

    anytime you change or update the network configuration settings.

    Please refer to section Network configuration.

    6 TROUBLESHOOTING AND DEBUGGING

    6.1 TROUBLESHOOTING WITH THE LEDS

    All LEDs are Off

    You need to check the power connection of the power supply, the connection of the cables and wiring.

    Processor board LEDs are Off

    You need to check if the power supply is sufficient for 24V DC and 60W.

    LAN LED is Off

    You need to check the proper connection of the cables to the computer or switch/access point on the

    hand and the CU018 LAN port on the other hand.

    6.2 CANNOT CONNECT TO THE SYSTEM TO CONFIGURE IT You have multiple ways to connect to the system.

    In the following section some typical issues are described:

    - If you are using DHCP and the CU018 does not get an IP assigned by your DHCP server, please

    check if MAC Filtering is disabled.

    - If you are using static IP addresses, please check the static IP address configuration locally on

    your computer. Please refer to your OS instruction on how to manage to do so.

  • - If you are using the roofSec-Portal as network connection no password is required. In order

    cross check a successful network link with the CU018 network, you can check the connection

    from your computer by pinging 10.3.141.1.

    6.3 CANNOT CONNECT TO THE CLOUD TO COMPLETE THE INSTALLATION Please first check the Test connection function in the Network configuration page to verify that you

    have an active link to the internet and the communication to the roofSec server is possible.

    Please cross-check all your input parameters as this is most likely the reason that you can finish the

    authentication process (be careful to use case sensitivity).

    6.3.1 Conflicting Ethernet Connection and Wireless Connection

    If you have configured a static IP for the Ethernet connection, the CU018 uses this interface as the

    primary interface for the connection test.

    In case you can’t establish a connection to the cloud Server, please check your settings and try either the

    Ethernet connection settings via DHCP and/or Wireless connection settings having DHCP enabled.